E26987

6 1 2 3 7
1
2

E32566
STR 43 ME %Ir >Ir >Isd test fault

Io Ir Isd µP
3 .71 .8 .90 .93 9 10
.63 .88 .95 8 11 > Ir
4 .56 .85 .98 7 12 A
.5 .8 .8 1 13 tr
5 x In x Io
6
x Ir
> Im

tsd
tr 20 20 > Ih
test 10 Ir I1 I2 I3
10
0 Ir Isd Ii I + - 10A 10A
Ir Isd li

1 long-time threshold class


IEC 947-4-1
2 tripping class
3 short-time pick-up
4 short-time tripping delay STR43ME trip unit
5 instantaneous pick-up Ratings (A) 20 to 70 °C Ir 120 200 320 500
6 test connector Circuit NS400N/H/L b b b -
7 percent load indication breakers NS630N/H/L - - - b
Overload protection (Long Time)
Current setting Ir adjustable, 40 settings - 0.4...0.8 x In
Tripping class 10A, 10, 20
(IEC 60947-4)
Time delay (s) adjustable
(min. ... max.) at 1.5 x Ir 144…198 270…357 433…595
at 6 x Ir 5.8…7.3 10.9…13.1 17.4…21.8
at 7.2 Ir 4…5 7.3…9.1 12…15
Phase-unbalance protection in compliance with IEC 60947-4.1
Tripping threshold u 40 % unbalance
Time delay 4 s ±10 %
Short-circuit protection (Short Time)
Pick-up Isd adjustable, 8 settings - 6...13 x Ir
Accuracy ±15 %
Time delay (ms) fixed
max. resettable time 10
max. break time 60
Short-circuit protection (Instantaneous)
Pick-up Ii fixed - 13 x Ir max.
Other functions
Motor-overload LED b
Indications module b
Options
Ammeter (I) b
SDTAM module b
Communication (COM) b

Options for STR43ME trip unit


Ammeter (I)
Possible A digital display continuously indicates the current of the phase with the greatest
combinations: load. The value of each current I1, I2, I3 and the long-time current setting Ir may be
bI successively displayed by pressing a scroll button.
b I + COM LEDs indicate the phase for which the current is displayed.
b SDTAM Ammeter display limits
b SDTAM + I b minimum current u 0.2 x In. Lower currents are not displayed
b SDTAM + I + COM b maximum current y 10 x In.

Optional SDTAM contactor tripping module


(Early-break thermal-fault signal)
See the information on this optional module on page A-42.

Communication (COM)
This option transmits data to Digipact distribution monitoring and control modules.
Transmitted data:
b settings
b phase currents (rms values)
b highest current of the three phases
b overload-condition alarm
b cause of tripping (overload, short-circuit, etc.).