CONTENTS

1. SAFETY INFORMATION P.4


2. INSTRUCTION P.6
3. ORDERING INFORMATION P.6
4. SPECIFICATION P.7
5. DIMENSIONS & PANEL CUTOUT P.11
6. TERMINAL ARRANGEMENT P.11
7 NAME & FUNCTION P.12
8. TABLE OF SETTING ITEMS P.13
10. SETTING METHOD P.15
20. GROUP SETTING P.16
21. FUNCTION P.23

2
1 SAFETY INFORMATION

Before using, please read this (SAFETY INFORMATION) and then use this controller.

RT9 It is most important that the instructions in this manual are followed when using this instrument.
Please keep this manual for future reference.
Precautions are classified in WARNING and CAUTION.

◆ Universal Input・Output/Small-sized Temperature controler & Recorder WARNING There is a possibility of death or heavy injury when handling in wrong way.

(±0.3 class high accuracy) CAUTION There is a possibility of injury or physical damage when handling in wrong way.

WARNING
Caution on wiring
● Use an external protection circuit if a fault in the control loop could possibly lead to a serious
problem.
● This instrument do not have a switch for power and a fuse, so please set them if it is needed.
(Fuse rating 250V, 0.5A)
Power supply
● Use a rated voltage to prevent damage or trouble.
● To avoid electrical shock or damage, do not turn ON the power until the wiring is completed.
Prohibit use in gas atmosphere
Do not use it at a place exposed to combustible or explosive gas.
Handling of unit
● To avoid malfunction, electrical shock or fire, this unit must not be disassembled or repaired.
● Do not touch the terminals to avoid electrical shock or malfunction.
Model : RT9 Caution on maintenance
● Turn OFF the power before mounting or removing the instrument.
● To ensure continuous and safe operation of the instrument, periodical maintenance is
recommended. Some parts are limited in life.
Features ● The warranty period is 1 year only if using in the correct way.

CAUTION
● Zoom function ● Free scale
Caution on handling
● Various Alarm ● PID auto tuning Do not install the instrument under any of the following condltions.
● The ambient temperature exceeds 0 ~ 50℃
● Universal Input・Output ● Record and Temperature ● The ambient humidity exceeds 20 ~ 90%RH.
● A place where temperature changes suddenly or icing occurs.
● Interface (RS485) control ● A place exposed to corrosive gas or combustible gas.
● Vibration or shock is likely to be transmitted to the instrument.
● A place exposed to water, oil, chemicals, steam, sunlight.
● A place exposed to much dust, salt or iron.
● A place with much inductive disturbance, static electricity, magnetism noise.
● A place where heat such as radiant heat stays.

3 4
② Installation
● For NX9, 7, 3 and 2, attach the brackets (2 units) on the fixed halls and tighten with a 2 INSTRUCTION
screwdriver.
Fixing torque is about 14.7N. cm (1.5kg.cm). NX1 and NX4 has a plastic bracket.
(Care should be taken not to tighten forcedly.) This instrument has process-value (PV) and set-value (SV) each 4 digits with 7 segment FND. This
instrument is divided Recorder and Recorder with Controller.
③ Caution on terminal connections Function and feature : Group P.I.D, Universal-input (19 types), Universal-output (Relay, SSR, 4~20mA),
● Use a compensating cable with thermocouple. Auto-tuning 2 types (standard type, low PV type), Communication (RS485),21 types of alarm,
● For R.T.D input use a cable which is a small lead wire resistance and without resistance Sampling cycle 250ms, ±0.3 of FS high accuracy. And there are Zoom function, Graphic or Text
difference to 3wires. printing selectable function, List function, Feed function, Free scale function. RTP is the smallest
● To avoid inductive noise to input wires seperate from the power and output wires. Recorder with controller.
● Keep input wires away from output wires and use shielded wires to earth.
● If the wiring has noise, use the following step: connect a surge absorber to the conductor
coil side if the conductors are connected to the load output, such as the relay contact output.
● Use an insulating transformer with a noise filter when the power suppy has much noise. 3 ORDERING INFORMATION
● Noise filter should be mounted on a panel which has been earthed and the wiring between
the noise filter output and the instrument power terminals should be shorten.
● It is effective to use a twisted cable for power supply against noise.
RT9
● The heater power supply and the instrument power supply should be connected using the
same power suppy when a heater break alarm. 0 : Recorder
● Time for preparation of contact output is required at power ON. When the output signal is 1 : Recorder & Temperature Controller
used for an extenal interlock circuit, connect a delay relay. 0 : ℃ exclusive use
1 : Others
④ For load circuit connection
● Use an extra relay when the frequency of operation is rather high. In thic case,
SSR output type is Recommended. 0 : None
• Electromagnetic switch : Proportional cycle time is Min. 30sec 1 : Alarm 1
2 : Alarm 1,2
• SSR : Proportional cycle time is Min. 1 sec
3 : RS485
• Contact output life : Mechanical : Min. 10 million times (no load)
4 : RS485/Alarm 1
Electrical : Min. 100 thousand times (rated load)
5 : RS485/Alarm 1,Alarm 2
• SSR drive pulse voltage, DC 4~20mA are not insulated with internal circuit.
Use non-grounded sensor to R.T.D and thermocouple.

