STANDARDS AUSTRALIA
Amendment No. 1
to
AS 2118.12006
Automatic fire sprinkler systems
Part 1: General systems
REVISED TEXT
The 2006 edition of AS 2118.1 is amended as follows; the amendments should be inserted in the appropriate
places.
SUMMARY: This Amendment applies to Clauses 1.3, 1.4.14, 1.4.24, 2.2, 2.3.2.3, 2.3.2.4, 2.3.2.5, 2.3.3.2.1,
2.3.3.3, 3.3.2, 3.3.3, 3.5.2.1, 4.1.2, 4.2.1, 4.2.2.2, 4.3.1.1, 4.3.1.5, 4.3.2.2, 4.3.4.1, 5.5.3, 5.7.2, 7.9.3, 7.10.2.1,
7.10.2.2, .13.1.3, 8.1.2, 9.3.2, 10.3.2, 11.4.1.1, 11.5.5, 11.5.1.2.4, 11.5.12.5, 11.7.5.1, 11.7.6.3, 11.7.7.4,
11.7.8.5, 11.7.8.9, 11.8.3 and 12.10, Tables 5.5.2, 11.5.12.2, 11.6.3(B), 11.6.3(C), 11.6.3(D), 11.6.3(E),
11.6.4(M), 11.4.6(N), 11.6.2, 11.6.3(B), 11.6.3(C), 11.6.3(D), 11.6.3(E), 11.6.4(M),, 11.6.4(N), 11.6.4(O),
11.6.4(P), 11.6.4(Q), 11.6.4(R) and 12.10(C), Figures 4.2.2.2(B), 11.6.2, 11.6.5 and 11.7.2.6 and 10 and
Appendices A, B, C, D, E and F.
Published on 23 August 2010.

AMDT
No. 1
AUG
2010

Clause 1.3
1

Delete 1668.1 (under AS/NZS listing) and replace with the following:
1668
1668.1

2
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010

The use of ventilation and airconditioning in buildings


Part 1: Fire and smoke control in multi-compartment buildings

Delete 1999 from the last item NFPA 13.

Clause 1.4.14
Delete (sprinkler) from the title and replace with (nominal).
Clause 1.4.24
Delete the duplicated commentary text (outside the borders).
Clause 2.2
In Item (c)(iii), delete A4.2.3 and replace with A4.3.
Clause 2.3.2.3
Delete the fourth paragraph, excluding Items (a) and (b), and replace with the following:
Alternate wet and dry systems shall be so designed that the water transit times from valve
trip to discharge of water at the most remote sprinkler shall not exceed 60 s. The maximum
floor area, including mezzanine floor areas, controlled by one control assembly, including
tail-end extensions (see Clauses 2.3.2.8 and 2.3.2.9), shall not exceed the following:

ISBN 978 0 7337 9634 0

AMDT
No. 1
AUG
2010

Clause 2.3.2.4
1

Delete the third paragraph and replace with the following:


The water transit time limitation and the floor area controlled by one control
assembly in a dry system shall comply with Clause 2.3.2.3 for alternate wet and dry
systems.

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010

In the last paragraph, delete piping shall be arranged with slope for drainage and
replace with Piping shall be galvanized and arranged with slope for drainage.

Clause 2.3.2.5
Delete the second last paragraph and replace with the following:
Piping shall be galvanized and, where subject to freezing, it shall be arranged with slope
for drainage (see Clause 7.5) and standard sprinklers shall be installed in the upright
position above the line of pipe.
Clause 2.3.3.2.1
Delete the second paragraph.
Clause 2.3.3.3
Delete the NOTE and replace with the following:
NOTE: Except as modified by this Standard, systems using Factory Mutual design requirements
and limitations for the particular ESFR sprinkler selected should also comply with the Factory
Mutual Data Sheets 2.0, 8.9 and other eight series data sheets. Systems using the Underwriters
Laboratories (UL) sprinkler listing requirements and limitations for the selected ESFR sprinkler
should also comply with the ESFR requirements of NFPA 13.

Clause 3.2.2
Delete Items (c), (d) and (e) and replace with the following:
(c)

Pendent sidewall (WP)mounted pendent and oriented to direct the spray towards
the window or wall.

(d)

Pendent sidewall (WP)mounted horizontally and oriented to direct the spray


downwards and parallel to the window or wall.

(e)

Horizontal sidewall (WH)mounted pendent and oriented to direct the spray


downwards and parallel to the window or wall.

Clause 3.3.2
Insert the following second paragraph (text transposed from Clause 3.3.3).
The following requirements shall apply (see Clause 8.13.4):
(a)

Where control assemblies are grouped in a single location, and each is fitted with a
manually resettable system operated indicating device, at least one alarm signal
shall be provided to the monitoring centre.

(b)

Where control assemblies are distributed in several locations on the one premise,
individual alarms to the monitoring centre shall be provided. Where activation of
distributed control assemblies is indicated at a single point within the premises, a
single signal may be provided to the monitoring centre.

(c)

For multiple installations identification, signage shall be provided in accordance with


Clause 8.1.1(l).

(d)

A permanent and securely affixed notice shall be located in close proximity to the
control assemblies to indicate that there is a direct alarm connection to the monitoring
centre (see Clause 8.3).

(e)

Prior to testing, where an alarm signal is to be transmitted, the monitoring service


provider shall be advised that a test is to be conducted. On completion of the test, the
alarm monitoring service provider shall confirm that the system has been restored to
normal.

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

NOTE: Advice may be by configuring the alarm signalling equipment into a test mode.
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010

Clause 3.3.3
Delete the second paragraph, including Items (a) to (e); (text transposed to Clause 3.3.2).
Clause 3.5.2.1
Delete the first paragraph and replace with the following:
Class A fault monitoring devices shall be installed except where the monitored components
are located within a ceiling space, a secure area or a room with access restricted by means
of a security device or system, where Class B devices may be used.
Clause 4.1.2
Delete the second paragraph and replace with the following:
Calculations for the sprinkler system design shall be based on the residual pressure
available to the premises from the source of supply at the required flow. Where the
acceptable source of supply is a town main, the residual pressure shall take into account the
effect of the required flow on the water supply system.
The residual pressure shall be
(a)

determined from local water agency modelling confirming that the pressure can be
maintained for 95% of the time; and

(b)

a minimum pressure obtained or calculated from local water agency records adjusted
for the effect of the system demand (excluding the pressures on the 5% of days
having the lowest pressures); or

(c)

determined by testing the water supply system using a method approved by the water
supply agency.

NOTE: The water supply agency may nominate a residual pressure limit at the point of
connection to the town main, below which draw-off is not permitted.
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010

Clause 4.2.1
In Item (b)(ii), delete the word pumps and replace with pump.
Clause 4.2.2.2
Insert the following note after Item (b); (note transposed from Clause 4.2.2.4):
NOTE: Where there are two or more installations in one building, it is permitted to have the
second and subsequent installation supplied by a single pipe taken downstream of the
interconnection of the two supplies [see Figure 4.2.2.2(B)].

