Part Number

Application

Wiring Diagram

4-port Junction Tee

JRBS-40-4/EX

Four cage clamp device ports


Approval: ATEX II 2 G EEx ib IIC/IIB T4

4-port Junction Tee

JRBS-40SC-4/EX

Four cage clamp device ports

Approval: ATEX II 2 G EEx ib IIC/IIB T4

Short-circuit protection: adjustable 30, 35, 45, 60 mA


Open circuit voltage: 32 V
Current consumption: 7 mA
LED indicators
Power: Green = On
Short-circuit: Red = On

6-port Junction Tee

JRBS-40-6/EX

Six cage clamp device ports


Approval: ATEX II 2 G EEx ib IIC/IIB T4

6-port Junction Tee

JRBS-40SC-6/EX

Six cage clamp device ports

Approval: ATEX II 2 G EEx ib IIC/IIB T4

Short-circuit protection: adjustable 30, 35, 45, 60 mA


Open circuit voltage: 32 V
Current consumption: 7 mA
LED indicators
Power: Green = On
Short-circuit: Red = On

8-port Junction Tee

JRBS-40-8/EX

Eight cage clamp device ports


Approval: ATEX II 2 G EEx ib IIC/IIB T4

8-port Junction Tee

JRBS-40SC-8/EX

Eight cage clamp device ports

Approval: ATEX II 2 G EEx ib IIC/IIB T4

Short-circuit protection: adjustable 30, 35, 45, 60 mA


Open circuit voltage: 32 V
Current consumption: 7 mA
LED indicators
Power: Green = On
Short-circuit: Red = On

R25
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Aluminum
PA (Nylon)
Gold Plated CuZn
NEMA 1 and IP 20
250 V
4A
-25 to +70C (-13 to +158F)

Dimensions
4 Channel

FOUNDATION fieldbus

6 Channel

8 Channel

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R26
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, Junction Box for Din Rail Mounting
IP 20 DIN Rail Mounted Junctions
8 Channel

Part Number

Application

Wiring Diagram

8-port Junction Tee

JRBS-49SC-8

Eight cage clamp device ports

Switchable terminating resistor

55 mA Short-circuit protected
Open circuit voltage: 33 V
Current consumption: 15 mA
LED indicators
Power: Green = On
Comm: Green = Data transfer
Short-circuit: Red = On

R27
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Contact Carrier:
Contacts:
Protection:
Connection Mode:
Ambient Temperature:

Aluminum
PA (Nylon)
Gold Plated CuZn
NEMA 1 and IP 20
Snap-on DIN RAIL (DIN 50022)
-25 to +70C (-13 to +158F)

Dimensions

FOUNDATION fieldbus

8 Channel

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R28
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Application

Wiring Diagrams

4-port Junction

JBBS-49-M413
JBBS-49-M414

No short-circuit protection

Bus in/bus out connections


(7/8-16UN) minifast

Four (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

6-port Junction

JBBS-49-M613
JBBS-49-M614

No short-circuit protection

Bus in/bus out connections


(7/8-16UN) minifast

Six (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

8-port Junction

JBBS-49-M813
JBBS-49-M814

No short-circuit protection

Bus in/bus out connections


(7/8-16UN) minifast

Eight (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

R29
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Anodized Aluminum
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40 to +75C (-22 to +167F)

Dimensions
6-Port

4-Port

Pinouts
minifast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R30
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

8-Port

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Electrical

JBBS-49SC-M413

Short-circuit protection: 55 mA (Isc)

Current consumption: <60 mA

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Electrical

JBBS-49SC-M613

Short-circuit protection: 55 mA (Isc)

Bus in/bus out connections


(7/8-16UN) minifast

Four (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)

6-port Junction

Bus in/bus out connections


(7/8-16UN) minifast

Six (7/8-16UN) minifast


connectors for field devices

Open circuit voltage: 33 VDC


Current consumption: <60 mA

Diagnostic
LED indicators
Power: Green = On
Short-circuit: Red = Shorted

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)

Electrical

JBBS-49SC-M813

Short-circuit protection: 55 mA (Isc)


