INSTRUMENT I/O LIST UNIT - 300

WBS NOS.
SAP010C300001EN1 SAP010C300002EN1 SAP010C300003EN1 SAP010C300004EN1 SAP010C300005EN1 SAP010C300006EN1 SAP010C300008EN1 SAP010C300009EN1 SAP010C500001EN1

CONFIDENTIAL AGREEMENT
ALL RIGHTS RESERVED. NO PART OF THIS DRAWING MAY BE REPRODUCED / STORED IN RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM FOR BY ANY MEANS ELECTRONIC, MECHANICAL, PHOTOCOPYING, XEROXING OR OTHERWISE WITHOUT PRIOR PERMISSION FROM CRISTAL

CLIENT

CRISTAL PIGMEN

THE NATIONAL TITANIUM DIO

YANBU AL-SINAIYAH, SA

KEAS CONTROL SYSTEM

PROJECT: 1 AS BUILT ISSUED FOR CONSTRUCTION ISSUED FOR APPROVAL


ISSUED FOR REVIEW & COMMENTS

5-Nov-11 25-Oct-10 24-Aug-10 23-Jul-10 DATE

JKA TA TA NS

MSR AAS AAS AAS

MSR MSR MSR MSR PROJECT NO: SAP010 TITLE:

6th OXIDIZ

AP - 206.1 TO AP - 545.7 AP - 001 TO AP - 004


DOCUMENT NO.

P & ID for 6 TH OXIDIZER P & ID SYMBOLS & LEGENDS DESCRIPTION REFERENCE DOCUMENT

0 B A REV

INSTRUMENT I/O
DOCUMENT NO. :

300-J3

REVISION DESCRIPTION

PREPARED CHECKED APPROVED CLIENT CONTRACT No:

ENT I/O LIST T - 300

WBS NOS.
SAP010C300001EN1 SAP010C300002EN1 SAP010C300003EN1 SAP010C300004EN1 SAP010C300005EN1 SAP010C300006EN1 SAP010C300008EN1 SAP010C300009EN1 SAP010C500001EN1

CRISTAL PIGMENT PLANT


THE NATIONAL TITANIUM DIOXIDE COMPANY YANBU AL-SINAIYAH, SAUDI ARABIA

KEAS CONTROL SYSTEMS INDIA PVT LTD

6th OXIDIZER PROJECT INSTRUMENT I/O LIST - UNIT 300 300-J3-3151


SIZE: A3 REV. 1 SHEET NO.: 1 OF 26

KEAS Control Systems India Pvt. Ltd.

Project SAP010

Document No. 300-J3-3151

REVISION INDEX SHEET


SL NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 SHEET NO 01 02 03 04 05 06 07 08 09 10 11 12 13 - 26 DESCRIPTION INSTRUMENT I/O LIST - COVER SHEET INSTRUMENT I/O LIST - INDEX SHEET INSTRUMENT I/O LIST - REVISION RECORD SHEET INSTRUMENT I/O LIST - SUMMARY SHEET INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 INSTRUMENT I/O LIST - UNIT 300 REV & DATE A A A A A A A A A A A A A 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 23-Jul-10 REV & DATE B B B B B B B B B B B B B 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 24-Aug-10 REV & DATE 0 0 0 0 0 0 0 0 0 0 0 0 0 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 25-Oct-10 REV & DATE 1 1 1 1 1 1 1 1 1 1 1 1 1 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 5-Nov-11 REV & DATE REV & DATE

Rev. 1

INDEX SHEET
REV & DATE

KEAS Control Systems India Pvt. Ltd.

Project SAP010

Document No. 300-J3-3151

REVISION RECORD SHEET


REV. NO. A B 0 1 PURPOSE ISSUED FOR REVIEW & COMMENTS ISSUED FOR APPROVAL ISSUED FOR CONSTRUCTION AS BUILT LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY

REV. B:- (TiCl4 & O2) Preheater Vendor instrument I/OS are removed from Instrument I/O List as per CRISTAL Comments during S Rev. 0:- Revised based on CRISTAL Comments. REV.1 :- Revised based on CRISTAL comments.

SHEET 2+1 OF 26

Document No. 300-J3-3151

Rev. 1

ECORD SHEET
LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY

ndor instrument I/OS are removed from Instrument I/O List as per CRISTAL Comments during Site Survey. Comments.

L comments.

SHEET 3+1 OF 26

KEAS Control Systems India Pvt. Ltd.

Project
SAP010

Document No.
300-J3-3151

I/O SUMMARY SHEET

DCS I/O SUMMARY

SL. NO.
1 2 3 4 5 6

TYPE
ANALOGUE INPUT (2 WIRE) ANALOGUE INPUT (4 WIRE) ANALOGUE OUTPUT DIGITAL INPUT (VOLT FREE CONTACT) DIGITAL INPUT (PROXIMITY) DIGITAL OUTPUT

QTY
86 18 31 66 18 64

REMARKS
A2 A4

C1 C2

SHEET 2+2 OF 26

Document No.
300-J3-3151

Rev.
1

MMARY SHEET

SHEET 3+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE
0 -60 0 - 60

Project SAP010

SEQ NO
1 2

TAG NO
3FT050 3FI050

INSTRUMENT TYPE
VORTEX FLOW METER FLOW TOTALIZER (BATCH)

SERVICE
PURE TICL4 FROM G-235A/B/C/D TO TICL4 HEATER E-323E/F PURE TICL4 FROM G-235A/B/C/D TO TICL4 HEATER E-323E/F

EQUIPT NO
E-323E/F E-323E/F

I/O TYPE
AI SCREEN DISPLAY

P & ID NO
AP-301 AP-301

LOOP NO (NOTE-1)

LOCATION
FIELD DCS

JB NO
3-JB-JS-36

POWER REQMT

DCS/PLC RANGE

UNIT
m3/hr m3/hr

LL ALARM

LO ALARM

HH ALARM

1 2 3 4

3HS050 3HY050 3HV050 3HHS050

HAND SWITCH (OPEN / CLOSE) ON POWER FAILURE SOLENOID VALVE HAND CONTROL VALVE (GLOBE) HAND SWITCH (RESET)

PURE TICL4 FROM G-235A/B/C/D TO TICL4 HEATER E-323E/F

E-323E/F

SCREEN DISPLAY DO

AP-301 AP-301 AP-301

DCS FIELD FIELD DCS 3-JB-JC-46

HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 HEATER E-323E/F E-323E/F HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 HEATER E-323E/F E-323E/F PURE TICL4 FROM G-235A/B/C/D TO TICL4 HEATER E-323E/F E-323E/F

SCREEN DISPLAY

AP-301

1 2 3 4 5

3TE065C 3TT065 3TIC065C 3TY065 3TV065C

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION / CONTROLLER E/P POSITIONER CONTROL VALVE (BUTTERFLY)

TICL4 FROM TICL4 HEATER E-323E/F TO ALCL3 DISSOLVING TANK E-323E/F D-303C TICL4 FROM TICL4 HEATER E-323E/F TO ALCL3 DISSOLVING TANK E-323E/F D-303C TICL4 FROM TICL4 HEATER E-323E/F TO ALCL3 DISSOLVING TANK E-323E/F D-303C PURE TICL4 FROM G-235A/B/C/D TO TICL4 HEATER E-323E/F PURE TICL4 FROM G-235A/B/C/D TO TICL4 HEATER E-323E/F E-323E/F E-323E/F AI SCREEN DISPLAY AO

AP-301 AP-301 AP-301 AP-301 AP-301

FIELD FIELD DCS FIELD FIELD 3-JB-JS-36 3-JB-JS-36 0-300 0-300 0 - 100 c c %

ALCL3 HANDLING
1 2 3 3XHS050C 3XY050C 3XV050C HAND SWITCH (RESET) ON POWER FAILURE SOLENOID VALVE ON / OFF VALVE (BALL) NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C D-340C D-340C D-340C SCREEN DISPLAY DO AP-302.1 AP-302.1 AP-302.1 DCS FIELD FIELD 3-JB-JC-46

1 2 3 4

3XY002C 3XV002C 3XZSC002C 3XZIC002C

SOLENOID VALVE ON / OFF VALVE (BALL) LIMIT SWITCH (CLOSE) VALVE STATUS INDICATION (CLOSE)

ALCL3 FROM ALCL3 VOLUMETRIC HOPPER D-301B TO ALCL3 PNEMATIC BLOW POT D-340C ALCL3 FROM ALCL3 VOLUMETRIC HOPPER D-301B TO ALCL3 PNEMATIC BLOW POT D-340C ALCL3 FROM ALCL3 VOLUMETRIC HOPPER D-301B TO ALCL3 PNEMATIC BLOW POT D-340C ALCL3 FROM ALCL3 VOLUMETRIC HOPPER D-301B TO ALCL3 PNEMATIC BLOW POT D-340C

D-340C D-340C D-340C D-340C

DO

AP-302.1 AP-302.1

DCS FIELD DCS DCS

3-JB-JC-46

DI SCREEN DISPLAY

AP-302.1 AP-302.1

3-JB-JC-46

1 2

3XY003C 3XV003C

SOLENOID VALVE ON/OFF VALVE(BALL)

ALCL3 FROM ALCL3 PNEUMATIC BLOW POT TO UNIT-300 SCRUBBER ALCL3 FROM ALCL3 PNEUMATIC BLOW POT TO UNIT-300 SCRUBBER

D-340C D-340C

DO

AP-302.1 AP-302.1

DCS FIELD

3-JB-JC-46

1 2

3XY004C 3XV004C

SOLENOID VALVE ON/OFF VALVE(BALL)

NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C

D-340C D-340C

DO

AP-302.1 AP-302.1

DCS FIELD

3-JB-JC-46

1 2

3XY005C 3XV005C

SOLENOID VALVE ON/OFF VALVE(BALL)

ALCL3 FROM PNEUMATIC BLOW POT D-340C TO ALCL3 DISSOLVING TANK D-303C ALCL3 FROM PNEUMATIC BLOW POT D-340C TO ALCL3 DISSOLVING TANK D-303C

D-340C D-340C

DO

AP-302.1 AP-302.1

DCS FIELD

3-JB-JC-46

1 2

3XY006C 3XV006C

SOLENOID VALVE ON/OFF VALVE(BALL)

NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C

D-340C D-340C

DO

AP-302.1 AP-302.1

DCS FIELD

3-JB-JC-46

SHEET 4+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

1 2 3

3XHS051C 3XY051C 3XV051C

HAND SWITCH (RESET) ON POWER FAILURE SOLENOID VALVE ON / OFF VALVE (BALL)

NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C NITROGEN TO ALCL3 PNEUMATIC BLOW POT D-340C

D-340C D-340C D-340C

SCREEN DISPLAY DO

AP-302.1 AP-302.1 AP-302.1

DCS FIELD FIELD 3-JB-JC-46

1 2

3PT004C 3PI004C

PRESSURE TRANSMITTER PRESSURE INDICATION

ALCL3 PNEUMATIC BLOW POT D-340C ALCL3 PNEUMATIC BLOW POT D-340C

D-340C D-340C

AI SCREEN DISPLAY

AP-302.1 AP-302.1

FIELD DCS

3-JB-JS-36

0-6 0 - 10

Barg Barg

1 2 3

3WE001C 3WT001C 3WI001C

LOAD CELL WEIGHT TRANSMITTER WEIGHT INDICATOR

ALCL3 VOLUMETRIC HOPPER D-301C ALCL3 VOLUMETRIC HOPPER D-301C ALCL3 VOLUMETRIC HOPPER D-301C

D-301C D-301C D-340C AI SCREEN DISPLAY

AP-302.1 AP-302.1 AP-302.1

FIELD FIELD DCS 3-JS-W001C

1 2

3LSH001C 3LAH001C

LEVEL SWITCH HIGH LEVEL HIGH ALARM

ALCL3 PNEUMATIC BLOW POT D-340C ALCL3 PNEUMATIC BLOW POT D-340C

D-340C D-340C

DI SCREEN DISPLAY

AP-302.1 AP-302.1

FIELD DCS

3-JB-JC-46

UPS POWER REQUIRED

1 2

3LSL002C 3LAL002C

LEVEL SWITCH LOW LEVEL LOW ALARM

ALCL3 PNEUMATIC BLOW POT D-340C ALCL3 PNEUMATIC BLOW POT D-340C

D-340C D-340C

DI SCREEN DISPLAY

AP-302.1 AP-302.1

FIELD DCS

3-JB-JC-46

UPS POWER REQUIRED YES

ALCL3 DISSOLVING
1 2 3LT036B 3LI036B LEVEL TRANSMITER (ULTRASONIC TYPE) LEVEL INDICATOR ALCL3 DISSOLVING TANK D-303C ALCL3 DISSOLVING TANK D-303C D 303C D 303C AI SCREEN DISPLAY AP303.2 AP303.2 FIELD DCS 3-JB-JS-36 0 - 100 0 - 100 % %

1 2 3

3TE002C 3TT002C 3TI002C

RTD (PT 100) TEMPERATURE TRANSMITER TEMPERATURE INDICATOR

ALCL3 DISSOLVING TANK D-303C ALCL3 DISSOLVING TANK D-303C ALCL3 DISSOLVING TANK D-303C

D 303C D 303C D 303C AI SCREEN DISPLAY

AP303.2 AP303.2 AP303.2

FIELD FIELD DCS 3-JB-JS-36 0 - 200 0 - 200 c c

1 2

3PSE007C 3PSA007C

PRESSURE / VACUUM RUPTURE DISC PRESSURE: 1 BARG) BURSTING DISC ALARM

(SET

ALCL3 DISSOLVING TANK D-303C ALCL3 DISSOLVING TANK D-303C

D 303C D 303C

DI SCREEN DISPLAY

AP303.2 AP303.3

FIELD DCS

3-JB-JC-46

300-J3-3156 1 3XL009C AGITATOR RUNNING INDICATION ALCL3 DISSOLVING TANK (D-303C) AGITATOR G-303C G-303C DI AP-303.2 (SHEET NO.189) DCS MCC

300-J3-3156 1 2 3 4 3HS003CA 3HS003CB 3IT001C 3II 001C AGITATOR SWITCH (START) AGITATOR SWITCH (STOP) CURRENT TRANSMITER CURRENT INDICATION ALCL3 DISSOLVING TANK (D-303C) AGITATOR G-303C ALCL3 DISSOLVING TANK (D-303C) AGITATOR G-303C ALCL3 DISSOLVING TANK (D-303C) AGITATOR G-303C ALCL3 DISSOLVING TANK (D-303C) AGITATOR G-303C G-303C G-303C G-303C G-303C DO DO AI SCREEN DISPLAY AP-303.2 (SHEET NO.189) 300-J3-3156 AP-303.2 (SHEET NO.189) AP-303.2 AP-303.2 MCC DCS MCC 0-200 0-200 Amps Amps DCS MCC DCS MCC