Figure 4.2.2.2(B)
Delete the figure and replace with the following:

Tow n m a i n A

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

AMDT
No. 1
AUG
2010

Sprinkler
c o ntr o l
a s s e m b li e s

Ty p i c a l tow n s
m a i n s wate r s u p p l y
a r r a n g e m e nt s to b e
i n a c c o r d a n c e wi t h
the requirements
of th e l o c a l wate r
s u p p l y a u th o r i t y

Building

A l te r n ative
c o n n e c ti o n
Pr o p e r t y b o u n d a r y

Tow n m a i n B

FIGURE 4.2.2.2(B) DUAL TOWN WATER MAIN WATER SUPPLIESUNBOOSTED

AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010

Clause 4.2.2.4
Delete Note (transposed to Clause 4.2.2.2).
Clause 4.3.1.1
In the first paragraph, delete the words whichever is the lesser.
Clause 4.3.1.5 (new)
Add a new clause as follows:
4.3.1.5 Shared water supplies
Sprinkler systems under separate ownership shall not share private water supplies, nor shall
they share connections to public water supplies.
Sprinkler system piping (with the exception of water supply connections to town mains)
shall not traverse ground that is not under the control of the owner.
C4.3.1.5 Water supplies, other than those parts under the control of the water supply
authority, should be under the control of the owner of the building containing the
installation.
Where there is a ring main or loop within the premises it is desirable to provide
isolating stop valves, so situated as to maintain the maximum possible service in the
event of fracture or, if it is necessary, to close down part of the ring main.

AMDT
No. 1
AUG
2010

Clause 4.3.2.2
Add the following commentary:
C4.3.2.2 Water conservation recommendations
To conserve water during periodic run and load testing of pumps drawing from a
town main supply, a recirculation tank and associated piping [see
Figure C4.3.2.2(A)], may be provided to permit re-use of water during pump
testing. In use the circulation tank is filled as required, the town main supply is
isolated and test water is recirculated via the tank. On completion of the test run,
the town main supply is restored. Tank capacity and dimensions are selected to
accommodate maximum pump duty flow and to prevent turbulence from tank return
lines. See HB 233,Fire Protection Systems Testing, Water Conservation Handbook.

A s p e r m e te r
m a n u f a c tu r e r s
recommendations
Fl ow m e te r

R e c i r c u l a ti o n
tank

C o ntr o l
assembly

Tow n m a i n

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

(f)

FIGURE C4.3.2.2(A) TYPICAL RECIRCULATION TANK ARRANGEMENT

(g)

Where a recirculation tank as in Figure C4.3.2.2(A) above cannot be provided, a


less acceptable means of conserving water during periodic run and partial load
testing of pumps drawing from a town main supply may involve piping for closed
circuit metering. A typical recirculation loop piping arrangement is shown in
Figure C4.3.2.2(B). Means for air release should be provided if air can be trapped
in the loop. Turbulence in the water entering the pump should be avoided to
prevent cavitation.
It should be noted that
(i)

prolonged recirculation can cause heat build-up unless some water is


wasted; and

(ii)

this arrangement cannot serve as the annual flow test facility (see
Clause 4.4.)

Air cock

Tow n m a i n

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

T h r ot tl e va lve

To c o ntr o l
a s s e m b l y ( i e s)

5 diameters min.

FIGURE C4.3.2.2(B) TYPICAL RECIRCULATION LOOP ARRANGEMENT

AMDT
No. 1
AUG
2010

(h)

If neither of the foregoing options is practicable, specifying pumpsets


incorporating variable speed pressure limiting control, that is, a speed control
system designed to limit the total discharge head by reducing the pump driver
speed (the speed duty point). This acts to eliminate or reduce the discharge of
water from the pressure relief valve during periodic pump run tests. Requirements
for variable speed control systems are set out in AS 2941.

(i)

Where discharge of some water is unavoidable, it should be captured and returned


to the sprinkler installation or redirected to another use. This may be accomplished
through the use of temporary on-site recirculating storage tank, grey water
recycling plant where it exists on site, or discharge directly to a tanker for off-site
use in council gardens and the like.

Clause 4.3.4.1
Add the following commentary:
C4.3.4.1 To conserve water at time of tank maintenance, the provision of dual
compartment (sectional) tanks or two half-capacity tanks is strongly recommended.
Such a tank arrangement not only permits conservation of half the stored water at time
of tank draining for maintenance (by pumping from one compartment or tank to the
other) but also ensures that at least half the required stored capacity is available
during tank maintenance.

AMDT
No. 1
AUG
2010

Clause 5.3.3
Add a new Item (j) as follows:
(j)

In the case of partial suspended ceiling panels, full protection is required above and
below the panels. Sprinklers suspended on droppers between ceiling panels shall be
positioned to comply with the requirements of Items (e), (f) and (h) above.

AMDT
No. 1
AUG
2010

Table 5.5.2
Delete the table and replace with the following:
TABLE 5.5.2
CLEARANCES FROM OBSTRUCTIONSSTANDARD SPRINKLERS

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

Dimension BMaximum height of deflector above obstruction/beam


Dimension A

Conventional
upright

Conventional
pendent

12 m 2
SSU/SSP

21 m 2
SSU/SSP

100

Not permitted

Not permitted

200

Not permitted

20

20

300

Not permitted

10

40

15

400

Not permitted

60

30

500

Not permitted

15

85

45

600

Not permitted

30

115

60

700

Not permitted

45

145

85

800

Not permitted

60

180

110

900

Not permitted

80

215

140

1000

200

100

250

170

1100

185

120

290

200

1200

170

140

320

230

1300

145

165

370

265

1400

120

190

410

300

1500

75

225

450

335

1600

30

260

370

1700

70

325

410

1800

170

390

NOTE: Where the sprinkler deflector is required to be below the obstruction, Dimension B is
shown as negative (ve).

AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010

Clause 5.7.2
Add the following at the end of Item (a):
Pipework in hoist and lift shafts shall be galvanized.
Clause 7.9.3
In the third line, delete 1.4 MPa and replace with 1.6 MPa.

AMDT
No. 1
AUG
2010

Clause 7.10.2.1
Delete the Clause and replace with the following:
7.10.2.1 Pipes above ground

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

Except in the case of dry pipe and pre-action system piping, which shall be galvanized
medium steel tube, pipes above ground shall be at least equivalent to medium steel tube
complying with the requirements of
(a)

AS 1074;

(b)

AS 1579; or

(c)

AS 4041.

NOTE: This does not preclude the use of corrosion-resistant pipe such as stainless steel or copper
alloy of equivalent pressure rating.
AMDT
No. 1
AUG
2010

Clause 7.10.2.2
In the first line of the first paragraph, delete Clause 1.5 and replace with Clause 1.3.

AMDT
No. 1
AUG
2010

Clause 7.13.1.3

AMDT
No. 1
AUG
2010

Clause 8.1.2

AMDT
No. 1
AUG
2010

In the second line of the first paragraph, delete Clause 1.5 and replace with Clause 1.3.

In the first line of the first paragraph, correct mutiple to read multiple.
Clause 9.3.2
1

After the sentence beginning subject to the provision .... the reduction within
30 min, which follows Item (b), add the following new sentence:
Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have a
combined capacity of less than 50 000 L.

After the sentence beginning The storage capacity of ... for the reduced tank
capacity, which is immediately before C9.3.2, add the following new sentence:
Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have a
combined capacity of less than 100 000 L.

AMDT
No. 1
AUG
2010

Clause 10.3.2
1

After the sentence beginning subject to the provision .... the reduction within
60 min, which follows Item (b), add the following new sentence:
Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have a
combined capacity of less than 50 000 L.