Open circuit voltage: 33 VDC
Current consumption: <60 mA

Diagnostic

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Wiring Diagrams

4-port Junction

Open circuit voltage: 33 VDC

Diagnostic

Application

8-port Junction

Bus in/bus out connections


(7/8-16UN) minifast

Eight (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)

R31
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Anodized Aluminum
Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40 to +75C (-22 to +167F)

Dimensions

8-Port

6-Port

4-Port

Pinouts
minifast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R32
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Application

Wiring Diagrams

4-port Junction

JBBS-49-M423
JBBS-49-M424

No short-circuit protection
Fiberglass housing

Bus in/bus out connections


(7/8-16UN) minifast

Four (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

6-port Junction

JBBS-49-M623
JBBS-49-M624

No short-circuit protection
Fiberglass housing

Bus in/bus out connections


(7/8-16UN) minifast

Six (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

8-port Junction

JBBS-49-M823
JBBS-49-M824

No short-circuit protection
Fiberglass housing

Bus in/bus out connections


(7/8-16UN) minifast

Eight (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

R33
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Fiberglass
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40 to +75C (-22 to +167F)

Dimensions
6-Port

4-Port

Pinouts
minifast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R34
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

8-Port

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Application

Wiring Diagrams

4-port Junction

JBBS-49-M413/EX

No short-circuit protection

Bus in/bus out connections


(7/8-16UN) minifast

Four (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

FISCO/ENTITY Field Device

6-port Junction

JBBS-49-M613/EX

No short-circuit protection

Bus in/bus out connections


(7/8-16UN) minifast

Six (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

FISCO/ENTITY Field Device

R35
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Anodized Aluminum
Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40 to +75C (-22 to +167F)

Dimensions
6-Port

FOUNDATION fieldbus

4-Port

Pinouts
minifast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R36
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Electrical

JBBS-49SC-M413/EX

Short-circuit protection: 55 mA (Isc)


Open circuit voltage: 35 VDC
Current consumption: 5 mA

Diagnostic

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Electrical

JBBS-49SC-M613/EX

Short-circuit protection: 55 mA (Isc)


Open circuit voltage: 35 VDC
Current consumption: 5 mA

Diagnostic

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Application

Wiring Diagrams

4-port Junction

Bus in/bus out connections


(7/8-16UN) minifast

Four (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)
FISCO/ENTITY Field Device

6-port Junction

Bus in/bus out connections


(7/8-16UN) minifast

Six (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)
FISCO/ENTITY Field Device

R37
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Anodized Aluminum
Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40 to +75C (-22 to +167F)

Dimensions
6-Port

FOUNDATION fieldbus

4-Port

Pinouts
minifast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R38
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Electrical

JBBS-49SC-T415B/EX

Short-circuit protection: 35 mA (Isc)


Voltage drop: 0.3 V
Current consumption: 7 mA

Diagnostic

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Electrical

JBBS-49SC-T615B/EX

Short-circuit protection: 35 mA (Isc)


Voltage drop: 0.3 V
Current consumption: 5 mA

Diagnostic

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Application

Wiring Diagrams

4-port Junction

Bus in/bus out connections


(7/8-16UN) minifast

Four (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)
FISCO/ENTITY Field Device

6-port Junction

Bus in/bus out connections


(7/8-16UN) minifast

Six (7/8-16UN) minifast


connectors for field devices

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)
FISCO/ENTITY Field Device

R39
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Anodized Aluminum
Cable Glands
TPU (Polyurethane)
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
300 V
9A
-40 to +75C (-22 to +167F)

Dimensions
6-Port

FOUNDATION fieldbus

4-Port

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R40
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, eurofast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Application

Wiring Diagrams

4-port Junction

JBBS-49-E413
JBBS-49-E414

No short-circuit protection

Bus in/bus out connections


(M12x1) eurofast

Four (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

6-port Junction

JBBS-49-E613/3GD
JBBS-49-E614

No short-circuit protection

Bus in/bus out connections


(M12x1) eurofast

Six (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

8-port Junction

JBBS-49-E813
JBBS-49-E814

No short-circuit protection

Bus in/bus out connections


(M12x1) eurofast

Eight (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

R41
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Anodized Aluminum
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
250 V
4A
-40 to +75C (-22 to +167F)

