Distorsin de Voltaje Provocada por cargas no lineales

Corriente de la carga

i (t)
+ Vs(t) +
Carga No Lineal

V L(t) -

Voltaje de la Fuente

Voltaje de la Carga (distorsionado)

Correcin de factor de potencia ante la presencia de cargas no lineales

Filtro
CARGA NO LINEAL

Banco de capacitores

Condicin Original (480V) Z

Conectando banco de capacitores (480V) Z

Instalando filtros (480V) Z

Efecto de incrementar el tamao del banco en la frecuencia de resonancia X= 50% X= 30%

Armnica (h) X= kVAR/kVAT

Niveles de distorsin permitidos por el estndar IEEE-519 Distorsin en Voltaje

Voltaje V < 69 kV 69 < V < 161 kV V > 161 kV

Armnicas Individuales (%) 3.0 1.5 1.0

THD(%) 5.0 2.5 1.5

Niveles de distorsin permitidos por el estndar IEEE-519 Distorsin en Corriente


Icc/IL <20 20 a 50 50 a 100 100 a 1000 > 1000 TDDh (%) (h<11) 4 7 10 12 15 TDDh (%) (11<=h<17) 2 3.5 4.5 5.5 7 TDDh (%) TDDh (%) (17<=h<23) (23<=h<35) 1.5 0.6 2.5 1 4 1.5 5 2 6 2.5 TDDh (%) (35<=h) 0.3 0.5 0.7 1 1.4 TDD(%) 5 8 12 15 20

Icc(kA) =

MVA CC 3[kVLL ]

TDD (%) = 100 h

I I

h L

TDD

(%) = 100

h =hmax h=2 IL

I h2

IL representa el valor de corriente correspondiente al valor promedio de la demanda mxima que se ha presentado en los ltimos doce meses

Estndar IEEE-519
13.8 kV

h 1 5 7

IL(A) @ 13.8 kV 34.8 3.5 1.7

PCC-1

MVA

CC1

=200

ICC/IL = 243

ICC = 8.4 kA

1 MVA Z=6.0% Valores Registrados h 1 5 7 IL (A) @ 480 V 1000 100 50


PCC-2

IL

MVA

CC2

=15.4

ICC/IL = 18.5

ICC = 18.5 kA

Icc/IL <20 20 a 50 50 a 100 100 a 1000 > 1000

<11 4 7 10 12 15

11<=h<17 2 3.5 4.5 5.5 7

17<=h<23 1.5 2.5 4 5 6

23<=h<35 0.6 1 1.5 2 2.5

35<=h 0.3 0.5 0.7 1 1.4

TDD 5 8 12 15 20

PCC-1 PCC-2

I 5=3.5 A, I 7=1.7 A I 5=100 A, I 7=50 A

I 5,7 mx=4.18 I 5,7 max=40

Cumple con Estndar IEEE-519 NO Cumple con Estndar IEEE-519

Figura 3. Aplicacin del estndar IEEE-519 en una planta industrial

IEEE-519
Distorsiones por debajo del 5% son recomendables Distorsiones arriba del 5% provocan efectos negativos en motores, transformadores, relevadores, medidores, etc. Distorsiones arriba del 10% son INACEPTABLES El Estandar IEEE-519 recomienda que las compaas suministradoras mantengan los niveles de distorsin de voltaje debajo del 5%, y que los clientes mantengan la inyeccin de corriente debajo de valores que dependen de la rigidez del sistema. Los lmites establecidos para la corriente son fijados de tal manera que si todos los usuarios los respetan, la compaa suministradora puede mantener la distorsin por debajo del 5%

Diseo y simulacin de filtros de armnicas (Fundamentos)


En la mayora de los sistemas elctricos, el agregar un rectificador de 6 pulsos de 500 HP (o mayor) , puede provocar distorsiones de voltaje mayores del 5%. An y cuando la mayor distorsin de voltaje suele ocurrir en terminales del variador, en ocasiones se presenta en un bus remoto donde se tienen conectados bancos de capacitores, probablemente en un alimentador adyacente suministrado por el mismo transformador. La mayora de los problemas relacionados con armnicas en sistemas de distribucin son debidos a la 5a y 7a armnica debido a que los capacitores utilizados para corregir factor de potencia tienden a producir una frecuencia de resonancia en este rango de frecuencias. Los rectificadores de 12 pulsos causan menos problemas ya que no producen estas componentes.

Diseo y simulacin de filtros de armnicas (Fundamentos)

Con el objeto de cumplir con las recomendaciones del estndar, los clientes (y las compaas suministradoras) pueden agragar filtros paralelo. El objetivo es proporcionar trayectorias de baja impedancia a las corrientes armnicas y evitar que estas fluyan al resto del sistema, evitando de esta manera distorsiones elevadas de voltaje En muchas ocasiones es suficente instalar un filtro de 5a. Si no resultara suficiente, se pudiera agregar un filtro de sptima y, en casos ms complicados,pueden agregarse filtros de 11a, 13a y paso alto.

