DESIGN OF SEISMIC ARRESTER IN LONGITUDINAL DIRN. A Stopper is provided at the end of Pedestal.

It is designed as cantilever fixed to pedestal is designed for twice the Seismic force of superstructure. Horz. Force due to Seismic effect on Superstructure 324.2 * 0.08 = 25.936 Design Force = 51.872 Tn 51.872 Force * ( 0.10 HT of Bearings +0.25 ) = 11.671 Tm

Refer Pier Cap design for Girder Load

BM at root [ Pedestal top ] =

Stopper projection above soffit Say

Area of Steel required =

11.671 *10^5 0.9*2000* ( 40.00 20.1

= -4.0-1.6/2 ) cm2 >

18.526 cm2

Provide

10 Layers of TOR16 =

18.526 cm2

Shear Calculations Max SF = 51.872 Tn Shear relief = M/d*Tan (Alpha) 51.872 *10^3 135.0* 40 = 11.671 0.35 0 0 0.000 Tn

Max Shear Stress =

9.61 Kg/cm2

Spacing required for TOR12 = = Provide

8*

8Legged Stirrups 35 2.3*135*40

1.131 *2000 51.872 *10^3 16.05 cms

8Legged TOR12 Stirrups at 150c/c

o.k

400mm

Pedestal

500mm

Pedestal Reinforcements

10TOR16 on Both Sides to be anchored in to Pier Cap