Berdasarkan psychrometric chart:


Tdp = 50 oF
T = 55 oF
RH = 84%
b. Entalpi (H) = H terbaca di grafik + Deviasi terbaca di grafik
Hin = 21,50 + (-0,01) = 21,49 Btu/lb dry
Hout = 30,10 + (-0,19) = 29,91 Btu/lb dry
Q = Hout Hin = 7,97 Btu/lb dry
Specific volume udara masuk = 13,14 ft3/lb dry air
Panas yg dimasukkan ke heater =
0,6065 Btu/ft3
c. Udara masuk heater:

Q
specific volume

7,97 Btu/ lb dry


13,14 ft 3/lbdry

Tin (dry) = 90 oF
win = 0,0076 lb water/lb dry air
Udara keluar pengering:
Tout (dry) = 70 oF
Tdp = 63 oF
wout = 0,0125 lb water/lb dry air
Lb water (H2O) teruapkan = wout win = 0,0049 lb water/lb dry air
d. Kandungan air dalam baju mula-mula:
Airawal =

40
196 lb
(100+40)

= 56 lb

Airakhir =

10
196 lb
(100+10)

= 17,8182 lb

Massa air yg harus diuapkan = 38,1818 lb


Fin pengering = 1750 ft3/menit
Uap air terbawa udara per ft3 (w)=

0,0049lb water /lb dry air


3
13,14 ft /lb dryair

water/ft3
Neraca massa air di pengering:

0Fin . w=

dm
dt

Fin . w dt=
0

17,8182 lb

dm

56 lb

Asumsi air yang terbawa udara selalu tetap

t=

( 17,818256 ) lb water
(1750 ft 3/menit)( 0,000373lb water / ft 3)

t=58,5084 menit

Make-up
water

T = 90 oF
RH =
65%

w=
0,022 lb
H2O/lb
dry air

= 0,000373 lb

Adiabatic
humidifying

a. Pembacaan psychrometric chart:


Gambar titik keadaan udara masuk yaitu T = 90 oF dan RH = 65%
(garis merah).
Tarik garis horizontal dari nilai kelembaban udara keluar yg diinginkan
(0,022 lb H2O/lb dry air) ke arah kiri (garis hijau).
Tarik garis dari keadaan awal (T = 90 oF dan RH = 65%) mengikuti
garis wet bulb/adiabatic cooling line hingga memotong garis
horizontal yg dibuat sebelumnya (garis biru).
Dari titik perpotongan tersebut ditarik garis vertikal ke bawah hingga
didapat suhu udara keluar yaitu 82 oF
b. Neraca massa total air di menara (chamber) keadaan steady state:
Input output = 0
(Fin.win + make-up water) Fout.wout = 0
Dengan Fin = Fout = lb dry air/s (massa udara kering tetap)
Make-up water
= Fout.wout - Fin.win
= Fin(wout - win)
Dari psychrometric chart diketahui specific volume udara = 14,27 ft3/lb
dry air pada keadaan udara masuk,
Maka Fin =

10 ft3 /s
14,27 ft3 /lb dry air

= 0,7008 lb dry air/s

Make-up water
= 0,7008 lb dry air/s.(0,022-0,020)lb H2O/lb dry air
= 0,0014 lb dry air/s
= 5,0456 lb dry air/jam

Udara segar
T= 35 oC
95 oF
Tdp= 20 oC
68 oF
T = 60 oC
140 oF
RH = 95%

T = 120 oC
248 oF

Padatan
15% air
100 kg/jam

Padatan
2,5% air

Ditanyakan:a. Jumlah udara segar


b. Jumlah udara direcycle
c. Beban heater
mair bahan masuk =

15
100 kg/jam
(100+15)

= 13,0435 kg/jam
= 28,7557 lb/jam
mpadatan

= 100 13,0435
= 86,9565 kg/jam
= 191,7043 lb/jam

mair bahan keluar =

2,5
191,7043 lb/jam
100

= 4,7926 lb/jam
mair teruapkan

= (28,7557 4,7926)

= 23,9630 lb/jam

x = jumlah udara kering recycle (lb dry air/jam)


y = jumlah udara kering segar (lb dry air/jam)
z = jumlah udara kering total masuk dryer (lb dry air/jam)
Dari psychrometric chart:
wx = 0,132 lb water/lb dry air
wy = 0,015 lb water/lb dry air
Neraca massa udara kering total:
Input Output = 0
y (z-x) = 0
(z-x) = y
Neraca massa total air keadaan steady state:
Input Output = 0
(28,7557 + 0,015y) {4,7926 + 0,132(z-x)} = 0
23,9630 = 0,117y
y = 204,8123 lb dry air/jam
Misal kadar uap air dalam arus z = w, maka neraca massa air
dalam dryer:
(w.z + 28,7557) (0,132z + 4,7926) = 0
(0,132 w)z = 23,9630
z=

23,9630
(0,132 w)

(1)

Ada 2 variabel yang masih belum diketahui, oleh karena itu butuh
persamaan 1 lagi yg memberikan hubungan z dan w, yaitu neraca
panas
Neraca panas udara dalam dryer:
Jika proses adiabatic, maka:
Hin = Hout (jika tidak adiabatic maka perlu diketahui nilai Q)
H didekati dengan persamaan:

H = cpdry airT + w(water+cpwater vaporT) (H dalam Btu/lb dry air, T dalam


o
F)
= 0,24T + w(1025,34 + 0,45T)
Hin = Hout
{0,24(248) + w[1025,34+0,45(248)]}z = {0,24(140) +
0,132[1025,34+0,45(140)]}z
59,52 + 1136,9385w = 177,2607
w = 0,1036
z=

23,9630
(0,132 0,1036)

= 842,5649 lb dry air/jam


Jumlah udara direcycle:
x=zy

(2)

x = 842,5649 - 204,8123
x = 637,7526 lb dry air/jam
Menghitung beban panas heater:

x, Hx

y,
Hy

z, Hz

Neraca panas di sekitar heater pada keadaan steady state:


Hin Hout + Q W = 0
(y.Hy + x.Hx) z.Hz + Q = 0
Q = z.Hz - (y.Hy + x.Hx)
Hz = 0,24(248) + 0,1036(1025,34+0,45(248))
= 177,3068 Btu/lb
Hy = 0,24(95) + 0,015(1025,34+0,45(95))
= 38,8213 Btu/lb

(3)

Hx = 0,24(140) + 0,132(1025,34+0,45(140))
= 177,2607 Btu/lb
Q = (842,5649)( 177,3068) {(204,8123)(38,8213) + (637,7526)
( 177,2607)}
Q = 28392,97 Btu/jam