3XY007C

SOLENOID VALVE

ALCL3 FROM D-340B TO D-303C

D-303C

DO

AP-303.2

FIELD

3-JB-JC-46

SHEET 5+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
2 3 4

TAG NO
3XV007C 3XZSO007C 3XZIO007C

INSTRUMENT TYPE
ON/OFFVALVE(BALL) LIMIT SWITCH (OPEN) LIMIT SWITCH (OPEN STATUS) INDICATION

SERVICE
ALCL3 FROM D-340B TO D-303C ALCL3 FROM D-340B TO D-303C ALCL3 FROM D-340B TO D-303C

EQUIPT NO
D-303C D-303C D-303C

I/O TYPE

P & ID NO
AP-303.2

LOOP NO (NOTE-1)

LOCATION
FIELD DCS DCS

JB NO

POWER REQMT

UNIT

HH ALARM

DI SCREEN DISPLAY

AP-303.2 AP-303.2

3-JB-JC-46

1 2

3PT006C 3PI006C

PRESSURE TRANSMITTER PRESSURE INDICATION

ALCL3 FROM D-340B TO D-303C ALCL3 FROM D-340B TO D-303C

D-340C D-340C

AI SCREEN DISPLAY

AP-303.2 AP-303.2

FIELD DCS

3-JB-JS-36

0 - 1.5 0 - 1.5

Barg Barg

1 2

3LT036 3LI036

LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION

AICL3 DISSOLVING TANK D-303C AICL3 DISSOLVING TANK D-303C

D-303C D-303C

AI SCREEN DISPLAY

AP-303.2 AP-303.2

FIELD DCS

3-JB-JS-36

0 - 100 0 - 100

% %

1 2 3

3HS004C 3HY004C 3HV004C

HAND SWITCH(OPEN/CLOSE) SOLENOID VALVE ON/OFFVALVE(BALL)

TICL4 FROM AICL3 DISSOLVING TANK D-303C TO TICL4 SURGE TANK D-304C TICL4 FROM AICL3 DISSOLVING TANK D-303C TO TICL4 SURGE TANK D-304C TICL4 FROM AICL3 DISSOLVING TANK D-303C TO TICL4 SURGE TANK D-304C

D-304C D-304C D-304C

SCREEN DISPLAY DO

AP-303.2 AP-303.2 AP-303.2

DCS FIELD FIELD 3-JB-JC-46

1 2

3LT050 3LI050

LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION

TICL4 SURGE TANK D-304C TICL4 SURGE TANK D-304C

D-304C D-304C

AI SCREEN DISPLAY

AP-303.2 AP-303.2

FIELD DCS

3-JB-JS-36

0 - 100 0 - 100

% %

1 2

3LT050A 3LI050A

LEVEL TRANSMITTER (RADAR TYPE) LEVEL INDICATION

TICL4 SURGE TANK D-304C TICL4 SURGE TANK D-304C

D-304C D-304C

AI SCREEN DISPLAY

AP-303.2 AP-303.2

FIELD DCS

3-JB-JS-36

0 - 100 0 - 100 %

1 2 3

3TE003C 3TT003C 3TI003C

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 SURGE TANK D-304C TICL4 SURGE TANK D-304C TICL4 SURGE TANK D-304C

D-304C D-304C D-304C AI SCREEN DISPLAY

AP-303.2 AP-303.2 AP-303.2

FIELD FIELD DCS 3-JB-JS-36 0 - 200 0 - 200 c c

1 2

3PSE007E 3PSE007E

PRESSURE / VACUUM RUPTURE DISC (SET PRESSURE: 1 BARG) BURSTING DISC ALARM

TICL4 SURGE TANK D-304C TICL4 SURGE TANK D-304C

D-304C D-304C

DI SCREEN DISPLAY

AP-303.2 AP-303.2

FIELD DCS

3-JB-JC-46

TICL4 VAPORIZER "TRAIN 6" (E-301F1)


1 2 3 4 5 3FE602 3FT602 3FIC602 3FY602 3FV602 FLOW ELEMENT (CORIOLIS TYPE) FLOW TRANSMITTER FLOW INDICATION / CONTROLLER E/P POSITIONER CONTROL VALVE (BUTTERFLY) TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-301F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-301F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-301F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-301F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-301F E-301F1 E-301F1 E-301F1 E-301F1 E-301F1 AI SCREEN DISPLAY AO AP-304.6 AP-304.6 AP-304.6 AP-304.6 AP-304.6 FIELD FIELD DCS FIELD FIELD 3-JB-JS-38 3-JB-JS-38 UPS POWER REQUIRED 0 - 14000 0 - 14000 0 - 100 Kg/hr Kg/hr %

1 2 3

3FE603 3FT603 3FIC603

FLOW ELEMENT (FLOW NOZZLE) FLOW TRANSMITTER (DP TYPE) FLOW INDICATION / CONTROLLER

TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F

E-301F1 E-301F1 E-301F1 AI SCREEN DISPLAY

AP-304.6 AP-304.6 AP-304.6

FIELD FIELD DCS 3-JB-JS-38 0-4500 0-4500 Kg/hr Kg/hr

SHEET 6+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE
0 - 100

Project SAP010

SEQ NO
4 5

TAG NO
3FY603 3FV603 E/P POSITIONER

INSTRUMENT TYPE

SERVICE
TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F

EQUIPT NO
E-301F1 E-301F1

I/O TYPE
AO

P & ID NO
AP-304.6 AP-304.6

LOOP NO (NOTE-1)

LOCATION
FIELD FIELD

JB NO
3-JB-JS-38

POWER REQMT

UNIT
%

LL ALARM

LO ALARM

HH ALARM

CONTROL VALVE (BUTTERFLY)

1 2 3

3HS602 3HY602 3HV602

HAND SWITCH(OPEN/CLOSE) SOLENOID VALVE ON/OFF VALVE(PLUG )

TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F

E-301F1 E-301F1 E-301F1

SCREEN DISPLAY DO

AP-304.6 AP-304.6 AP-304.6

DCS FIELD FIELD 3-JB-JC-48

3HZSC001A

LIMIT SWITCH (CLOSE)

VAPORIZER E-301F1 INLET LINE

E-301F1

DI

AP-304.6

FIELD

3-JB-JC-48

1 2 3 4 5 6

3FT604 3FIC604 3HS603 3FY604AA 3FY604AB 3FV604

VORTEX FLOW METER FLOW INDICATION / CONTROLLER HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE E/P POSITIONER CONTROL VALVE (GLOBE)

NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE

E-301F1 E-301F1 E-301F1 E-301F1 E-301F1 E-301F1

AI SCREEN DISPLAY DO

AP-304.6 AP-304.6 AP-304.6 AP-304.6

FIELD DCS DCS FIELD FIELD FIELD

3-JB-JS-38

0 - 200 0 - 200

Nm3/hr Nm3/hr

3-JB-JC-48

AO

AP-304.6 AP-304.6

3-JB-JS-38

0 - 100

1 2 3 4 5 6

3FT605 3FIC605 3HS604 3FY605AA 3FY605AB 3FV605

VORTEX FLOW METER FLOW INDICATION / CONTROLLER HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE E/P POSITIONER CONTROL VALVE (GLOBE)

NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE NITROGEN TO TICL4 VAPOUR LINE

E-301F1 E-301F1 E-301F1 E-301F1 E-301F1 E-301F1

AI SCREEN DISPLAY DO

AP-304.6 AP-304.6 AP-304.6 AP-304.6

FIELD DCS DCS FIELD FIELD FIELD

3-JB-JS-38

0 - 600 0 - 600

Nm3/hr Nm3/hr

3-JB-JC-48

AO

AP-304.6 AP-304.6

3-JB-JS-38

0 - 100

1 2 3 4 5 6

3LT601A 3LIC601A 3LY601AA 3LY601AB 3LV601A 3HS601A

LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION / CONTROLLER SOLENOID VALVE E/P POSITIONER CONTROL VALVE (DIAPHRAGM ) HAND SWITCH (RESET)

TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1

E-301F1 E-301F1 E-301F1 E-301F1 E-301F1 E-301F1

AI SCREEN DISPLAY DO AO

AP-304.6 AP-304.6 AP-304.6 AP-304.6 AP-304.6

FIELD DCS FIELD FIELD FIELD DCS

3-JB-JS-37

0 - 100 0 - 100

% %

3-JB-JC-48 3-JB-JS-37 0 - 100 %

SCREEN DISPLAY

AP-304.6

1 2

3LT602A 3LI602A

LEVEL TRANSMITTER (RADAR TYPE) LEVEL INDICATION

TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1

E-301F1 E-301F1

AI SCREEN DISPLAY

AP-304.6 AP-304.6

FIELD DCS

3-JB-JS-37

UPS POWER REQUIRED

0 - 100 0 - 100

% %

1 2 3

3TE601A 3TT601A 3TI601A

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1

E-301F1 E-301F1 E-301F1 AI SCREEN DISPLAY

AP-304.6 AP-304.6 AP-304.6

FIELD FIELD DCS 3-JB-JS-37 0 - 300 0 - 300 c c

1 2 3

3HS601A 3HY601A 3HV601A

HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE ON/OFF VALVE (PLUG)

TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F

E-301F1 E-301F1 E-301F1

SCREEN DISPLAY DO

AP-304.6 AP-304.6 AP-304.6

DCS FIELD FIELD 3-JB-JC-48

SHEET 7+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

1 2 3 4

3XZSC006A 3XZIC006A 3XZSO006A 3XZIO006A

VALVE POSITION SWITCH (CLOSE) VALVE STATUS INDICATION (CLOSE) VALVE POSITION SWITCH (OPEN) VALVE STATUS INDICATION (OPEN)

TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F TICL4 FROM TICL4 FEED VAPORIZER E-301F1 TO VAPORIZER DISCHARGE B-310F

E-301F1 E-301F1 E-301F1 E-301F1

DI SCREEN DISPLAY DI SCREEN DISPLAY

AP-304.6 AP-304.6 AP-304.6 AP-304.6

FIELD DCS FIELD DCS

3-JB-JC-47

3-JB-JC-47

1 2

3PSE603A 3PSA603A

PRESSURE / VACUUM RUPTURE DISC PRESSURE: 5 BARG) BURSTING DISC ALARM

(SET

TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1

E-301F1 E-301F1

DI SCREEN DISPLAY

AP-304.6 AP-304.6

FIELD DCS

3-JB-JC-47

1 2 3 4 5 6 7 8

3XY06A 3XY06B 3PT602A 3PIC602A 3PY602AA 3PY602AB 3PV602A 3PHS602A

VAPORIZER - A SELECTION SWITCH VAPORIZER - B SELECTION SWITCH PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER SOLENOID VALVE E/P POSITIONER CONTROL VALVE (GLOBE) HAND SWITCH (RESET)

TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1 HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F1 TICL4 FEED VAPORIZER E-301F1

E-301F1 E-301F1 E-301F1 E-301F1 E-301F1 E-301F1 E-301F1 E-301F1

SCREEN DISPLAY SCREEN DISPLAY AI SCREEN DISPLAY DO AO

AP-304.6 AP-304.6 AP-304.6 AP-304.6 300-J3-3156 AP-304.6 (SHEET NO.176) AP-304.6 AP-304.6 300-J3-3156

DCS DCS FIELD DCS FIELD FIELD FIELD DCS (SHEET NO.176) 3-JB-JC-48 3-JB-JC-48 3-JB-JS-37 0 -100 % 3-JB-JS-37 0-6 0-6 Barg Barg

DI

AP-304.6

1 2 3

3FE601A 3FT601A 3FI601A

FLOW ELEMENT (ORIFICE) FLOW TRANSMITTER FLOW INDICATION

HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F1 HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F1 HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F1

E-301F1 E-301F1 E-301F1 AI SCREEN DISPLAY

AP-304.6 AP-304.6 AP-304.6

FIELD FIELD DCS 3-JB-JS-37 0 - 1200 Kg/hr

1 2 3

5LSHL052 5LAL052 5LAH052

LEVEL SWITCH LEVEL LOW ALARM LEVEL ALARM HIGH

SPILL SUMP F-5503E SPILL SUMP F-5503E SPILL SUMP F-5503E

F-5503E F-5503E F-5503E

AP-304.6 AP-304.6 AP-304.6

FIELD MCC MCC

MCC YES

TICL4 VAPORIZER "TRAIN 6" (E-301F2)


1 2 3 4 5 6 3LT601B 3LIC601B 3LY601BA 3LY601BB 3LV601B 3HS601C LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION / CONTROLLER SOLENOID VALVE E/P POSITIONER CONTROL VALVE (DIAPHRAGM) HAND SWITCH (RESET) TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 E-301F2 E-301F2 E-301F2 E-301F2 E-301F2 E-301F2 SCREEN DISPLAY AI SCREEN DISPLAY DO AO AP-304.7 AP-304.7 AP-304.7 AP-304.7 AP-304.7 FIELD DCS FIELD FIELD FIELD DCS 3-JB-JC-48 3-JB-JS-37 0 - 100 % 3-JB-JS-37 0 - 100 0 - 100 %

AP-304.7

1 2

3LT602B 3LI602B

LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION

TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2

E-301F2 E-301F2

AI SCREEN DISPLAY

AP-304.7 AP-304.7

FIELD DCS

3-JB-JS-37

UPS POWER REQUIRED 0 - 100 %

3TE601B

RTD (PT100)

TICL4 FEED VAPORIZER E-301F2

E-301F2

AP-304.7

FIELD

SHEET 8+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE
0 - 300 0 - 300

Project SAP010

SEQ NO
2 3

TAG NO
3TT601B 3TI601B

INSTRUMENT TYPE
TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

SERVICE
TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2

EQUIPT NO
E-301F2 E-301F2

I/O TYPE
AI SCREEN DISPLAY

P & ID NO
AP-304.7 AP-304.7

LOOP NO (NOTE-1)

LOCATION
FIELD DCS

JB NO
3-JB-JS-37

POWER REQMT

DCS/PLC RANGE

UNIT
c c

LL ALARM

LO ALARM

HH ALARM

1 2 3

3HS601B 3HY601B 3HV601B

HAND SWITCH (OPEN/CLOSE) SOLENOID VALVE ON/OFF VALVE(PLUG)

