19.02.2016
Rahul Srivastava
Contents
1. Typical System Architecture of Fire Alarm System and Clean Agent System
2. Classification of Devices and Application
3. Description of the Fire Alarm System Components
4. System Design
5. Design Procedure of Fire Alarm System
6. Design tools
7. AutoCAD , SPEL and SP3D interfacing
Types
Application
Application
2. Rate-of-Rise-Compensated Fixed
Temperature Detector
2. Pre-signal
3.Rate-of-Rise Detector
4.Combination Detector
5. Linear Heat Detector
Non Integrated type
Integrated type
2. Design
Each clean agent fire suppression system is uniquely designed to match the specific needs of the
protected area. This includes considerations for the type of detection, control panels, tank
size/quantity, actuation devices, distribution piping, discharge nozzles, notification devices, and
other components.
i) Nozzle: The type and size of discharge nozzles are determined during the design phase of the
project. The nozzles, which are manufactured with the precise orifice size required for the
system, are UL Listed and FM Approved specifically for clean agent systems.
ii) Piping: Schedule 40 seamless steel pipe is often used for connecting the nozzles to the clean
agent cylinders. The steel piping network is then connected to the tank by a flexible steel hose.
Since discharge pressures can approach 360 720 psi, metallic piping is the material of choice.
10
10
11
11
12
12
13
13
Application
Rate compensation
14
14
Application
Early warning or life safety. This detector is most efficient when flaming
fires are expected.
Photoelectric, spot-type
Most efficient when smoldering fires are expected or where the smoke
has to travel a distance before reaching the detector (aged smoke).
Photoelectric, beam-type
Used in high value applications, such as computer rooms; also used air
sampling-type in high airflow areas and some rack storage application
Notification of occupants or others of potentially dangerous conditions,
such as the presence of fuel gases or toxic gases such as carbon
monoxide shall be permitted.
15
15
Application
Gas Detectors
Gas detection equipment shall be listed for detection of the specific gas
or vapor to be encountered.
16
16
(a) Contains a normally open or closed switch that is housed within a distinctive
enclosure. Once actuated, the box must be reset to restore the unit to normal.
(b) Contact and circuit arrangements may very to provide a number of functions
simultaneously.
2. Coded
3. Break-glass
To initiate an alarm, one must first break glass or some other element. The purpose is
to identify which box was operated and to discourage tampering with the box when
there is no fire to report.
4. Non-Break-glass
A manual fire alarm box that does not have a break-glass feature.
5. Single Action
6. Double Action
Two actions are necessary to initiate an alarm. Either break a glass to open a door or
lift a cover to gain access to a switch or lever to initiate an alarm.
17
17
Addressable
Module
Initial fire alarm signals only sound at designated areas. The subsequent actuation of a
key switch on the box (or control panel) causes an evacuation signal to sound throughout
the premises.
Initial
Pre-Actuator
Actuator
18
1. Heat Detectors
Used where speed of operation is not required.
Used where other types cannot be used.
Less sensitive.
The oldest type of automatic fire detection device.
Exhibit the lowest false alarm rate of all automatic fire detector devices.
Combination of Fixed Temp & Rate of Rise Heat Detectors are available.
19
c. Rate-of-Rise Detector:
A rate-of-rise detector will operate when the rate of temperature increases from a fire exceeds a
predetermined level, typically around 5F in twenty seconds or 15F per minute. Small, normal changes
in ambient temperature that can be expected under non-fire conditions will not operate the detector. These
detectors are available as both line-type or spot-type detectors, and are restorable.
Shall be used in stable but dusty environments, example garages, battery room.
Shall not be used where sudden rise is expected, Example kitchen.
d. Combination Detector:
Detectors can contain more then one element to respond to a fire. Examples include a combination rate-ofrise and fixed-temperature heat detector, or a combination of a smoke detector and a heat detector.
20
20
21
21
For some applications, the use of a linear heat detector is an option to consider. These may be installed in
head to reach areas, or areas that are subject to high heat. The detector is contained within a cable which
when exposed to heat that is greater than its rating, will short circuit, causing an alarm.
Non Integrated type
2 current-carrying wires held separated by heat-sensitive insulation of a fixed melting point.
Used to provide rapid localized detection of abnormal temperature rises.
Used for overloaded or short-circuited high voltage power wiring.