Dimensions
6-Port

4-Port

Pinouts
eurofast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R42
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

8-Port

TURCK
Network Media Products
FOUNDATION fieldbus, eurofast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Electrical

JBBS-49SC-E413

Short-circuit protection: 55 mA (Isc)

Current consumption: 5 mA

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Electrical

JBBS-49SC-E613

Short-circuit protection: 55 mA (Isc)

Bus in/bus out connections


(M12x1) eurofast

Four (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)

6-port Junction

Bus in/bus out connections


(M12x1) eurofast

Six (M12x1) eurofast


connectors for field devices

Open circuit voltage: 35 VDC


Current consumption: 5 mA

Diagnostic
LED indicators
Power: Green = On
Short-circuit: Red = Shorted

CL I, Div 2; Groups A-D see TURCK


drawing N1-2.400
T6, Ta = 70C (SC Only)

8-port Junction

Electrical

JBBS-49SC-E813

Short-circuit protection: 55 mA (Isc)


Open circuit voltage: 35 VDC
Current consumption: 5 mA

Diagnostic

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Wiring Diagrams

4-port Junction

Open circuit voltage: 35 VDC

Diagnostic

Application

Bus in/bus out connections


(M12x1) eurofast

Eight (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D


see TURCK drawing
N1-2.400
T6, Ta = 70C (SC Only)

R43
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Anodized Aluminum
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
250 V
4A
-40 to +75C (-22 to +167F)

Dimensions
8-Port

4-Port

Pinouts
eurofast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R44
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

6-Port

TURCK
Network Media Products
FOUNDATION fieldbus, eurofast Passive Multiport Junctions
Rugged, Fully Encapsulated Enclosure
For Connecting I/O in Concentrated
Areas

Part Number

Specs

Application

Wiring Diagrams

4-port Junction

JBBS-49-E423
JBBS-49-E424

No short-circuit protection

Bus in/bus out connections


(M12x1) eurofast

Four (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

6-port Junction

JBBS-49-E623
JBBS-49-E624

No short-circuit protection

Bus in/bus out connections


(M12x1) eurofast

Six (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

8-port Junction

JBBS-49-E823
JBBS-49-E824

No short-circuit protection

Bus in/bus out connections


(M12x1) eurofast

Eight (M12x1) eurofast


connectors for field devices

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

R45
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Fiberglass
Nickel Plated CuZn or Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 67, IP 68, IP 69K
250 V
4A
-40 to +75C (-22 to +167F)

Dimensions
6-Port

4-Port

Pinouts
eurofast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R46
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

8-Port

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Junction Tees
Indoor Use Only (for outdoor applications
use JBBS family)

Multi-port Junction Provides a Rugged


Connection to Network Devices

Bus-in/Bus-out Feature Eliminates Need for


Splitter Tee

Short-Circuit Protection Available


Part Number

JTBS-49-M433

Specs
No short-circuit protection

Application
4-port Junction Tee

(7/8-16UN) minifast bus in/bus


out connections

Four (7/8-16UN) minifast


device ports

For nickel plated brass


connectors change part number
to JTBS 49SC-M434

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

Electrical

JTBS-49SC-M433

Short-circuit protection: 55 mA (Isc)


Open circuit voltage: 35 VDC
Current consumption: 5 mA

Diagnostic

JTBS-49-M633

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Wiring Diagrams

No short-circuit protection
6-port Junction Tee

(7/8-16UN) minifast bus in/bus


out connections

Six (7/8-16UN) minifast


device ports

For nickel plated brass


connectors change part number
to JTBS 49SC-M634

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

Electrical

JTBS-49SC-M633

Short-circuit protection: 55 mA (Isc)


Open circuit voltage: 35 VDC
Current consumption: 5 mA

Diagnostic

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

R47
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
POM (Nylon)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 68
250 V
4A
-40 to +75C (-22 to +167F)

Dimensions
6-port

FOUNDATION fieldbus

4-port

Pinouts
minifast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R48
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, eurofast Junction Tees
Indoor Use Only (for outdoor applications
use JBBS family)

