Anda di halaman 1dari 4

Bulletin No.

0613DB9902
June 1999
Data Bulletin Cedar Rapids, IA USA

ANSI® C37 Standard and UL® 489 Standard Comparison

EVOLUTION OF PRODUCTS AND Since Ben Franklin discovered electricity, people have been struggling to
MARKETS harness its energy and use it safely. As the use of electricity spread into
residences and commercial businesses, the need for personal safety and
protection against fires became clear.
People needed products that were safe to use and afforded protection against
the hazards of fire. They used electricity in their homes and businesses but
were not trained to determine the types of products they needed to protect
themselves and their property.
Underwriters Laboratories Inc.® (UL®) Underwriters Laboratories Inc. (UL), was set up in the late 1800s to test many
products for the insurance industry. Fire safety and prevention were a major
concern. UL, working with electrical manufacturers, developed standards for
electrical products and provided third-party certification assuring that the
products provide safe and intended functionality regardless of manufacturer.
The products began as safety switches evolving into circuit breakers and load
centers.
The molded case circuit breakers designed for this market are Listed to the
UL 489 Standard. UL 489 requires that these circuit breakers meet specific
construction and testing requirements to provide necessary protection while
requiring little or no maintenance. One important feature of these types of
circuit breakers is the enclosed molded case which provides personal safety
as well as assuring proper dielectric clearances.
The American National Standards As the need and dependence on electricity grew, power generation along with
Institute® (ANSI®) large industrial users and continuous process industries became a large part
of our industrial complex. Safety and fire prevention were major
considerations but continuity of service and equipment performance were
also primary requirements. These users had highly trained staffs that worked
with manufacturers and the International Electrical and Electronics Engineers,
Inc. (IEEE®) committee to design, test and produce electrical equipment that
provided the safety, performance and continuity of service they required.
The American National Standards Institute (ANSI) compiled these
accumulated design and test documents, provided by IEEE and
manufacturers, into ANSI Standards. These standards then became the basis
for designing and testing low-voltage power circuit breakers (LVPCBs) and
switchgear.
Switchgear is designed with strict standards for compartmentalization,
drawout construction and steel barriers between circuit breaker, bus and
instrument compartments. Because of the compartmentalization and barriers,
LVPCBs were designed with an open construction to allow for strength, heat
dissipation and maintenance that was necessary for long service life.
CIRCUIT BREAKER AND EQUIPMENT UL incorporated ANSI Standard C37 into the UL 1558 Standard for
STANDARDS switchgear in 1982 and into the UL 1066 standard for low-voltage power circuit
breakers in 1985. These two UL standards provide the basis for third-party
witnessing and certification to the ANSI Standard.

Circuit Breaker Standards  UL 489


 ANSI C37.13 and C37.50 or UL 1066

Equipment Standards  UL67 Panelboards


 UL 891 Switchboards
 ANSI Switchgear or UL1558 Switchgear or UL 891 Switchboards
© 1999 Square D All Rights Reserved
ANSI® C37 Standard and UL® 489 Standard Comparison Bulletin No. 0613DB9902
Data Bulletin June 1999

DIFFERENCES BETWEEN THE UL 489 The UL and ANSI Standards differ in four basic areas:
STANDARD AND THE ANSI C37  Philosophy
STANDARD  Construction
 Performance testing
 Certification

Philosophy
UL 489 Standard Design and Test Philosophy The scope of the UL 489 Molded Case Circuit Breaker Standard includes
miniature circuit breakers (MCBs), molded case circuit breakers (MCCBs)
and insulated case circuit breakers (ICCBs). These circuit breakers are
typically rated 10–6000 A and up to 600 Vac and 500 Vdc. Circuit breakers
designed and tested to this standard typically exhibit the following
characteristics:
 Sealed molded case
 Little or no maintenance
 No user replaceable parts
 Good performance and reliability
 Long service life
ANSI C37 Standard Design and Test The scope of the ANSI C37 Low Voltage Power Circuit Breaker Standard
Philosophy includes 2- or 3-pole stationary and drawout circuit breakers. The
specifications of these circuit breakers are 254, 508 or 635 Vac maximum,
fused or unfused, and manually- or power-operated with or without
electromechanical or electronic trip units. These circuit breakers typically
exhibit the following characteristics:
 Iron frame—older designs are open, newer designs are closed
 Maintainable for long service life
 Most parts can be replaced in the field
 High performance and reliability
 High maintenance costs

Construction The main construction differences between UL 489 Listed and ANSI C37
Certified circuit breakers are maintainability, ampere interrupting ratings
(AIRs), heat rise and endurance. These construction differences result from
the design and test philosophies outlined above. These differences will be
discussed under Performance Testing.
UL 489 Listed circuit breakers are sealed and require no maintenance for a
long service life. ANSI C37 Certified circuit breakers typically require
maintenance for long life and have been designed with an open case to
facilitate maintenance.

