PART II - SECTION F : TECHNICAL DATA SHEETS

TDS 2C - BALANCE OF PLANT, ELECTRICAL WORKS


REQUIREMENTS

DESCRIPTIONS
C. MV CABLES
1
MANUFACTURER/BRAND
2
MANUFACTURING STANDARDS
3
VOLTAGE
4
NO. OF CORES
5
CONDUCTOR
5.1
MATERIAL
5.2
DESIGN
5.3
CROSS-SECTIONAL AREA, mm2
6
CONDUCTOR INSULATION
6.1
MATERIAL
6.2
THICKNESS, mm
6.3
DIAMETER OF INSULATION, mm
7
CONDUCTOR SCREEN
7.1
MATERIAL
7.2
THICKNESS, mm
8
CORE SCREEN
8.1
MATERIAL
8.2
THICKNESS, mm
8.3
DIAMETER OVER SCREEN, mm
9
FILLERS MATERIAL
10
BINDERS OVER LAID UP CORES
10.1
MATERIAL
10.2
THICKNESS, mm
10.3
DIAMETER OVER BINDER, mm
11
METALLIC LAYER/SCREEN
11.1
MATERIAL
11.2
NO. OF WIRES AND SIZE
11.3
NO. OF TAPES AND SIZE
11.4
CROSS-SECTION, mm2
11.5
BEDDING MATERIAL
11.5.1
THICKNESS, mm
12
VERMIN PROTECTION / ARMOUR
12.1
TYPE
12.1.1
12.2
13
13.1
13.2
15
15.1
15.2
15.3
15.3.1
15.4
15.5
16
16.1
16.2
16.3
17
17.1
17.2
18
19

By Bidder
IEC 60502 & IEC 60811
By Bidder
single core

Phelps Dodge
IEC 60502 & IEC 60811
18/30 (36) kV
single core

COPPER
STRANDED, SECTORAL
By Bidder

Copper
Circular Compacted
95 mm

XLPE
By Bidder
By Bidder

TR-XLPE
8.0 mm
28.70 mm

By Bidder
By Bidder

Semiconductive XLPE
0.30 mm

By Bidder
By Bidder
By Bidder
By Bidder

Semiconductive XLPE
0.60 mm
30.70 mm
N/A

By Bidder
By Bidder
By Bidder

N/A
N/A
N/A

By Bidder
By Bidder
By Bidder
By Bidder
By Bidder
By Bidder

Copper Tape
N/A
0.1016 mm
N/A
PVC
1.20 mm

TERMITE/RODENT

ARMOUR TYPE

By Bidder

Anti-termite Additive
on Jacket
Plastic Coated
Aluminum Tape
2 x 0.2032 mm

PVC
By Bidder

PE
2.2 mm

By Bidder
By Bidder
By Bidder
By Bidder
By Bidder
By Bidder

39.48 mm
2.35 kg/m
2000 m
1000 m
2450 mm
4800 kg

By Bidder
By Bidder
By Bidder

290 A
268 A
227 A

By Bidder
By Bidder
By Bidder
By Bidder

90C
90C
0.84
13.46

By Bidder

NOMINAL THICKNESS, mm
OUTER COVERING
MATERIAL
MINIMUM AVERAGE THICKNESS, mm
COMPLETED CABLE
OVERALL DIAMETER, mm
WEIGHT PER METER, kg/m
MAXIMUM DRUM LENGTH, m
NORMAL SHIPPING LENGTH, m
DRUM OVERALL DIAMETER, mm
DRUM OVERALL WEIGHT, kg
CONTINUOUS CURRENT CARRYING CAPACITY
LAID IN GROUND, ONE CIRCUIT, amp
LAID IN GROUND, TWO CIRCUITS, amp
LAID IN GROUND, THREE CIRCUITS, amp
MAXIMUM CONDUCTOR TEMPERATURE
LAID DIRECT IN GROUND, C
DRAWN INTO DUCTS, C
CONDUCTOR SHORT CIRCUIT CURRENT, kA
SCREEN EARTH FAULT CURRENT, kA

OFFER

BURGOS WIND PROJECT


EDC 09-029

PART II - SECTION F : TECHNICAL DATA SHEETS


TDS 2C - BALANCE OF PLANT, ELECTRICAL WORKS
REQUIREMENTS

DESCRIPTIONS
C. MV
20 CABLES
MAXIMUM DIELECTRIC STRESS
20.1
20.2
21
21.1
21.2
21.3
21.4
22
23
24
24.1
24.2
25
26
27
28

29
30
30.1

30.2
31
31.1
31.2

AT CONDUCTOR SURFACE, kV/mm


AT INSULATION SURFACE, kV/mm
MAXIMUM BENDING RADIUS
LAID DIRECT IN GROUND, m
DRAWN INTO DUCTS, m
DURING INSTALLATION W/OUT DAMAGE, m
AT TERMINATIONS, m
MAXIMUM CONDUCTOR DC RESISTANCE, ohm/km
MAXIMUM CONDUCTOR AC RESISTANCE, ohm/km
INSULATION RESISTANCE, per km of cable core
AT 20C, Megaohms
AT MAXIMUM RATED TEMP., Megaohms
EQUIVALENT STAR REACTANCE, ohm/km
EQUIVALENT CAPACITANCE, F/km
MAXIMUM CHARGING CURRENT, A/km
MAXIMUM DIELECTRIC LOSS OF CABLE, W/m
per meter of 3 phase circuit when laid direct in
ground at nominal voltage and frequency at
maximum conductor temperature
CORE IDENTIFICATION FOR 3 CORE
Manufacturer's Experience
The manufacturer should have been in the business
of manufacturing power cables for
not less than : years
The materials to be supplied should have been in
the actual service for not less than (years):
SUBMITTALS
Descriptive materials, brochures, drawings, etc.
Reference Lists

OFFER

By Bidder
By Bidder

3.34568
1.48049

By Bidder
By Bidder
By Bidder
By Bidder
By Bidder
By Bidder

790 mm (20 x OD)


790 mm (20 x OD)
790 mm (20 x OD)
790 mm (20 x OD)
0.193
0.19353

By Bidder
By Bidder
By Bidder
By Bidder
By Bidder
By Bidder

129.75381
1.29754
0.30172
0.17035
1.11243
25

WHITE, RED, BLUE

N/A

15 years

20 years

3 years

25 years

yes
yes

Attached
Attached

Name of Bidder:

PHELPS DODGE PHILIPPINES ENERGY PRODUCTS CORP.

Name & Signature of Representative:

ABRAHAM V. SANCHEZ

Designation:

Vice-President, Sales

Date:

August 4, 2010

FOR ENERGY DEVELOPMENT CORPORATION USE ONLY

1
REV.

ISSUED FOR BID

03/06/09

DESCRIPTION

DATE

ENERGY DEVELOPMENT CORP.

AMLR/RMBA/DDA
PREPARED

MJVL
APPROVED

ELECTRICAL - MEDIUM VOLTAGE CABLES

ENGINEERING DESIGN DEPT.

BURGOS WIND PROJECT

BURGOS WIND PROJECT


EDC 09-029

TDS 2A