FUNGSI

SEBAGAI PENGAMAN UTAMA ATAU CADANGAN


UNTUK GANGGUAN HUBUNG SINGKAT
FASA FASA
FASA TANAH

APLIKASI
PENGAMAN UTAMA
JTM ( DISTRIBUSI )
GENERATOR ( Kapasitas kecil )
TRAFO DAYA ( Kapasitas kecil )
MOTOR
SEBAGAI PENGAMAN CADANGAN

PENGERTIAN

RELAI ARUS LEBIH


SUATU RELAI YANG BEKERJANYA
BERDASARKAN ADANYA KENAIKAN
ARUS YANG MELAMPAUI NILAI
SETTINGNYA .

JENIS RELAI ARUS LBIH :


1.
2.
3.
4.

NON DIRECTIONAL
DIRECTIONAL
KONTROL TEGANGAN
RESTRAINT TEGANGAN

KARAKTERISTIK
@ ARAH
1. TIDAK BERARAH ( NON DIRECTIONAL )
2. BERARAH ( DIRECTIONAL )

@ ARUS WAKTU
1. TANPA TUNDA ( MOMENT = INSTANT )
2. TUNDA WAKTU ( TIME DELAY )
# DEFINITE ( TERTENTU ) = INDEPENDEN
# INVERSE ( I t BERBANDING TERBALIK )
= DEPENDEN

SI / NI = Standard / Normal Iverse


VI
= Very Inverse
EI
= Exteremely Inverse
LTI
= Long Time Invers

KARAKTERISTIK INSTANT = MOMENT


t

t >t 0.1

SET

..x Is
I SET MOMENT

KARAKTERISTIK TUNDA WAKTU


TERTENTU ( DEFINITE TIME )
t

t1= t2 = t3 ..

t SET

2
I SET

5 .. X Is

KARAKTERISTIK TUNDA WAKTU


INVERSE
t
t1
t2
t3
t4
t5

t SET
t SET
t SET
t SET

1 23
I SET

.. X Is

KARAKTERISTIK KOMBINASI INSTANT


DENGAN TUNDA WAKTU TERTENTU
(DEFINITE TIME )
t

t SET

I SET

I SET MOMENT

KARAKTERISTIK KOMBINASI INSTANT


DENGAN TUNDA WAKTU INVERSE
t

I SET

I SET MOMENT

TIPE PLUNGER
KONTAK
PLUNGER

PEGAS
0.6

BELITAN

0.8
1.0
1.2
INTI LUAR

SETTING

Fe = GAYA ELEKTROMEKANIK
Fp = GAYA PEGAS
Fe < Fp
Fe > Fp

DROP OFF
PICK UP

TIPE KWH
L U
2

L
2
KUMPARAN LAGGING

PIRINGAN

Is

KUMPARAN UTAMA

SETTING ARUS DAN WAKTU

TAP SETTING

TAP / PLUG SETING


KUMPARAN
UTAMA

ARUS DARI
CT

KONTAK DIAM

TIME DIAL SETTING


DENGAN MENGATUR
JARAK KONTAK

KONTAK GERAK

TIPE RELAI STATIK

A CT

SUPLAI DC

RECTIFIER

R
SETTING

Vin

LEVEL
DETECTOR

Vo
RELAI
BANTU

VREF VIN VO 0 ( Pickup)


VREF VIN VO 0 (Re set )

BLOK DIAGRAM RELAI ARUS LEBIH STATIK


CURVE
SHAPER

FILTER

CS
Ia
Ib
Ic

MAX
I
GATE
&
RECT.

Is
LD
1

Is
INSTANT
LD = LEVEL DETECTOR
T = TIMER
R = REGULATOR

IBA DOC

SETTING
INSTANT

LD
2

LD
3

RL
3

RL
1

HS OUTPUT
RELAY

STATIC OVER CURRENT RELAY


MCGG

OUTPUT
DRIVER
HS

TIME / CURRENT
OUTPUT RELAY
TIME
0.4/0

INTERPOSSING
CT

FULLWAVE
RECTIFIER

MICRO
COMPUTER

INPUT

A/D

0.2/0.1
0.4/0
0.8/0
0.2/0
0.4/0
CURRENT SETTING

0.2/0
0.2/0
0.1/0
0.05/0
0.05/0.025
TMS SWITH SETTING

16/0
8//0
4//0
2/0
1/0

HIGH SET SWITH


SETTING

CURVE SELECT SWITCH


IBA DOC

INST

t
I > Is

IS IN

xt
I INST

Is

RELAI
OCR / GFR
TIPE
MCGG 82

INST

t
I > Is

IS IN

xt

NAME
PLATE

RESET

KARAK
TERISTIK

I INST

Is

IBA DOC

PRINSIP SETTING OCR

Iset Tunda waktu


* Is = k In

* Plug Setting

IBA DOC

In = Arus Nominal
k = Faktor pabrik ( 1 s/d 2 )
atau 0,05 s/d 2,4 dengan
step 0.05

# Waktu kerja

tIs

tk

* Definite ( Langsung atau dengan Tms )


* Inverse ( Td atau Tms dan Mps = I /

Tms ( td )