Multi-port Junction Provides a Rugged


Connection to Network Devices

Bus-in/Bus-out Feature Eliminates Need for


Splitter Tee

Short-Circuit Protection Available


Part Number

Specs

Application

Wiring Diagrams

4-port Junction Tee

JTBS-49-E433

No short-circuit protection
Electrical

JTBS-49SC-E433

JTBS-49-E633

Open circuit voltage: 35 VDC

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Electrical

JTBS-49SC-E633

Four (M12x1) eurofast


device ports

For nickel plated brass


connectors change part number
to JTBS 49SC-E434

Short-circuit threshold: 280 mA

Open circuit voltage: 35 VDC

(M12x1) eurofast bus in/bus out


connections

Six (M12x1) eurofast


device ports

For nickel plated brass


connectors change part number
to JTBS 49SC-E634

Short-circuit threshold: 280 mA

Current consumption: 5 mA

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

6-port Junction Tee

Short-circuit protection: 55 mA (Isc)

Diagnostic

Current consumption: 5 mA

No short-circuit protection

(M12x1) eurofast bus in/bus out


connections

Short-circuit protection: 55 mA (Isc)

Diagnostic

CL I, Div 2; Groups A-D see


TURCK drawing N1-2.400
T6, Ta = 70C (SC Only)

R49
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

PUR (Polyurethane)
Nickel Plated CuZn or Stainless Steel
POM (Nylon)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 68
250 V
4A
-40 to +75C (-22 to +167F)

Dimensions
6-port

FOUNDATION fieldbus

4-port

Pinouts
minifast
Female

eurofast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R50
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, minifast Conduit Adapters
Gasket and Mounting Screws Provided
Same Housing Style for Single or Double
Port

Housing

Part Number

BCA 49-M123

Specs

Application

Pinout

Nylon Housing
300 V, 9 A
-40 to +75C

Electrical

BCA 49SC-M123

Short-circuit protection: 55 mA
Open circuit voltage: 35 VDC
Current consumption: 5 mA

Diagnostics

BCA 49-M223

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

Nylon Housing
300 V, 9 A
-40 to +75C

Attaches to standard
conduit body* for
transition to 4-wire
(7/8-16UN) minifast
connector

Female

*Crouse Hinds 3/4" Form


8, Mark 9 or equivalent

Electrical

BCA 49SC-M223

Short-circuit protection: 55 mA
Open circuit voltage: 35 VDC
Current consumption: 5 mA

Diagnostics

1-port Wiring Diagram

LED indicators
Power: Green = On
Short-circuit: Red = Shorted

2-port Wiring Diagram

R51
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
FOUNDATION fieldbus, eurofast Conduit Adapters
Gasket and Mounting Screws Provided
Same Housing Style for Single or Double
Port

Housing

Part Number

Specs

Application

Pinout

Attaches to standard conduit


body* for transition to
4-wire (M12x1) eurofast
connector

BCA 49-E123

*Crouse-Hinds 3/4" Form 8,


or Mark 9 or equivalent.

Nylon Housing
250 V, 4 A
-40 to +75C

BCA 49-E223

Attaches to standard conduit


body* for transition to
4-wire (M12x1) eurofast
connector
*Crouse-Hinds 3/4" Form 8,
or Mark 9 or equivalent.

1-port Wiring Diagram

2-port Wiring Diagram

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R52
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

Female

TURCK
Network Media Products
FOUNDATION fieldbus, Power Supply Conditioner
Meets the Needs of Redundant Power
Supplies for FOUNDATION fieldbus

Has Primary and Secondary Power Inputs


to Supply Two Fieldbus H1 Segments

Filters the Fieldbus Signal from the


Power Source
Part Number

Specs

Application

Electrical

BRPC-49-M213

Supply voltage (Supply A & B): 12-32 VDC

Output voltage (Segment 1 & 2): Input Voltage - 3 Volts

Supply surge protection (Supply A & B): >36 VDC


Supply redundancy (Supply A & B):
Supply "A" is primary. If Supply "A" Voltage drops below 11 Volts, Supply "B" becomes Active.
Supply "A" becomes active once voltage >11 Volts

4-port Power Supply Conditioner

Primary and secondary power


inputs

Diagnostics for each power supply

Output current (Segment 1 & 2): <1 Amp


Short-circuit protection (Segment 1 & 2): > 1 Amp to infinite

Diagnostic

Power LED indications:


Green - Active / Red - No Power

Segment LED indications: Green - Active

Internal switches for terminators

Supply monitor contacts (Supply A & B): Solid State, AC/DC <400 Volts, <70 mA when supply
voltage >11 Volts, contact is closed.