TICL4 FROM TICL4 FEED VAPORIZER E-301F2 TO TICL4 FEED VAPORIZER E-301F1 TICL4 FROM TICL4 FEED VAPORIZER E-301F2 TO TICL4 FEED VAPORIZER E-301F1 TICL4 FROM TICL4 FEED VAPORIZER E-301F2 TO TICL4 FEED VAPORIZER E-301F1

E-301F2 E-301F2 E-301F2

SCREEN DISPLAY DO

AP-304.7 AP-304.7 AP-304.7

DCS FIELD FIELD 3-JB-JC-48

3HZSC001B

LIMIT SWITCH (CLOSE)

VAPORIZER E-301F2 INLET LINE

E-301F2

DI

AP-304.7

FIELD

3-JB-JC-48

1 2 3 4

3XZSC006B 3XZIC006B 3XZSO006B 3XZIO006B

VALVE POSITION SWITCH (CLOSE) VALVE STATUS INDICATION (CLOSE) VALVE POSITION SWITCH (OPEN) VALVE STATUS INDICATION (OPEN)

TICL4 FROM TICL4 FEED VAPORIZER E-301F2 TO EXTRACTION HEADER D-557 TICL4 FROM TICL4 FEED VAPORIZER E-301F2 TO EXTRACTION HEADER D-557 TICL4 FROM TICL4 FEED VAPORIZER E-301F2 TO EXTRACTION HEADER D-557 TICL4 FROM TICL4 FEED VAPORIZER E-301F2 TO EXTRACTION HEADER D-557

E-301F2 E-301F2 E-301F2 E-301F2

DI SCREEN DISPLAY DI SCREEN DISPLAY

AP-304.7 AP-304.7 AP-304.7 AP-304.7

FIELD DCS FIELD DCS

3-JB-JC-47

3-JB-JC-47

PRESSURE / VACUUM RUPTURE DISC 1 2 3PSE603B BARG) 3PSA603B BURSTING DISC ALARM TICL4 FEED VAPORIZER E-301F2 E-301F2 SCREEN DISPLAY AP-304.7 (SHEET NO.161) (SET PRESSURE: 5 TICL4 FEED VAPORIZER E-301F2 E-301F2 DI AP-304.7 300-J3-3156 DCS FIELD 3-JB-JC-47

1 2 3 4 5 6 7 8

3XY06C 3XY06D 3PT602B 3PIC602B 3PY602BA 3PY602BB 3PV602B 3PHS602B

VAPORIZER-A SELECTION SWITCH VAPORIZER-B SELECTION SWITCH PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER SOLENOID VALVE E/P POSITIONER CONTROL VALVE (GLOBE) HAND SWITCH (RESET)

TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2 HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F2 TICL4 FEED VAPORIZER E-301F2

E-301F2 E-301F2 E-301F2 E-301F2 E-301F2 E-301F2 E-301F2 E-301F2

SCREEN DISPLAY SCREEN DISPLAY AI SCREEN DISPLAY DO AO

AP-304.7 AP-304.7 AP-304.7 AP-304.7 300-J3-3156 AP-304.7 (SHEET NO.177) AP-304.7 AP-304.7 300-J3-3156

DCS DCS FIELD DCS FIELD FIELD FIELD DCS (SHEET NO.177) 3-JB-JC-48 3-JB-JC-48 3-JB-JS-37 0 - 100 % 3-JB-JS-37 0 -6 0-6 Barg Barg

DI

AP-304.7

1 2 3

3FE601B 3FT601B 3FI601B

FLOW ELEMENT (ORIFICE) FLOW TRANSMITTER FLOW INDICATION

HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F12 HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F2 HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 FEED VAPORIZER E-301F2

E-301F2 E-301F2 E-301F2 AI SCREEN DISPLAY

AP-304.7 AP-304.7 AP-304.7

FIELD FIELD DCS 3-JB-JS-37 0 - 1200 Kg/hr

TICL4 PREHEATER "TRAIN 6"


1 2 3 3TE602 3TT602 3TI602 THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 HEATER B-301F B-301F HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 HEATER B-301F B-301F HIGH PRESSURE STEAM FROM STEAM HEADER TO TICL4 HEATER B-301F B-301F AI SCREEN DISPLAY AP-305.6 AP-305.6 AP-305.6 FIELD FIELD DCS 3-JB-JS-38 0 - 300 0 - 300 c c

1 2

3PT606 3PI606

PRESSURE TRANSMITTER PRESSURE INDICATION

NITROGEN FROM NITROGEN HEADER TOTICL4 FEED VAPORIZER E-301F1 NITROGEN FROM NITROGEN HEADER TOTICL4 FEED VAPORIZER E-301F1

B-301F B-301F

AI SCREEN DISPLAY

AP-305.6 AP-305.6

FIELD DCS

3-JB-JS-38

0-3 0-3

Barg Barg

1 2

3TE629 3TT629

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER

TICL4 HEATER B-301F TICL4 HEATER B-301F

B-301F B-301F AI

AP-305.6 300-J3-3156 AP-305.6 (SHEET NO.108)

FIELD FIELD 3-JB-JS-622F 0 - 800 c

SHEET 9+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE
0 - 800

Project SAP010

SEQ NO
3

TAG NO
3TI629

INSTRUMENT TYPE
TEMPERATURE INDICATION TICL4 HEATER B-301F

SERVICE

EQUIPT NO
B-301F

I/O TYPE
SCREEN DISPLAY

P & ID NO
AP-305.6

LOOP NO (NOTE-1)

LOCATION
DCS

JB NO

POWER REQMT

UNIT
c

LL ALARM

LO ALARM

HH ALARM

300-J3-3156 1 3TAH630 TEMPERATURE ALARM HIGH TICL4 HEATER B-301F B-301F DI AP-305.6 (SHEET NO.180) DCS 0 - 1200 c

1 2 3

3TE603 3TT603 3TI603

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 HEATER B-301F TICL4 HEATER B-301F TICL4 HEATER B-301F

B-301F B-301F B-301F AI SCREEN DISPLAY

AP-305.6 AP-305.6 AP-305.6

FIELD FIELD DCS 3-JB-JS-622F 0-500 0-500 c c

1 2 3

3TE604 3TT604 3TI604

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 HEATER B-301F TICL4 HEATER B-301F TICL4 HEATER B-301F

B-301F B-301F B-301F AI SCREEN DISPLAY

AP-305.6 AP-305.6 AP-305.6

FIELD FIELD DCS 3-JB-JS-622F 0-500 0-500 c c

1 2 3

3TE605 3TT605 3TI605

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 HEATER B-301F TICL4 HEATER B-301F TICL4 HEATER B-301F

B-301F B-301F B-301F AI SCREEN DISPLAY

AP-305.6 AP-305.6 AP-305.6

FIELD FIELD DCS 3-JB-JS-622F 0-500 0-500 c c

1 2 3

3TE606 3TT606 3TI606

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 HEATER B-301F TICL4 HEATER B-301F TICL4 HEATER B-301F

B-301F B-301F B-301F AI SCREEN DISPLAY

AP-305.6 AP-305.6 AP-305.6

FIELD FIELD DCS 3-JB-JS-622F 0-500 0-500 c c

1 2 3

3TE607 3TT607 3TI607

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 HEATER B-301F TICL4 HEATER B-301F TICL4 HEATER B-301F

B-301F B-301F B-301F AI SCREEN DISPLAY

AP-305.6 AP-305.6 AP-305.6

FIELD FIELD DCS 3-JB-JS-622F 0-1200 0-1200 c c

1 2 3 4 5 6

3TE639 3TT639 3TIC639 3TY639 3TV639 3TZIC639

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION / CONTROLLER E/P POSITIONER CONTROL VALVE (GLOBE VALVE) LIMIT SWITCH INDICATION (CLOSE)

PREHEATED TICL4 FROM B-301F TO NITROGEN TO B-309F OXIDISER PREHEATED TICL4 FROM B-301F TO NITROGEN TO B-309F OXIDISER PREHEATED TICL4 FROM B-301F TO NITROGEN TO B-309F OXIDISER FUEL GAS TO TICL4 HEATER B-301F FUEL GAS TO TICL4 HEATER B-301F FUEL GAS TO TICL4 HEATER B-301F

B-309F B-309F B-309F B-301F B-301F B-301F DI AI SCREEN DISPLAY AO

AP-307.6 300-J3-3156 AP-307.6 (SHEET NO.111) AP-307.6 300-J3-3156 AP-305.6 (SHEET NO.111) AP-305.6 300-J3-3156 AP-305.6 (SHEET NO.184) 300-J3-3156

FIELD FIELD DCS FIELD FIELD DCS 3-JB-JS-622F 3-JB-JS-622F 0 - 1200 0 - 1200 0 - 100 c c %

1 2 3 4

3UA601 3UA602 3HS609 3HS637

COMMON ALARM COMMON SHUTDOWN ALARM REMOTE EMERGENCY SHUTDOWN PERMISSIVE FOR MAIN BURNER LIGHT UP

COMMON ALARM SIGNAL FROM BMS PANEL TO DCS COMMON SHUTDOWN ALARM FROM BMS PANEL TO DCS EMERGENCY SHUTDOWN SIGNAL FROM DCS TO BMS PANEL START PERMISSIVE SIGNAL FROM BMS PANEL TO DCS

B-301F B-301F B-301F B-301F

DI DI DO DI

AP-305.6 (SHEET NO.185) 300-J3-3156 AP-305.6 (SHEET NO.186) AP-305.6 AP-305.6

DCS DCS DCS DCS

1 2

3FT607 3FI607

FLOW TRANSMITTER (VORTEX METER) FLOW INDICATOR

FUEL GAS TO TICL4 HEATER B-301F FUEL GAS TO TICL4 HEATER B-301F

B-301F B-301F

AI SCREEN DISPLAY

AP-305.6 AP-305.6

FIELD DCS

3-JB-JS-38

0 - 150

Nm3/hr

SHEET 10+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

OXYGEN PREHEATER "TRAIN 6"


1 2 3 4 5 6 7 8 9 3HS614A 3HS614B 3HHS614 3HY614 3HV614 3HZSC614 3HZIC614 3HZSO614 3HZIO614 HAND SWITCH (OPEN / CLOSE) HAND SWITCH (OPEN / CLOSE) HAND SWITCH (RESET) SOLENOID VALVE ON / OFF VALVE (BALL) LIMIT SWITCH (CLOSE) VALVE STATUS INDICATION (CLOSE) LIMIT SWITCH (OPEN) VALVE STATUS INDICATION (OPEN) OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F B-305F B-305F B-305F B-305F B-305F B-305F B-305F B-305F B-305F DI SCREEN DISPLAY DI SCREEN DISPLAY SCREEN DISPLAY DI DI DO AP-306.6 AP-306.6 AP-306.6 AP-306.6 AP-306.6 AP-306.6 AP-306.6 AP-306.6 AP-306.6 DCS FIELD FIELD FIELD FIELD FIELD DCS FIELD DCS 3-JB-JC-49 3-JB-JC-49 3-JB-JC-49 3-JB-JC-49 3-JB-JC-49

1 2 3 4

3PT609 3PIC609 3PY609 3PV609

PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER E/P POSITIONER PRESSURE CONTROL VALVE (SET PRESSURE: 3.8 BARG)

OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F

B-305F B-305F B-305F B-305F

AI SCREEN DISPLAY AO

AP-306.6 AP-306.6 AP-306.6 AP-306.6

FIELD DCS FIELD FIELD

3-JB-JS-39

0-3 0-3

Barg Barg %

3-JB-JS-39

0 - 100

1 2 3 4

3FT609 3FIC609 3FY609 3FV609

FLOW TRANSMITTER(COROLIS TYPE) FLOW INDICATION / CONTROLLER E/P POSITIONER FLOW CONTROL VALVE (GLOBE VALVE)

OXYGEN TO OXYGER HEATER B-305F OXYGEN TO OXYGER HEATER B-305F OXYGEN TO OXYGER HEATER B-305F OXYGEN TO OXYGER HEATER B-305F

B-305F B-305F B-305F B-305F

AI SCREEN DISPLAY AO

AP-306.6 AP-306.6 AP-306.6 AP-306.6

FIELD DCS FIELD FIELD

3-JB-JS-39

UPS POWER REQUIRED

0 - 1500 0 - 1500

Nm3/hr Nm3/hr %

3-JB-JS-39

0 - 100

1 2

3PT611 3PI611

PRESSURE TRANSMITTER PRESSURE INDICATOR

OXYGEN TO OXYGEN HEATER B-305F OXYGEN TO OXYGEN HEATER B-305F

B-305F B-305F

AI SCREEN DISPLAY

AP-306.6 AP-306.6

FIELD DCS

3-JB-JS-39

0-3 0-3

Barg Barg

1 2

3HY636 3HV636

SOLENOID VALVE HAND VALVE

UTILITY AIR TO OXYGEN HEATER B-305F UTILITY AIR TO OXYGEN HEATER B-305F

B-305F B-305F

DO SCREEN DISPLAY

AP-306.6 AP-306.6

FIELD DCS

3-JB-JC-49

300-J3-3156 1 2 3 4 3UA603 3UA604 3HS612 3HS638 COMMON ALARM COMMON SHUTDOWN ALARM REMOTE EMERGENCY SHUTDOWN PERMISSIVE FOR MAIN BURNER LIGHT UP AT MINIMUM FIRING COMMON ALARM SIGNAL FROM BMS PANEL TO DCS COMMON SHUTDOWN ALARM FROM BMS PANEL TO DCS EMERGENCY SHUTDOWN SIGNAL FROM DCS TO BMS PANEL START PERMISSIVE SIGNAL FROM BMS PANEL TO DCS B-305F B-305F B-305F B-305F DI DI DO DI AP-306.6 (SHEET NO.187) 300-J3-3156 AP-306.6 (SHEET NO.188) AP-306.6 AP-306.6 DCS DCS DCS DCS

1 2 3

3FE608 3FT608 3FI608

FLOW ELEMENT (INTEGRAL ORIFICE) FLOW TRANSMITTER FLOW INDICATOR

FUEL GAS TO OXYGEN PREHEATER B-305F FUEL GAS TO OXYGEN PREHEATER B-305F FUEL GAS TO OXYGEN PREHEATER B-305F

B-305F B-305F B-305F AI SCREEN DISPLAY

AP-306.6 AP-306.6 AP-306.6

FIELD FIELD DCS 3-JB-JS-39 0 - 90 Nm3/hr

SHEET 11+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
1 2 3 5 6

TAG NO
3TE615A 3TT615A 3TIC615A 3TY615 3TV615

INSTRUMENT TYPE
THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION/CONTROLLER E/P POSITIONER CONTROL VALVE (GLOBE VALVE)