After the sentence beginning The storage capacity of ... for the reduced tank
capacity, which is immediately before C10.3.2, add the following new sentence:
Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have a
combined capacity of less than 100 000 L.

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010

Clause 11.4.1.1
Delete the first paragraph and replace with the following:
Roof/ceiling sprinklers for process occupancies or categorized commodities shall be
15 mm or 20 mm orifice standard response spray type, extra large orifice (ELO) or control
mode sprinklers defined by K factor (see Clause 1.4.14).
Clause 11.5.5
Third line, delete Clause 5.8.1 and 5.8.3 and replace with Clauses 5.6.1 and 5.6.3.
Table 11.5.12.2
In the headings of the fourth and fifth columns, correct Minium to read Minimum.
Clause 11.5.12.4
Delete the first paragraph and replace with the following:
Where the clearance between roof/ceiling sprinklers and the top of rack storage exceeds
6.1 m and design criteria are not provided within the relevant area/density tables, one of the
following four options shall be applied:
Commentary 11.5.12.5
In the second paragraph of the commentary, delete Clause 5.8 and replace with
Clause 5.6.

AMDT
No. 1
AUG
2010

Figure 11.6.2
Delete the Figure and replace with the following:

Ta b l e n o.

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

BB
s to r a g e

S P, P,S h S
s to r a g e

Cat. 5

11.6. 3 ( D)

Cat. 6

11.6. 3 ( E )

Ca t. 1 to 4

11.6. 3 ( A )

Cat. 5

11.6. 3 ( B)

Cat. 6

11.6. 3 (C)
11.6.4( A )

WS S
Cat. 1

Cat. 2

Cat. 3
H e i g ht
7.6 m
Cat. 4

Cat. 5

Cat. 6
Pa ll e ti s e d
rack
s to r a g e

PS S

11.6.4( B)

SS

11.6.4(C)

WS S

11.6.4( D)

PS S

11.6.4( E )

SS

11.6.4( F )

WS S

11.6.4(G)

PS S

11.6.4( H )

SS

11.6.4( I )

WS S

11.6.4(J )

PS S

11.6.4( K )

SS

11.6.4( L)

WS S

11.6.4( M )

PS S

11.6.4( N )

SS

11.6.4(O)

WS S

11.6.4( P)

PS S

11.6.4(Q)
11.6.4( R)

SS

SRR

Cat.
1 to 5

WS S ,
PS S,S S

DRR

Aisle
1. 2 m
Aisle
1. 2 m
Aisle
1. 2 m
Aisle
1. 2 m

D e pth
2.7 m
D e pth
2.7 m
D e pth
2.7 m
D e pth
2.7 m

MRR
H e i g ht
7.6 m

SRR

Cat. 6

WS S ,
PS S,S S

DRR

MRR

Aisle
1. 2 m
Aisle
1. 2 m
Aisle
1. 2 m

D e pth
2.7 m
D e pth
2.7 m

Fi g u r e n o.

11.6. 5(C)

11.6. 5(C)

11.6. 5( A )

11.6. 5( A )

11.6. 5( D)

11.6. 5( D)

11.6. 5(C)

11.6. 5(C)

11.6. 5( B)

11.6. 5( B)

11.6. 5( D)

11.6. 5( D)

11.6. 5(C)

11.6. 5(C)

11.6. 5( A )

11.6. 5( A )

11.6. 5( F )

11.6. 5( F )

11.6. 5( E )

11.6. 5( E )

11.6. 5( F )

11.6. 5( F )

Aisle
1. 2 m

FIGURE 11.6.2 CATEGORIZED COMMODITIES DESIGN DECISION TREE

AMDT
No. 1
AUG
2010

Table 11.6.3(B)
Delete the Table and replace with the following:
TABLE 11.6.3(B)

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

DESIGN CRITERIACATEGORY 5SOLID PILE,


PALLETIZED AND SHELF STORAGE5
Maximum
storage
up to 4.6 m
height,
m
rDD rDA

Maximum roof/ceiling height


4.7 to 6.1 m 6.2 to 7.6 m

7.7 to 9.1 m

9.2 to 10.7 m

rDD

rDA

rDD

rDA

rDD

rDA

RDD

rDA

10.8 to 12.2 m
rDD

rDA

1.5

8.0

230

12.0

185

12.0

185

18.0

230

24.0

230

Note 2

1.6

8.0

230

12.4

188

12.4

188

18.0

230

24.0

230

Note 2

1.8

8.0

230

13.2

194

13.2

194

18.0

230

24.0

230

Note 2

2.0

8.0

230

14.0

200

14.0

200

18.0

230

24.0

230

Note 2

2.2

8.0

230

14.8

206

14.8

206

18.0

230

24.0

230

Note 2

2.4

8.0

230

15.6

212

15.6

212

18.0

230

24.0

230

Note 2

2.6

8.0

230

16.4

218

16.4

218

18.0

230

24.0

230

Note 2

2.8

8.0

230

17.2

224

17.2

224

18.0

230

24.0

230

Note 2

3.0

8.0

230

18.0

230

18.0

230

18.0

230

24.0

230

Note 2

3.2

12.1

230

18.8

230

18.8

230

18.8

230

24.0

230

Note 2

3.4

16.2

230

19.5

230

19.5

230

19.5

230

24.0

230

Note 2

3.6

20.3

230

20.3

230

20.3

230

20.3

230

24.0

230

Note 2

3.8

n/p

21.0

230

21.0

230

21.0

230

24.0

230

Note 2

4.0

n/p

21.8

230

21.8

230

21.8

230

24.0

230

Note 2

4.2

n/p

22.5

230

22.5

230

22.5

230

24.0

230

Note 2

4.4

n/p

23.3

230

23.3

230

23.3

230

24.0

230

Note 2

4.6

n/p

24.0

230

24.0

230

24.0

230

24.0

230

Note 2

4.8

n/p

24.0

230

24.0

230

24.0

237

Note 2

Note 2

5.0

n/p

24.0

230

24.0

230

24.0

244

Note 2

Note 2

5.2

n/p

24.0

230

24.0

251

Note 2

Note 2

5.4

n/p

24.0

230

24.0

259

Note 2

Note 2

5.6

n/p

24.0

230

24.0

266

Note 2

Note 2

5.8

n/p

24.0

230

24.0

273

Note 2

Note 2

6.0

n/p

24.0

230

24.0

280

Note 2

Note 2

6.1

n/p

24.0

230

24.0

280

Table 11.6.3(B) design constraints


Delete Item (f) and replace with the following:
(f)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.3(B)


Delete Note 2 replace with the following:
2

For excessive clearances, see Clause 11.5.12.4.

