Anda di halaman 1dari 313

SOLUTION MANUAL

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful. Requests for permission or further information should be addressed to the Permission Department, John Wiley & Sons, Inc, 111 River Street, Hoboken, NJ 07030.

Chapter 1

1-1

(a) 98 Btu/(hr-ft-F) x1.7307 = 170 W/(m-K) (b) 0.24 Btu/(Ibm-F) x4186.8=1.0 kJ/kg-K (c)

0.04 Ibm/(ft-hr) Ns x1.488 = 16.5 3600 sec/hr m2 Btu J 1 2.20462 Ibm MJ x x = 2.44 Ibm 9.48x104 Btu kg kg
Btu 1 x = 3.52 kW Ibm 3.412
x 6894.76 = 101 kPa

(d) 1050

(e) 12,000

(f) 14.7

Ibf in2

1-2

(a) 120 kPa x

lbf / in2 = 17.4 lbf/in2 6.89476kPa

(b) 100

W x 0.5778 = 57.8 Btu/hr-ft-F m K

(c) 0.8

W m K
2

x 0.1761 = 0.14 Btu/hr-ft2-F

(d) 10-6 N-s/m2 x

1 lbm = 6.7 x 10-7 1.488 ft sec

(e) 1200 kW x 3412 = 4.1 x 10-6 Btu/hr

(f) 1000

1 Btu 1 kg Btu kJ x x = 430 1.055 kJ 2.2046 lbm lbm kg m ) = 15.2 m ft

1-3

Hp = 50 (ft) x 0.3048 ( P =

15.2 m 9.807 N x ( ) x 1000 (kg/m3) = 149 kPa 1000 Pa/kPa 1 kg

1-4

P =

m kg 4 9.807 N (ft) x 0.3048 ( ) x ( ) x 1000 ( 3 ) ft 12 1 kg m

P = 996 Pa 1.0 kPa 1-5 TOTAL BILL = ENERGY CHARGE + DEMAND CHARGE + METER CHARGE

( 96,000 )

kw - hrs ( 0.045 ) $ / kw hr + ( 624 ) kw (11 50 ) $ / kw

+ $68 = $4,320 + $7,176 + $68 = $11,564

1-6

7 AM to 6 PM

11 hrs/day, 5 days/wk

(11)

hrs days (22) = 242 hrs / month day months

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

ratio =

( 624 ) kw = 1.57 ( 96,000 ) kw hr ( 242 ) hr

1-7

This is a trial and error solution since eq. 1-1 cannot be solved explicitly for i. Answer converges at just over 4.2% using eq. 1-1

1-8 Determine present worth of savings using eq. 1-1

$1000 ) 1( P=

0.012 1+ 12 0.012 12

(12 )(12 )

P = $134,000

1-9

(a) Q = VA = 2 x 3.08 x 10-3 = 6.16 x 10-3m3/s

m = Q = 6.16 x 10-3 x 998 = 6.15 kg/s


(b) A=

(0.3)2 = 7.07 x 10-2 m2

Q = 7.07x10-2 x 4 = 0.283 m3 / s; = 1.255 kq/m3


m = 1.225 x 0.283 = 0.347 kg/s
V = 3x10x20 = 600m3

1-10

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

Qi = 600 x

1 1 x = 4.17 x 10-2 m3/s 4 3600

1-11

q = mc p T

c p = 4.183 kJ/(kg-K)

= 983.2 kg/m3

1-11 (contd)

m3 kg kJ kJ q = (1) ( 983.2) 3 ( 4.183 ) ( 5 )c = 20,564 s kg K s m q = 20,564 kw

1-12

qwat = qair
11,200(1)(10) =

5000x60x14.7x144x0.24(t 2 50) (53.35x510)

11,200 = 5601.5 (t2-50); t2 = (11,200/5601.5) + 50 = 70 F 1-13 Diagram as in 1-12 above.

q wat = - q air
1.5 (4186)(90-t2) = 2.4 (1.225)(1.0)(30-20)(1000) 6279(90-t2) = 29,400

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

5 t2 = 90 -

29,400 = 85.3 C 6279

1-14 q = hA(ts- t ) A= (1/12) x 10 = 2.618 ft2

t s = t 212 F sur
q = 10x2.618x(212-50) = 4241 Btu/hr
1-15 A= x 0.25x4 = 3.14 16 m2

q = hA(ts- t ) q 1250 = ; h = 4.42 W/(m2 C) h= A(t s -t ) 3.1416(100 10)


1-16 q = mcp (t2-t1) ; m = Q x

= P/RT = 14.7x144/53.35(76+460) = 0.074 lbm/ft3


m = 5000x0.074x60 = 22,208 lbm/hr

c p = 0.24 Btu/lbm-F
q = 22,208x0.24(58-76) = -95,939 Btu/hr
Negative sign indicates cooling

1-17 m1cp (t3-t1) +


Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

m2cp2 (t3-t2) = 0 c p1 = c p2
t3 =

(m1t1 + m2t 2 ) (m1 + m2 ) 14.7x144 = 73.5 lbm/min 53.35(460 + 50)

m1 = Q2 1 = 1000x

1-17 (contd)

m2 = Q2 2 = 600x
t3 =

14.7x144 = 46.7 lbm/min 53.35(460 + 50)

(73.5x80) + (46.7 x 50) = 68.3 F (73.5 + 46.7)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

7
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful. Requests for permission or further information should be addressed to the Permission Department, John Wiley & Sons, Inc, 111 River Street, Hoboken, NJ 07030.

