LUM 1
UN CIRCUITO PARA 6 LUMINARIAS DE 75VA (FLUORESCENTE) Y UN
TOMACORRIENTE DE BAO:
6 LUMINARIAS
P = 6*71.25W = 427.5 W
PKW = 427.5W/1000 = 0.4275KW
PKVA = 0.4275KW/0.95 = 0.45KVA
I = P/V = 427.5 W /120 = 3.65A
UN TOMACORRIENTE
P = 150W
PKW = 150W/1000 = 0.15KW
PKVA = 0.15KW/.85 = 0.1765KVA
I = P/V = 150W/120 = 1.25A
LUM 2
UN CIRCUITO PARA 6 LUMINARIAS DE 75VA (FLUORESCENTE) Y UN
TOMACORRIENTE DE BAO:
6 LUMINARIAS
P = 6*71.25W = 427.5 W
PKW = 427.5W/1000 = 0.4275KW
PKVA = 0.4275KW/0.95 = 0.45KVA
I = P/V = 427.5 W /120 = 3.65A
UN TOMACORRIENTE
P = 150W
PKW = 150W/1000 = 0.15KW
PKVA = 0.15KW/.85 = 0.1765KVA
I = P/V = 150W/120 = 1.25A
LUM 3
UN CIRCUITO PARA 4 LUMINARIAS DE 75VA (FLUORESCENTE) Y UN
TOMACORRIENTE DE BAO:
4 LUMINARIAS
P = 4*71.25W = 285 W
PKW = 285 W /1000 = 0.285KW
PKVA = 0.285KW/0.95 = 0.3KVA
I = P/V = 285 W /120 = 2.375A
UN TOMACORRIENTE
P = 150W
PKW = 150W/1000 = 0.15KW
PKVA = 0.15KW/.85 = 0.1765KVA
I = P/V = 150W/120 = 1.25A
LUM 4
UN CIRCUITO PARA 6 LUMINARIAS DE 75VA (FLUORESCENTE) Y UN
TOMACORRIENTE DE BAO:
6 LUMINARIAS
P = 6*71.25W = 427.5 W
PKW = 427.5W/1000 = 0.4275KW
PKVA = 0.4275KW/0.95 = 0.45KVA
I = P/V = 427.5 W /120 = 3.65A
UN TOMACORRIENTE
P = 150W
PKW = 150W/1000 = 0.15KW
PKVA = 0.15KW/.85 = 0.1765KVA
I = P/V = 150W/120 = 1.25A
LUM 5
UN CIRCUITO PARA 6 LUMINARIAS DE 75VA (FLUORESCENTE)
P = 6*71.25W = 427.5 W
PKW = 427.5W/1000 = 0.4275KW
PKVA = 0.4275KW/0.95 = 0.45KVA
I = P/V = 427.5 W /120 = 3.65A
BCK=3.65A/0.8=4.56 A=10AMP
TC1
UN CIRCUITO PARA 5 TOMACORRIENTES:
P = 5*150W = 750W
PKW = 750W/1000 = 0.75KW
PKVA = 0.75KW/.85 =0.88 KVA
I = P/V = 750/120 = 6.25 AMP.
BCK=6.25 A/0.8=7.81 A=10AMP
TC2
UN CIRCUITO PARA 6 TOMACORRIENTES:
P = 6*150W = 900W
PKW = 900W/1000 = 0.9 KW
PKVA = 0.9KW/.85 = 1.06 KVA
I = P/V = 900/120 = 7.5 AMP.
BCK=7.5 A/0.8=9.38 A=10AMP
TC3
UN CIRCUITO PARA 6 TOMACORRIENTES:
P = 6*150W = 900W
PKW = 900W/1000 = 0.9 KW
PKVA = 0.9KW/.85 = 1.06 KVA
I = P/V = 900/120 = 7.5 AMP.
BCK=7.5 A/0.8=9.38 A=10AMP
TC4
UN CIRCUITO PARA 7 TOMACORRIENTES:
P = 7*150W = 1050W
PKW = 1050W/1000 = 1.05 KW
PKVA = 1.05KW/.85 = 1.24 KVA
I = P/V = 1050/120 = 8.75 AMP.
BCK=8.75 A/0.8=10.94 A=15AMP
TC5
UN CIRCUITO PARA AIRE ACONDICIONADO DE 2200W A 120V:
P = 2200W
PKW = 2200W/1000 = 2.2 KW
PKVA = 2.2KW/.85 = 2.5 KVA
I = P/V = 2200/120 = 18.33 AMP.
BCK=18.33 A/0.8=22.91 A=30AMP
TC6
UN CIRCUITO PARA AIRE ACONDICIONADO DE 12200W A 120V:
P = 1200W
PKW = 1200W/1000 = 1.2 KW
PKVA = 1.2KW/.85 = 1.41 KVA
I = P/V = 1200/120 = 10 AMP.