SERVICE
OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F FUEL GAS TO OXYGEN PREHEATER B-305F FUEL GAS TO OXYGEN PREHEATER B-305F

EQUIPT NO
B-305F B-305F B-305F B-305F B-305F

I/O TYPE

P & ID NO
AP-306.6

LOOP NO (NOTE-1)

LOCATION
FIELD FIELD DCS FIELD FIELD

JB NO

POWER REQMT

UNIT

HH ALARM

AI SCREEN DISPLAY AO

AP-306.6 AP-306.6 AP-306.6 AP-306.6

3-JB-JS-632F

0 - 1200 0 - 1200

c c %

3-JB-JS-632F

0 - 100

1 2 3

3TE617 3TT617 3TI617

THEMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F

B-305F B-305F B-305F AI SCREEN DISPLAY

AP-306.6 AP-306.6 AP-306.6

FIELD FIELD DCS 3-JB-JS-632F 0-1100 0-1100 c c

1 2 3

3TE638A 3TT638A 3TI638A

THERMOCOUPLE (KTYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F

B-305F B-305F B-305F AI SCREEN DISPLAY

AP-306.6 300-J3-3156 AP-306.6 (SHEET NO.110) AP-306.6

FIELD FIELD DCS 3-JB-JS-632F 0-1200 0-1200 c c

1 2 3

3TE616A 3TT616A 3TI616A

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F

B-305F B-305F B-305F AI SCREEN DISPLAY

AP-306.6 AP-306.6 AP-306.6

FIELD FIELD DCS 3-JB-JS-632F 0-1100 0-1100 c c

1 2 3

3TE614A 3TT614A 3TI614A

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F

B-305F B-305F B-305F AI SCREEN DISPLAY

AP-306.6 AP-306.6 AP-306.6

FIELD FIELD DCS 3-JB-JS-632F 0-1200 0-1200 c c

1 2 3

3TE613A 3TT613A 3TI613A

THERMOCOUPLE (KTYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F OXYGEN PREHEATER B-305F

B-305F B-305F B-305F AI SCREEN DISPLAY

AP-306.6 AP-306.6 AP-306.6

FIELD FIELD DCS 3-JB-JS-632F 0-1200 0-1200 c c

OXIDISER "TRAIN 6"


1 2 3 4 5 3FE612 3FT612 3FIC612 3FY612 3FV612 FLOW ELEMENT (INTEGRAL ORIFICE) FLOW TRANSMITTER FLOW INDICATION / CONTROLLER E/P POSITIONER FLOW CONTROL VALVE (GLOBE VALVE) NITROGEN TO B-309F OXIDISER NITROGEN TO B-309F OXIDISER NITROGEN TO B-309F OXIDISER NITROGEN TO B-309F OXIDISER NITROGEN TO B-309F OXIDISER B-309F B-309F B-309F B-309F B-309F AI SCREEN DISPLAY AO AP-307.6 AP-307.6 AP-307.6 AP-307.6 AP-307.6 FIELD FIELD DCS FIELD FIELD 3-JB-JS-42 0 - 100 % 3-JB-JS-42 0 - 7176 mmWC

1 2

3LSH603 3LAH603

LEVEL SWITCH HIGH LEVEL ALARM HIGH

SAND SURGE HOPPER F-305F SAND SURGE HOPPER F-305F

F-305F F-305F

DI SCREEN DISPLAY

AP-307.6 AP-307.6

FIELD DCS

3-JB-JC-50

3HS605

HAND SWITCH

SAND FROM D-1305 TO SAND SURGE HOPPER F-305F

F-305F

SCREEN DISPLAY

AP-307.6

DCS

SHEET 12+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
2 3

TAG NO
3HY605 3HV605

INSTRUMENT TYPE
SOLENOID VALVE HAND VALVE

SERVICE
SAND FROM D-1305 TO SAND SURGE HOPPER F-305F SAND FROM D-1305 TO SAND SURGE HOPPER F-305F

EQUIPT NO
F-305F F-305F

I/O TYPE
DO

P & ID NO
AP-307.6 AP-307.6

LOOP NO (NOTE-1)

LOCATION
FIELD FIELD

JB NO
3-JB-JC-50

POWER REQMT

UNIT

HH ALARM

1 2 3 4 5 6

3PT684 3PIC684 3PY684A 3PV684A 3PY684B 3PV684B

PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER E/P POSITIONER PRESSURE CONTROL VALVE E/P POSITIONER PRESSURE CONTROL VALVE

VENT FROM SAND SURGE HOPPER F-305F TO OUTSIDE OF THE BUILDING VENT FROM SAND SURGE HOPPER F-305F TO OUTSIDE OF THE BUILDING VENT FROM SAND SURGE HOPPER F-305F TO OUTSIDE OF THE BUILDING VENT FROM SAND SURGE HOPPER F-305F TO OUTSIDE OF THE BUILDING NITROGEN TO SAND SURGE HOPPER F-305F NITROGEN TO SAND SURGE HOPPER F-305F

F-305F F-305F F-305F F-305F F-305F F-305F

AI SCREEN DISPLAY AO (0-50%)

AP-307.6 AP-307.6 AP-307.6 AP-307.6

FIELD DCS FIELD FIELD FIELD FIELD

3-JB-JS-42

0-1 0-1

Barg Barg %

3-JB-JS-42

0 - 50

AO (50100%)

AP-307.6 AP-307.6

3-JB-JS-42

50 - 100

1 2

3LSL604 3LAL604

LEVEL SWITCH LOW LEVEL ALARM LOW

SAND SURGE HOPPER F-305F SAND SURGE HOPPER F-305F

F-305F F-305F

DI SCREEN DISPLAY

AP-307.6 AP-307.6

FIELD DCS

3-JB-JC-50 YES

1 2 3

3TE637 3TT637 3TI637

THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

PREHEATED TICL4 FROM B-301F TO NITROGEN TO B-309F OXIDISER PREHEATED TICL4 FROM B-301F TO NITROGEN TO B-309F OXIDISER PREHEATED TICL4 FROM B-301F TO NITROGEN TO B-309F OXIDISER

B-309F B-309F B-309F AI SCREEN DISPLAY

AP-307.6 300-J3-3156 AP-307.6 (SHEET NO.109) AP-307.6

FIELD FIELD DCS 3-JB-JS-622F 0 - 500 0 - 500 c c

1 2 3

3TE656A 3TT656A 3TI656A

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

DEIONISED COOLING WATER TO OXYGEN NOZZLE B-309F DEIONISED COOLING WATER TO OXYGEN NOZZLE B-309F DEIONISED COOLING WATER TO OXYGEN NOZZLE B-309F

B-309F B-309F B-309F AI SCREEN DISPLAY

AP-307.6 AP-307.6 AP-307.6

FIELD FIELD DCS 3-JB-JS-40 0-150 0-150 c c

1 2 3

3TE656B 3TT656B 3TI656B

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

DEIONISED COOLING WATER FROM OXYGEN NOZZLE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM OXYGEN NOZZLE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM OXYGEN NOZZLE B-309F TO DEIONISED COOLING WATER HEADER

B-309F B-309F B-309F AI SCREEN DISPLAY

AP-307.6 AP-307.6 AP-307.6

FIELD FIELD DCS 3-JB-JS-40 0-150 0-150 c c

1 2 3

3TE656 3TT656 3TI656

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

DEIONISED COOLING WATER FROM OXYGEN NOZZLE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM OXYGEN NOZZLE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM OXYGEN NOZZLE B-309F TO DEIONISED COOLING WATER HEADER

B-309F B-309F B-309F AI SCREEN DISPLAY

AP-307.6 AP-307.6 AP-307.6

FIELD FIELD DCS 3-JB-JS-40 0-150 0-150 c c

1 2 3

3TE618 3TT618 3TI618

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

DEIONISED COOLING WATER FROM TICL4 SPOOL B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM TICL4 SPOOL B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM TICL4 SPOOL B-309F TO DEIONISED COOLING WATER HEADER

B-309F B-309F B-309F AI SCREEN DISPLAY

AP-307.6 AP-307.6 AP-307.6

FIELD FIELD DCS 3-JB-JS-39 0 - 150 0 - 150 c c

1 2 3

3TE619 3TT619 3TI619

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER

B-309F B-309F B-309F AI SCREEN DISPLAY

AP-307.6 AP-307.6 AP-307.6

FIELD FIELD DCS 3-JB-JS-40 0 - 150 0 - 150 c c

1 2 3

3TE620 3TE620 3TE620

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER

B-309F B-309F B-309F AI SCREEN DISPLAY

AP-307.6 AP-307.6 AP-307.6

FIELD FIELD DCS 3-JB-JS-40 0 - 150 0 - 150 c c

SHEET 13+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

300-J3-3156 1 2 3SS602 3SAL602 SPEED SWITCH LOW SPEED ALARM LOW PORTABLE KCL FEEDER PACKAGE C-325L PORTABLE KCL FEEDER PACKAGE C-325L C-325L C-325L DI SCREEN DISPLAY AP-307.6 (SHEET NO.178) AP-307.6 DCS YES FIELD 3-JB-JC-49

300-J3-3156 1 2 3SS601 3SAL601 SPEED SWITCH LOW SPEED ALARM LOW PORTABLE KCL FEEDER PACKAGE C-325L PORTABLE KCL FEEDER PACKAGE C-325L C-325L C-325L DI SCREEN DISPLAY AP-307.6 (SHEET NO.178) AP-307.6 DCS YES FIELD 3-JB-JC-49

1 2 3 4

3FT614 3FIC614 3FY614 3FV614

FLOW TRANSMITTER(VORTEX TYPE) FLOW INDICATION / CONTROLLER E/P POSITIONER FLOW CONTROL VALVE (GLOBE VALVE)

DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER DEIONISED COOLING WATER FROM CONE FLANGE B-309F TO DEIONISED COOLING WATER HEADER

B-309F B-309F B-309F B-309F

AI SCREEN DISPLAY AO

AP-307.6 AP-307.6 AP-307.6 AP-307.6

FIELD DCS FIELD FIELD

3-JB-JS-40

0 - 100 0 - 100

m3 / hr m3 / hr %

3-JB-JS-40

0 - 100

1 2

3PT617 3PI617

PRESSURE TRANSMITTER PRESSURE INDICATOR

NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F

B-316F B-316F

AI SCREEN DISPLAY

AP-307.6 AP-307.6

FIELD DCS

3-JB-JS-40

0-1 0-1

Barg Barg

1 2 3 4 5 6 7

3HS606 3XY603 3XV603 3XY604 3XV604 3XY605 3XV605

HAND SWITCH SOLENOID VALVE ON/OFF VALVE(BALL) SOLENOID VALVE ON/OFF VALVE(BALL) SOLENOID VALVE ON/OFF VALVE(BALL)

NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F NITROGEN FROM HEADER TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B-316F UTILITY AIR FROM HEADER

X-399E B-316F B-316F B-316F B-316F B-316F B-316F

SCREEN DISPLAY DO

AP-307.6 AP-307.6 AP-307.6

DCS FIELD FIELD FIELD FIELD FIELD FIELD 3-JB-JC-50 3-JB-JC-50 3-JB-JC-50

DO

AP-307.6 AP-307.6

DO

AP-307.6 AP-307.6

1 2 3 4 5 6 7

3FT615 3FIC615 3FY615 3FV615 3TE614 3TT614 3TI614

FLOW TRANSMITTER (COROLIS TYPE) FLOW INDICATION / CONTROLLER E/P POSITIONER FLOW CONTROL VALVE (GLOBE VALVE) THERMOCOUPLE (K TYPE) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO OXIDISER FUEL GAS TO OXIDISER FUEL GAS TO OXIDISER

B-316F B-316F B-316F B-316F B-316F B-316F B-316F

AI SCREEN DISPLAY AO

AP-307.6 AP-307.6 AP-307.6 AP-307.6 AP-307.6

FIELD DCS FIELD FIELD FIELD FIELD DCS

3-JB-JS-42

UPS POWER REQUIRED

3-JB-JS-42

0 - 100

AI SCREEN DISPLAY

AP-307.6 AP-307.6

3-JB-JS-42

0 - 100 0 - 100

c c

1 2 3 4 5 6 7

3HS616 3XY606 3XV606 3XY607 3XV607 3XY608 3XV608

RESET SWITCH SOLENOID VALVE ON/OFF VALVE(BALL) SOLENOID VALVE ON/OFF VALVE(BALL) SOLENOID VALVE ON/OFF VALVE(BALL)

FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F

X-399E B-316F B-316F B-316F B-316F B-316F B-316F

DI DO

AP-307.6 AP-307.6 AP-307.6

DCS FIELD FIELD FIELD FIELD FIELD FIELD

3-JB-JC-49 3-JB-JC-50

DO

AP-307.6 AP-307.6

3-JB-JC-50

DO

AP-307.6 AP-307.6

3-JB-JC-50

1 2

3PSH620 3PAH620

PRESSURE SWITCH HIGH PRESSURE ALARM HIGH

FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F

B-316F B-316F

DI SCREEN DISPLAY

AP-307.6 300-J3-3156 AP-307.6 (SHEET NO.167)

FIELD DCS

3-JB-JC-50

SHEET 14+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

SHEET 15+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
1 2

TAG NO
3PSL621 3PAL621

INSTRUMENT TYPE
PRESSURE SWITCH LOW PRESSURE ALARM LOW

SERVICE
FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F FUEL GAS TO ADIABATIC ENCLOSURE CS, KAGWOOL LINED B316F

EQUIPT NO
B-316F B-316F

I/O TYPE
DI SCREEN DISPLAY

P & ID NO
AP-307.6

LOOP NO (NOTE-1)

LOCATION
FIELD

JB NO
3-JB-JC-50

POWER REQMT

UNIT

HH ALARM

300-J3-3156 AP-307.6 (SHEET NO.170) DCS YES

1 2 3

3TE621 3TT621 3TI621

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

TICL4 VAPOUR FROM E-301E TO DUAL SLOT OXIDISER B-310F TICL4 VAPOUR FROM E-301E TO DUAL SLOT OXIDISER B-310F TICL4 VAPOUR FROM E-301E TO DUAL SLOT OXIDISER B-310F