Mps = 4 x Is

IBA DOC

Td = Time dial setting


Tms = Time multiple seting
Mps = Multiple plug setting
. X Is

x Is

# Is instant ( moment )
* Is instant = k In atau
k Is
In = Arus Nominal
Is = Arus setting tunda waktu
k = Faktor pabrik
* Plug setting

IBA DOC

@ SETTING ARUS OCR /GFR DENGAN TUNDA WAKTU

IS

0.05
0
0
0

IS

ARUS SETTING

0.2
0.4

IN

ARUS NOMINAL RELAI

0.4
0.4

0
0

0.8

FAKTOR PABRIK

IBA DOC

0.1
0.1

# MISAL ARUS SETTING Is = 6 A.


Is = 1.2 In
POSISI SAKLAR :

IBA DOC

0.1
0.1

0.05
0

0.2
0.4

0
0

0.4
0.4

0
0

0.8

Is = ( 0.1 + 0.1 + 0.2 + 0 + 0 + 0 + 0.8 ) x 5A


= 1,2 x 5A
= 6A

PEMILIHAN KARAKTERISTIK

SI

VI

EI LTI D2 D4 D8

0
0
0

1
0
0

0
1
0

TRIP TEST :

0
0
0
IBA DOC

1
1
0

0
0
1

1
0
1

CURVA SI :

1
1
1

0
0
0

1
1
1

0
1
1

KURVA / KARAKTERISTIK

@ STANDARD / NORMAL INVERSE ( SI )

0,14
t 0, 02
tms
I
1
@ VERY INVERSE ( VI )

13,5
t
tms
I 1
@ EXTREMELY INVERSE ( EI )

80
t 2 tms
I 1
@ LONG TIME INVERSE ( LTI )

120
t
tms
I 1
IBA DOC

SETTING WAKTU

MISAL :

KARAKTERISTIK EI
ARUS GANGGUAN 3 x Is ( I = 3 )
WAKTU KERJA = 1 DETIK

PEMILIHAN TMS :

I 2 1
32 1
tms
tk
1 0,1det ik
80
80

POSISI SAKLAR

0,025
0
0
0
0
0

0,05
0,05
0,1
0,2
0,2
0,4

IBA DOC

SETTING INSTANT

I S inst 18 A
IS 6A
18
6 3
I S inst I S

POSISI SAKLAR
0
0
0
0
0
0

1
2
4
8
16

IBA DOC

SAMBUNGAN ( WIRING )

OCR

PMT

R
P1

CT

OCR
S

S1

GFR
E

T
OCR

S2

P2

3 Buah OCR
1 Buah GFR

IBA DOC

SAMBUNGAN ( WIRING )

PMT

OCR
R

P1

CT

GFR
E

S1

T
OCR

S2

P2

2 Buah OCR
1 Buah GFR

IBA DOC

PENGUJIAN RELAI ARUS LEBIH


1.

PENGUJIAN INDIVIDUAL
MENGUJI INDIVIDU RELAI ITU SENDIRI , UNTUK
MENGETAHUI
APAKAH MASIH DALAM KEADAAN STANDAR ATAU TIDAK

2.

PENGUJIAN FUNGSI
MENGUJI FUNGSI DARI SISTEM PROTEKSI
SECARAKESELURUHANAPAKAH MASIH BERFUNGSI ATAU
TIDAK

PENGUJIAN INDIVIDUAL

HAL HAL YANG PERLU DIPERHATIKAN :


1.
2.
3.
4.
5.
6.

CARA SETTING
INTERNAL DIAGRAM RELAI
ALAT UJI / RANGKAIAN PENGUJIAN
ITEM PENGUJIAN
PROSEDUR PENGUJIAN
HASIL UJI DAN KESIMPULAN

JENIS / ITEM PENGUJIN

1.

ARUS PICK UP DAN ARUS DROP OFF


SERTA
RASIO ARUS PICK UP DENGAN DROP OFF

2.

KARAKTERISTIK ARUS WAKTU

3.

KARAKTERISTIK INSTANTANEOUS

1.

ARUS PICK UP [ ARUS AWAL / MULA ]


ARUS MINIMUM YANG MENYEBABKAN RELAI BEKERJA

2.

ARUS DROP OFF [RESET/ KEMBALI ]


ARUS MAKSIMUM YANG MENYEBABKAN RELAI TIDAK BEKERJA.

3.

RASIO ARUS PICK UP DENGAN DROP OFF

ID
KD
100%
IP

I pick up
I reset
I beban
t
t gangguan

PENGUJIAN INDIVIDUAL
RELAI ARUS LEBIH

21
22
23
24
25
26
27
28

TIMER
START

STOP
220 Vac
R
A

220 Vac

SLIDE

TRAFO ISOLASI

RANGKAIAN PENGUJIAN

29
30

13
14

Vdc

(+)
KONTAK
OCR/GFR

DIAGRAM
KONTROL DC

(+)

RELAI
BANTU
RE 1
(-)

TRIP PMT

(+)

RE 2
RELAI
BANTU
RE 3

(-)

ALARM

RANGKAIAN SIGNALISASI

(+)
KONTAK
RELAI
RESET

TEST LAMP
RELAI BANTU
RE

LAMPU
SIGNAL