BCK=10 A/0.8=12.5 A=15AMP
TC7
UN CIRCUITO PARA AIRE ACONDICIONADO DE 12200W A 120V:
P = 1200W
PKW = 1200W/1000 = 1.2 KW
PKVA = 1.2KW/.85 = 1.41 KVA
I = P/V = 1200/120 = 10 AMP.
BCK=10 A/0.8=12.5 A=15AMP
TC8
UN CIRCUITO PARA CALENTADOR DE AGUA DE 2100W A 240V:
P = 2100W
PKW = 2100W/1000 = 2.1 KW
PKVA = 2.2KW/.1 = 2.1 KVA
I = P/V = 2100/240 = 10.94AMP.
BCK=10.94 A/0.8=22.91 A=15AMP
TC9
UN CIRCUITO PARA NEVERA DE 750W A 120V:
P = 750W
PKW = 750W/1000 = 0.75 KW
PKVA = 0.75KW/.85 = 0.88 KVA
I = P/V = 750W/120 = 6.25 AMP.
BCK=6.25 A/0.8=7.81A=10AMP
TC10
UN CIRCUITO PARA BOMBA DE AGUA DE 1.5 HP A 240 V:
P = 1119W
PKW = 1119W/1000 = 1.119 KW
PKVA = 1.119KW/.85 = 1.32 KVA
I = P/V = 1119W/240 = 4.66 AMP.
BCK=4.66 A/0.8=5.83 A=10AMP POR SER A 240= 30 AMP
TC11
UN CIRCUITO PARA TOSTADORA:
P = 1500W
PKW = 1500W/1000 = 1.5 KW
PKVA = 1.5KW/.85 = 1.77 KVA
I = P/V = 1500/120 = 12.5 AMP.
BCK=12.5 A/0.8=15. 63A=20AMP
TC12
UN CIRCUITO PARA EXTRACTOR Y ESTUFA:
P = 1500W
PKW = 1500W/1000 = 1.5 KW
PKVA = 1.5KW/.85 = 1.77 KVA
I = P/V = 1500/120 = 12.5 AMP.
BCK=12.5 A/0.8=15. 63A=20AMP
TC13
UN CIRCUITO PARA SECADORA A 1500W Y 120V:
P = 1500W
PKW = 1500W/1000 = 1.5 KW
PKVA = 1.5KW/.85 = 1.77 KVA
I = P/V = 1500/120 = 12.5 AMP.
BCK=12.5 A/0.8=15. 63A=20AMP
TC14
UN CIRCUITO PARA MICROONDA DE 1500W A 120 V:
P = 1500W
PKW = 1500W/1000 = 1.5 KW
PKVA = 1.5KW/.85 = 1.77 KVA
I = P/V = 1500/120 = 12.5 AMP.
BCK=12.5 A/0.8=15. 63A=20AMP
TC15
UN CIRCUITO PARA PLANCHA:
P = 1000W
PKW = 1000W/1000 = 1.0 KW
PKVA = 1.000KW/1 = 1.77 KVA
I = P/V = 1000/120 = 8.33 AMP.
BCK=8.33 A/0.8=10. 42A=20AMP
TC16
UN CIRCUITO PARA LAVADORA A 1500W Y 120V:
P = 1500W
PKW = 1500W/1000 = 1.5 KW
PKVA = 1.5KW/.85 = 1.77 KVA
I = P/V = 1500/120 = 12.5 AMP.
BCK=12.5 A/0.8=15. 63A=20AMP
TC17
UN CIRCUITO PARA PLANCHA:
P = 1000W
PKW = 1000W/1000 = 1.0 KW
PKVA = 1.000KW/1 = 1.77 KVA
I = P/V = 1000/120 = 8.33 AMP.
BCK=8.33 A/0.8=10. 42A=20AMP
TOTAL DE
CIRCUITOS
22
24.264
29.056
AMPERAJE
TOTAL
189.51A
UN TOMACORRIENTE
P = 150W
PKW = 150W/1000 = 0.15KW
PKVA = 0.15KW/.85 = 0.1765KVA
I = P/V = 150W/120 = 1.25
LUM 7
UN CIRCUITO PARA 5 LUMINARIAS DE 75VA (FLUORESCENTE) Y UN
TOMACORRIENTE DE BAO:
6 LUMINARIAS
P = 5*71.25W = 356.25 W
PKW = 356.25 /1000 = 0.356KW
PKVA = 0.356KW/0.95 = 0.338KVA
I = P/V = 356.25 W /120 = 2.97A
UN TOMACORRIENTE
P = 150W
PKW = 150W/1000 = 0.15KW
PKVA = 0.15KW/.85 = 0.1765KVA
I = P/V = 150W/120 = 1.25
LUM 8
UN CIRCUITO PARA 6 LUMINARIAS DE 75VA (FLUORESCENTE) Y UN
TOMACORRIENTE DE BAO:
6 LUMINARIAS
P = 6*71.25W = W
PKW = 427.5W/1000 = 0.4275KW
PKVA = 0.4275KW/0.95 = 0.45KVA
I = P/V = 427.5 W /120 = 3.65A
UN TOMACORRIENTE
P = 150W
PKW = 150W/1000 = 0.15KW
PKVA = 0.15KW/.85 = 0.1765KVA
I = P/V = 150W/120 = 1.25
TC18
UN CIRCUITO PARA 6 TOMACORRIENTES:
P = 6*150W = 900W
PKW = 900W/1000 = 0.9 KW
PKVA = 0.9KW/.85 = 1.06 KVA
I = P/V = 900/120 = 7.5 AMP.