B-310F B-310F B-310F AI SCREEN DISPLAY

AP-307.6 300-J3-3156 AP-307.6 (SHEET NO.102) AP-307.6

FIELD FIELD DCS 3-JB-JS-40 0 - 300 0 - 300 c c

1 2 3

3TE622 3TT622 3TI622

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

DEIONISED COOLING WATER FROM DUAL SLOT OXIDISER B-310F B-310F TO OXIDISER B-309F DEIONISED COOLING WATER FROM DUAL SLOT OXIDISER B-310F B-310F TO OXIDISER B-309F DEIONISED COOLING WATER FROM DUAL SLOT OXIDISER B-310F B-310F TO OXIDISER B-309F AI SCREEN DISPLAY

AP-307.6 300-J3-3156 AP-307.6 (SHEET NO.103) AP-307.6

FIELD FIELD DCS 3-JB-JS-40 0 - 150 0 - 150 c c

1 2

3PT623 3PI623

PRESSURE TRANSMITTER PRESSURE INDICATION

NITROGEN PURGING (DUAL SLOT OXIDISER B-310F) NITROGEN PURGING (DUAL SLOT OXIDISER B-310F)

B-310F B-310F

AI SCREEN DISPLAY

AP-307.6 AP-307.6

FIELD DCS

3-JB-JS-40

0-2 0-2

Barg Barg

3FMPS620

FLOW MONITORING PRESSURE SWITCH

FUEL GAS TO OXIDISER B-309F

B-309F

DI

AP-307.6

FIELD

3-JB-JC-50

0-2

Barg

PIGMENT SEPARATION & RECYCLE GAS "TRAIN 6"


1 2 3PSE628 3PSA628 PRESSURE / VACUUM RUPTURE DISC BURSTING DISC ALARM CHLORINE RELIEF FROM SAND SEPERATOR S-301F TO RELIEF SYSTEM CHLORINE RELIEF FROM SAND SEPERATOR S-301F TO RELIEF SYSTEM E-305F E-305F DI SCREEN DISPLAY AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.162) DCS FIELD 3-JB-JC-51

1 2 3

3TE624 3TT624 3TI624

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

SAND SEPERATOR S-301F SAND SEPERATOR S-301F SAND SEPERATOR S-301F

S-301F S-301F S-301F AI SCREEN DISPLAY

AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.104) AP-308.6

FIELD FIELD DCS 3-JB-JS-43 0 - 1200 0 - 1200 c c

1 2 3

3TE625 3TT625 3TI625

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

BAG FILTER S-304F BAG FILTER S-304F BAG FILTER S-304F

S-304F S-304F S-304F AI SCREEN DISPLAY

AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.105) AP-308.6

FIELD FIELD DCS 3-JB-JS-43 0 - 300 0 - 300 c c

1 2 3 4 5 6 7

3FT615A 3FI615A 3FT615B 3FI615B 3XL611 3HS607A 3HS607B

FLOW TRANSMITTER (ROTAMETER) FLOW INDICATION FLOW TRANSMITTER (ROTAMETER) FLOW INDICATION BLOWER RUNNING INDICATION HAND SWITCH (START ) HAND SWITCH ( STOP)

NITROGEN FROM HEADER TO RECYCLE GAS BLOWER G-301F SEAL NITROGEN FROM HEADER TO RECYCLE GAS BLOWER G-301F SEAL NITROGEN FROM HEADER TO RECYCLE GAS BLOWER G-301F SEAL NITROGEN FROM HEADER TO RECYCLE GAS BLOWER G-301F SEAL NITROGEN FROM HEADER TO RECYCLE GAS BLOWER G-301F SEAL RECYCLE GAS BLOWER G-301F RECYCLE GAS BLOWER G-301F

G-301F G-301F G-301F G-301F G-301F G-301F G-301F

AI SCREEN DISPLAY AI SCREEN DISPLAY DI DO DO

AP-308.6 AP-308.6 AP-308.6 AP-308.6 AP-308.6 AP-308.6 AP-308.6

FIELD DCS FIELD DCS DCS DCS DCS

3-JB-JS-41

0 - 15 0 - 15

m3 / hr m3 / hr m3 / hr 0 - 15 m3 / hr

3-JB-JS-41

0 - 15

MCC

1 2

3IT615 3II615

CURRENT TRANSMITTER CURRENT INDICATION

RECYCLE GAS BLOWER G-301F RECYCLE GAS BLOWER G-301F

G-301F G-301F

AI SCREEN DISPLAY

AP-308.6 AP-308.6

MCC DCS

MCC

0-75 0-75

Amps Amps

SHEET 16+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

1 2 3

3TE650 3TT650 3TI650

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

RECYCLE GAS BLOWER G-301F BEARING TEMPERATURE RECYCLE GAS BLOWER G-301F BEARING TEMPERATURE RECYCLE GAS BLOWER G-301F BEARING TEMPERATURE

G-301F G-301F G-301F AI SCREEN DISPLAY

AP-308.6 AP-308.6 AP-308.6

FIELD FIELD DCS 3-JB-JS-41 0 - 150 0 - 150 c c

1 2 3 4 5

3FE617 3FT617 3FIC617 3FY617 3FCV617

FLOW ELEMENT (INTEGRAL ORIFICE PLATE) FLOW INDICATION TRANSMITTER FLOW INDICATION CONTROLLER E/P POSITIONER FLOW CONTROL VALVE (GLOBE VALVE)

NITROGEN FROM HEADER TO SAND SEPERATOR S-301F NITROGEN FROM HEADER TO SAND SEPERATOR S-301F NITROGEN FROM HEADER TO SAND SEPERATOR S-301F NITROGEN FROM HEADER TO SAND SEPERATOR S-301F NITROGEN FROM HEADER TO SAND SEPERATOR S-301F

S - 301F S - 301F S - 301F S - 301F S - 301F AI SCREEN DISPLAY AO

AP-308.6 AP-308.6 AP-308.6 AP-308.6 AP-308.6

FIELD FIELD DCS FIELD FIELD 3-JB-JS-41 0 - 100 % 3-JB-JS-41 0 - 600 mBar

1 2 3 4 5 6

3XY609 3XV609 3XZSO609 3XZSC609 3XZIO609 3XZIC609

SOLENOID VALVE ON/OFF VALVE(GATE) LIMIT SWITCH (OPEN) LIMIT SWITCH (CLOSE) LIMIT SWITCH (OPEN) INDICATION LIMIT SWITCH (CLOSE) INDICATION

SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK

S - 301F S - 301F S - 301F S - 301F S - 301F S - 301F

DO

AP-308.6 AP-308.6

FIELD FIELD FIELD FIELD DCS DCS

3-JB-JC-51

DI DI SCREEN DISPLAY SCREEN DISPLAY

AP-308.6 AP-308.6 AP-308.6 AP-308.6

3-JB-JC-51 3-JB-JC-51

1 2 3 4 5 6 7

3HS611 3XY610 3XV610 3XZSO610 3XZSC610 3XZIO610 3XZIC610

HAND SWITCH (TIMER ON / OFF) SOLENOID VALVE ON/OFF VALVE(GATE) LIMIT SWITCH (OPEN) LIMIT SWITCH (CLOSE) LIMIT SWITCH (OPEN STATUS) INDICATION LIMIT SWITCH (CLOSE STATUS) INDICATION

SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK SAND SEPERATOR SOILDS S - 301F TO PRETREAMENT SUMP TANK

S - 301F S - 301F S - 301F S - 301F S - 301F S - 301F S - 301F

SCREEN DISPLAY DO

AP-308.6 AP-308.6 AP-308.6

DCS FIELD FIELD FIELD FIELD DCS DCS 3-JB-JC-51 3-JB-JC-51 3-JB-JC-51

DI DI SCREEN DISPLAY SCREEN DISPLAY

AP-308.6 AP-308.6 AP-308.6 AP-308.6

300-J3-3156 1 2 3TT626 3TI626 TEMPERATURE TRANSMITER TEMPERATURE INDICATOR BAG FILTER TO RECYCLE GAS BLOWER G-301F BAG FILTER TO RECYCLE GAS BLOWER G-301F S - 304F S - 304F AI SCREEN DISPLAY AP-308.6 (SHEET NO.106) AP-308.6 DCS 0 - 300 c FIELD 3-JB-JS-43 0 - 300 c

1 2

3PT631 3PI631

PRESSURE TRANSMITER PRESSURE INDICATOR

BAG FILTER TO RECYCLE GAS BLOWER G-301F BAG FILTER TO RECYCLE GAS BLOWER G-301F

S - 304F S - 304F

AI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JS-41

0-4 0-4

Barg Barg

1 2 3

3HS608 3HY608 3HV608

HAND SWITCH (START / STOP) SOLENOID VALVE ON/OFF VALVE(BALL)

BAG FILTER TO RECYCLE GAS BLOWER G-301F BAG FILTER TO RECYCLE GAS BLOWER G-301F BAG FILTER TO RECYCLE GAS BLOWER G-301F

S - 304F S - 304F S - 304F

SCREEN DISPLAY DO

AP-308.6 AP-308.6 AP-308.6

DCS FIELD FIELD 3-JB-JC-51

1 2 3 4 5

3HS613 3HY613 3HV613 3HZSO613 3HZSC613

HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE ON/OFF VALVE(BALL) LIMIT SWITCH (OPEN) LIMIT SWITCH (CLOSE)

G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F

SCREEN DISPLAY DO

AP-308.6 AP-308.6 AP-308.6

DCS FIELD FIELD FIELD FIELD 3-JB-JC-52 3-JB-JC-52 3-JB-JC-52

DI DI

AP-308.6 AP-308.6

SHEET 17+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
6 7

TAG NO
3HZIO613 3HZIC613

INSTRUMENT TYPE
LIMIT SWITCH (OPEN) INDICATION LIMIT SWITCH (CLOSE) INDICATION

SERVICE

EQUIPT NO

I/O TYPE
SCREEN DISPLAY SCREEN DISPLAY

P & ID NO
AP-308.6 AP-308.6

LOOP NO (NOTE-1)

LOCATION
DCS DCS

JB NO

POWER REQMT

UNIT

HH ALARM

G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F

1 2

3PSE634 3PSA634

PRESSURE / VACUUM RUPTURE DISC PRESSURE 1 BARG) BURSTING DISC ALARM

(SET

G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F G-301F FROM RECYCLE GAS BLOWER TO OXIDIZER VENT HEADER G-301F

DI SCREEN DISPLAY

AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.163)

FIELD DCS

3-JB-JC-52

1 2

3VXT615 3VXI615

VIBRATION TRANSMITTER VIBRATION INDICATION

RECYCLE GAS BLOWER G-301F RECYCLE GAS BLOWER G-301F

G-301F G-301F

AI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JS-41

1 2 3

3XY620 3XV620 3XHS620

SOLENOID VALVE ON / OFF VALVE (BALL) HAND SWITCH (RESET) ON POWER FAILURE

NITROGEN FROM HEADER TO BAG FILTER S-304F NITROGEN FROM HEADER TO BAG FILTER S-304F NITROGEN FROM HEADER TO BAG FILTER S-304F

S-304F S-304F S-304F

DO

AP-308.6 AP-308.6

FIELD FIELD DCS

3-JB-JC-51

SCREEN DISPLAY

AP-308.6

1 2 3 4

3LT605 3LI605 3LAH605 3LAL605

LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION LEVEL ALARM HIGH LEVEL ALARM LOW

SAND SEPERATOR S-301F SAND SEPERATOR S-301F SAND SEPERATOR S-301F SAND SEPERATOR S-301F

S-301F S-301F S-301F S-301F

AI SCREEN DISPLAY SCREEN DISPLAY SCREEN DISPLAY

AP-308.6 AP-308.6 AP-308.6 AP-308.7

FIELD DCS DCS DCS

3-JB-JS-43

0 - 100 0 - 100

% %

YES

1 2 3 4 5 6

3PT630 3PIC630 3PY630A 3PV630A 3PY630B 3PV630B

PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER E/P POSITIONER PRESSURE CONTROL VALVE(BUTTERFLY) E/P POSITIONER PRESSURE CONTROL VALVE(BUTTERFLY)

CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SS-304F 304F CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SS-304F 304F CHLORINE FROM RECYCLE GAS BLOWER G-301F TO D-307C CHLORINE FROM RECYCLE GAS BLOWER G-301F TO D-307C CHLORINE FROM RECYCLE GAS BLOWER G-301F TO OXIDIZER VENT HEADER CHLORINE FROM RECYCLE GAS BLOWER G-301F TO OXIDIZER VENT HEADER D-307C D-307C G-301F G-301F

AI SCREEN DISPLAY AO (50100%)

AP-308.6 AP-308.6 AP-308.6 AP-308.6

FIELD DCS FIELD FIELD FIELD FIELD

3-JB-JS-43

0-1 0-1

Barg Barg %

3-JB-JS-43

50 - 100

AO (0-50%)

AP-308.6 AP-308.6

3-JB-JS-43

0 - 50

1 2

3PSE635 3PSA635

PRESSURE / VACUUM RUPTURE DISC BURSTING DISC ALARM

BAG FILTER S-304F BAG FILTER S-304F

S-304F S-304F

DI SCREEN DISPLAY

AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.164)

FIELD DCS

3-JB-JC-51

1 2

3PDT629 3PDI629

DIFFERENTIAL PRESSURE TRANSMITTER DIFFERENTIAL PRESSURE INDICATION

BAG FILTER S-304F BAG FILTER S-304F

S-304F S-304F

AI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JS-43

0 - 50

mBar

1 2

3PT632 3PI632

PRESSURE TRANSMITTER PRESSURE INDICATION

RECYCLE GAS BLOWER G-301F DISCHARGE RECYCLE GAS BLOWER G-301F DISCHARGE

G-301F S-304F

AI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JS-43

0 - 1.6 0 - 1.6

Barg Barg

1 2

3AT010 3AI010

ANALYSER TRANSMITTER ANALYSER INDICATION

OXYGEN ANALYSER OXYGEN ANALYSER

AI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JS-44

UPS POWER REQUIRED

1 2

3HY610 3HV610

E/P POSITIONER HAND VALVE(BUTTERFLY)

CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SE-325F 304F CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SE-325F 304F

AO

AP-308.6 AP-308.6

FIELD FIELD

3-JB-JS-41

0 - 100

SHEET 18+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
3

TAG NO
3HIC610

INSTRUMENT TYPE
HAND VALVE POSITION INDICATION / CONTROLLER

SERVICE

EQUIPT NO

I/O TYPE
SCREEN DISPLAY

P & ID NO
AP-308.6

LOOP NO (NOTE-1)