Integrated type
Electrical Insulation is Temperature dependent.
Actuators
Protective Tape
Heat Sensitive
Material
Outer Insulation
22
22
2. Smoke Detectors
The result of full-scale fire tests, using typical fires in family living units, have shown that detectable
quantities of smoke precede detectable levels of heat in nearly all cases. Thus fire alarm system designers
use smoke detectors more extensively today. The common operating characteristics of smoke detectors
include the ionization spot-type smoke detector, the photoelectric spot-type smoke detector, liner beamtype smoke detector, the air-sampling smoke detector and the duct-type smoke detector.
23
Light
Emitting
Diode
Photo
Diode
Partition
24
24
Transmitter/Receiver(Transceiver), A
Motorized Optical Beam
reflector and an Integrated Control Unit. Smoke Detector Technology
25
25
More Compact.
Less Compact.
Fire alarm is activated when the signal strength is reduced to between 40 90 % for a
period of 5 seconds.
If the transmitted signal is reduced by 90% for more than 1 sec (event of power failure),
fault alarm is generated.
Shall be mounted above man/obstruction level
26
26
27
28
28
NFPA 72-2010, Chapter 18 requires that audible appliances provide a minimum sound pressure level of
15dBA above the ambient noise level or 5dBA above a maximum sound level lasting for at least 60 seconds,
whichever is greater. In addition the Life Safety Code 2010 edition and the Americans with Disabilities Act
(ADA) requires that visible appliances be installed to assist in the alarm notification of the hearing impaired.
Strobes must be placed in accordance with NFTA 72-2010, Chapter 4 requirements to ensure proper
coverage while avoiding excessive flash rates that may trigger a seizure with photosensitive epileptic prone
individuals.
NFPA 72 also requires that all audible evacuation signals conform to the American National Standard
Evacuation Signal, ANSI S3.41. This temporal code 3 signal must be synchronized within a notification zone.
The temporal three code is only to be used when total evacuation of a building is to occur.
29
29
Bells may be used for fire alarm signals where their sound is distinctive and will not be
confused with similar audible signals used for other purposes. Bells are normally
operated by 12 or 24 volts DC (direct current) and may be of the single-stroke or vibration
type connected in parallel.
Bells may be provided with 4-inch through 12-inch gongs (in 2-inch increments). The 6and 10-inch sizes are the most commonly used. Usually, bells with 4-inch gongs are
reserved for use as trouble signals. Generally, the larger the diameter of the gongs the
lower the frequency and the louder the audible signal (expressed in terms of decibels
[dB]).
b. Horns
Horns are provided for applications that require louder or more distinctive signals, or both. Horns may be
operated by either alternate or direct current and may be connected in series or parallel. Care should be
exercised to see that circuits are electrically compatible when powering both types of appliances. Horns that
are manufactured today are generally 12 or 24 VDC.
Horns are usually of the continuous vibrating or electronic type and may be used to provide either coded of
non-coded audible alarm signals. They may be of the surface, flush, semi-flush, single projector, double
projector, or trumpet type.
In very noisy areas, resonating, air-powered or motor-driven horns are sometimes used because of their
inherently higher decibel output. NFPA 72 stipulates that the sound pressure from a notification appliance
may not exceed 110 dBA.
30
30
Speakers are frequently used as fire alarm signaling appliances. Since they reproduce
electronic signals, they can be made to sound like any mechanical signaling device and
have the capability of reproducing unique sounds that are not practical on mechanical
appliances. In addition, they may be used to give live or recorded voice instructions.
Speakers are either direct radiating cone type, or of the compression driver and horn
type.
Speakers are generally operated from audio amplifiers delivering standard output line
levels of 70.7 or 25 volt AC rms. The speakers are driven by an electronic tone generator,
microphone, or voice synthesizer and an electronic amplifier. Two types are in wide use:
Integral that type in which the tone generator amplifier, and speaker are enclosed in a
common housing.
Remote that type in which the speaker is energized from a remotely located tone
generator, microphone and/or voice
synthesizer and amplifier.
d. Sirens:
Sirens usually are limited to outdoor applications but are sometimes used in
extremely noisy indoor areas. Sirens are motor-driven or electronic appliances and
may be either alternating or direct current operated. They are not very practical for
use as coded audible signals.