⑤ For waterproof (Waterproof type)


※ 제어출력구성
The instrument has IP65. Use rubber packing when installing the instrument to panel.
Please attach the rubber in correct way.
Recorder &
⑥ Caution on key operation / trouble Output code Control Output
Temperature Controller
● If alarm function is not set correctly, alarm output can not be operated at a trouble.
Be sure to check the alarm operation. 0 Relay (ON/OFFcontrol)
● If the input cable is disconnected, the display shows“ ”.
1 SSR
When replacing the sensor, please turn OFF the power supply.
RT9 - 1 2 SCR (4~20mADC)
⑦ Other
3 Relay (P.I.Dcontro)
Do not use organic solvents such as alcohol, benzine when cleaning. (Use neutral detergent)

5 6
4 3) FUNCTION
SPECIFICATION
Input correction (Bias): -100.0~100.0% for instrument range
1) INPUT Measurement input Scaling : According to SH, SL of measurement range
Filter : OFF, 1~120 sec.
Thermocouple: K, J, E, T, R, S, B, L, N, U, WRe 5-26, PL-Ⅱ
3 settings (SV1, SV2 and SV3) and P.I.D setting each
Input R.T.D: Pt 100Ω, KPt 100Ω
Direct voltage: 1~5V, -10~20mV, 0~100mV(Programmable scale type) Auto tuning : According to set value (Standard type, Low PV type)
Sampling time 250mS Proportional Band : 0.1~999.9% (Max. range)
Integral Time : OFF, 1~6000 sec.
Input resolution Below decimal point of measurement range Derivative Time : OFF, 1~6000 sec.
ON/OFF control: By selecting output code (OT)“ 0 ”
Input impedance T/C and mV input: 1MΩ min., DC V: 1MΩ
P.I.D selection : Zone PID/Auto 1,2,3, selectable
Lead wire tolerable Control
resistance R.T.D: 10Ωmax. / wire Manual Reset : -5.0~105.0% of output (valid when I=OFF)
Input ±10V (T/C, R.T.D, Voltage: mV DC) Direct / Reverse action : Changeable by parameter
tolerable voltage ±20V (Voltage: V DC) Preset output limit : -5.0~105.0% of output value
NMRR(normal mode): 40dB min. ON/OFF hysteresis (HYS): 0.0~100.0% of instrument range (valid when ON/OFF control)
Noise removal rate CMRR(common mode): 120dB min. (50/60Hz ±1%) A.R.W(Anti Reset Wind-up): AUTO, 50.0~200.0%
Standard T/C, R.T.D: KS, IEC, DIN Fuzzy : selection ON/OFF by parameter
Standard junction temp.
±1.5℃(15~35℃), ±2.0℃(0~50℃) Ramp function
compensation tolerance
T/C: OFF, Up/Down selectable Set point : 2 Points
Burn-out R.T.D: Up scale (Detection current: 50mA) Multi-alarm : High/Low process alarm, High/Low deviation alarm, Hold function of alarm,
Accuracy ±0.3% (Full scale) Alarm output Heater break alarm (H.B.A)
Refer to“Input signal and Measurement range” Setting range : Process alarm …… 0~100% of instrument range
Input range T/C and R.T.D are changeable within range of input signal and measurement range. Deviation alarm …… -100~100% of instrument range
Voltage: min. voltage and max. voltage are available within range of measurement.
Measuring point : 1
Scaling available.
Response time : According to chart speed
2) OUTPUT Record Record type : Thermal line
① ALARM (HBA OUTPUT)
Contact capacity: 240VAC 1A, 30V DC 1A(resistive load)
Relay
Contact: 1a
contact output
Output points: 2 Points (AL1,AL2)
4) OPERATING ENVIRONMENT
② CONTROL OUTPUT
Continuous vibration (5~14Hz): Forward width 1.2mm max.
Contact capacity: 240VAC 3A, 30VDC 3A (resistive load) (4~150Hz): 4.9㎨ (0.5G) max.
Contact: 1C
Output operation: P.I.D control, ON/OFF Installation environment Vibration : 14.7㎨ (1.5G), 15 sec. max. (each 3 direction)
Relay Proportional cycle: 1~1,000 sec. Shock : 147㎨ (15G), 11msec max. (6 direction each 3 times)
contact output Output limit: 0.0~100.0% range, higher limit(OH) or lower limit(OL) Panel cutout: Page 11, 12
selectable (valid when AT) Ambient temperature : 0~50℃
ON/OFF hysteresis: 0~100%(Full scale)
Time resolution: 0.1% or 10mS Normal operation Ambient humidity : 20~90%RH (no condensation)
ON voltage:24VDC min.(resistive load 600Ω min., 30mA limit when short) condition Influence of magnetic : 400AT/m max.
OFF voltage: 0.1VDC max. Warm-up time: 30 min. min.
SSR drive Proportional cycle: 1~1,000 sec. T/C, Voltage input : ±1μV/℃ or ±0.01%/℃ of max. range
voltage output Output operation: P.I.D control Influence of ambient
Output limit: 0.0~100.0% range, higher limit(OH) or lower limit(OL) R.T.D input : ±0.05Ω/℃ max.
temperature Analog output : ±0.05%/℃ max. (continuous output)
selectable (valid when AT)
Time resolution: 0.1% or 10mS
Current output range: 4~20mA DC
Resistive load: 600Ω max. 5) STORAGE CONDITION
Accuracy: ±0.5% of full scale (4~20mA range), Resolution: Approx. 3,000 Storage temperature -25~70℃
Output ripple: 0.3%(P-P) of max. scale (150Hz)
Current output Storage humidity 5~95%RH (no condensation)
Sampling time: 250mS
Output operation: P.I.D control Shock 1m max. in packing condition
Output limit: -5.0~105.0% range, higher limit(OH) or lower limit(OL)
selectable (valid when AT)