BCK=7.5 A/0.8=9.38 A=10AMP
TC19
UN CIRCUITO PARA 6 TOMACORRIENTES:
P = 6*150W = 900W
PKW = 900W/1000 = 0.9 KW
PKVA = 0.9KW/.85 = 1.06 KVA
I = P/V = 900/120 = 7.5 AMP.
BCK=7.5 A/0.8=9.38 A=10AMP
TC20
UN CIRCUITO PARA 6 TOMACORRIENTES:
P = 6*150W = 900W
PKW = 900W/1000 = 0.9 KW
PKVA = 0.9KW/.85 = 1.06 KVA
I = P/V = 900/120 = 7.5 AMP.
BCK=7.5 A/0.8=9.38 A=10AMP
TC21
UN CIRCUITO PARA 6 TOMACORRIENTES:
P = 6*150W = 900W
PKW = 900W/1000 = 0.9 KW
PKVA = 0.9KW/.85 = 1.06 KVA
I = P/V = 900/120 = 7.5 AMP.
BCK=7.5 A/0.8=9.38 A=10AMP
TC22
UN CIRCUITO PARA AIRE ACONDICIONADO DE 12200W A 120V:
P = 1200W
PKW = 1200W/1000 = 1.2 KW
PKVA = 1.2KW/.85 = 1.41 KVA
I = P/V = 1200/120 = 10 AMP.
BCK=10 A/0.8=12.5 A=15AMP
TC23
UN CIRCUITO PARA AIRE ACONDICIONADO DE 12200W A 120V:
P = 1200W
PKW = 1200W/1000 = 1.2 KW
PKVA = 1.2KW/.85 = 1.41 KVA
I = P/V = 1200/120 = 10 AMP.
BCK=10 A/0.8=12.5 A=15AMP
TC24
UN CIRCUITO PARA CALENTADOR DE AGUA DE 2100W A 240V:
P = 2100W
PKW = 2100W/1000 = 2.1 KW
PKVA = 2.2KW/.1 = 2.1 KVA
I = P/V = 2100/240 = 10.94AMP.
BCK=10.94 A/0.8=22.91 A=15AMP
TC25
UN CIRCUITO PARA 6 TOMACORRIENTES:
P = 6*150W = 900W
PKW = 900W/1000 = 0.9 KW
PKVA = 0.9KW/.85 = 1.06 KVA
I = P/V = 900/120 = 7.5 AMP.
BCK=7.5 A/0.8=9.38 A=10AMP
TC26
UN CIRCUITO PARA AIRE ACONDICIONADO DE 12200W A 120V:
P = 1200W
PKW = 1200W/1000 = 1.2 KW
PKVA = 1.2KW/.85 = 1.41 KVA
I = P/V = 1200/120 = 10 AMP.