LOCATION
DCS

JB NO

POWER REQMT

UNIT

HH ALARM

CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SE-325F 304F

1 2 3 4 5

3TE627C 3TT627C 3TIC627C 3TY627C 3TV627C

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION / CONTROLLER E/P POSITIONER TEMPERATURE CONTROL VALVE (BUTTERFLY VALVE)

CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SE-325F 304F CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SE-325F 304F CHLORINE FROM RECYCLE GAS COOLER E-325F TO BAG FILTER SE-325F 304F COOLING WATER RETURE FROM RECYCLE GAS COOLER E-325F COOLING WATER RETURE FROM RECYCLE GAS COOLER E-325F E-325F E-325F AI SCREEN DISPLAY AO

AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.107) AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.107) AP-308.6

FIELD FIELD DCS FIELD FIELD 3-JB-JS-41 3-JB-JS-41 0 - 300 0 - 300 0 - 100 c c %

300-J3-3156 1 2 3TSH641 3TAH641 TEMPERATURE SWITCH HIGH TEMPERATURE ALARM HIGH LUBE OIL SKID LUBE OIL SKID G-301F G-301F DI SCREEN DISPLAY AP-308.6 (SHEET NO.181) AP-308.6 DCS FIELD 3-JB-JC-601

1 2

3LSL611 3LAL611

LEVEL SWITCH LOW LEVEL ALARM LOW

LUBE OIL SKID LUBE OIL SYSTEM

G-301F G-301F

DI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JC-601 YES

1 2

3PSH648 3PAH648

PRESSURE SWITCH HIGH PRESSURE ALARM HIGH

LUBE OIL SKID LUBE OIL SKID

G-301F G-301F

DI SCREEN DISPLAY

AP-308.6 300-J3-3156 AP-308.6 (SHEET NO.168)

FIELD DCS

3-JB-JC-601

1 2

3PDSH644 3PDSH644

DIFFERENTIAL PRESSURE SWITCH HIGH DIFFERENTIAL PRESSURE ALARM HIGH

LUBE OIL SKID LUBE OIL SKID

G-301F G-301F

DI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JC-601

1 2

3PSLL649 3PALL649

PRESSURE SWITCH LOW LOW PRESSURE ALARM LOW LOW

LUBE OIL SKID LUBE OIL SKID

G-301F G-301F

DI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JC-601 YES

300-J3-3156 1 2 3TSHH642 3TAHH642 TEMPERATURE SWITCH HIGH HIGH TEMPERATURE ALARM HIGH HIGH LUBE OIL SKID LUBE OIL SKID G-301F G-301F DI SCREEN DISPLAY AP-308.6 (SHEET NO.182) AP-308.6 DCS YES FIELD 3-JB-JC-601

300-J3-3156 1 2 3TSL643 3TAL643 TEMPERATURE SWITCH HIGH HIGH TEMPERATURE ALARM HIGH HIGH LUBE OIL SKID LUBE OIL SKID G-301F G-301F DI SCREEN DISPLAY AP-308.6 (SHEET NO.183) AP-308.6 DCS YES FIELD 3-JB-JC-602

3XS618

LUBE OIL SYSTEM STANDBY PUMP G-302M (START)

STANDBY G-302M LUBE OIL PUMP

G-302M

DO

AP-308.6

DCS

3XS619

LUBE OIL SYSTEM STANDBY PUMP G-302M (STOP)

STANDBY G-302M LUBE OIL PUMP

G-302M

DO

AP-308.6

DCS

1 2

3PSL646 3PAL646

PRESSURE SWITCH LOW PRESSURE ALARM LOW

LUBE OIL SKID LUBE OIL SKID

G-301F G-301F

DI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JC-601 YES

1 2

3PSL647 3PAL647

PRESSURE SWITCH LOW PRESSURE ALARM LOW

LUBE OIL SKID LUBE OIL SKID

G-301F G-301F

DI SCREEN DISPLAY

AP-308.6 AP-308.6

FIELD DCS

3-JB-JC-601 YES

SHEET 19+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

3XL616

RUNNING INDICATION

LUBE OIL SKID

G-301F

DI

AP-308.6

DCS

MCC

RAW PIGMENT COLLECTION


300-J3-3156 1 3XL035A MOTOR RUNNING INDICATION PRETREATMENT SUMP SCRUBBER FAN G-327C G-327C DI AP-310.2 (SHEET NO.195) 300-J3-3156 1 3XL036A MOTOR RUNNING INDICATION PRETREATMENT SUMP SCRUBBER PUMP G-325C G-325C DI AP-310.2 (SHEET NO.196) 300-J3-3156 1 3XL014A AGITATOR RUNNING INDICATION PRETREATMENT SUMP AGITATOR G-307C G-307C DI AP-310.2 (SHEET NO.191) 300-J3-3156 1 3XL015A MOTOR RUNNING INDICATION PRETREATMENT SUMP PUMP G-306C G-306C DI AP-310.2 (SHEET NO.192) 300-J3-3156 1 3XL016A AGITATOR RUNNING INDICATION PRETREATMENT SUMP AGITATOR G-307D G-307D DI AP-310.2 (SHEET NO.193) DCS MCC DCS MCC DCS MCC DCS MCC DCS MCC

1 2 3 4

3LT037C 3LIC037C 3LY037C 3LV037C

LEVEL TRANSMITTER (RADAR TYPE) LEVEL INDICATION / CONTROLLER E/P POSITIONER LEVEL CONTROL VALVE (DIAPHRAGM VALVE)

PRETREATMENT SUMP TANK F-306C PRETREATMENT SUMP TANK F-306C TITANIUM OXIDE FROM PRIMARY SAND CLASSIFIER S-320B TO PRETREATMENT SUMP TANK F-306C TITANIUM OXIDE FROM PRIMARY SAND CLASSIFIER S-320B TO PRETREATMENT SUMP TANK F-306C

F-306C F-306C S-320B S-320B

AI SCREEN DISPLAY AO

AP-310.2 AP-310.2 AP-311 AP-311

FIELD DCS FIELD FIELD

3-JB-JS-41

UPS POWER REQUIRED

0 - 100

3-JB-JS-41

0 - 100

1 2 3

3DIC003C 3DY003C 3DV003C

DENSITY INDICATION / CONTROLLER E/P POSITIONER DENSITY CONTROL VALVE (DIAPHRAGM VALVE)

TITANIUM OXIDE FROM PRETREATMENT SUMP TANK F-306C TO PRIMARY SAND SCREEN S-1320 TITANIUM OXIDE FROM PRIMARY SAND CLASSIFIER S-320B TO PRETREATMENT SUMP TANK F-306C TITANIUM OXIDE FROM PRIMARY SAND CLASSIFIER S-320B TO PRETREATMENT SUMP TANK F-306C

F-306C S-320B S-320B

SCREEN DISPLAY AO

AP-310.2 AP-310.2 AP-310.2

DCS FIELD FIELD 3-JB-JS-41 0 - 100 %

1 2 3 4 5

3FT020C 3FI020C 3XL013A 3HS040A 3HS040B

FLOW TRANSMITTER (ELECTRO MAGNETIC TYPE) FLOW INDICATOR MOTOR RUNNING INDICATION HAND SWITCH (START) HAND SWITCH (STOP)

MAKEUP WATER TO PRETREATMENT SUMP TANK F-306C MAKEUP WATER TO PRETREATMENT SUMP TANK F-306C CALGON METERING PUMP G-371C CALGON METERING PUMP G-371C CALGON METERING PUMP G-371C

F-306C F-306C G-371C G-371C G-371C

AI SCREEN DISPLAY DI DO DO

AP-310.2 AP-310.2 300-J3-3156 AP-310.2 (SHEET NO.190) 300-J3-3156 AP-310.2 (SHEET NO.190) 300-J3-3156 AP-310.2 (SHEET NO.190)

FIELD DCS DCS DCS DCS

3-JB-JS-41

UPS POWER REQUIRED

0 - 34

m3 / hr

MCC

1 2 3

5LSHL051 3LAL051 3LAH051

LEVEL SWITCH LEVEL LOW ALARM LEVEL HIGH ALARM

SPILL SUMP F-5503F SPILL SUMP F-5503F SPILL SUMP F-5503F

F-5503F F-5503F F-5503F

DI

AP-310.2 AP-310.2 AP-310.2

FIELD MCC MCC

MCC YES

SAND RECOVERY SYSTEM


1 2 3 3HS051 3HY051 3HV051 HAND SWITCH (TIMER OFF) SOLENOID VALVE HAND VALVE (PINCH VALVE) PIGMENT / SAND SLURRY FROM G-306C TO PRIMARY SAND CLASSIFIER S-320B PIGMENT / SAND SLURRY FROM G-306C TO PRIMARY SAND CLASSIFIER S-320B PIGMENT / SAND SLURRY FROM G-306C TO PRIMARY SAND CLASSIFIER S-320B S-320B S-320B S-320B SCREEN DISPLAY DO AP-311.1 AP-311.1 AP-311.1 DCS FIELD FIELD 3-JB-JC-51

1 2

3LSH050 3LAH050

LEVEL SWITCH HIGH LEVEL ALARM HIGH

PRIMARY SAND CLASSIFIER S-320B PRIMARY SAND CLASSIFIER S-320B

S-320B S-320B

DI SCREEN DISPLAY

AP-311.1 AP-311.1

FIELD DCS

3-JB-JC-51

SHEET 20+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

1 2 3 4 5

3AE004 3AT004 3AIC004 3AY004 3AV004

ANALYSER ELEMENT (pH SENSOR) ANALYSER TRANSMITTER ANALYSER INDICATION / CONTROLLER E/P POSITIONER CONTROL VALVE (DIAPHRAGM)

PRIMARY SAND CLASSIFIER S-320B PRIMARY SAND CLASSIFIER S-320B PRIMARY SAND CLASSIFIER S-320B CAUSTIC SOLUTION TO PRETREATMENT SUMP TANK F-306C CAUSTIC SOLUTION TO PRETREATMENT SUMP TANK F-306C

S-320 S-320 S-320 F-306C F-306C AI SCREEN DISPLAY AO

AP-311.1 AP-311.1 AP-311.1 AP-310.2 AP-310.2

FIELD FIELD DCS FIELD FIELD 3-JB-JS-41 3-JB-JS-41

UPS POWER REQUIRED 300-J3-3156 (SHEET NO-12) 0 - 14 0 - 14 0 - 100 ph ph %

300-J3-3156 1 3XL050 MOTOR RUNNING INDICATION PRIMARY SAND CLASSIFIER S-320B SCREW CONVEYOR S-320B DI AP-311.1 (SHEET NO.197) DCS MCC

RECYCLE GAS SCRUBBER


1 2 3 3HS053 3HY053 3HV053 HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE ON / OFF VALVE (PLUG) CHLORINE TO SULPHURIC ACID SCRUBBER D-307 CHLORINE TO SULPHURIC ACID SCRUBBER D-307 CHLORINE TO SULPHURIC ACID SCRUBBER D-307 D-307 D-307 D-307 SCREEN DISPLAY DO AP-312 AP-312 AP-312 DCS FIELD FIELD 3-JB-JC-54

1 2 3

3HS054 3HY054 3HV054

HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE ON / OFF VALVE (PLUG)

CHLORINE TO SULPHURIC ACID SCRUBBER D-307 CHLORINE TO SULPHURIC ACID SCRUBBER D-307 CHLORINE TO SULPHURIC ACID SCRUBBER D-307

D-307 D-307 D-307

SCREEN DISPLAY DO

AP-312 AP-312 AP-312

DCS FIELD FIELD 3-JB-JC-54

1 2 3

3HS055 3HY055 3HV055

HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE ON / OFF VALVE (PLUG)

RECYCLE CHLORINE TO SULPHURIC ACID SCRUBBER D-307 RECYCLE CHLORINE TO SULPHURIC ACID SCRUBBER D-307 RECYCLE CHLORINE TO SULPHURIC ACID SCRUBBER D-307

D-1307 D-1307 D-1307

SCREEN DISPLAY DO

AP-312.1 AP-312.1 AP-312.1

DCS FIELD FIELD 3-JB-JC-54

1 2 3 4 5 6 7

3HS048 3HY048 3HV048 3HZSO048 3HZSC048 3HZIO048 3HZIC048

HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE ON / OFF VALVE (BALL) LIMIT SWITCH (OPEN) LIMIT SWITCH (CLOSE) LIMIT SWITCH (OPEN) INDICATION LIMIT SWITCH (CLOSE) INDICATION

CHLORINE GAS FROM G-301F TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301F TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301F TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301F TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301F TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301F TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301F TO SULPHURIC ACID SCRUBBER DD-307C 307C

SCREEN DISPLAY DO

AP-312.2 AP-312.2 AP-312.2

DCS FIELD FIELD FIELD FIELD DCS DCS 3-JB-JC-54 3-JB-JC-54 3-JB-JC-54

DI DI SCREEN DISPLAY SCREEN DISPLAY

AP-312.2 AP-312.2 AP-312.2 AP-312.2

1 2 3 4 5 6 7

3HS046 3HY046 3HV046 3HZSO046 3HZSC046 3HZIO046 3HZIC046

HAND SWITCH (OPEN / CLOSE) SOLENOID VALVE ON / OFF VALVE (BALL) LIMIT SWITCH (OPEN) LIMIT SWITCH (CLOSE) LIMIT SWITCH (OPEN) INDICATION LIMIT SWITCH (CLOSE) INDICATION

CHLORINE GAS FROM G-301E TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301E TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301E TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301E TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301E TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301E TO SULPHURIC ACID SCRUBBER DD-307C 307C CHLORINE GAS FROM G-301E TO SULPHURIC ACID SCRUBBER DD-307C 307C

SCREEN DISPLAY DO

AP-312.2 AP-312.2 AP-312.2

DCS FIELD FIELD FIELD FIELD DCS DCS 3-JB-JC-20 3-JB-JC-20 3-JB-JC-20

DI DI SCREEN DISPLAY SCREEN DISPLAY

AP-312.2 AP-312.2 AP-312.2 AP-312.2

SHEET 21+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

1 2 3

3TE037A 3TT037A 3TI037A

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

SULPHURIC ACID SCRUBBER D-307C SULPHURIC ACID SCRUBBER D-307C SULPHURIC ACID SCRUBBER D-307C

D-307C D-307C D-307C AI SCREEN DISPLAY

AP-312.2 AP-312.2 AP-312.2

FIELD FIELD DCS 3-JB-JS-44 c c

0 - 100 0- 100

1 2

3LT051 3LI051

LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION

SULPHURIC ACID SCRUBBER D-307C SULPHURIC ACID SCRUBBER D-307C

D-307C D-307C

AI SCREEN DISPLAY

AP-312.2 AP-312.2

FIELD DCS

3-JB-JS-44

0 - 100 0 - 100

% %

1 2

3PSH051 3PAH051

PRESSURE SWITCH PRESSURE ALARM HIGH

SULPHURIC ACID SCRUBBER D-307C SULPHURIC ACID SCRUBBER D-307C

D-307C D-307C

DI SCREEN DISPLAY

AP-312.2 300-J3-3156 AP-312.2 (SHEET NO.166)

