Anda di halaman 1dari 1

Data sheet

Project:
Editor:
Date :

CLARO ORTEZAL
ma
13.02.2015

Unit
Unit type:
Cooling capacity (total):
Cooling capacity (sensible):
Net total cooling capacity:
Net sensible cooling capacity:
Condensing temperature:
EER:
Sound power level:
LpA (2m freefield):
Number of refrigerant circuits:

ASU 562 A
52,2
52,2
47,6
47,6
41
3,48
81,6
62,1
2

kW
kW
kW
kW
C
kW/kW
dB(A)
dB(A)

Airflow:
Air velocity:
Return air temperature:
Return air humidity:
Supply air temperature:
Altitude above sea level:
Height:
Width:
Depth:
Weight:
Refrigerant:
Frequency:

20.450
3,0
22
45
12
2.600
1.980
2.200
890
661
R407C
60

m/h
m/s
C
rel.%
C
m
mm
mm
mm
kg
Hz

Fan (Data per unit)


Fan type:
Number:
Max. revolutions:
Nominal power:
Revolutions:

R3G595_AB23_08
2
1.412 U/min
5,8 kW
1.410 rpm

Power consumption:
ESP external static pressure:
Total pressure drop:
Control voltage:
Motor-efficiency:

4,6
50
502
9,5
89

kW
Pa
Pa
V

Electrical power consumption:


Heat rejection:
COP:
Number:
Evaporating temperature:

5,2
31,2
5,06
2
8,0

kW
kW
kW/kW

Weight:
Current consumption (per fan):
Power consumption (per fan):
Height:
Width:
Depth:
Airflow:
LpA (5m freefield):

128
3,20
0,74
990
1.860
920
13.310
61,0

Compressor (Data per compressor)

Condenser
Unit type:
Ambient temperature:
Sound pressure group:
Required condenser capacity:
Available condenser capacity:
Difference:
Number of fans:
Number of condensers:

KSV045A21pE
30
Standard
31,2
29,8
-4,5
2
2

C
kW
kW
%

The above mentioned data are subject to the measuring tolerances of Eurovent. Unless otherwise stated, all data refer to a product in basic version.
StulzSelect Vers. 2.3.2 - Proj.: UPSISTEMAS / CLARO ORTEZAL 2 x ASU 562 A

kg
A
kW
mm
mm
mm
m/h
dB(A)

Page 1 of 1