7 8
6) STRUOTURE
MODEL External Dimension Weight Material 10) INPUT SIGNAL and MEASUREMENT RANGE
Input type (Input signal) Input code Range (℃) Range(℉) Accuracy Remarks
RT9 96(W)×96(H)×100(D) mm 530 g Plastic case(ABS)
K 2 1 -200~1370 -300~2500
K 2 2 -199.9~999.9 0~2300
J 2 3 -199.9~999.9 -300~2300 ±0.5% of F.S
E 2 4 -199.9~999.9 -300~1800 ±1digit
7) POWER SUPPLY T 2 5 -199.9~400.0 -300~750
Power supply 100~240VAC(90~264VAC) R 2 6 0~1700 32~3100 •F.S is maxium value ~
Thermocouple
Frequency 50/60Hz (T.C) B 1 7 0~1800 32~3300 ±0.5% of F.S minimum value of
Power consumption 6.0W max., 10VA max. S 8 0~1700 32~3100 ±1digit each RANGE.
Between primary terminal and secondary terminal : DC 500V, 20MΩ min. L 2 9 -199.9~900.0 -300~1300 ±0.5% of F.S ±1digit •Digit is minimum value
Insulation resistance Between primary terminal and ground : DC 500V, 20MΩ min. N 10 -200~1300 -300~2400 ±1.0% of F.S ±1digit of display
Between ground and secondary terminal : DC 500V, 20MΩ min. U 2 11 -199.9~400.0 -300~750 1 0~400℃ :
±0.5% of F.S ±10% of F.S±1digit
Between primary terminal and secondary terminal : 2,300VAC 50/60Hz for 1 min. W 12 0~2300 32~4200
±1digit 2 0℃ and below :
Dielectric strength Between primary terminal and ground : 2,300VAC 50/60Hz for 1 min. PlatinelⅡ 13 0~1390 32~2500
Between F・G and secondary terminal : 1,500VAC 50/60Hz for 1 min. KSPt100 3 20 -199.9~500.0 -199.9~999.9 ±1.0% of F.S±1digit
R.T.D
Pt100 3 21 -199.9~640.0 -300~1180 3 -150.0~150.0℃ range
1~5V 30 1~5V : ±1.0% of F.S±1digit
Direct voltage -10~20mV 32 -10~20mV ±0.5% of F.S
(VDC/mVDC)
8) SAFETY AND EMC STANDARD 0~100mV 33 0~100mV ±1digit ※ 20 KPt100
※ When using current input, ※ 21 DPt100
Safety standard Under process Direct voltage DC 4~20mA ※ 30 use the resistor 250Ω
(mV) 0.1% on input terminal.
EMC standard Under process