Performance Testing The UL 489 and ANSI C37 Standards require the same basic tests including
the following:
 Dielectric
 Calibration
 Overload
 Temperature
 Endurance
 Short circuit
Both the UL 489 and ANSI C37 Standards demonstrate the circuit breaker’s
ability to protect conductors under overload or short-circuit conditions. The
major differences in performance testing occur during the details and
sequences of the tests for overload, temperature, endurance and short-
circuit conditions.

2 © 1999 Square D All Rights Reserved


Bulletin No. 0613DB9902 ANSI® C37 Standard and UL® 489 Standard Comparison
June 1999 Data Bulletin

Overload Testing
Overload testing is done to demonstrate making
UL 489 ANSI C37
and breaking current values that might be
Power Factor: 0.45–0.50 Power Factor: 0.50
obtained when initially energizing a motor load.
Frame size Number of operations at Frame size Number of operations
Each time the circuit breaker is closed and (A) rated voltage (A) at rated voltage
opened on a high current load (600%), the contact 50–1600 50 600% current 225–800 50 600% current
surfaces are subjected to arcing and heat. This 1601–2500 25 600% current 1600–2000 38 600% current
action simulates an accelerated life test to make 2501–6000 3 600% current* >2000 0
sure the contacts provide adequate conductivity *An additional 25 operations at 200% current.
through many operations. The UL 489 Standard
tests all circuit breaker ratings with significant
operations to ensure the design is capable of a
long service life with no maintenance. The ANSI
C37 Standard tests circuit breakers rated only up
to 2000 A.

Temperature Testing
The UL 489 Standard allows for two types of UL 489 ANSI C37
ratings. Standard circuit breakers cannot exceed Temperature 50°C temperature rise at line and load 55°C temperature rise at line and
a maximum of 50°C temperature rise at the wire terminals load terminal bus connections
and 85°C temperature rise on
terminal connection at 100% current in 40°C open circuit breaker contacts
air. 100% rated circuit breakers may have a Current Standard circuit breaker: 100% rated current in smallest
temperature rise of 60°C at the wire terminal  100% rated current in open air at 40°C enclosure
connection in the smallest allowable enclosure if  80% rated current in smallest enclosure
the circuit breakers are connected with wire rated Exceptions 100% rated circuit breaker: Trip unit defeated
 100% rated current in smallest enclosure
at 90°C wiring insulation sized to the 75°C chart  Temperature rise may be 60°C if 90°C
(Table 310-16, National Electric Code®—NEC®). wire is used sized to the 75°C chart (NEC)
The ANSI C37 Standard requires a maximum of
55°C temperature rise at 100% in the smallest
enclosure and a maximum of 85°C temperature
rise on the contacts.

Endurance Testing
Circuit breakers tested to the UL 489 Standard UL 489 ANSI C37
must pass a significant number of operations Power factor: 0.75–0.80 Power factor: 0.85
without any maintenance. This test verifies that Maintenance not allowed Maintenance allowed
the design is capable of a long service life. The Max. frame Number of operations at Max. frame Number of operations
ANSI C37 Standard tests circuit breakers for size (A) rated voltage size (A) at rated voltage
further operations but then allows for 100 6000 At rated current 225 4000 At rated current
maintenance of the circuit breaker at relatively 4000 Without current 10000 Without current
2500 Between maintenance
short intervals.
225 4000 At rated current 600 2800 At rated current
NOTE: No manufacturer currently offers 225 A or 4000 Without current 9700 Without current
1750 Between maintenance
600 A frame circuit breakers tested to ANSI C37.
600 1000 At rated current 800 2800 At rated current
5000 Without current 9700 Without current
1750 Between maintenance
Short-circuit Testing 800 500 At rated current 1600 800 At rated current
The short-circuit tests reflect differences in the 3000 Without current 3200 Without current
philosophies between the UL and ANSI circuit 500 Between maintenance
breaker standards. The UL 489 Standard requires 2500 500 At rated current 2000 800 At rated current
2000 Without current 3200 Without current
that the tests be conducted at several values of 500 Between maintenance
short-circuit current. A separate test sequence 6000 400 At rated current 3200 400 At rated current
evaluates the maximum interrupting rating 1100 Without current 1100 Without current
claimed by the manufacturer. Tests are conducted 250 Between maintenance