AMDT
No. 1
AUG
2010

Table 11.6.3(C)
Delete the Table and replace with the following:
TABLE 11.6.3(C)
DESIGN CRITERIACATEGORY 6
SOLID PILE, PALLETIZED AND SHELF STORAGE 6

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

Maximum roof/ceiling height


Maximum
storage
height,
m

rDD

rDA

rDD rDA

RDD

rDA

rDD

rDA

rDD

rDA

1.50

12.0

186

12.0

186

12.0

186

24.0

280

24.0

465

Note 2

1.60

12.8

188

12.8

192

12.8

192

24.0

280

24.0

465

Note 2

1.80

14.4

191

14.4

205

14.4

205

24.0

280

24.0

465

Note 2

2.00

16.0

194

16.0

217

16.0

217

24.0

280

24.0

465

Note 2

2.20

17.6

197

17.6

230

17.6

230

24.0

280

24.0

465

Note 2

2.40

19.2

200

19.2

242

19.2

242

24.0

280

24.0

465

Note 2

2.60

20.8

204

20.8

255

20.8

255

24.0

280

24.0

465

Note 2

2.80

22.4

207

22.4

267

22.4

267

24.0

280

24.0

465

Note 2

3.00

24.0

210

24.0

280

24.0

280

24.0

280

24.0

465

Note 2

3.20

24.0

242

24.0

289

24.0

303

24.0

303

24.0

465

Note 2

3.40

24.0

274

24.0

298

24.0

326

24.0

326

24.0

465

Note 2

3.60

24.0

306

24.0

306

24.0

349

24.0

349

24.0

465

Note 2

up to 4.6 m

4.7 to
6.1 m

6.2 to 7.6 m

7.7 to 9.1 m

9.2 to 10.7 m

10.8 to 12.2 m
rDD

rDA

3.80

n/p

24.0

315

24.0

373

24.0

373

24.0

465

Note 2

4.00

n/p

24.0

324

24.0

396

24.0

396

24.0

465

Note 2

4.20

n/p

24.0

333

24.0

419

24.0

419

24.0

465

Note 2

4.40

n/p

24.0

341

24.0

442

24.0

442

24.0

465

Note 2

4.60

n/p

24.0

350

24.0

465

24.0

465

24.0

465

Note 2

Table 11.6.3(C) design constraints


Delete Item (f) and replace with the following:
(f)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.3(C)


Delete Note 2 replace with the following:
2

For excessive clearances, see Clause 11.5.12.4.

AMDT
No. 1
AUG
2010

Table 11.6.3(D)
Delete the Table and replace with the following:
TABLE 11.6.3(D)

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

DESIGN CRITERIACATEGORY 5BIN BOX STORAGE


Maximum
Maximum roof/ceiling height
storage
up to 4.6 m. 4.7 to 6.1 m. 6.2 to 7.6 m. 7.7 to 9.1 m.
9.2 to 10.7 m.
height,
m
rDD rDA rDD rDA rDD rDA rDD
rDA
rDD
rDA

10.8 to 12.2 m.
rDD

rDA

1.50

8.0

230

12.0

185

12.0

185

12.0

230

18.0

230

24.0

230

1.60

8.0

230

12.0

188

12.0

188

12.0

230

18.0

230

24.0

230

1.80

8.0

230

12.0

194

12.0

194

12.0

230

18.0

230

24.0

230

2.00

8.0

230

12.0

200

12.0

200

12.0

230

18.0

230

24.0

230

2.20

8.0

230

12.0

206

12.0

206

12.0

230

18.0

230

24.0

230

2.40

8.0

230

12.0

212

12.0

212

12.0

230

18.0

230

24.0

230

2.60

8.0

230

12.0

218

12.0

218

12.0

230

18.0

230

24.0

230

2.80

8.0

230

12.0

224

12.0

224

12.0

230

18.0

230

24.0

230

3.00

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

3.20

13.4

230

12.8

230

12.8

230

12.8

230

18.0

230

24.0

230

3.40

18.9

230

13.5

230

13.5

230

13.5

230

18.0

230

24.0

230

3.60

14.3

230

14.3

230

14.3

230

14.3

230

18.0

230

24.0

230

3.80

n/p

15.0

230

15.0

230

15.0

230

18.0

230

24.0

230

4.00

n/p

15.8

230

15.8

230

15.8

230

18.0

230

24.0

230

4.20

n/p

16.5

230

16.5

230

16.5

230

18.0

230

24.0

230

4.40

n/p

17.3

230

17.3

230

17.3

230

18.0

230

24.0

230

4.60

n/p

18.0

230

18.0

230

18.0

230

18.0

230

24.0

230

4.80

n/p

18.0

230

18.0

230

18.9

230

18.9

230

24.0

230

5.00

n/p

18.0

230

18.0

230

19.7

230

19.7

230

24.0

230

5.20

n/p

18.0

230

20.6

230

20.6

230

24.0

230

5.40

n/p

18.0

230

21.4

230

21.4

230

24.0

230

5.60

n/p

18.0

230

22.3

230

22.3

230

24.0

230

5.80

n/p

18.0

230

23.1

230

23.1

230

24.0

230

6.00

n/p

18.0

230

24.0

230

24.0

230

24.0

230

6.20

n/p

20.0

230

24.0

230

n/p

6.40

n/p

22.0

230

24.0

230

n/p

6.60

n/p

24.0

230

24.0

230

n/p

6.80

n/p

24.0

230

n/p

7.00

n/p

24.0

230

n/p

7.20

n/p

24.0

230

n/p

7.40

n/p

24.0

230

n/p

7.60

n/p

24.0

230

n/p

Table 11.6.3(D) design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.3(D)


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

For excessive clearances, see Clause 11.5.12.4.

AMDT
No. 1
AUG
2010

Table 11.6.3(E)
Delete the Table and replace with the following:
TABLE 11.6.3(E)

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

DESIGN CRITERIACATEGORY 6BIN BOX STORAGE


Max.
storage
up to 4.6 m
height,
m
rDD rDA

Maximum roof/ceiling height


4.7 to 6.1 m

6.2 to 7.6 m

7.7 to 9.1 m

9.2 to 10.7 m

10.8 to 12.2 m

rDD

rDA

RDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

1.50

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

1.60

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

1.80

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

2.00

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

2.20

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

2.40

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

2.60

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

2.80

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

3.00

8.0

230

12.0

230

12.0

230

12.0

230

18.0

230

24.0

230

3.20

12.5

229

12.8

230

12.8

230

12.8

230

18.0

230

24.0

230

3.40

13.0

223

13.5

230

13.5

230

13.5

230

18.0

230

24.0

230

3.60

14.0

217

14.3

230

14.3

230

14.3

230

18.0

230

24.0

230

3.80

n/p

15.0

230

15.0

230

15.0

230

18.0

230

24.0

230

4.00

n/p

15.8

230

15.8

230

15.8

230

18.0

230

24.0

230

4.20

n/p

16.5

230

16.5

230

16.5

230

18.0

230

24.0

230

4.40

n/p

17.3

230

17.3

230

17.3

230

18.0

230

24.0

230

4.60

n/p

18.0

230

18.0

230

18.0

230

18.0

230

24.0

230

4.80

n/p

18.0

230

18.0

230

18.9

230

18.9

230

24.0

230

5.00

n/p

18.0

230

18.0

230

19.7

230

19.7

230

24.0

230

5.20

n/p

18.0

230

20.6

230

20.6

230

24.0

230

5.40

n/p

18.0

230

21.4

230

21.4

230

24.0

230

5.60

n/p

18.0

230

22.3

230

22.3

230

24.0

230

5.80

n/p

18.0

230

23.1

230

23.1

230

24.0

230

6.00

n/p

18.0

230

24.0

230

24.0

230

24.0

230

6.20

n/p

24.0

230

24.0

230

n/p

6.40

n/p

24.0

230

24.0

230

n/p

6.60

n/p

24.0

230

24.0

230

n/p

6.80

n/p

24.0

230

n/p

7.00

n/p

24.0

230

n/p

7.20

n/p

24.0

230

n/p

7.40

n/p

24.0

230

n/p

7.60

n/p

24.0

230

n/p

Table 11.6.3(E) design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.3(E)