9) INTERFACE
Standard EIA RS485
Communication address 0~31, 1~99 setting available
Communication method 2 wire half duplex or 4 wire half duplex
Synchronization Start-stop synchronous mode
Communication sequence None
Communication distance 1.2Km max.
600, 1200, 2400, 4800, 9600 BPS
Communication speed
(Speed is changeable by parameter)
Start bit 1 BIT
Data bit 7 or 8 BIT
Parity bit None, even numbers, odd numbers
Stop bit 1 or 2 BIT
Communication protocol PC LINK WITHOUT SUM(0), PC LINK WITH SUM(1)
Response time Reception treatment time + (Response time × 10mS)

9 10
5 DIMENSIONS & PANEL CUTOUT 7 NAME & FUNCTION

1) Front
● RT9 ( 96×96 mm ) ●Panel cutout

(Unit : mm )

6 TERMINAL ARRANGEMENT

2) Displays

Name Functions
① P.END No paper.
② RUN Under recording.
③ AL1 Alarm 1 ON.
④ AL2 Alarm 2 ON.
Displays set value and various parameters.
⑤ Set-value(SV)
(RT9-0 : Displays input type)
⑥ Process-value(PV) Display the process value. When setting, display various modes.
⑦ AT Flickers when the auto tuning operates.
● Terminal
⑧ OUT Lights when the control output is ON.
Relay(Terminal no. )
1) Control Output ⑨ RT9 Model name
SSR / SCR (Termina no. )
⑩ HANYOUNG Manufacturer
2) POWER 100 - 240 VAC 50/60 Hz. (Termina no. )

Termocouple: →+, →- 3) Control keys


3) Input sensor R.T.D: A, →B
Key Functions

Alarm1 (Termina no. ) ⑪ 모드버튼 Used to change mode.


4) AL1 / AL2 Alarm2 (Termina no. )

Sending data ( ) ⑫ 증가버튼 Used to increase set-value.


5) Communication Receiving data ( )
Earth ( ) ⑬ 감소버튼 Used to decrease set-value.

⑭ 쉬프트버튼 Used to select digit for changing.

11 12
8 TABLE OF SETTING ITEMS

전원투입

1)Operation 2)Menu

Operation display status.

3sec.

Set value changeable


Group Control Group Group P.I.D Group Alarm Group Group Output Group Input Group
Autotuning Communication Time setting

Output volume display

※Set a number

Parameter structure
○ Recorder exclusive use(RT9-0):
•Control group
•Alarm group (Optional)
•Communication group (Optional)
•Input group
•Time setting group will be displayed.

13 14
9 SETTING METHOD 10 GROUP SETTING

●After completion of wiring, apply power ON. ※ Display level setting


(1)Management version indicated as below and then present PV and SV will be indicated.
(Record exclusiue use : Input type and PV will be indicated) Signal Display Name Discription Condition Initial
(2)For setting a level, press button for 3 sec. to enter setting mode.(Initial value : 3 ) Divide display levels into
Display level setting 3 stages (1~3) Always 3
(3)In the condition, press button to enter group control.

This controller has 3 different levels of setting, thereby restricting operator access if so desired.