at the rated voltage(s) of the circuit breaker which 4000 400 At rated current
1100 Without current
is typically 240, 480 or 600 V. 250 Between maintenance

© 1999 Square D All Rights Reserved 3


ANSI® C37 Standard and UL® 489 Standard Comparison Bulletin No. 0613DB9902
Data Bulletin June 1999

Three-pole circuit breakers are tested under


three-phase conditions during the maximum
Short UL 489 ANSI C37
interrupting ability sequence. Each pole is tested Circuit
individually at a reduced current level. The circuit Power factor ≤10,000 A 0.45–0.50 0.15 Unfused
breaker must safely interrupt the short-circuit 10,001–20,000 A 0.25–0.30 0.20 Fused
current and protect the rated wire in the circuit. ≥ 20,000 A 0.15–0.20
Voltage and Rated voltage with low-, medium- Rated current at the three voltage
The ANSI C37 Standard requires that a three- current and high-level current levels: 254, 508 and 635 Vac
pole circuit breaker be tested under three-phase Operations Open—close/open on all three Open—close/open on all three poles.
conditions at the maximum interrupting rating and poles First open at closing angle to ensure
peak current of 2.3 x rated current in
also that each individual pole be tested at 87% of Open—close/open on each
one phase
individual pole at reduced current
the maximum interrupting rating. Both the three- level Open—close/open individual pole at
phase and the individual-pole tests are conducted 87% of rated current
at rated maximum voltages of 254, 508 and 635 V. Short-time withstand—first ON cycle,
The ANSI C37 Standard also includes a separate closing angle must ensure a peak
current of 2.3 x rated current in one
sequence to evaluate the short-time withstand phase. Circuit breaker remains
current of the circuit breaker. The short-time closed, tripping disabled—0.5 sec.
withstand current is a high-level current that can ON, 15 sec. OFF, 0.5 sec. ON

be maintained for 0.5 seconds without damage to


the circuit breaker.

Certification Certification tests to the UL 489 Standard are witnessed by UL engineering


representatives. At the successful completion of the test program, UL permits
circuit breakers to bear a UL Listing mark combined with the product identity
of “CIRCUIT BREAKER” or “CIRCUIT BREAKER FRAME.” These circuit
breakers are then required to undergo subsequent follow-up testing on a
regular basis: quarterly, semiannually or biannually depending on the circuit
breaker size and quantities produced. All follow-up tests are witnessed by UL
field representatives.
Certification tests to the UL 1066 Standard (which include the requirements
of the ANSI C37 Standard) are witnessed by UL engineering representatives.
At the successful completion of both UL test programs, UL permits the circuit
breaker to bear a UL Listing mark combined with the product identity of “LOW
VOLTAGE AC POWER CIRCUIT BREAKER” or “LOW VOLTAGE AC
POWER CIRCUIT BREAKER FRAME.” While UL conducts follow-up
inspections on the UL 1066 Standard tested products to ensure that the
construction has not changed from that which was originally tested, they do
not require subsequent follow-up testing.

Square D and are registered trademarks of Square D/Schneider Electric or related companies.
Underwriters Laboratories Inc. and UL are registered trademarks of Underwriters Laboratories Inc.
Square D Company ANSI is a registered trademark of American National Standards Institute, Inc.
PO Box 3069, 3700 Sixth St. SW National Electric Code and NEC are registered trademarks of National Fire Protection Association, Inc.
Cedar Rapids, IA 52406-3069 IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
Field Services: 1-800-634-2003 All other trademarks are the intellectual property of their respective companies.
www.squared.com Bulletin No. 0613DB9902 June 1999 © 1999 Square D All Rights Reserved.

Anda mungkin juga menyukai