THE BRACE HAS TO FOLLOW THE BOTTOM OF

STEEL OF THE PURLINS AND THUS CANNOT


HAVE A BOLTED CONNECTION AT THIS END.
PLEASE REFER SKT-01 FOR CLARITY.
PURLINS RUN OVER WHERE THE BRACE HAVE TO
BE BOLTED TO THE GUSSET PLATES (ZERO GAP B/W
THE BRACE AND THE PURLIN)

SKT-01
IT SEEMS THAT THEY ARE PLANNING TO HOLD THE BRACE IN PLACE
WITH THESE ERECTION BOLTS AND THEN FIELD WELD THEM.
BUT THE PROBLEM OF BRACE CLASH WITH THE GUSSET AS IN SKT-03 IS
UNEXPLAINED.

SKT-02
BRACE SEEMS TO BE CLASHING WITH THE GUSSET
BECAUSE THE INDICATED SUPPORT RUNS PARALLEL TO THE
GROUND AND THE BRACE IS INCLINED TO MATCH ROOF SLOPE
(SINCE IT IS BOLTED TO THE PURLIN BOTTOM)

SKT-03