71-2 © IEC: 1996 —119—

Table A.1 — Correlation between standard lightning impulse withstand


voltages and minimum air clearances
Standard lightning impulse Minimum clearance
withstand voltage
mm
kV Rod-structure Conductor-structure
.9 H 20 60
40 60
wt -

60 90
75 120
95 160
125 220
145 270
170 320
250 480
325 630

—1 450
550 .
900
1100 C
4 650 1300
750 1500
850 1700 1600
950 1900 1700
1050 2100 1900
1175 2350 2200
1300 2600 2400
1425 2850 2600
1550 - 3100 2900
1675 3350 3100
1800 3600 3300
1950 3900 3600
2100 4200 3900
NOTE The standard lightning impulse is applicable phase-to-phase and

phase-to-earth.
For phase-to-earth, the minimum clearance for conductor-structure and rod-
structure is applicable.
For phase-to-phase, the minimum clearance fQr rod-structure is applicable
C
71-2 ©IEC: 1996 —121—

Table A.2 — Correlation between standard switching impulse withstand


voltages and minimum phase-to-earth air clearances
Standard switching impulse Minimum phase-to-earth
withstand voltage mm

kV Conductor-structure Rod-structure

750 1600 1900


850 1800 2400

950 2200 2900


1050 2600 3400
1175 3100 4100

1300 3600 4800


1425 4200 5600
1550 4900 6400

Table A.3 — Correlation between standard switching impulse withstand


voltages and minimum phase-to-phase air clearances
Standard switching impulse Minimuni phase-to-phase clearance
withstand voltage
mm

Phase-to-phase
Phase-to- value Phase-to- Conductor-conductor Rod-
earth — phase parallel conductor
Phase-to-earth
kV value <V

750 t,5 1125 2300 2600

850 1,5 1275 2600 3100

850 1,6 1360 2900 3400

• 950 1,5 1425 3100 3600


950 1,7 1615 3700 4300

1050 1,5 1575 3600 4200

1050 1,6 1680 3900 4600

1175 1,5 1763 4200 5000


1300 1,7 2210 6100 7400
1425 1,7 2423 7200 9000

1550 1,6 2480 7600 9400