8BK80

Genuine metal-clad single busbar switchgear with


Vacuum Circuit Breaker on withdrawable truck upto 36kV

Power Transmission and Distribution


8BK80
The Safe and True Metal-Clad Switchgear
Construction • Earthed metal partitions
• True metal-clad and air and shutters Front View
insulated switchgear • User friendly for
• Single Busbar System installation and
2250
• Circuit breaker mounted maintenance
on withdrawable truck • Padlockable shutters for
bus and cable side
Standards • Access to cable terminals
• IS 3427 and 12729 from the rear
• IEC 60298 and 60694 • Simplicity and robustness
1500
of operating mechanism
Personal Safety with minimum linkages
8
• All switching operations • Independent pressure
including VCB rack in- relief vents for all HT 3 1
2
7
rack out performed with compartments
front door closed 4
• Earthed metal partitions Design Philosophy 5 6
prevents contact with live • Total operational safety
parts • High reliability
• Earthed metallic shutters • User friendly 1) Inspection window
2) Spring charging.
3) Mechanical on/off
Tolerance to Environment Application ranges: indicator+spring
0
• Full metal enclosure The versatile use of the 1100 charged indicator
ensures high resistance 8BK80 cubicles is suitable 4) Mechanical off P. B.
to ingress and for installation in 5) Cranking lever
interference under all 6) Key for cranking lever
operating conditions • Power stations 7) Mechanical on P. B.
• Insulators have high anti- • Distribution stations 8) Door handle
tracking qualities • Industries

Operational Safety /
Maintenance Technical Data Dimensions
• Full mechanical
interlocking ensures Rated voltage and insulation Width (mm) 1100 mm
human Safety List as per IEC 60298 & 60694 36 kV
• Fail safe interlocking Height (mm) 2250 mm
• Access door fully Power frequency withstand voltage (RMS ) value 70kV
integrated in interlock Depth (mm) 2700 mm
system Lightning impulse withstand voltage (peak) value 170kV
• Service proven vacuum
circuit breaker, Rated short circuit breaking current (RMS) value 31.5kA
maintenance free
vacuum interrupters, low Rated short -time current (3sec) (RMS) value 31.5kA
maintenance drive
mechanism Rated short time current (peak) value 78.75 kA

Special Features Rated current for feeders 25001A


• Circuit breaker mounted Fully Typed Tested
on withdrawable truck Rated current for main busbars 3150 A 1 including
• Safe and easy truck Internal Arc Test
movement behind closed
cubicle door Note:
1. Higher values on request

Siemens Ltd.
Power Transmission & Distribution
Systems Division
Kalwa works :
Thane Belapur Road
Thane - 400 601
Tel.: +91 2762 3544
Fax: +91 2762 3718

“Product development is a continuous process. Consequently the data indicated in this booklet is subject to change without prior notice.
For latest issue contact our Sales Office.”

Siemens Ltd.
PTD-03-152-033

Anda mungkin juga menyukai