● Parameter shift
Power ON
1) Control group setting
Signal Name Description Condition Initial

●Recorder ●Recorder Control group display Set a control mode Always


(Model:RT9-0) & Controller
(Model:RT9-1) Zone selection 1 OFF / ON Except ON/OFF OFF
・Recorder:Displays input
Fuzzy function OFF / ON Always OFF
type and PV
・Recorder & controller: For 3 sec
Initial increasing temperature OFF / EUS (0~100 %) Always OFF
Displays SV and PV

Initial decreasing temperature OFF / EUS (0~100 %) Always OFF

Time unit HOUR / MIN Always HOUR

Set speed of transmission 24 ~ 900 mm/hour Always 60

Zome OFF / ON Always OFF


How to operate RECORDER

① RUN
buttons simultaneously Group Group Control
(RUN lamp will be ON) Control
Group Auto tuning
② Stop
buttons simultaneously Group PID
(RUN lamp will be OFF) Group
Alarm Group Alarm
③ Graphic or Word selection
In condition of printing, press Group Group
Communication
button for 3 sec.(Graphic →Word Commu
→Graphic→...) nication Group Output
④ List printing Group
Group Inputl
In condition of printing, press Inputl
button for 3 sec. Group Group
Time setting Time setting

15 16
2) Auto tuning group setting (Model: RT9-1)
When checking P.I.D. values or setting SV in manual
Signal Name Description Condition Initial mode, this can be done in P.I.D. Group. Maximum Range (Eu:100%)
Press key to get Anti Reset Wind value by auto or
Auto tuning group Indicates Auto-turing RT9-1
manual and then press once more to be indicated Zone 3
P.I.D mode which is selectable 3 types of P.I.D group Set point of Zone 2 (2,RP)
Auto tuning type / ABS STD Zone 2
(0~3). Example, “0”is no P.I.D mode and after seleting
Auto tuning start “1”using or and pressing , it is available to Set point of Zone 1 (1,RP)
OFF / 1~3 / ABS OFF Zone 1
change P.I.D value in zone “1”. “2” ( and “3”are same as
Time
① Auto-tuning “1”) Minimum (Eu: 0%)
The Auto tuning function automatically measures, computes and set the optimum P.I.D value. When integral time is OFF, manual reset mode is indicated
and then you could set reset value to remove off set.
【Note】After setting all group, select“ AUTO ” in Auto tuning group.
(range: -5%~105.0% of proportional band). You could set
② Auto-tuning type 3 zones by selecting zone mode ON.
This controller has two type of auto tuning as STD (standard type) and Low (Low PV type : SV-10%) . ※ In diagram,“n”is available to set 1~3 and proportional band of cooling side, integral time of
cooling side, hysteresis are indicated in Heating / Cooling type.
③ Auto-tuning start・stop
ⓐ Auto tuning start : 1~ 3 selection
(After auto tuning , P.I.D value will be stored at a selected number)
ⓑ Selection
When setting a value on L.RP and 2.RP, it is stored in group 1,2,3 automatically
ⓒ Auto tuning stop : Select OFF
4) Alarm group setting (Optional)

There are 2 alarm outputs available per conrtoller. In Alarm Group, setting are made for mode, dead
band and value of each alarm. Refer to the next page for the 20 different types of alarm functions.
In Heating・Cooling type of, is not indicated when selecting 10,11,12 (Refer to page 21.)
3) P.I.D설정그룹 (모델: RT9-1)
Signal Name Description Condition Initial value
Signal Name Description Condition Initial
Alarm group Set alarm mode
P.I.D group Set P.I.D mode RT9-1
Type of Alarm 1 OFF / 1~22 1
ANTI RESET WIND-UP Auto / 50.0~200.0 % Except ON/OFF Auto Refer to“Alarm type and code” Always
Type of Alarm 2 2
P.I.D group selection 0 / 1~3 Always 0
Dead band of Alarm 1
n.Proportional band (P) 0.1~999.9 % P.I.D group 5.0 % EUS ( 0.0~100.0% ) Always EUS(0.5%)
Dead band of Alarm 2
n.Integral time (I) OFF / 1~6000초 P.I.D group 240 sec
Set value of Alarm 1 PV alarm, Deviation alarm
Always EU(100.0%)
n.Derivative time (D) OFF / 1~6000초 P.I.D group 60 sec EU ( -100.0~100.0% ) EU(0.0%)
Set value of Alarm 2
n.Manual reset -5.0~105.0 % Integral time: OFF 50.0 %
※ Reference : Display lamp will be OFF when output ON in inverted type.
n.Zone position EU(0) < 1.RP < 2.RP < EU(100.0 %) ZONE : ON시 EU(100.0 %)