FIELD DCS

3-JB-JC-54

1 2 3

3TE036B 3TT036B 3TI036B

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

RECYCLE CHLORINE FROM D-307C TO GAS COMPRESSORS RECYCLE CHLORINE FROM D-307C TO GAS COMPRESSORS RECYCLE CHLORINE FROM D-307C TO GAS COMPRESSORS

D-307C D-307C D-307C AI SCREEN DISPLAY

AP-312.2 AP-312.2 AP-312.2

FIELD FIELD DCS 3-JB-JS-44

0 - 300 0 - 300

c c

1 2

3FT051 3FI051

FLOW TRANSMITTER (ULTRASONIC TYPE) FLOW INDICATION

SULPHURIC ACID SCRUBBER D-307C TO ACID CHILLERS E-314E/F E-314E/F SULPHURIC ACID SCRUBBER D-307C TO ACID CHILLERS E-314E/F E-314E/F

AI SCREEN DISPLAY

AP-312.2 AP-312.2

FIELD DCS

3-JB-JS-44

UPS POWER REQUIRED

0 - 700

GPM

300-J3-3156 1 3XL079 MOTOR RUNNING INDICATION ACID SCRUBBER CIRCULATION PUMP G-314G G-314G DI AP-312.2 (SHEET NO.199) DCS MCC

300-J3-3156 1 3XL080 MOTOR RUNNING INDICATION ACID SCRUBBER CIRCULATION PUMP G-314H G-314H DI AP-312.2 (SHEET NO.200) DCS MCC

300-J3-3156 1 3XL081 MOTOR RUNNING INDICATION ACID SCRUBBER CIRCULATION PUMP G-314J G-314J DI AP-312.2 (SHEET NO.201) DCS MCC

PRESSURE / VACUUM RUPTURE DISC 1 3PSE051 (SET PRESSURE 1.7 BARG) SULPHURIC ACID SCRUBBER D-307C D-307C DI AP-312.2 FIELD 3-JB-JC-54

CHLORINE GAS COMPRESSION


1 2 3 4 3PT069C 3PIC069C 3PY069C 3PV069C PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER E/P POSITIONER PRESSURE CONTROL VALVE (GLOBE VALVE) CHLORINE FROM D-315C TO GARO COMPRESSOR G-310J/K CHLORINE FROM D-315C TO GARO COMPRESSOR G-310J/K CHLORINE FROM D-315C TO GARO COMPRESSOR G-310J/K CHLORINE FROM D-315C TO GARO COMPRESSOR G-310J/K G-310J/K G-310J/K G-310J/K G-310J/K AI SCREEN DISPLAY AO AP-313.2 AP-313.2 AP-313.2 AP-313.2 FIELD DCS FIELD FIELD 3-JB-JS-44 3-JB-JS-44 0.2 - 0.4 0.2 - 0.4 0 - 100 Barg Barg %

1 2

3XY111J 3XV111J

SOLENOID VALVE BUTTERFLY VALVE

RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G-310J G-310J RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G-310J G-310J

DO

AP-313.2 AP-313.2

FIELD FIELD

3-JB-JC-54

1 2

3PS092J 3PALL092J

PRESSURE SWITCH PRESSURE ALARM LOW LOW

RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G-310J G-310J RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G-310J G-310J

DI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JC-54 YES

1 2

3TE057J 3TT057J

RTD(PT 100) TEMPERATURE TRANSMITTER

GARO COMPRESSOR G-310J WINDING TEMPERATURE GARO COMPRESSOR G-310J WINDING TEMPERATURE

G-310J G-310J AI

AP-313.2 AP-313.2

FIELD FIELD 3-JB-JS-44 0-150 c

SHEET 22+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE
0-150

Project SAP010

SEQ NO
3 3 4

TAG NO
3TI057J 3TAH057J 3TAHH057J

INSTRUMENT TYPE
TEMPERATURE INDICATION TEMPERATURE ALARM HIGH TEMPERATURE ALARM HIGH HIGH

SERVICE
GARO COMPRESSOR G-310J WINDING TEMPERATURE GARO COMPRESSOR G-310J WINDING TEMPERATURE GARO COMPRESSOR G-310J WINDING TEMPERATURE

EQUIPT NO
G-310J G-310J G-310J

I/O TYPE
SCREEN DISPLAY SCREEN DISPLAY SCREEN DISPLAY

P & ID NO
AP-313.3 AP-313.2 AP-313.2

LOOP NO (NOTE-1)

LOCATION
DCS DCS DCS

JB NO

POWER REQMT

UNIT
c

LL ALARM

LO ALARM

HH ALARM

1 2

3FT031J 3FI031J

FLOWMETER (ULTRASONIC TYPE) FLOW INDICATION

SULPHURIC ACID TO GARO COMPRESSOR G-310J SULPHURIC ACID TO GARO COMPRESSOR G-310J

G-310J G-310J

AI SCREEN DISPLAY

AP-312.2 AP-312.2

FIELD DCS

3-JB-JS-44

UPS POWER REQUIRED

0 - 40 0 - 40

m3 / hr m3 / hr

1 2

3XY109J 3XV109J

SOLENOID VALVE ON/OFF VALVE(BALL)

SULPHURIC ACID TO GARO COMPRESSOR G-310J SULPHURIC ACID TO GARO COMPRESSOR G-310J

G-310J G-310J

DO

AP-313.2 AP-313.2

FIELD FIELD

3-JB-JC-54

1 2

3XY110J 3XV110J

SOLENOID VALVE ON/OFF VALVE(BALL)

CHLORINE TO D-315C CHLORINE TO D-315C

G-310J G-310J

DO

AP-313.2 AP-313.2

FIELD FIELD

3-JB-JC-54

1 2 3 4 5

3PT108J 3PI108J 3PY108JA 3PY108JB 3PV108J

PRESSURE TRANSMITTER PRESSURE INDICATION E/P POSITIONER SOLENOID VALVE ON/OFF VALVE(BALL)

RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G-310J G-310J RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G-310J G-310J GARO COMPRESSOR G-310J FEEDBACK LINE GARO COMPRESSOR G-310J FEEDBACK LINE GARO COMPRESSOR G-310J FEEDBACK LINE G-310J G-310J G-310J

AI SCREEN DISPLAY AO DO

AP-313.2 AP-313.2 AP-313.2 AP-313.2 AP-313.2

FIELD DCS FIELD FIELD FIELD

3-JB-JS-44

-500 - 100 -500 - 100

mBar(G) mBar(G)

3-JB-JS-44 3-JB-JC-54

1 2

3PSE096J 3PSA096J

PRESSURE /VACCUM RUPTURE DISC BURSTING DISC ALARM

PROCESS GAS FROM THE GARO COMPRESSOR G-310J PROCESS GAS FROM THE GARO COMPRESSOR G-310J

G-310J G-310J

DI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JC-54

1 2

3PS094J 3PAHH094J

PRESSURE SWITCH PRESSURE ALARM HIGH HIGH

GARO COMPRESSOR G-310K DISCHARGE GARO COMPRESSOR G-310K DISCHARGE

G-310J G-310J

DI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JC-54 YES

1 2 3

3TE064J 3TT064J 3TI064J

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

GARO COMPRESSOR G-310J DISCHARGE GARO COMPRESSOR G-310J DISCHARGE GARO COMPRESSOR G-310J DISCHARGE

G-310J G-310J G-310J AI SCREEN DISPLAY

AP-312.2 AP-312.2 AP-312.2

FIELD FIELD DCS 3-JB-JS-44

0-100 0-100

c c

1 2

3PT097J 3PI097J

PRESSURE TRANSMITTER PRESSURE INDICATION

GARO COMPRESSOR G-310J DISCHARGE GARO COMPRESSOR G-310J DISCHARGE

G-310J G-310J

AI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JS-44

0-6 0-6

Barg Barg

300-J3-3156 1 3HS310JA HAND SWITCH (START) GARO COMPRESSOR G-310J G-310J DO AP-313.2 (SHEET NO.202) DCS MCC

SHEET 23+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
2 3

TAG NO
3HS310JB 3XL111J

INSTRUMENT TYPE
HAND SWITCH (STOP) MOTOR RUNNING INDICATION GARO COMPRESSOR G-310J GARO COMPRESSOR G-310J

SERVICE

EQUIPT NO
G-310J G-310J

I/O TYPE
DO DI

P & ID NO
AP-313.2

LOOP NO (NOTE-1)

LOCATION
DCS

JB NO
MCC MCC

POWER REQMT

UNIT

HH ALARM

300-J3-3156 AP-313.2 (SHEET NO.202) DCS

1 2

3IT006J 3II006J

CURRENT TRANSMITTER CURRENT INDICATION

GARO COMPRESSOR G-310J GARO COMPRESSOR G-310J

G-310J G-310J

AI SCREEN DISPLAY

AP-313.2 AP-313.2

MCC DCS

MCC

0-200 0-200

Amps Amps

1 2

3XY111K 3XV111K

SOLENOID VALVE ON/OFF VALVE ( BUTTERFLY )

RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G310JK RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G310JK

G-310K G-310K

DO

AP-313.2 AP-313.2

FIELD FIELD

3-JB-JC-54

1 2

3PSL092K 3PALL092K

PRESSURE SWITCH LOW PRESSURE ALARM LOW LOW

RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G310K RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G310K

G-310K G-310K

DI SCREEN DISPLAY

AP-313.2 300-J3-3156 AP-313.2 (SHEET NO.169)

FIELD DCS

3-JB-JC-54 YES

1 2 3 4 5

3TE057K 3TT057K 3TI057K 3TAH057K 3TAHH057K

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION TEMPERATURE ALARM HIGH TEMPERATURE ALARM HIGH HIGH

GARO COMPRESSOR G-310K WINDING TEMPERATURE GARO COMPRESSOR G-310K WINDING TEMPERATURE GARO COMPRESSOR G-310K WINDING TEMPERATURE GARO COMPRESSOR G-310K WINDING TEMPERATURE GARO COMPRESSOR G-310K WINDING TEMPERATURE

G-310K G-310K G-310K G-310K G-310K AI SCREEN DISPLAY SCREEN DISPLAY SCREEN DISPLAY

AP-313.2 AP-313.2 AP-313.2 AP-313.2 AP-313.2

FIELD DCS DCS DCS DCS YES 3-JB-JS-44 0-150 0-150


O

C C

1 2

3FT031K 3FI031K

FLOWMETER (ULTRASONIC TYPE) FLOW INDICATION

SULPHURIC ACID TO GARO COMPRESSOR G-310K SULPHURIC ACID TO GARO COMPRESSOR G-310K

G-310K G-310K

AI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JS-44

UPS POWER REQUIRED

0 - 40 0 - 40

m3 / hr m3 / hr

1 2 3 4 5

3PT108K 3PIC108K 3PY108KA 3PY108KB 3PV108K

PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER E/P POSITIONER SOLENOID VALVE ON/OFF VALVE(BALL)

RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G310JK RECYCLE CHLORINE FROM D-307C TO GARO COMPRESSOR G310JK GARO COMPRESSOR G-310K FEEDBACK LINE GARO COMPRESSOR G-310K FEEDBACK LINE GARO COMPRESSOR G-310K FEEDBACK LINE

G-310K G-310K G-310K G-310K G-310K

AI SCREEN DISPLAY AO DO

AP-313.2 AP-313.2 AP-313.2 300-J3-3156 AP-313.2 (SHEET NO.175) AP-313.2

FIELD DCS FIELD FIELD FIELD

3-JB-JS-44

-500 - 100 -500 - 100

mBar(G) mBar(G)

3-JB-JS-44 3-JB-JC-54

1 2

3XY109K 3XV109K

SOLENOID VALVE ON/OFF VALVE(BALL)

SULPHURIC ACID TO GARO COMPRESSOR G-310K SULPHURIC ACID TO GARO COMPRESSOR G-310K

G-310K G-310K

DO

AP-313.2 AP-313.2

FIELD FIELD

3-JB-JC-54

1 2

3XY110K 3XV110K

SOLENOID VALVE ON/OFF VALVE(BALL)

CHLORINE TO D-315C CHLORINE TO D-315C

G-310K G-310K

DO

AP-313.2 AP-313.2

FIELD FIELD

3-JB-JC-54

1 2

3PSE096K 3PSA096K

PRESSURE / VACUUM RUPTURE DISC BURSTING DISC ALARM

PROCESS GAS FROM THE GARO COMPRESSOR G-310K PROCESS GAS FROM THE GARO COMPRESSOR G-310K

G-310K G-310K

DI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JC-54

1 2

3PS094K 3PAHH094K

PRESSURE SWITCH HIGH PRESSURE ALARM HIGH HIGH

GARO COMPRESSOR G-310K DISCHARGE GARO COMPRESSOR G-310K DISCHARGE

G-310K G-310K

DI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JC-54 YES

SHEET 24+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO

TAG NO

INSTRUMENT TYPE

SERVICE

EQUIPT NO

I/O TYPE

P & ID NO

LOOP NO (NOTE-1)

