OPERATIONS
TYPE OF EXPLOSION IN CFBC BOILERS
Most of the explosions faced in CFBC boilers are dust explosions caused by
small particles of coal in the bed and in the free board kept under suspension by
fluidizing air fans. However, explosion due to FO/ HSD/LDO used in duct burners and/
or
load
carrying
burners
has
also
been
reported.
Fuel should never be fed into the furnace continuously for more than 12
seconds when there is no fire.
Furnace is completely purged of the explosive mixture and then fired.
Fuel supply is stopped immediately if fire/flame is not established and repurging is surely done before restart.
Correct air fuel ratio is maintained so that dust concentration within
explosive limits is never achieved.
Tripping of PF boiler with fuel supply shut off would result in complete flame
failure (barring slag burning). This may not be true in case of a CFBC boiler
where coal on bed may continue to smolder.
Failure of flame or complete loss of ignition in PF boiler immediately gives the
indication that any fuel supply under such condition would form explosive
mixture. Since loss of complete/ partial ignition cannot be ascertained in CFBC
boiler (due to non- availability of flame sensing device), it becomes extremely
difficult to judge whether such mixture is being formed or not.
Incorporation of furnace safe guard systems in PF boiler which completely
shuts off the fuel supply when actuated by flame sensing device greatly helps
operation staff in preventing explosions. CFBC boilers are not fortunate in this
regard. In this boiler, even after stopping the fuel supply, coal on the bed
continues to remain present in the furnace unless boiler is cooled and those
materials are taken out.
The only parameter that would indicate whether combustion is being
established in a CFBC boiler is the reducing oxygen / increasing CO2 % in flue
gas at furnace outlet.
Operation Sequence
I.
II.
h. Feed coal and adjust air as per normal operation. It is assumed that the
control room/ shift charge engineers are well experienced in normal
operation of plant and equipment.
B. RESTART AFTER A SHORT PERIOD OF STOPPAGE
Caution:
Purging with SA fan and ID fan should continue since bed contains
smoldering coal
PA fan to be stopped to avoid bed temperature falling sharply.
Operation Sequence
Precondition -1: Bed temperature> 7600C
Precondition -2: 6500C <="" 7600C=""
a. Load carrying oil burners, if provided, should be switched on to increase the
temperature while following the procedure described under Restart after a trip
out.
b. Boilers not equipped with load carrying burners to follow the same
procedure described under Restart after a trip out. A very high degree of
vigilance is needed for establishing the ignition.
Precondition 3: Bed temperature < 6500C
a. Boilers not equipped with load carrying burners are normally provided with
hot gas generators wherein oil is fired and resultant flue gases are admitted
into the furnace. When bed temperature drops below 6500C, heating of
bed must be done by firing hot gas generator.
As bed temperature rises, keep constant watch on oxygen % in flue gas
because rapid drop in this parameter will indicate that coal has caught
fire. Never allow oxygen %age to fall below 2.5 %.
b. Adjust promptly the recommended air fuel ratio when coal starts burning.
Note: A well structured control logic incorporating above particulars with suitable
interlocks can be provided in the process cycles so that human errors during such
situation can be avoided altogether.