17 18
5) Communication group setting (Optional)
※ ALARM TYPE AND CODE
NX series are equipped with 4 wire /2 wire half-duplex the RS485 / RS422 communication
(Notice) : Display lamp will be ON when output OFF in inverted type. interfaces.Using the interfaces, communications are available with maximum 31 devices.
Hysteresis Signal Name Description Condition Initial value
(△ : Set point , : Minus Alarm set point , ▲ : Alarm set point )
Code Communication group Set communication mode
NO. Alarm type Function
RS485/RS422
1 High absolute value PC.LINK(Set value:0) / PC.LINK SUM (Set value:1) 0
Protocol
Communication rate 600(SV:0) / 1200(SV:1) / 2400(SV:2)
2 Low absolute value 4800(SV:3) / 9600(SV:4) 4
(B.P.S)
Parity check NONE(SV:0)/EVEN(SV:1)/ODD(SV:2) 1
* 3 High deviation value
Stop bit 1bit (SV:1) / 2bit (SV:2)
Optional
1
* 4 Low deviation value
Data length
7bit (SV:7) / 8bit (SV:8)
8
(Except PC LINK :8)
* 5 High deviation value (inverted)
Address 1~99 , maximum 31 devices 1
* 6 Low deviation value (inverted)
Response time 0~10. response time = (handling time + response 0
time) X 10ms
* 7 High・Low deviation value

6) Output group setting (Model : RT9-1)


* 8 High・Low band
Signal Name Description Conditi Initial value
9 High absolute (inverted)

Output group Output type and mode selection Model:RT9-1


10 Low absolute (inverted)
Output signal Refor to type of control output Always 3
11 High absolute with hold function
Output code
Output operation REV: Reverse DIR: Direct action
1~3 REV
12 Low absolute with hold function
Cycle time 1~1000 sec Relay / SSR 30 sec

* 13 High deviation with hold function Hysteresis of universal type EUS(0.0~100.0%)


Hysterecis of Heating/Cooling type 0.0~10.0%
ON/OFF Control
Heating/Cooling
0
0.5%
* 14 Low deviation with hold function
Output volume when input
disconnection Output (Out)
-5.0~105.0%
Always 0.0%
* 15 High deviation with hold function
(inverted)
Maximum value of output OL-L + 1Digit~ 105.0% Except ON/OFF 100.0%
* 16 Low deviation with hold function
(inverted) Minimum value of output -0.5%~ OL-H-1Digit Except ON/OFF 0.0 %
* 17 High・Low deviation with hold
function
CAUTION
* 18 High・Low band with hold
function
When setting, “Input type selection number” must be selected in the input type selection
19 High absolute value with hold
function (inverted) mode and also“Output type selection number”must be selected in the output type selection
Low absolute value with hold mode before moving to other mode.
20 function (inverted) If not, data of other group will be changed to prior value.
Output is selectable from Relay, SSR and Current(4~20mA DC)
*
Marked alarms are not available in RT9-0
For Recorder & Controller, output code 0~3 are available for your use.

19 20
7) Input group setting ③ Decimal point
Parameter is not indicated in T.C and R.T.D input, but when selecting voltage input “Decimal
point”mode is indicated. (set 1 : 0.0, set 2 : 0.00, set 3 : 0.000)
Signal Name Description Condition Initial value

Input group Input type and mode selection Always ④ Maximum and Minimum on scale
It is the same function as Maximum and Minimum Range setting when R.T.D or thermocouple
Selection
Input signal selection Refer to input signal and rang Always NO.1 input. This mode is indicated when voltage input ( 30, 31, 32, 33 )

High limit Refer to input signal and range Always 1370 ⑤ PV filter
( Notice : FR-H > FR-L ) When PV value becomes unstable due to effects of noise, the filter helps suppress the unstable
Low limit Always -200
status. (Range: OFF or 1~120sec. initial value: OFF)
Thermocouple or R.T.D : decimal point On voltage
Decimal point(on voltage input) 1
of instrument / DC Voltage : 0~3 input (mV,V)
Maximum on scale
⑥ PV bias
-1999~9999 100.0
(on voltage input) Use this function to adjust PV value in cases where it is necessary for PV value to agree with
Notice : SL-H › SL-L On voltage
Minimum on scale input (mV,V) another recorder or indicator, or when the sensor cannot be mounted in correct location.
(on voltage input) Deimal point : according to DP-P 0.0
(Range : -100.0~100.0% of SPAN, lnitial value : 0.0%)
PV filter OFF/1~120sec Always OFF Setting a value using or or key and press key to finish.