LOCATION

JB NO

POWER REQMT

UNIT

HH ALARM

1 2 3

3TE064K 3TT064K 3TI064K

RTD (PT100) TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

GARO COMPRESSOR G-310K DISCHARGE GARO COMPRESSOR G-310K DISCHARGE GARO COMPRESSOR G-310K DISCHARGE

G-310K G-310K G-310K AI SCREEN DISPLAY

AP-313.2 AP-313.2 AP-313.2

FIELD FIELD DCS 3-JB-JS-44 0-100 0-100 c c

1 2

3PT097K 3PI097K

PRESSURE TRANSMITTER PRESSURE INDICATION

GARO COMPRESSOR G-310K DISCHARGE GARO COMPRESSOR G-310K DISCHARGE

G-310K G-310K

AI SCREEN DISPLAY

AP-313.2 AP-313.2

FIELD DCS

3-JB-JS-44

0-6 0-6

Barg Barg YES

1 2 3

3HS310KA 3HS310KB 3XL111K

HAND SWITCH (START) HAND SWITCH (STOP) MOTOR RUNNING INDICATION

GARO COMPRESSOR G-310K GARO COMPRESSOR G-310K GARO COMPRESSOR G-310K

G-310K G-310K G-310K

DO DO DI

AP-313.2 AP-313.2 AP-313.2

DCS DCS DCS

MCC MCC MCC

1 2

3IT006K 3II006K

CURRENT TRANSMITTER CURRENT INDICATION

GARO COMPRESSOR G-310K GARO COMPRESSOR G-310K

G-310K G-310K

AI SCREEN DISPLAY

AP-313.2 AP-313.2

MCC DCS

MCC

0-200 0-200

Amps Amps

DEMIN.WATER CIRCULATION
300-J3-3156 1 3XL053 MOTOR RUNNING INDICATION DEIONIZED WATER CURCULATING PUMP G-322E G-322E DI AP-315.1 (SHEET NO.198) DCS MCC

CHLORINE GAS COOLING AND DRYING


1 2 3LT018C 3LI018C LEVEL TRANSMITTER (DP TYPE) LEVEL INDICATION SULPHURIC ACID SURGE DRUM D-315C SULPHURIC ACID SURGE DRUM D-315C D-315C D-315C AI SCREEN DISPLAY AP-314.2 AP-314.2 FIELD DCS 3-JB-JS-45 0 -100 0 -100 % %

1 2

3PDT023C 3PDI023C

DIFFERENTIAL PRESSURE TRANSMITTER DIFFERENTIAL PRESSURE INDICATOR

FROM SULPHURIC ACID SURGE DRUM D-315C TO C.S DEMESTER FROM SULPHURIC ACID SURGE DRUM D-315C TO C.S DEMESTER

D-315C D-315C

AI SCREEN DISPLAY

AP-314.2 AP-314.2

FIELD DCS

3-JB-JS-45

0 - 80

mBar

1 2

3PT028C 3PI028C

PRESSURE TRANSMITTER PRESSURE INDICATION

FROM SULPHURIC ACID SURGE DRUM D-315C TO C.S DEMESTER D-315C (S-321 E) FROM SULPHURIC ACID SURGE DRUM D-315C TO C.S DEMESTER D-315C (S-321 E)

AI SCREEN DISPLAY

AP-314.2 AP-314.2

FIELD DCS

3-JB-JS-45

0-4 0-4

Barg Barg

1 2

3PSH034C 3PAH034C

PRESSURE SWITCH PRESSURE ALARM HIGH

FROM SULPHURIC ACID SURGE DRUM D-315C TO VENT & RELIEF D-315C HEADER FROM SULPHURIC ACID SURGE DRUM D-315C TO VENT & RELIEF D-315C HEADER

DI SCREEN DISPLAY

AP-314.2 300-J3-3156 AP-314.2 (SHEET NO.165)

FIELD DCS

3-JB-JC-53

1 2 3 4

3PT051 3PIC051 3PY051 3PV051

PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER E/P POSITIONER CONTROL VAVLE (BUTTERFLY VALVE)

C.S DEMISTER S-321E DISCHARGE TO VENT & RELIEF HEADER C.S DEMISTER S-321E DISCHARGE TO VENT & RELIEF HEADER C.S DEMISTER S-321E DISCHARGE TO VENT & RELIEF HEADER C.S DEMISTER S-321E DISCHARGE TO VENT & RELIEF HEADER

D-315C D-315C D-315C D-315C

AI SCREEN DISPLAY AO

AP-314.2 AP-314.2 AP-314.2 AP-314.2

FIELD DCS FIELD FIELD

3-JB-JS-45

0-4 0-4

Barg Barg %

3-JB-JS-45

0 - 100

1 2 3

3HS015C 3HY015C 3HV015C

HAND SWITCH SOLENOID VALVE ON/OFF VALVE(BUTTERFLY)

SULPHURIC ACID COOLER E-315E/F DISCHARGE SULPHURIC ACID COOLER E-315E/F DISCHARGE SULPHURIC ACID COOLER E-315E/F DISCHARGE

E-315E/F E-315E/F E-315E/F

SCREEN DISPLAY DO

AP-314.2 AP-314.2 AP-314.2

DCS FIELD FIELD 3-JB-JC-53

SHEET 25+2 OF 26

KEAS Control Systems India Pvt. Ltd.


TRANSMITTER RANGE DCS/PLC RANGE LL ALARM LO ALARM

Project SAP010

SEQ NO
1 2 3

TAG NO
3TE018C 3TT018C 3TI108C RTD (PT100)

INSTRUMENT TYPE

SERVICE
SULPHURIC ACID COOLER E-315E/F DISCHARGE SULPHURIC ACID COOLER E-315E/F DISCHARGE SULPHURIC ACID COOLER E-315E/F DISCHARGE

EQUIPT NO
E-315E/F E-315E/F E-315E/F

I/O TYPE

P & ID NO
AP-314.2

LOOP NO (NOTE-1)

LOCATION
FIELD FIELD DCS

JB NO

POWER REQMT

UNIT

HH ALARM

TEMPERATURE TRANSMITTER TEMPERATURE INDICATION

AI SCREEN DISPLAY

AP-314.2 AP-314.2

3-JB-JS-45

0 - 200 0 - 200

c c

1 2 3 4 5 6 7 8

3CT002C 3CI002C 3CHS002C 3CY002E 3CV002E 3CY002F 3CV002F 3CHS002C

CONDUCTIVITY TRANSMITTER CONDUCTIVITY INDICATION HIGH CONDUCTIVITY HAND SWITCH (FIELD RESET) SOLENOID VALVE ON/OFF VALVE (BUTTERFLY VALVE) SOLENOID VALVE ON/OFF VALVE (BUTTERFLY VALVE) RESET PUSH BUTTON

SULPHURIC ACID COOLER E-315F DISCHARGE SULPHURIC ACID COOLER E-315F DISCHARGE SULPHURIC ACID COOLER E-315F DISCHARGE SULPHURIC ACID COOLER E-315F DISCHARGE SULPHURIC ACID COOLER E-315F DISCHARGE SULPHURIC ACID COOLER E-315F DISCHARGE SULPHURIC ACID COOLER E-315F DISCHARGE SULPHURIC ACID COOLER E-315F DISCHARGE

E-315F E-315F E-315F E-315F E-315F E-315F E-315F E-315F

AI SCREEN DISPLAY DI DO

AP-314.2 AP-314.2 AP-314.2 AP-314.2 AP-314.2

FIELD DCS FIELD FIELD FIELD FIELD FIELD DCS

3-JB-JS-45

UPS POWER REQUIRED

0-8 0-8

msiemens msiemens

3-JB-JC-53 3-JB-JC-53

DO

AP-314.2 AP-314.2

3-JB-JC-53

SCREEN DISPLAY

AP-314.2

1 2 3 4

3PT033C 3PIC033C 3PY033C 3PV033C

PRESSURE TRANSMITTER PRESSURE INDICATION / CONTROLLER E/P POSITIONER CONTROL VAVLE (BUTTERFLY VALVE)

COOLING WATER LINE FROM SULPHURIC ACID COOLER E-315F COOLING WATER LINE FROM SULPHURIC ACID COOLER E-315F COOLING WATER LINE FROM SULPHURIC ACID COOLER E-315F COOLING WATER LINE FROM SULPHURIC ACID COOLER E-315F

E-315F E-315F E-315F E-315F

AI SCREEN DISPLAY AO

AP-314.2 AP-314.2 AP-314.2 AP-314.2

FIELD DCS FIELD FIELD

3-JB-JS-45

0-6 0-6

Barg Barg %

3-JB-JS-45

0 - 100

3PSE025C

PRESSURE / VACUUM RUPTURE DISC

FROM SULPHURIC ACID SURGE DRUM D-315C TO VENT & RELIEF D-315C HEADER

DI

AP-314.2

FIELD

3-JB-JC-53

NOTES:
DETAILS TO BE FILLED IN PROGRESSIVELY BASED ON DETAILED ENGINEERING / DATA AVAILABILITY.

SHEET 26+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE
A2

REV

1
REV
B 1

REMARKS

A B A A

A A2 1 1 B A

A B A RESET on power failure from DCS vendor panel 300-VP-0340C

B A C2 B A

B A

B A

B A

B A

SHEET 27+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

A B A RESET on power failure from DCS vendor panel 300-vp-0340c

A2

B A

B A4 B 1 UPS Power Required. Junction Box sahll be supplied by Transmitter Vendor.

C1 YES

B A

C1

B A

A2

1 1

A A2 B A

C1

B A

C1

0 0 A4 B A

SHEET 28+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
A C2 B A

REV

1
REMARKS

A2

B A

A2

B 1

A B A

A2

B 1

A2

1 1

RADAR TYPE

A A2 B A

C1

B A

A A4 1 1 B A

A A2 1 1

SHEET 29+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
B A

REV

1
REMARKS

A B A

C1

A2

1 1 B A B A

A2

1 1 B A B A

A2

B A B B A A

A4

B A

RADAR TYPE

A A2 B A

B B A

SHEET 30+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

C2

B A

C2

B A

C1

B A

A A A2 1 1 B B A C1 B

A A2 B A

B A YES A

To be linked with Motor Starter

A2

B A B B A A

A4

B A

RADAR TYPE

SHEET 31+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE
A2

REV

1
REV
B A

REMARKS

A B A

C2

B A

C2

B A

C1

B A

A A A2 1 1 B B A C1 B

A A2 B A

A A2 B A

A2

B A

A A2 1

SHEET 32+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
1

REV

1
REMARKS

YES

C1

HARDWIRED Connection from BMS PANEL to DCS

A A2 B A

A A2 B A

A A2 B A

A A2 B A

A A2 1 1

A A2 B A B A C2 A HARDWIRE Connection from BMS Panel to DCS

C1 C1

A A A

HARDWIRE Connection from BMS Panel to DCS HARDWIRE Connection from BMS Panel to DCS HARDWIRE Connection from BMS Panel to DCS HARDWIRE Connection from BMS Panel to DCS

C1

A2

B 1

SHEET 33+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

A C1 C1 B B B A C2 B A C2 B A

DO Signal from DCS Close Command from Local Push Button Station Reset Command from Local Push Button Station

A2

B A B A

A4

B A B A

A2

B 1

B A

C1 C1

A A A

HARDWIRE Connection from BMS Panel to DCS HARDWIRE Connection from BMS Panel to DCS HARDWIRE Connection from BMS Panel to DCS HARDWIRE Connection from BMS Panel to DCS

C1

A A2 B 1

SHEET 34+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
A A2 B A B A

REV

1
REMARKS

A A2 B A

A A2 B A

A A2 B A

A A2 B A

A A2 B A

A A2 B A B A

C1 YES

B A

SHEET 35+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
B A

REV

1
REMARKS

A2

1 1 B A B A (12-20mA) for the Nitrogen line Valve which Opens 0% at 12mA and Open 100% at 20mA. Split range control (4-12mA) for the Vent Valve which Opens 100% at 4mA and Closes to 100% at 12mA.

C1

B A

A A2 1 1

A A2 B A

A A2 B A

A A2 B A A

A2

B A

A A2 B A

A A2 B A

SHEET 36+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

C1

B A

C1

B A

A2

B A B A

A2

B 1

A B A B A B A

A4

B A B A 1

A2

1 1

C1

B B A B A B A

C1 YES

B A

SHEET 37+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

SHEET 38+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE
C1

REV

1
REV
B A

REMARKS

A A2 B A

A A2 B A

A2

B A

C1

C1

B A

A A2 1 1

A A2 B A

A2

1 1

A2

1 1

C1

B A A

A4

B A

SHEET 39+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
A A A2 B A

REV

1
REMARKS

A A2 B A B A

C2 C2

B B

A B A C2 C2 B B A A

A2

B A

A2

1 1

A B A

B B A C2 C2 B B

SHEET 40+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
A A

REV

1
REMARKS

C1

B A

1 1

B A A

A2

B A

YES

A A

A2

B A B A B A

C1

B A

A2

B A

A2

B A

A4

B A

B A

SHEET 41+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
A

REV

1
REMARKS

A A2 1 1 B A

C1 YES

1 A

C1

1 A

C1 YES

B A

C1 YES

1 A

C1

B A

C1

1 A

C1

0 0

Interlock DO Start Signal from DCS to Lube Oil System Satandby Pump (G-302M).

Interlock DO Stop Signal from DCS to Lube Oil System Satandby Pump (G-302M).

C1

0 0

C1

B A

SHEET 42+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

C1

C1

C1

C1

C1

C1

A4

1 A B A CRISTAL to confirm the Tag Number. Refer TQ KEAS/CEP/INST-001 CRISTAL to confirm the Tag Number. Refer TQ KEAS/CEP/INST-001

A B A

A4

1 1

C1

B 0 0

C1

B A

YES

A B A

C1 YES

B A

SHEET 43+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

A A4 B A B A

C1

A B A

A B A

A B A

A B A C2 C2 B B A A

A 1 A C2 C2 1 1 A A

SHEET 44+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

A A2 1 1

A2

1 A

C1 YES

B A

1 A2 1 A

A4

1 A

C1

C1

C1

C1

A2

1 1 B A

B A

C1

B A

A A2 B

SHEET 45+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
A A A

REV

1
REMARKS

A4

0 A

B A

0 0

A2

B A B B A

C1

B A

C1

B A

A A2 B A

A2

B A Start Command for GARO Compressor 0 (G-310J) from CRISTAL DCS.

SHEET 46+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
0 C1 B

REV

1
Stop Command for GARO Compressor (G-310J) from CRISTAL DCS.

REMARKS

A4

B A

B A

C1

B A

A A2 B A YES A A

A4

0 A

A2

B A B B A

B A

B A

C1

B A

C1

B A

SHEET 47+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV

REV

1
REMARKS

A A2 B A

A2

B A Start Command for GARO Compressor 0 0 Stop Command for GARO Compressor (G-310K) from CRISTAL DCS. (G-310K) from CRISTAL DCS.

C1

A4

B A

C1

A2

1 1

A2

B A

A2

B A

C1 YES

B A

A2

1 1 B A

A B A

SHEET 48+2 OF 26

Document No. 300-J3-3151


HI ALARM INP TYPE REV
A A2 B A

REV

1
REMARKS

A4

B 1

C1

B B A B A B

A2

B A B A

SHEET 49+2 OF 26