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(M)
Delete the Table and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

TABLE 11.6.4(M)
DESIGN CRITERIACATEGORY 5RACK STORAGE HEIGHT UP TO 7.6 m, WITHOUT SOLID SHELVES
Maximum roof/ceiling height

Max.
storage
height,
m

up to
4.6

4.7 to 6.1 m

6.2 to 7.6 m

7.7 to 9.1 m

9.2 to 10.7 m

10.8 to 12.2 m

12.3 to 13.7 m

IRS
levels

IRS levels

IRS levels

IRS levels

IRS levels

IRS levels

IRS levels

rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD

2
rDA

rDD

1
rDA

rDD

2
rDA

rDD

1
rDA

rDD rDA

18

rDD

185

rDA

3.1

12.0 185 18.0 185 12.0 185

n/r

18.0 185 12.0 185

n/r

18.0 185 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

3.2

13.2 185 18.0 185 12.0 185

n/r

18.4 188 12.0 185

n/r

18.4 188 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

n/p

12.0

n/r
185

3.4

15.6 185 18.0 185 12.0 185

n/r

19.2 194 12.0 185

n/r

19.2 194 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

n/p

12.0

185

3.6

18.0 185 18.0 185 12.0 185

n/r

20.0 200 12.0 185

n/r

20.0 200 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

n/p

12.0

185

3.8

n/p

18.0 185 12.0 185

n/r

20.8 206 12.0 185

n/r

20.8 206 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185

12.0 185

n/p

12.0

185

4.0

n/p

18.0 185 12.0 185

n/r

21.6 212 12.0 185

n/r

21.6 212 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

n/p

12.0

185

4.2

n/p

18.0 185 12.0 185

n/r

22.4 218 12.0 185

n/r

22.4 218 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

n/p

12.0

185

4.4

n/p

18.0 185 12.0 185

n/r

23.2 224 12.0 185

n/r

23.2 224 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

n/p

12.0

185

4.6

n/p

18.0 185 12.0 185

n/r

24.0 230 12.0 185

n/r

24.0 230 12.0 185

n/r

24.0 230 12.0 185

n/r

18.0 185 12.0 185

n/p

12.0

185

4.8

n/p

n/p n/p n/p 185 12.0 185 24.0 230 12.9 185 12.0 185

n/p

12.9 185 12.0 185

n/p

12.9 185 12.0 185 18.0 185 12.0 185

n/p

12.0

185

5.0

n/p

n/p n/p n/p 185 12.0 185 24.0 230 13.7 185 12.0 185

n/p

13.7 185 12.0 185

n/p

13.7 185 12.0 185 18.0 185 12.0 185

n/p

12.0

185

5.2

n/p

24.0 230 14.6 185 12.0 185

n/p

14.6 185 12.0 185

n/p

14.6 185 12.0 185 18.0 185 12.0 185

n/p

12.0

185

5.4

n/p

24.0 230 15.4 185 12.0 185

n/p

15.4 185 12.0 185

n/p

15.4 185 12.0 185 18.0 185 12.0 185

n/p

12.0

185

5.6

n/p

24.0 230 16.3 185 12.0 185

n/p

16.3 185 12.0 185

n/p

16.3 185 12.0 185 18.0 185 12.0 185

n/p

12.0

185

5.8

n/p

24.0 230 17.1 185 12.0 185

n/p

17.1 185 12.0 185

n/p

17.1 185 12.0 185 18.0 185 12.0 185

n/p

12.0

185

6.0

n/p

24.0 230 18.0 185 12.0 185

n/p

18.0 185 12.0 185

n/p

18.0 185 12.0 185 18.0 185 12.0 185

n/p

12.0

185

6.2

n/p

n/p

18.8 179 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

6.4

n/p

n/p

19.5 174 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

6.6

n/p

20.3 168 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

6.8

n/p

n/p

21.0 163 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

7.0

n/p

21.8 157 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

7.2

n/p

22.5 151 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

7.4

n/p

23.3 146 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

7.6

n/p

24.0 140 12.0 185

n/p

12.0 185

n/p

12.0 185

n/p

12.0

185

Table 11.6.4(M) design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(M)


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(N)
Delete the Table and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

TABLE 11.6.4(N)
DESIGN CRITERIACATEGORY 5RACK STORAGE HEIGHT UP TO 7.6 m, SOLID SHELVES 1.9 TO 5.9 m 2
Maximum roof/ceiling height
Max.
up to 4.6
storage
height, IRS levels
m
0