PV bias EUS (-100.0~100.0%) Always EUS(0.0%)


8) Time group setting
Burn-out OFF / UP / DOWN Always UP

Signal Name Description Condition I nitial value


CAUTION
Time setting Set Y, M, D, T. Always
When setting, “Input type selection number” must be selected in the input type selection
Present
mode and also“Output type selection number”must be selected in the output type selection Set Year 2000 ~ 2099 Always value
mode before moving to other mode. Present
If not, data of other group will be changed to prior value. Set Month 1 ~ 12 Always value

Set Day Present


① Input type selection 1 ~ 31 Always value
Present
After power ON and when PV is indicating, press key for 3 sec to be displayed at Set Mour 0 ~ 23 Always value
PV and 3 at SV. (If it is not indicated 3, set again in the level setting mode) Present
Control group is indicated when press key once more. At the time, input group is indicated Set Minute 0 ~ 59 Always value
when press key and then “Input type and range selection is shown at SV when press . Present
Set Second 0 ~ 59 Always
At this time the input and range is selected by or key. Press key to confirm value

② Maximum and Minimum range


Press key to set Maximum and Minimum range using or
or key. Press key once more to finish.

21 22
11 FUNCTION 5) F U Z ZY C O N T R O L 8) HOLD FUNCTION
Fuzzy control eliminates overshoot using Fuzzy Logic. Without hold function, Low limit alarm will be ON
Employing Fuzzy control and Auto-tuning, the when increasing temperature. (Picture 1)
1) AUTO TUNING 2) Auto-tuning in Zone PID controller effectively control as below.
The Auto tuning function automatically measures, Zone PID automatically sets PID group in accordance When the controller starts control at the position
computes and sets the optimum Proportional band(P), with a measured value. In Zone PID, auto-tuning sets which has a big gap between SV and PV. Hold function : None
Integral time(I), and Deri-vative time(D). When Auto-tuning, the proper PID value by recognizing a mid-value of When reducing warming up time PV
the controller performs ON/OFF reference point as set point value. When the load is fluctuating extreamly SV
control and determine proper P.I and D. (Limit cycle type) When changing a set point value frequently (low limit alarm)
max. value of
RT9-1 series controller have two types of Auto-tuning as measuriag
below. range (SV) Power ON
PID 3 Set point value Subsidary target value
Standard type auto-tuning : Reference Alarm output ON OFF ON OFF
Target set
point 2 value
This type is based on set point value (SV) PID 2
Low PV type auto-tuning : Reference measured (Picture 1)
This type is based on the value 10% lower than point 1 value
PID 1 Hold function
the set point value (SV) Time(t)
Time ( t )
min. value of measuring range Fuzzy Logic start PV
a) STANDARD TYPE AUTO-TUNING SV
(low limit alarm)

Temperature Under AT 3) RAMP FUNCTION


AT started AT finished 6) OUTPUT LIMIT Power ON
It is a rate of set value to arrive to set value
Set point according to setting temperature and time. Control output is set in high and low limit as operating range.
Alarm output OFF OFF ON OFF
value(SV)
ex) Present temp 20℃, set value 100℃,20℃ per min. Output limit is -5~105% of output.
Process 1) Initial uprising set value(up,rt) : 100℃ (Picture 2)
value(PV)
2) Unit time : Minute min) 9) RECORDER
Time(t) Output signal
① Run/Stop : You can record or stop when you need.
Control ON OFF ON OFF ON
output ℃ 20mA
Time(t) ② Feed : Paper be transmitted forcedly.
ON/OFF operation PID control 100
12mA
③ Graphic or Text selectable
80

60 Graphic Text
4mA

40
b) LOW PV TYPE AUTO-TUNING Output limit (%)
현재온도 20 ℃ -5% 50% 105%

Under AT 시간/분( t ) OL-L setting range OL-H


Temperature AT finished 1 2 3 4
AT started
Set point
value(SV) 4) ZOOM FUNCTION
SV-10% When you choose Zoom function ON in Group control,
you can see a temperature with zooming as soon as you 7) Emergency output
List printing : You can check and keep an im portant data
Process select ON. The tenperature will be in center of paper. When A/D error or input disconnection occur in auto which is set in each parameter.
value(PV)
Time(t) ex) Scale : 0.0 ~ 100.0 ℃ mode, PID output is cut and than Pre-set output is
Zoom ON : ZOOM IN 》PV. 25.5℃ at the center operated. (PO Output)
Control ON OFF ON OFF ON
output Time(t)
ON/OFF operation PID control

23 24