31
31
Strobe lights operate on the energy discharge principle to produce a high intensity flash of
short duration. These lights are very efficient. The short bright flash is not only attention
getting but is effective when general visibility is low. Strobe appliances come in a wide range
of light intensities and operating voltages. Repetition rates are not allowed to exceed two
flashes per second nor less the one flash every second throughout the listed voltage range
of the appliance.
f. Combination units:
The audible and visible functions can be combined in one unit to produce both sound and light from a single
appliance. For example, the sounder can be a horn, bell, or speaker. The light is required to be a strobe with
specific characteristics as described in Chapter 18 of the 2010 National Fire Alarm and Signaling Code.
Advantages of the combined signals are:
The visible signal localizes the particular audible alarm appliance that is operating.
The visible signal produces a recognizable alarm when an ambient noise level may affect the audible signal.
Persons having impaired hearing can see the visible portion of the alarm signals.
The combined signals are available in all voltages up to line voltage. Twenty-four volt dc units are the most
prevalent. Polarized versions facilitate line monitoring. Two or four-wire connected types permit application
of either a common or separate power supply.
Combination appliances are not required at every location throughout a building. Fire alarm system
designers normally (following the requirements in Chapter 18 of NFPA 72-2010) will design the visible
appliance layout first and then design the audible appliance layout. Then wherever both audible and visible
appliances are in the same general location, those units would be specified as combination units.
32
32
Horn/Strobe
Speaker/Strobe
33
Chime/Strobe
33
System Design
SCOPE
Fire Alarm Plan shall depict the following major details:
Location of Central Fire Alarm Control Panel, MIMIC / HMI display.
Location of Local Fire Alarm Panel.
Location of Smoke Detectors, Heat Detectors (including below false floor & above false
ceiling), Linear Beam Detectors, Manual call points inside every building.
Location of Horn, Strobe inside every building.
Location of Manual Call Points and Horn, Strobe, Siren in plant and Utility areas.
Location of Linear Heat Sensing Cable.
Cable type details and routing in each building, plant & utility areas.
Location of Junction boxes.
Loop diagram for each loop.
Typical installation details of detectors, manual call points, horn, strobe, linear heat sensing
cable, junction box etc.
Relevant Notes & Legends shall be included.
Note:
In case, Clean Agent System Panel is combined with local Fire Alarm Panel as per ITB / project
requirement, all clean agent system panel devices e.g. pre-discharge lamp, discharge lamp,
manual release station, abort switch, solenoid valve etc. shall also be shown in Fire Alarm Plan.
34
34
System Design
3. REFERENCES
Following references shall be used while preparing the Fire Alarm Plan:
ITB
Electrical Design Basis
Job Specifications
Plot Plan with sections
General Notes & Legends
Typical Installation Standards
Civil/ Architectural & Structural drawings of all buildings
Hazardous Area Classification Drawings
Fire Fighting Block Diagram
Fire & Gas Block Diagram
Cause & Effect Diagram
Recommended National and International Codes and Standards
BP / LL / COPQ of past project
Related Drawings issued from Electrical and other department such as Plot Plan, Building
Drawing etc.
35
35
System Design
INSTRUCTIONS
5.1 Requirement for preparing Fire Alarm Plan
a) Fire Alarm Plan shall be prepared based on latest Plot Plan drawings only.
b) Fire Alarm Plan for buildings shall be as per latest Civil / Architectural drawings.
c) HVAC air change data required to calculate indoor detectors quantity.
d) Fire Fighting Block Diagram
e) Fire & Gas Block Diagram
f) Fire Alarm Detection System calculation based on NFPA/ local regulation.
5.2 Key Activities
a) Detectors and MCPs shall be located based on guidelines of NFPA / Local regulation
requirement.
b) Block Diagram for Fire Alarm System shall be prepared based on Fire Fighting Block
Diagram / Fire & Gas Block Diagram / Fire Alarm Calculation / NFPA / Local regulation /
ITB requirement.
c) Fire Alarm Plan shall be prepared in co-ordination / interface with other systems such as
i. F&G (Instrumentation)
ii. HVAC (Piping)
iii. Fire Fighting e.g. Clean Agent System (Piping)
iv. PAGA (Electrical)
v. Lighting (Electrical)
d) Fire Alarm detector shall be located keeping in view the spacing between detectors/
clearance from wall & HVAC duct etc.