4.7 to 6.1 m

6.2 to 7.6 m

IRS levels
0

IRS levels

2
rDA

7.7 to 9.1 m

IRS levels

1
rDA

IRS levels

rDD rDA rDD rDA rDD RDA rDD

10.8 to 12.2 m

12.3 to 13.7 m

IRS levels

IRS levels
2

rDD

rDA rDD rDA rDD

rDD

rDA

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

3.1

12.0

185 18.0 185 12.0 185

18.0 185 12.0 185

18.0 185 12.0

185

24.0

230

12.0

185

18.0

185

18.0

185

3.2

13.2

185 18.0 185 12.0 185

18.4 188 12.0 185

18.4 188 12.0

185

24.0

230

12.0

185

18.0

185

12

185

3.4

15.6

185 18.0 185 12.0 185

19.2 194 12.0 185

19.2 194 12.0

185

24.0

230

12.0

185

18.0

185

12

185

3.6

18.0

185 18.0 185 12.0 185

20.0 200 12.0 185

20.0 200 12.0

185

24.0

230

12.0

185

18.0

185

12

185

20.8 206 12.0

185

24.0

230

12.0

185

18.0

185

3.8

n/p

18.0 185 12.0 185

4.0

n/p

18.0 185 12.0 185

21.6 212 12.0 185

21.6 212 12.0

185

24.0

230

12.0

185

18.0

185

4.2

n/p

18.0 185 12.0 185

22.4 218 12.0 185

22.4 218 12.0

185

24.0

230

12.0

185

18.0

185

4.4

n/p

18.0 185 12.0 185

23.2 224 12.0 185

23.2 224 12.0

185

24.0

230

12.0

185

18.0

185

4.6

n/p

18.0 185 12.0 185

24.0 230 12.0 185

24.00 230 12.0

24.0

4.8

n/p

5.0

n/p

n/r

rDD

9.2 to 10.7 m

20.8 206 12.0 185

18.0 185

n/p

18.0 185

n/p

n/r

12.9 185 12.0 185

n/p

12.9

n/r

185

185

12.0

185

230
n/p

n/r

n/r

n/p

12.0

185

18.0

185

12.0

185

12.9

185

12.0

185

18.0

185

12.0

185

12

185

12

185

12

185

12

185

12

185

12

185

n/p

13.7 185 12.0 185

n/p

13.7

185

12.0

185

n/p

13.7

185

12.0

185

18.0

185

12.0

185

12

185

5.2

n/p

14.6 185 12.0 185

n/p

14.6

185

12.0

185

n/p

14.6

185

12.0

185

18.0

185

12.0

185

12

185

5.4

n/p

15.4 185 12.0 185

n/p

15.4

185

12.0

185

n/p

15.4

185

12.0

185

18.0

185

12.0

185

12

185

5.6

n/p

16.3 185 12.0 185

n/p

16.3

185

12.0

185

n/p

16.3

185

12.0

185

18.0

185

12.0

185

12

185

5.8

n/p

17.1 185 12.0 185

n/p

17.1

185

12.0

185

n/p

17.1

185

12.0

185

18.0

185

12.0

185

6.0

n/p

18.0 185 12.0 185

n/p

18.0

185

n/p

18.0

185

18.0

12.0

185

12.0

185

12.0

185

6.2

n/p

12.0 185

n/p

12.0

185

n/p

12.0

185

n/p

185

12.0

185

6.4

n/p

12.0 185

n/p

12.0

185

n/p

12.0

185

n/p

12.0

185

6.6

n/p

12.0 185

n/p

12.0

185

n/p

12.0

185

n/p

12.0

185

12.0

185

12.0

185

12.0

185

12.0

185

n/p

6.8

n/p

12.0

185

n/p

12.0

185

n/p

12.0

185

12.0

185

7.0

n/p

12.0

185

n/p

12.0

185

n/p

12.0

185

12.0

185

7.2

n/p

12.0

185

n/p

12.0

185

n/p

12.0

185

12.0

185

7.4

n/p

12.0

185

n/p

12.0

185

n/p

12.0

185

12.0

185

7.6

n/p

12.0

185

n/p

12.0

185

n/p

12.0

185

12.0

185

n/p

Table 11.6.4(N) design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(N)


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(O)
Delete the Table and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

TABLE 11.6.4(O)
DESIGN CRITERIACATEGORY 5RACK STORAGE HEIGHT UP TO 7.6 m,
SOLID SHELVES GREATER THAN 5.9 m2
Maximum roof/ceiling height
Max.
storage
height,
m

7.6

4.7 to 6.1 m

6.2 to 7.6 m

7.7 to 9.1 m

9.2 to 10.7 m

10.8 to
12.2 m

12.3 to 13.7 m

IRS levels

IRS levels

IRS levels

IRS levels

IRS levels

IRS levels

IRS levels

ET

ET

1
rDD

3.1

up to 4.6

ET
rDA

12.0 185

rDD

rDA

n/r

1
rDD

ET
rDA

12.0 185

rDD

rDA

n/r
n/p

1
rDD

ET
rDA

12.0 185

rDD

rDA

n/r

1
rDD

ET
rDA

12.0 185

rDD

rDA

rDD

rDA

rDD

12.0

185

18.0 185

12.0 185 12.0

185

12.0 185 12.0

n/r

rDA

rDD

rDA

18

185
185

Table 11.6.4(O) design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(O)


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(P) Part A


Delete the Table and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

TABLE 11.6.4(P)PART A
DESIGN CRITERIACATEGORY 6RACK STORAGE HEIGHT UP TO 7.6 m, WITHOUT
SOLID SHELVES MAXIMUM ROOF/CEILING HEIGHT UP TO 9.1 m
Maximum roof/ceiling height
Max.
storage
height,
m
3.1

up to 7.6 m

7.7 to 9.1 m

IRS levels

IRS levels

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

24.0

280

12.0

185

24.0

280

12.0

185

3.2

n/p

12.4

185

12.4

185

3.4

n/p

13.2

185

13.2

185

3.6

n/p

14.0

185

n/p

14.0

185

3.8

n/p

14.8

185

14.8

185

4.0

n/p

15.6

185

15.6

185

4.2

n/p

16.4

185

16.4

185

n/r

n/r

n/r

n/r

n/r

n/r

4.4

n/p

17.2

185

17.2

185

4.6

n/p

18.0

185

12.0

185

18.0

185

12.0

185

4.8

n/p

18.9

185

185

18.9

185

12.9

185

5.0

n/p

19.7

185

185

5.2

n/p

20.6

185

185

5.4

n/p

21.4

185

185

5.6

n/p

22.3

185

185

5.8

n/p

23.1

185

6.0

n/p

24.0

185

n/r

19.7

185

13.7

185

n/p

20.6

185

14.6

185

21.4

185

15.4

185

22.3

185

16.3

185

n/r

n/r

n/r

185

23.1

185

17.1

185

18.0

185

24.0

185

18.0

185

6.2

n/p

24.0

185

18.0

185

n/p

18.8

185

6.4

n/p

24.0

185

18.0

185

n/p

19.5

185

6.6

n/p

24.0

185

18.0

185

n/p

20.3

185

6.8

n/p

21.0

185

7.0

n/p

21.8

185

7.2

n/p

22.5

185

7.4

n/p

23.3

185

7.6

n/p

24.0

185

18.0

185

12.0

185

Table 11.6.4(P) Part A design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(P) Part A


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(P) Part B


Delete the Table and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

TABLE 11.6.4(P)PART B
DESIGN CRITERIACATEGORY 6RACK STORAGE HEIGHT UP TO 7.6 m, WITHOUT SOLID SHELVES
MAXIMUM ROOF/CEILING HEIGHT FROM 9.2 m UP TO 13.7 m
Maximum roof/ceiling height
Max.
storage
height,
m