R53
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
Specifications
Housing:
Coupling Nut:
Contact Carrier:
Contacts:
Protection:
Rated Voltage:
Rated Current:
Ambient Temperature:

Anodized Aluminum
Stainless Steel
TPU (Polyurethane)
Gold Plated CuZn
NEMA 1, 3, 4, 6P and IEC IP 68
250 V
4A
-40 to +75C (-22 to +167F)

Dimensions

FOUNDATION fieldbus

BRPC-49-M213

Pinouts
minifast
Female

eurofast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R54
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

TURCK
Network Media Products
FOUNDATION fieldbus, Tees
Creates a Drop or Branch from the Main
Bus Line

minifast Connectors on Bus Line


minifast or eurofast Connectors on
Dropline
Housing

Part Number

Specs

Application

Wiring Diagrams

minifast Tee

RSV 2RKV 49

RSV FKV RKV 49

PUR (Polyurethane)
250 V, 4 A
-40 to +75C

Data, ground, shield


Stainless steel
coupling nuts

minifast to eurofast Drop

Data, ground, shield


Stainless steel
coupling nuts

eurofast Tee

RSCV 2RKCV 49

Stainless steel
coupling nuts

Pinouts
minifast
Male

eurofast
Female

Male

Female

R55
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Industrial
Automation
FOUNDATION fieldbus, Gender Changers and Elbow Connectors
Allows Quick and Easy Changes from
Male to Female minifast Connectors

Housing

Part Number

Specs

Application

Wiring Diagrams

Male minifast Gender


Changer

RSV RSV 49

Changes female cordset


to male receptacle

Female minifast Gender

RKV RKV 49

TPU (Polyurethane)
Changer
250 V, 4 A
Changes female cordset
-40 to +75C

minifast Elbow

WSV RKV 49

Right angle male to


female connector

Pinouts
minifast
Male

Female

TURCK Inc. Tech


3000 Campus
Drive 800.894.0412
Minneapolis, MN 55441
Support: 1-800-544-7769
Fax: (763) 553-0708
www.turck.com
R56
Clearwater
- Phone:
- Fax:Application
208.368.0415
- Web: www.clrwtr.com
- Email:
info@clrwtr.com

FOUNDATION fieldbus

to male receptacle

TURCK
Network Media Products
FOUNDATION fieldbus, Surge Suppressor
Protects Data Communication Lines (V+ and V-)
Absorbs the Front End of the Transient,
Responding in Less Than a Nanosecond

Diverts the Surge Energy to Ground


Automatically Resets and waits for Next Surge

Housing

Part Number

Specs

Application

Pinouts

Electrical

See Drawing 1

RSV RKV 49 SS

Male

Maximum operating voltage: 27 Volts


Maximum operating current: 200mA
Clamping action turn-on: 28.5 Volts
Maximum clamping at 2 kA: (8 x 20 Sec): 44 Volts
Maximum surge voltage: 20 kV
Maximum surge current: 2.5 kA
Current leakage/line at operating voltage: 5 A

Male and Female minifast ,


4-pin

Female

Capacitance /line at operating voltage: 500 pF


Response time: less than 1 nanosecond

Mechanical

Ground stud: 10-32 stainless steel


Operating temperature: -40 to +85C

R57
3000 Campus
Drive Minneapolis,
MN 208.368.0415
55441 Application Support:
Fax: (763)
553-0708
www.turck.com
ClearwaterTURCK
TechInc.- Phone:
800.894.0412
- Fax:
- Web:1-800-544-7769
www.clrwtr.com
- Email:
info@clrwtr.com

Anda mungkin juga menyukai