BCK=10 A/0.8=12.5 A=15AMP
TOTAL DE
CIRCUITOS
12
11.79
= 13.28
AMPERAJE
TOTAL
91.69 A
Descripcion
P/U
Valor Total
44
UD
RD$117,12
RD$5.153,28
44
UD
RD$35,86
RD$1.577,84
44
UD
RD$23,91
RD$1.052,04
15
UD
RD$48,23
RD$723,45
13
UD
RD$73,63
RD$957,19
UD
Interruptor 3w modus p
RD$57,51
RD$345,06
72
UD
RD$23,91
RD$1.721,52
72
UD
RD$61,00
RD$4.392,00
UD
Tomacorriente 240v
RD$81,96
RD$327,84
33
UD
RD$23,91
RD$789,03
UD
RD$78,00
RD$702,00
10
UD
RD$47,73
RD$477,30
72
UD
RD$18,08
RD$1.301,76
UD
RD$22,00
RD$88,00
UD
RD$59,00
RD$59,00
UD
Timbre Melodico
RD$500,23
RD$500,23
17
UD
RD$126,99
RD$2.158,83
UD
RD$288,09
RD$1.152,36
UD
RD$1.616,82
RD$3.233,64
132
pie
RD$17,31
RD$2.284,92
132
pie
RD$17,31
RD$2.284,92
132
pie
RD$17,31
RD$2.284,92
860
pie
RD$9,81
RD$8.436,60
860
pie
RD$9,81
RD$8.436,60
860
pie
RD$9,81
RD$8.436,60
790
pie
RD$6,05
RD$4.779,50
650
pie
RD$6,05
RD$3.932,50
55
pie
RD$6,05
RD$332,75
460
pie
RD$6,05
RD$2.783,00
150
pie
RD$1,80
RD$270,00
125
pie
Alambre Coaxial
RD$3,00
RD$375,00
UD
RD$35,00
RD$70,00
UD
RD$74,43
RD$372,15
88
UD
RD$54,26
RD$4.774,88
UD
RD$4,30
RD$34,40
160
UD
RD$2,54
RD$406,40
gal
Cemento PVC
RD$560,00
RD$560,00
UD
RD$171,31
RD$171,31
75
pie
RD$17,50
RD$1.312,50
UD
RD$1.731,42
RD$3.462,84
UD
RD$58,63
RD$58,63
UD
RD$63,53
RD$63,53
UD
Pararrayo 9Kv
RD$1.780,01
RD$3.560,02
210,3
pie
RD$70,71
RD$14.868,90
UD
RD$1.303,55
RD$2.607,10
UD
87
pie
RD$71,65
RD$6.233,55
52
pie
RD$46,00
RD$2.392,00
59
pie
RD$30,13
RD$1.777,67
UD
RD$1.858,88
RD$3.717,76
UD
RD$8.357,83
RD$8.357,83
RD$350,00
RD$350,00
UD
RD$112,15
RD$224,30
UD
RD$221,25
RD$442,50
RD$39,00
RD$78,00
UD
RD$262,71
RD$262,71
UD
RD$275,00
RD$550,00
UD
RD$3.650,00
RD$3.650,00
UD
RD$342,00
RD$342,00
RD$315,00
RD$315,00
RD$46.500,00 RD$46.500,00
UD
RD$38,65
RD$38,65
22
UD
RD$626,27
RD$13.777,94
UD
RD$430,64
RD$3.445,12
210,3
pie
Cinta de Peligro
RD$0,50
RD$105,14
UD
Viento Completo
RD$2.300,00
RD$4.600,00
UD
RD$2.500,00
RD$5.000,00
Total Materiales
RD$205.832,51
Mano de Obra
Canti
d
UD
Descripcion
P/U
Valor Total
44
UD
Rosetas
RD$140,00
RD$6.160,00
15
UD
Interruptor Sencillo
RD$200,00
RD$3.000,00
13
UD
Interruptor Doble
RD$225,00
RD$2.925,00
UD
Interruptor 3W
RD$270,00
RD$1.620,00
UD
RD$275,00
RD$2.475,00
10
UD
Salida Toma Tv
RD$180,00
RD$1.800,00
17
UD
Breaker 20 amp
RD$175,00
RD$2.975,00
UD
Breaker 30 amp
RD$200,00
RD$800,00
UD
Panel de Distribucion
RD$1.750,00
RD$3.500,00
UD
Pulsador de Timbre
RD$225,00
RD$225,00
UD
Timbre
RD$180,00
RD$180,00
UD
Switch piloto
RD$150,00
RD$150,00
UD
Conexin Tranformador
72
UD
RD$200,00
RD$14.400,00
UD
RD$250,00
RD$1.000,00
UD
RD$350,00
RD$700,00
UD
RD$1.600,00
RD$1.600,00
UD
RD$2.700,00
RD$5.400,00
465
m2
Diseo
RD$25,00
RD$11.625,00
RD$13.500,00 RD$13.500,00
RD$74.035,00
Total de Gastos
RD$279.867,51
Adicionales
Descripcion
Valor Total
Supervicion tecnica
18,00%
RD$50.376,15
Transporte
6,00%
RD$16.792,05
Viatico
4,00%
RD$11.194,70
Imprevistos
9,00%
RD$25.188,08
Total Adicionales
RD$103.550,98
HONORARIOS
COSTO
RD$279.867,51
RD$383.418,49
COBRO %
TOTAL
30%
RD $ 83,961.00
Total RD $363,829.00
INSTALACIONES ELCTRICAS
3ER PARCIAL
PROFESOR:
ING. JUAN JOS LIRIANO
PRESENTADO POR:
NOMBRE:
JEREMIAS DE JESUS ABREU
MATRICULA:
1-05-2978
GRUPO
003
FECHA
22/12/2008
SANTIAGO DE LOS CABALLEROS
R.D.