9.2 to 10.7 m

10.8 to 12.2 m

IRS levels
1

12.3 to 13.7 m

IRS levels

ET

ET

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

185

24.0 185

3.2

18.0

185

24.0 185

24.0

185

18.0

185

12.0

185

3.4

18.0

185

24.0 185

24.0

185

18.0

185

12.0

185

3.6

18.0

185

24.0

185

18.0

185

12.0

185

3.8

18.0

185

24.0 185

4.0

18.0

185

24.0 185

4.2

18.0

185

24.0 185

4.4

18.0

185

24.0 185

4.6

18.0

185

12.0

185

24.0 185

18.0

185

4.8

18.9

185

12.9

185

5.0

19.7

185

13.7

185

5.2

20.6

185

14.6

185

5.4

21.4

185

15.4

185

5.6

22.3

185

16.3

185

5.8

23.1

185

17.1

185

6.0

24.0

185

n/r

n/r

n/r

rDA

rDD

ET

rDA

24.0 185

rDD

rDD

n/r

rDA rDD rDA

18.0

n/r

rDA

3.1

n/r

rDD

IRS levels

Note 2

rDA

rDD

Note 2

rDA

Note 2

24.0

185

18.0

185

12.0

185

24.0

185

18.0

185

12.0

185

24.0

185

18.0

185

12.0

185

24.0

185

18.0

185

12.0

185

24.0

185

18.0

185

12.0

185

24.0 185

18.0

185

24.0

185

18.0

185

12.0

185

24.0 185

18.0

185

24.0

185

18.0

185

12.0

185

24.0 185

18.0

185

24.0

185

18.0

185

12.0

185

24.0 185

18.0

185

24.0

185

18.0

185

12.0

185

24.0 185

18.0

185

24.0

185

18.0

185

12.0

185

24.0 185

18.0

185

24.0

185

18.0

185

12.0

185

n/r

n/r

n/r

n/r

18.0

185

12.0

185

24.0 185

18.0

185

12.0

185

24.0

185

18.0

185

12.0

185

6.2

n/p

18.8

185

12.8

185

n/p

18.8

185

12.8

185

24.0

185

18.0

185

12.0

185

6.4

n/p

19.5

185

13.5

185

n/p

19.5

185

13.5

185

24.0

185

18.0

185

12.0

185

6.6

n/p

20.3

185

14.3

185

6.8

n/p

21.0

185

15.0

185

7.0

n/p

22.5

185

15.8

185

7.2

n/p

23.3

185

16.5

185

7.4

n/p

24.0

185

17.3

185

7.6

n/p

24.0

185

18.0

185

n/p

20.3

185

14.3

185

24.0

185

18.0

185

12.0

185

n/p

21.0

185

15.0

185

24.0

185

18.0

185

12.0

185

n/p

22.5

185

15.8

185

24.0

185

18.0

185

12.0

185

n/p

23.3

185

16.5

185

24.0

185

18.0

185

12.0

185

n/p

24.0

185

17.3

185

24.0

185

18.0

185

12.0

185

12.0

185

n/p

24.0

185

18.0

185 12.0 185

24.0

185

18.0

185

12.0

185

Table 11.6.4(P) Part B design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(P) Part B


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(Q) Part A


Delete the Table and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

TABLE 11.6.4(Q)PART A
DESIGN CRITERIACATEGORY 6RACK STORAGE HEIGHT UP TO 7.6 m, SOLID SHELVES 1.9 TO 5.9 m 2
Maximum roof/ceiling height
Max.
storage
height,
m

3.1

7.7 to 9.1 m

9.2 to 10.7 m

IRS levels

IRS levels

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

24.0

280

12.0

185

rDD

1
rDA

rDD

rDA

rDD

rDA

rDD

rDA

rDD

rDA

18.0

185

3.2

12.8

185

18.0

185

3.4

13.5

185

18.0

185

3.6

14.3

185

n/r

18.0

185

3.8

15.0

185

18.0

185

4.0

15.8

185

18.0

185

4.2

16.5

185

18.0

185

4.4

17.3

185

18.0

185

4.6

n/p

18.0

185

12.0

185

18.0

185

12.0

185

4.8

18.9

185

12.9

185

18.9

185

12.9

185

5.0

19.7

185

13.7

185

19.7

185

13.7

185

5.2

20.6

185

14.6

185

20.6

185

14.6

185

5.4

21.4

185

15.4

185

21.4

185

15.4

185

5.6

22.3

185

16.3

185

22.3

185

16.3

185

5.8

23.1

185

17.1

185

23.1

185

17.1

185

6.0

24.0

185

24.0

185

n/r

n/r

n/r

n/r

n/r

18.0

185

n/r

18.0

185

12.0

185

n/r

6.2

18.4

185

18.8

18.8

185

12.8

185

6.4

19.2

185

19.5

19.5

185

13.5

185

6.6

20.0

185

20.3

20.3

185

14.3

185

6.8

n/p

20.8

185

21.0

n/p

21.0

185

15.0

185

7.0

21.6

185

21.8

21.8

185

15.8

185

7.2

22.4

185

22.5

22.5

185

16.5

185

7.4

23.3

185

24.0

23.3

185

17.3

185

7.6

24.0

185

24.0

185

24.0

185

18.0

185

Table 11.6.4(Q) Part A design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(Q) Part A


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(Q) Part B


Delete the Table and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

TABLE 11.6.4(Q)PART B
DESIGN CRITERIACATEGORY 6RACK STORAGE HEIGHT UP TO 7.6 m, SOLID SHELVES 1.9 TO 5.9 m 2
Maximum roof/ceiling height
Max.
storage
height,
m

10.8 to 12.2 m

12.3 to 13.7 m

IRS levels

IRS levels

rDA

rDD

rDA

rDD

rDA

3.1

24.0

185

3.2

24.0

185

24.0

185

18.0

185

12.0

185

3.4

24.0

185

24.0

185

18.0

185

12.0

185

3.6

24.0

185

24.0

185

18.0

185

12.0

185

3.8

24.0

185

24.0

185

18.0

185

12.0

185

4.0

24.0

185

24.0

185

18.0

185

12.0

185

4.2

24.0

185

24.0

185

18.0

185

12.0

185

4.4

24.0

185

24.0

185

18.0

185

12.0

185

4.6

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

4.8

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

5.0

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

5.2

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

5.4

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

5.6

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

5.8

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

6.0

24.0

185

n/r

rDA

rDD

ET

rDD

n/r

rDD

Note 2

rDA

rDD

Note 2

rDA
Note 2

18.0

185

12.0

185

24.0

185

18.0

185

12.0

185

6.2

18.8

185

12.8

185

24.0

185

18.0

185

12.0

185

6.4

19.5

185

13.5

185

24.0

185

18.0

185

12.0

185

6.6

20.3

185

14.3

185

24.0

185

18.0

185

12.0

185

6.8

n/p

21.0

185

15.0

185

24.0

185

18.0

185

12.0

185

7.0

21.8

185

15.8

185

24.0

185

18.0

185

12.0

185

7.2

22.5

185

16.5

185

24.0

185

18.0

185

12.0

185

7.4

23.3

185

17.3

185

24.0

185

18.0

185

12.0

185

7.6

24.0

185

18.0

185

24.0

185

18.0

185

12.0

185

Table 11.6.4(Q) Part B design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(Q) Part B


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

2
AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Table 11.6.4(R)
Delete the Table and replace with the following:
TABLE 11.6.4(R)
DESIGN CRITERIACATEGORY 6RACK STORAGE HEIGHT
UP TO 7.6 m, SOLID SHELVES GREATER THAN 5.9 m 2
Maximum roof/ceiling height
Max.
storage
height,
m

up to 9.1 m

9.2 to 10.7 m

10.8 to 12.2 m

12.3 to 13.7 m

IRS levels

IRS levels

IRS levels

IRS levels

ET

ET

ET

ET

rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD
3.1

12.0

185

n/r

18.0

185

n/r

24.0

185

n/r

rDA

Note 2

3.2

12

185

12.0

185

18.0

185

24.0

185

3.4

12

185

12.0

185

18.0

185

24.0

185

3.6

12

185

12.0

185

18.0

185

24.0

185

3.8

n/p

12

185

n/p

12.0

185

n/p

18.0

185

24.0

185

4.0

12

185

12.0

185

18.0

185

24.0

185

4.2

12

185

12.0

185

18.0

185

24.0

185

4.4

12

185

12.0

185

18.0

185

24.0

185

4.6

12

185

12.0

185

18.0

185

24.0

185

4.8

12

185

12.0

185

18.0

185

23.1

185

5.0

n/p

12

185

n/p

12.0

185

n/p

18.0

185

22.3

185

5.2

12

185

12.0

185

18.0

185

21.4

185

5.4

12

185

12.0

185

18.0

185

20.6

185

5.6

12

185

12.0

185

18.0

185

19.7

185

5.8

12

185

12.0

185

18.0

185

18.9

185

6.0

n/p

12

185

n/p

12.0

185

n/p

18.0

185

18.0

185

6.2

12

185

12.0

185

17.3

185

17.3

185

6.4

12

185

12.0

185

16.5

185

16.5

185

6.6

12

185

12.0

185

15.8

185

15.8

185

6.8

12

185

12.0

185

15.0

185

15.0

185

7.0

12

185

12.0

185

14.3

185

14.3

185

7.2

n/p

12

185

n/p

12.0

185

n/p

13.5

185

13.5

185

7.4

12

185

12.0

185

12.8

185

12.8

185

7.6

12

185

12.0

185

12.0

185

12.0

185

Table 11.6.4(R) design constraints


Delete Item (e) and replace with the following:
(e)

Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).

