AND
LIST OF SYMBOLS
Nominal source voltage ( V ).
Instantaneous magnetizing current ( A ) .
Steady-state peak flux density ( T ) .
Remanent flux density ( T ) .
Magnetic field intensity ( A / M ) .
Source resistance ( Q ) .
Transformer primary winding resistance ( Q )
Source inductance ( Hy ).
Transformer leakage inductance ( Hy )
Total primary circuit resistance ( R = R,$ R , )
(Q).
+
+ L,)
I. INTRODUCTION
HE PHENOMENON of magnetizing inrush current
in transformers at energization has long been a problem in the design and performance of differential protective relays used in power transmission and distribution
systems.
The steady-state magnetizing current of a transformer
may be only 1-2 percent of the rated current, but it may
reach 10-20 times rated current when the transformer is
switched on to a source. This transient effect may persist
AMITAVA BASAK
Authorized licensed use limited to: IMAG - Universite Joseph Fourrier. Downloaded on June 4, 2009 at 09:47 from IEEE Xplore. Restrictions apply.
3218
IV
Gff
Transient
11. FACTORS
AFFECTING
THE MAGNETIZING
INRUSH
CURRENT
When a transformer is energized from a voltage source
the peak magnetizing current may reach a very high value
and cause a momentary dip in the voltage resulting in an
unwanted tripping of the differential protective relay. The
phenomenon of the inrush of the magnetizing current is
due to the temporary overfluxing of the transformer core
at the instant of energization. This temporary overfluxing
effect is governed by the following factors:
a) the point-on-voltage wave at the instant of energization;
b) the magnitude and polarity of the remanent flux in
the transformer core at the instant of energization;
c) the total resistance of the primary winding circuit;
d) the power source inductance;
e) the inductance of the air core in between the energizing winding and the transformer core;
f ) the geometry of the transformer core;
g) the maximum flux-carrying capability of the core
materials.
Under steady-state conditions, the core flux density B
lags behind the source voltage V by 90". In order to induce one half cycle of the required back EMF, a total
change of flux density of 2B,, is needed. When the excitation of the transformer ceases, the magnetizing current
follows the hysteresis loop to zero and the flux density
remains at some residual value known as remanent flux
density B,. If the transformer were to be switched in at
the instant corresponding to a point on the flux density
wave which had the same value and polarity as that of the
remanent flux density, then no inrush current would occur. Fig. 1 shows the waveforms of a source voltage V ,
flux density B , and magnetizing current I at three different
periods, a) steady state, b) interruption, and c) re-energization, respectively. It can be noticed that at the beginning of period c) the transformer is re-energized at 0" of
the source voltage with the remanent flux density, B, and
both the transient flux density and the inrush current are
large. However, it is possible to prevent the transformer
core overfluxing at energization thus eliminating the inrush current in the primary circuit of the transformer. In
order to achieve this, the switching-off angle on the
source-voltage wave must be precisely obtained. For example, in Fig. 1 , if the transformer is switched off at angle QoR, then the re-energization at Q = QoR will prevent
the appearance of magnetizing inrush current because the
switching-on point will coincide with the previous interruption point thus allowing the continuation of the steadystate condition.
The decay of the magnetizing inrush current is in part
a function of the impedance of the energizing circuit and
can be regarded as a simple network of resistors and inductors connected in series to an infinite busbar. The time
constant of the inrush curent decay can be expressed as
shown in (1) and ( 2 ) .
Id,
T,.
V exp (UT,)
R
( L s + L,)
(RS + 4 ) .
(1)
(2)
Under normal operating conditions, the leakage inductance of a transformer is small because of the B / H characteristic of the transformer core material. It has been
found that the higher the circuit resistance, the less the
number of transient cycles, the time constant and also the
magnitude of the first cycle of the inrush current. In practice, the circuit resistance is very small compared with the
power rating of a transformer, hence a power transformer
has a large primary circuit time constant resulting in a
long transient decay.
At present, the use of improved electrical steels in
Authorized licensed use limited to: IMAG - Universite Joseph Fourrier. Downloaded on June 4, 2009 at 09:47 from IEEE Xplore. Restrictions apply.
3219
2. C . D.
111. DEVELOPMENT
OF A MEASURING
SYSTEMFOR
INRUSH
CURRENT
MEASUREMENT
A measuring system has been developed using an electronic switch and a microcomputer with a view to minimizing the large number of calculations and measurement
procedures. The system is illustrated schematically in Fig.
