Commissioning Testing of New Distance Relay: Micom P443

Report Time: 2/12/2016 5:04:34 PM

Zone Verification
Test objects

Test Time:2016-02-12 17:01:38

Test Object: Protection Panel-2


Line: 220KV KSK-Mangla2 (D4Q1&D4Q3)
Tested by: Adeel Zafar, Assistant Manager (P&I)
Device name: P443
Device type: Distance Relay
Serial/model:

Substation: 220KV G/S Kala Shah Kaku NTDC


LHR
Test Item: Zone Verification
Manufacturer: ALSTOM
Device address:
note: Forward Zones Impedance Reach

Setting
Set fixed value: Zone 1(A)=1 , Zone 2(A)=2
Zone 3(A)=2 , Zone 4(A)=2 , Zone 5(A)=2
Prefault: 1 ; Postfault: 0.5
Health voltage after fault: No
.
Select fault: A-E, B-E, C-E, A-B, B-C, C-A, A-B-C,

Test mode: Auto


Earth Compensation
Mode: KL , KL: 0.6 , Angle: -6
Close angle: 0
CT Direction : Object
Zone 1:
Test points: 0.9, 1.05,
Z Setting(L-L): Z=7 , Angle=81
Zone 2:
Test points: 0.9, 1.05,
Z Setting(L-L): Z=9.87 , Angle=81
Zone 3:
Test points: 0.9, 1.05,
Z Setting(L-L): Z=16.46 , Angle=81
.
Binary input setting:
Bin 1
Bin 2
Bin 3
Bin 4
Bin 5
Trigger Logic : or

Z Setting(L-N): Z=7. , Angle=81.


Time Setting(s): 0.03
Select fault: A-E, B-E, C-E, A-B, B-C, C-A, A-B-C,
Z Setting(L-N): Z=9.87 , Angle=81.
Time Setting(s): 0.35
Select fault: A-E, B-E, C-E, A-B, B-C, C-A, A-B-C,
Z Setting(L-N): Z=16.46 , Angle=81.
Time Setting(s): 0.7
.
.
Input name: Trip1
Input name: Trip2
Input name: Trip3
Input name:
Input name:

Test results
Trip time(s)

Fault Type

Z Setting(ohm)

Fixed Val

Judge

0.025

A-E

Zone 1: 7.

90

1 A

Passed

No Trip

A-E

Zone 1: 7.

105

1 A

Passed

1/3

Page

Commissioning Testing of New Distance Relay: Micom P443


Report Time: 2/12/2016 5:04:34 PM

0.0235

B-E

Zone 1: 7.

90

1 A

Passed

No Trip

B-E

Zone 1: 7.

105

1 A

Passed

0.0195

C-E

Zone 1: 7.

90

1 A

Passed

No Trip

C-E

Zone 1: 7.

105

1 A

Passed

0.028

A-B

Zone 1: 7

90

1 A

Passed

No Trip

A-B

Zone 1: 7

105

1 A

Passed

0.028

B-C

Zone 1: 7

90

1 A

Passed

No Trip

B-C

Zone 1: 7

105

1 A

Passed

0.021

C-A

Zone 1: 7

90

1 A

Passed

No Trip

C-A

Zone 1: 7

105

1 A

Passed

0.0265

A-B-C

Zone 1: 7

90

1 A

Passed

No Trip

A-B-C

Zone 1: 7

105

1 A

Passed

0.398

A-E

Zone 2: 9.87

90

2 A

Passed

No Trip

A-E

Zone 2: 9.87

105

2 A

Passed

0.4095

B-E

Zone 2: 9.87

90

2 A

Passed

No Trip

B-E

Zone 2: 9.87

105

2 A

Passed

0.403

C-E

Zone 2: 9.87

90

2 A

Passed

No Trip

C-E

Zone 2: 9.87

105

2 A

Passed

0.369

A-B

Zone 2: 9.87

90

2 A

Passed

No Trip

A-B

Zone 2: 9.87

105

2 A

Passed

0.37

B-C

Zone 2: 9.87

90

2 A

Passed

No Trip

B-C

Zone 2: 9.87

105

2 A

Passed

0.37

C-A

Zone 2: 9.87

90

2 A

Passed

No Trip

C-A

Zone 2: 9.87

105

2 A

Passed

0.372

A-B-C

Zone 2: 9.87

90

2 A

Passed

No Trip

A-B-C

Zone 2: 9.87

105

2 A

Passed

0.724

A-E

Zone 3: 16.46

90

2 A

Passed

No Trip

A-E

Zone 3: 16.46

105

2 A

Passed
2/3

Page

Commissioning Testing of New Distance Relay: Micom P443


Report Time: 2/12/2016 5:04:34 PM

0.7545

B-E

Zone 3: 16.46

90

2 A

Passed

No Trip

B-E

Zone 3: 16.46

105

2 A

Passed

0.745

C-E

Zone 3: 16.46

90

2 A

Passed

No Trip

C-E

Zone 3: 16.46

105

2 A

Passed

0.7275

A-B

Zone 3: 16.46

90

2 A

Passed

No Trip

A-B

Zone 3: 16.46

105

2 A

Passed

0.718

B-C

Zone 3: 16.46

90

2 A

Passed

No Trip

B-C

Zone 3: 16.46

105

2 A

Passed

0.72

C-A

Zone 3: 16.46

90

2 A

Passed

No Trip

C-A

Zone 3: 16.46

105

2 A

Passed

0.7425

A-B-C

Zone 3: 16.46

90

2 A

Passed

No Trip

A-B-C

Zone 3: 16.46

105

2 A

Passed

3/3