NOTES to Table 11.6.4(R)


Delete Note 2 replace with the following:
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

AMDT
No. 1
AUG
2010

For excessive clearances, see Clause 11.5.12.4.

Clause 11.7.5.1
Style the two separate NOTES as follows:
NOTES:
1

Consideration should also be given to the use of large drop sprinklers. Factory Mutual Loss
Prevention Data 8-18 provides design and installation requirements for Large Drop sprinklers
protecting hanging garment storage.

A brief description of each of the terms used throughout the requirements for hanging
garments storage can be found in Clause 11.2.

AMDT
No. 1
AUG
2010

Figure 11.7.5.7(A)

AMDT
No. 1
AUG
2010

Clause 11.7.6.3

AMDT
No. 1
AUG
2010

Clause 11.7.8.5

AMDT
No. 1
AUG
2010

Clause 11.7.8.9

AMDT
No. 1
AUG
2010

In the caption, correct ERTICAL to read VERTICAL.

Delete the NOTE to Item (c) and replace with the following:
NOTE: Vertical barriers in racks should not be considered as a substitute for in-rack sprinklers.
The racking shown in Figure 11.7.6.4(A) assumes solid shelving with a minimum 100 mm
transverse flues at rack uprights.

In the NOTES to Item (b), delete the second word NOTES:

Delete the second paragraph and replace with the following:


Level 2 and Level 3 aerosols, subject to the design prerequisites of Appendix F, shall be
protected in accordance with the requirements of Table 11.7.8.14.
Clause 11.8.3
Insert the following after the first paragraph (including Notes):
Where pumps drawing directly from a town main supply are not permitted by the water
supply authority, pump suction tanks may take the form of break tanks the capacity of
which shall be not less than one third of the quantity (V min ) or 30 000 L, whichever is the
greater. Break tanks shall incorporate the following inflow arrangements:
(a)

Inflow shall be via two automatic mechanical float valves and one manually operated
valve, each sized to deliver not less than the maximum system demand (Q max ).

(b)

Inflow piping shall incorporate means for flow measurement.

(c)

Unless a lesser dimension is acceptable to the relevant authority, the outlet of any
inflow piping shall be not less than 3.0 m horizontally from suction piping inlets.

(d)

Inflow arrangements shall be accessible for inspection.

AMDT
No. 1
AUG
2010

Clause 12.10
Delete the equation and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

P = 6.05
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010

Q1.85
102
C1.85 d 4.87

Table 12.10(C)
In the headings of second and fourth columns, place parentheses around the word internal.
Appendix A, Paragraph A4.1
Delete the title and first paragraph and replace with the following:
A4.1 High Hazard Process occupancies
The following shall be classified as High Hazard Process Occupancies:

AMDT
No. 1
AUG
2010

AMDT
No. 1
AUG
2010

Appendix A, Paragraph A4.2


Delete the title replace with the following:
A4.2.1 High Hazard Storage occupancies
Appendix A, Paragraph A4.2.1
Delete the first paragraph replace with the following:
The sprinkler protection of storage occupancies shall take into consideration the method of
storage, the hazardous nature of the materials being stored and the height of the storage.

AMDT
No. 1
AUG
2010

Appendix A, Paragraph A4.2.4


1

Delete the title and text and replace with the following:
A4.2.4 Categories of High Hazard storage
High Hazard storage occupancies shall be classified as follows:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

(a)

High HazardStorage occupanciesCategory 1


Category 1 commodities include non-combustible products stored on wood
pallets, or within single layer cardboard cartons.

(b)

High HazardStorage occupanciesCategory 2


Category 2 commodities include Category 1 products stored in wooden crates
and boxes, or within multiple thickness cardboard cartons on wood pallets.

(c)

High HazardStorage occupanciesCategory 3

Category 3 commodities generally include paper or food products.


(d)

High HazardStorage occupancies Category 4


Category 4 goods would include Category 1, 2 and 3 goods containing in them,
or in their packaging, no more than 25% by volume of expanded (foamed)
plastic or polyurethane, or 15% by weight of unexpanded plastics or
polyurethane.

(e)

High HazardStorage occupanciesCategory 5


Category 5 goods include cartoned or uncartoned unexpanded plastics and
cartoned expanded plastics.

(f)

High HazardStorage occupanciesCategory 6


Category 6 goods include uncartoned expanded plastics.

Add a second Note as follows:


2

AMDT
No. 1
AUG
2010

Foamed or cellular (expanded) plastics are those in which the density is reduced by the
presence of numerous small cells throughout their mass.

Appendix D, Figure D1(b)


Delete the figure and replace with the following:

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

Fu l l c a p a c i t y t a n k

( b) Pu m p s u c ti o n t a nk a s d u a l s u p p l y
AMDT
No. 1
AUG
2010

Appendix D, Figure D2
1

Delete (b) from sub-caption and replace with (a).

Delete (c) from sub-caption and replace with (b).

AMDT
No. 1
AUG
2010

Appendix D, Figure D3

AMDT
No. 1
AUG
2010

Appendix E, Paragraph E5

Delete the entire sub-caption (c)

In Example 1, Item (i), renumber (A) and (B) to read (i) and (ii) respectively.

Appendix E, Figure E6(C)


Delete the Figure and replace with the following:

PR ES SU R E

Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on network prohibited.

AMDT
No. 1
AUG
2010

13 0 0
1250
120 0
1150
110 0
10 50
10 0 0
9 50
900
8 50
800
750
70 0
6 50
600
550
50 0
4 50
400
350
300
250
20 0
150
10 0
50

50 k Pa m a r g i n

Max.
f l ow r ate
of th e
sys te m

G
J

F
H

0 1 2

7
FLOW

8
N 1. 8 5

10

x 50 0

L EG EN D:
F = Mi ni m u m tow n s m a i n 1 s u p p l y at p u m p
G = M a x i m u m tow n s m a i n 2 s u p p l y at p u m p
H = Pu m p c h a r a c te r i s ti c c u r ve
J = Mi ni m u m c o m b i n e d s u p p l y (tow n s m a i n 1 a n d p u m p)
K = M a x i m u m c o m b i n e d wate r s u p p l y (tow n s m a i n 2 a n d p u m p)
L = D e m a n d c u r ve fo r m o s t u nfavo u r a b l e d e s i g n a r e a
M = D e m a n d c u r ve fo r m o s t favo u r a b l e d e s i g n a r e a

FIGURE E6(C) WORKED EXAMPLESDETERMINATION OF


MAXIMUM FLOW RATES

AMDT
No. 1
AUG
2010

Appendix F, Table F1.3(B)

AMDT
No. 1
AUG
2010

Appendix F, Table F1.3(B)

Row beginning 67-56-1, last column, remove the space between 1 and 9.

Number Notes from 1 to 7 respectively.