36
36
System Design
d) Fire Alarm detector shall be located keeping in view the spacing between detectors/
clearance from wall & HVAC duct etc.
e) Fire Alarm cable route for outdoor shall follow Electrical/ Instrument cable routes as far as
possible or as specified in ITB.
f) Connection of Fire Alarm devices shall be as per Star / Ring topology and necessary JBs
etc. shall be properly located.
g) Field equipment to be installed in classified hazardous area shall have appropriate Ex
protection as per Hazardous Area Classification.
h) The fire detection system in process, storage and utilities area consists of the following:
i. Alarm Push Buttons (Manual Call Points / Break Glass Units)
ii. Linear Heat Sensing Cable for Floating Roof (where ever applicable as per ITB).
i) Fire Alarm in the Plant consists of visual alarm (red flashing light) and audible alarm located
near Alarm Push Buttons.
j) Fire detection system in the buildings consists of the following:
i. Smoke Detectors.
ii. Heat Detectors.
iii. Alarm Push Buttons (Manual Call Points / Break Glass Units).
iv. Heat Sensitive Cable.
v. Linear Beam Detectors.
k) Fire Alarm Plan in the buildings shall cover optical/ acoustical alarm (horn / beacon) located
outside the building near the main entrance and inside the building in the corridor/ main
entrance or in appropriate location as per relevant standard.
37
37
Installation Details
5 ft (1.5 m)
Explanation
17.14.1
Manually actuated alarm-initiating devices for initiating signals other than for fire alarm shall
be permitted if the devices are differentiated from manual for fire alarm boxes by a color
other than red and labeling.
17.14.5
The operable part of a manually actuated alarm initiating device shall be not less than 42 in.
(1.07 m) and not more than 48 in. (1.22 m) from the finished floor.
17.14.6
Installation Details
NFPA-72
(2013) Clause
Explanation
17.14.8.1
Manual fire alarm boxes shall be used only for fire alarm initiating purposes.
17.14.8.2
Manual fire alarm boxes shall be installed so that they are conspicuous, unobstructed, and
accessible.
17.14.8.3
Unless installed in an environment that precludes the use of red paint or red plastic, manual
fire alarm boxes shall be red in color.
17.14.8.4
Manual fire alarm boxes shall be located within 5 ft (1.5 m) of each exit doorway on each
floor.
17.14.8.5
Additional manual fire alarm boxes shall be provided so that the travel distance to the nearest
manual fire alarm box will not exceed 200 ft (61 m), measured horizontally on the same floor.
17.14.8.6
Manual fire alarm boxes shall be mounted on both sides of grouped openings over 40 ft (12.2
m) in width, and within 5 ft (1.5 m) of each side of the grouped opening.
39
Explanation
17.4.7
Where smoke detectors are installed in concealed locations more than 10 ft (3.0 m) above the
finished floor or in arrangements where the detectors alarm or supervisory indicator is not
visible to responding personnel, the detectors shall be provided with remote alarm or
supervisory indication in a location acceptable to the authority having jurisdiction.
17.4.8
If a remote alarm indicator is provided for an automatic fire detector in a concealed location,
the location of the detector and the area protected by the detector shall be prominently
indicated at the remote alarm indicator by a permanently attached placard or by other
approved means.
17.4.9
Where required by 17.4.7 and unless the specific detector alarm or supervisory signal is
indicated at the control unit (and on the drawings with its specific location and functions),
remote alarm or supervisory indicators shall be installed in an accessible location and shall be
clearly labeled to indicate both their function and any device or equipment associated with
each detector.
40
Installation Details
For areas where people are sleeping, sounder devices should produce a minimum 75dB(A) at
the bed-head with all doors shut. In buildings likely to provide sleeping accommodation for the
hearing impaired, consideration should be given to the incorporation of both audio and visual
devices.
41
Types of CI Cable
CIC - Requires Strict Compliance to the Installation Criteria for the CIC Electrical Circuit
Protective Systems.
CI Follow NEC 760 applicable criteria for Power-Limited Fire Alarm Circuits.
42
43
References
Document Number
Document Title
SEI-HC-EL-C015
SEI-HC-EL-C027
SEI-HC-EL-F014
SEI-HC-EL-W009
SSD0023EEC
44
45