2 . The triggering circuit consists of a zero crossing detector (ZCD) and an adjustable phase shifting network. The
output voltage of the latter, along with the primary voltage of the transformer, is fed into the summing point of
the ZCD; as a result a train of pulses is produced. These
pulses are phase-shifted from the zero-crossing point of
the primary voltage wave. The phase shifting network is
also connected to one of the triacs in such a way that as
soon as the triacs are fired by the first pulse, the inputs to
the phase shifter are short-circuited. This method allows
the transformer to be energized at any predetermined point
on the primary voltage wave and once it is energized, the
full power is delivered to it as the trigger pulses shift back
to the zero-crossing points of the voltage wave. A dc excitation coil is used to set up various levels of remanent
flux density up to 1.7 T of either polarity.
One of the components of the current sampling unit is
a variable shunt resistor which provides various primary
circuit resistances for investigating the effect of primary
circuit resistance on magnetizing inrush currents. A variable-gain amplifier has been employed to ensure that an
adequate voltage is fed into the analog-to-digital converter (ADC).
The inrush current harmonics are evaluated using a
software based on the Fourier series technique. Twenty
two thousand data values of magnetizing inrush current
are sampled over a period of fifty cycles and for each cycle
of the inrush current, various harmonics are determined.
A . Point-on-Supply Voltage Wave Switching Circuit
The main component of this circuit, shown in Fig. 3,
is a multistage ZCD type CA3059 [8] which was designed
to handle ac voltage inputs (typically 240 V) directly. The
CA3059 features a self-powered dc supply, a protection
circuit, and a Darlington output stage to provide sufficient
gate current to trigger triac T , and hence triac T2. The
values of R2 and R3 have been chosen to satisfy the condition given by 0.33 < R 3 / R z < 3.0, so as to enable an
internal gate to generate trigger pulses at pin 4. The internal protection circuit is activated by connecting pins 13
and 14 together. This protection circuit, when alarmed by
any unsatisfied conditions, removes power from the load
by interrupting the gate current output to pin 4.
In order to allow the energization of a transformer at
different points on the voltage wave, an adjustable phase
shifter has been employed. Its output voltage V , is fed
SHIFTER
SUMMING
POINT
CURRENT,
SAMPLING
PRIMARY
MICRO
A D C
B. Computational Work
Software has been developed to obtain information on
the magnetizing inrush current, in terms of magnitude,
duration, and harmonic content of each cycle. This program performs two major functions. First, it carries out
data sampling at a time interval of 47 ps over a period of
first 50 cycles of the inrush current. Secondly, it evaluates
cycle by cycle the magnitude, duration, and harmonic
content of the inrush current.
Determination of harmonic contents has been based on
Fourier series. Close approximations of real-time integra-
Authorized licensed use limited to: IMAG - Universite Joseph Fourrier. Downloaded on June 4, 2009 at 09:47 from IEEE Xplore. Restrictions apply.
3220
n
Start
PROGRAM TERMINATION
'
'
H &
E n t e r no.of c y c l e
TI
R &
S e t counter f o r
to be a n a l y s e d
iT
corresponding
locations
C a l c u l a t e sine
and c o s i n e terms
D a t a input routine
consecutive
locations
Calculate
F ( r ) cos ( k a t ) dt
Ak =
routine
(3)
component
2
M
M-l
F ( r ) COS ( k l m ) .
m=O
(4)
B~ =
2
M
M-'
F ( r ) sin ( k ~ m ) .
in=O
(51
+ B;).
(6)
Print a n s w e r s
YES
Fig. 5 . Flow chart of the harmonic analysis and assembly language subroutine.
Authorized licensed use limited to: IMAG - Universite Joseph Fourrier. Downloaded on June 4, 2009 at 09:47 from IEEE Xplore. Restrictions apply.
322 1
200
150
100
50
0'
45'
SO'
135~
(a)
401
lad
Fig. 6. First peak of inrush current with various angles of switching at B,,,
= 1 . 7 T , B r = + l . S T , a n d R = 1.36Q.