Utility

~
Low Voltage Bus

Nonlinear Load (VFD)

Filter

Effect of filter on voltage distortion


jh KVAn

jh SCKVA

Zs(h)

h2 n Zn(h)

I(h)

j h KVAn

an(h) = Attenuation factor of the h-th harmonic due to the n-th harmonic filter
an ( h ) = 1 + where
k=

kVA n ( 1 ) N kVA n ( N ) +L + SCKVA SCKVA


1

h 2 h (k ) n 2 h h n (k )

( (

) )
2

FlowChart for the computer program


Read system data Utility SCMVA, XFMR(Z and kVA) Drive KVA, Harmonic Spectra (%I(h)), Displacement power factor Filter(s) kVAr, Detuning Factors() Maximum allowed THDV(THDVmax)

Evaluate harmonic Voltages and THDV without filters DrivekVA V (h) = [%I(h)][h] SCKVA
THDV =

Calculate harmonic filter loading and harmonics flowing into the system V (h) I(h) In(h) = Zn(h) ; I s (h) = an(h)

[V (h )] h=5

43

Calculate filter specs using spredasheet filters.xls

Calculate attenuation factors an(h), resulting harmonic voltages and THDV


an( h) = 1 + 1 kVAn (1) kVAn ( N ) + L+ N SCKVA SCKVA

Generate Report *Voltage/current distortion * Filter sepecifications)


13.8 kV

SCMVA 50

5.75%

1000 kVA

Vf (h) =

V(h) an(h)

THDV =

[Vf (h)]
h=5

43

12903.2 SCKVA

480 V THDV 3.58% 0.031911 500kVAr @ 600V 472.50 A RMS 0.03256 233.62 A RMS 250kVAr @ 600V 5-th 7-th

Modify filter(s) kVAr

NO
THDV<THDVmax?

YES

900 kVA 6-pulse 250 HP 480-V CSI VFD(measured)

Case Study
UTILITY

~
480 V

13.8 kV
SCMVA=50 1000 KVA Z (%) = 5.75

...
150-HP PWM VFDs TOTAL LOAD =900 KVA

5th

7th

300 kVAR

150 kVAR

=0.95

=0.95

Simulation Results

Simulation Results
NO FILTERS %I(h) % V(h) 33.7 11.753 1.09 0.5322 7.37 5.6546 3.5 3.1736 3.5 4.1501 2.1 2.783 1.6 2.5668 1.4 2.4413 0.8 1.6182 0.9 1.946 0.6 1.4648 0.5 1.2904 0.4 1.1439 0.3 0.8998 15.176 FILTERS a(h) 6.03 7.66 2.55 2.39 2.25 2.22 2.18 2.17 2.15 2.15 2.14 2.14 2.13 2.13

h 5 7 11 13 17 19 23 25 29 31 35 37 41 43 THDV(%)

% Vf(h) 1.9504 0.0695 2.2158 1.3287 1.8409 1.2526 1.1759 1.1247 0.7513 0.906 0.6848 0.6042 0.537 0.4228 4.5581

Simulation Results

FUNDAMENTAL 5 7 11 13 17 19 23 25 29 31 35 37 41 43 HARM. CURRENT RMS CURRENT THDI (%)

XFMR(NO FILTERS) XFMR(FILTERS) 5TH FILTER 7TH FILTER I(AMPS) I(AMPS) I(AMPS) I(AMPS) 1082.5 982.62 402.75 196.90 364.8 60.54 347.45 43.18 11.8 1.54 1.60 8.66 79.8 31.26 21.50 27.02 37.9 15.86 10.24 11.78 37.9 16.81 10.20 10.88 22.7 10.23 6.11 6.39 17.3 7.93 4.64 4.75 15.2 6.98 4.05 4.12 8.7 4.02 2.31 2.33 9.7 4.54 2.60 2.61 6.5 3.04 1.73 1.73 5.4 2.53 1.44 1.44 4.3 2.03 1.15 1.14 3.2 1.53 0.86 0.86 379.2 1147.0 35.0% 73.85 985.39 7.52% 348.55 532.63 55.01 204.44

Simulation Results (Filter specs)


Low Voltage Filter Calculations:
SYSTEM INFORMATION: Filter Specification: Capacitor Bank Rating(Available) Rated Bank Current: Nominal Bus Voltage: Capacitor Current (actual): Filter Tuning Harmonic: Cap Impedance (wye equivalent): Reactor Impedance: Filter Full Load Current (actual): Filter Full Load Current (rated): Transformer Nameplate: (Rating and Impedance) Load Harmonic Current: Utility Harmonic Current: CAPACITOR DUTY CALCULATIONS: Filter RMS Current: Harmonic Cap Voltage: RMS Capacitor Voltage: 579.3 Amps 103.9 Volts 512.9 Volts Fundamental Cap Voltage: Maximum Peak Voltage: Maximum Peak Current: FILTER CONFIGURATION: 502.3 Volts 606.1 Volts 819.1 Amps 5 th 500 k V A r 481 A m p s 480 384.9 A m p s 4.75 0.7200 0.0319 402.8 A m p s 503.4 A m p s 1000 5.75 86.54 % F u n d 67.8 Amps Power System Frequency: Capacitor Rating: Derated Capacitor: Total Harmonic Load: Filter Tuning Frequency: Cap Value (wye equivalent): Reactor Rating: Supplied Compensation: Utility Side Vh: (Utility Harmonic Voltage Source) Load Harmonic Current: Max Total Harm. Current: 60 H z 600 V o l t s 60 H z 320 k V A r 900 k V A 285 H z 3 6 8 4 . 1 uF 0.0846 m H 335 k V A r 2.00 % T H D

Example Filter Design Spreadsheet

348.6 A m p s 416.4 A m p s

CAPACITOR LIMITS: (IEEE Std 18-1980) <> <> <> <>

Peak Voltage: Current: KVAr: RMS Voltage:

120% 180% 135% 110%

101% 120% 103% 85%

XL =>

0.0319

500 kVAR 600 V

FILTER REACTOR DESIGN SPECIFICATIONS: Reactor Impedance: Fundamental Current: 0.0319 402.8 Amps Reactor Rating: Harmonic Current: 0.0846 mH 416.4 Amps