1 KW=3412.14 BTU
1 Ton=12,000 BTU
1 KW=0.284345 Ton
1100 cft= 1 Ton

Rupayan MSC room dimension:


Total:
Width= 38 ft
Length= 58.5 ft
Height= 10 ft

Volume= 38*58.5*10=22,230 cft

Excluding Store:
Volume= (18.5*18.5*10) + (38*40*10) =18,622.5 cft

[Sore Volume=(22,230-18,622.5) cft = 3,607.5 cft]*

Required AC Capacity (Ton) = 18,622.5/1100= 16.9 Ton~17 Ton=17/0.284345 KW=59.7 KW

[59.7/2=29.8KW per AC]**


**Two 29.8 KW AC.

Existing AC Capacity:

Brand 2.5 Ton 1.5 Ton 1 Ton Total

Gree 7 Nos 17.5 Ton

Transtec 2 Nos 3 Ton

Hisense 2 Nos 3 Ton

Total 23.5 Ton

Energy Efficiency Ratio (EER)


Cooling capacity in BTU/hr divided by electrical energy consumed in watts.

EER (Energy Efficiency Ratio): A measure of the efficiency of central and room air
conditioners. It measures instantaneous efficiency and is the cooling capacity in Btu/hr divided
by the watts of power consumed for a specific outdoor temperature (usually 95 degrees
Fahrenheit). In hotter climates, SEER and EER are more important than HSPF.
HSPF (Heating Season Performance Factor): Laboratory test attempts to take into account the
reductions in efficiency caused by defrosting, temperature fluctuations, supplemental heat, fans
and on/off cycling. The higher the HSPF, the more efficient the heat pump.

SEER (Seasonal Energy Efficiency Ratio): It is the most commonly used measure of the
efficiency of consumer central air conditioning systems.

EER:
Energy Efficiency Ratio. The ratio of the cooling capacity of the air conditioner in BTUs per
hour to the total electrical input in watts. This measure is determined by comparing test units to
the Air Conditioning and Refrigeration Institute specifications.