CYCLE NUMBER
(a)
Circuit Resistance
203
(ohm)
BrKlr/O
I .7T/+1 .5T10deq
145
871\
116
I .7Ti+l .5T,90deq
1 .7TI-I .STlBdeq
' "1
%, 2nd
58
CYCLE
NUMBER
C Y C L E NUMBER
(b)
100,
0
LL
C Y C L E NUMBER
(C)
Harmonic analysis of an individual cycle of the magnetizing inrush current was carried out at various switching conditions. Fig. 8(a), (b), and (c) illustrates these for
three different switching conditions. The oscillograms of
Authorized licensed use limited to: IMAG - Universite Joseph Fourrier. Downloaded on June 4, 2009 at 09:47 from IEEE Xplore. Restrictions apply.
3222
-10
mseclcm
(a)
tant, not only for the design of the harmonic restraint differential relay, but also for the effect of interference on
other electrical networks. It may be concluded that a large
reduction in magnetizing inrush current is possible with a
given combination of switching parameters. Point-onvoltage wave switching is feasible provided the polarity
and magnitude of remanent flux density are known. Preinsertion of resistors in the primary circuit has also been
proved to be effective; however, the resistor must have a
large value thus resulting in a large voltage dip in the
transformer. The correlation of the switching parameters
may be used to reduce magnetizing inrush currents, but
the main argument still remains in the area of economical
aspects and its applications in the existing power systems.
REFERENCES
_ j 10 m s e c l c m
(C)
L. F. Blume, G. Camilli, S . B. Farnham, and H. A. Peterson, Transformer magnetizing inrush currents and influence on system operation, AIEE Trans. PowerApp. S y s f . , vol. 63, pp. 366-375, Jan. 1944.
T. R. Specht, Transformer magnetizing inrush current, AIEE Trans.
Power App. Sysf., vol. 70, pp. 323-327, Jan. 1951.
R. Yacamini and A . Abu-Nasser, Numerical calculation of inrush
current in single phase transformers. Proc. Inst. Elec. E n g . , vol. 128,
pt. B, no. 6, pp. 327-334, Nov. 1981.
-, The calculation of inrush current in three phase transformers,
Proc. Inst. E k e . Eng., vol. 133, pt. B, no. I , pp, 31-40, Jan. 1986.
H. Digneffe, Electronic control of power transformers, Electron.
Eng.. vol. 55, pp. 53-60, Apr. 1983.
J . A . Sykes and I. F . Morrison, A proposal method of harmonic restraint differential protection of transformer by digital computer, IEEE
Trans. P o w e r A p p . S y s t . , vol. PAS-91, no. 3 , pp. 1266-1272. May/
June 1972.
E. 0. Schweitzer, R . R. Larson, and A. J . Flechsig, J r . , An efficient
inrush current dectection algorithm for digital computer, in Proc.
IEEEPower Eng. Sue. Summer Meet. (Mexico), pt. A77, p. 510, July
1977.
A . C. N. Sheng, and G . J. Granieri, J. Yellin, and T . McNulty, Features and applications RCA integrated circuit zero-voltage switches
CA3059, RCA Solid State, Tech. Rep. ICAN-6182, Oct. 1973.
*
Paul C. Y. Ling was born in Hong Kong in 1961. He received the B.Sc.
degree in electrical and electronic engineering from University College,
Cardiff, UK. in 1984.
In the same year he joined the university working in the Wolfson Centre
for Magnetics Technology as a Research Assistant in the field of transient
phenomena in power transformers. He is also working in the field of soft
magnetic materials in particular the geometry effect of tape wound core on
magnetic performances.
Mr. Ling is an Associate member of the Institution of Electrical Engineers of the UK.
*
Amitava Basak was born in Calcutta. India. He received the B.E. degree
in electrical engineering from the University of Calcutta, in 1966 and the
M.Sc. and Ph.D. degrees from the University of Wales, UK, in 1971 and
1975, respectively.
From 1973 to 1979 he was a research fellow at the Wolfson Centre for
Magnetic Technology, University College, Cardiff, UK. He is currently a
Lecturer in the Department of Electrical and Electronic Engineering of the
same college. His main research interests are the flux distribution and power
loss in electrical machines and the use of permanent magnets in dc linear
motors.
Dr. Basak is a member of the Institution of Electrical Engineers and the
Institute of Physics.
Authorized licensed use limited to: IMAG - Universite Joseph Fourrier. Downloaded on June 4, 2009 at 09:47 from IEEE Xplore. Restrictions apply.