Chapter 2
2-1 through 2-20 Solutions are not furnished since many acceptable responses exist for each problem. It is not expected that the beginning student can handle these questions easily. The objective is to make the student think about the complete design problem and the various functions of the system. These problems are also intended for use in class discussions to enlarge the text material.

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful. Requests for permission or further information should be addressed to the Permission Department, John Wiley & Sons, Inc, 111 River Street, Hoboken, NJ 07030.

Chapter 3
3-1 (a) Pv = r Ps = 0.45(3.17)kPa = 1.43 kPa or 0.45(0.435) = 0.196 psia Pa = 101 1.43 = 99.57 kPa or 14.696-0.196 = 14.5 psia (b)

P 1430 Pv = 0.0104 kg/m3 = RvT or v = v ; v = Rv T 462.5(297) v


or

0.196(144) = 0.00062 lbv/ft3 85.78(535)


0.6219 (1.43) = 0.00893 kgv/kga (99.57)

(c) W =

or

0.6219(0.196) = 0.00854 lbv/lba 14.5

3-2

(a) English Units t = 80F; P = 14.696 psia; Pv = 0.507 psia Table A-1a W = 0.6219

Pv 0.6219 (0.507) = = 0.0222 lbv/lba Pa (14.696 0.507)

i = 0.24t + W(1062.2 + 0.444t) i = 0.24 (80) + 0.0222[1061.2 + 0.444(80)] = 43.55 Btu/lbm

v=

Ra T 53.35(460 + 80) = = 13.61 ft3/lbm Pa (14.696 0.507)144

(b) English Units 32F, 14.696 psia Pv = 0.089 psia (Table A-1) 3-2 (contd) W=

0.6219(0.089) lbmv = 0.00379 (14.696 0.089) lbma

i = 0.24(32) + 0.00379 [1061.2 + 0.444(32)] = 11.76 Btu/lbma v= 3-2

53.35(492) = 12.48 ft3/lbma (14.696 0.089)144

(a) SI Units 27C; 101.325 kPa Pv = 3.60 kPa, Table A-1b W = 0.6219

Pv 0.6219(3.6) kgv = = 0.0229 Pa (101.325 3.6) kga

i = 1.0t + W(2501.3 + 1.86t) kJ/kga i = 27 + 0.0229(2501.3 + 1.86 x 27) = 85.43 kJ / kga v=

Ra T 0.287(300) = =0.88 m3 /kga Pa (101.325 - 3.6)

(b) SI Units 0.0C; 101.325 kPa Pv = 0.61 kPa, Table A-1b W=

0.6219(0.61) =0.00377 kgv/kga (101.325 - 0.61)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

i = 0.0 + 0.00377 (2501.3 1.86 x 0.0) = 9.42 kJ/kga v=

0.287(273) = 0.778 m3 /kga (101.325 - 0.61)

3-3

(a) English Units 5000 ft elevation, P = 12.24 psia = 24.92 in.Hg t = 80 F; Pv = 0.507 psia (Table A-1a) W = 0.6219

Pv 0.6219(0.507) = = 0.0269 lbv/lba Pa (12.24 - 0.507)

i = 0.24(80) + 0.0269 [1061.2 + 0.444(80)] = 48.7 Btu/lbma v=

RaT 53.35(540) = = 17.05 ft3 / lbma Pa (12.24 - 0.507) 144

(b) English Units t = 32 F, Pv = 0.089 psia ( Table A-1a) W=

0.6219(0.089) = 0.00456 lbmv/lbma (12.24 0.089)

i = 0.24(32) + 0.00456 [1061.2 + 0.444(32)] =12.58 Btu/lbma v= 3-3

53.35(492) = 15.00 ft3/lbma (12.24 0.089)144

(a) SI Units -27 C, 1500 m elevation P = 99.436 + 1500(-0.01) = 84.436 kPa Pv = 3.60 kPa, Table A-1b

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

10 W=

0.6219x3.60 = 0.0277 kgv/kga (84.436 3.60)

i = 27 + 0.0277 (2501.3 + 1.86 x 27) = 97.68 kJ/kga

3-3 (contd) v=

0.287x300 (84.436 - 3.60)

= 1.065 m3 / kga

(b) SI Units 0.0C; 1500m or 84.436 kPa Pv = 0.61 kPa; Table A-1b W=

0.6219 x 0.61 = 0.00453 kgv / kga (84.436 - 0.61)

i = 0.0 + 0.00453 (2501.3 0.0 x 1.86) = 11.33 kJ / kga v=

0.287 x 273 = 0.935 m3 / kga (84.436 - 0.61)

3-4 (a)

English Units 70F, Pv = 0.363 psia

Pv = Pg = 0.75(0.363) = 0.272 psia W=

0.6219 (0.272) (14.696 - 0.272)

= 0.0117 lbmv / lbma

i = 0.24 (70) + 0.0117 [1061.2 + 0.444 (70)] = 29.58 Btu / lbma (b) Pv = 0.75 (0.363) = 0.272 psia; P = 12.24 psia

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

11 W=

0.6219 (0.272) = 0.0141 lbmv / lbma (12.24 - 0.272)

i = 0.24(70) + 0.0141 [1061.2 + 0.444 (70)] = 32.20 Btu/ lbma 3-4 SI Units (a) 20C, 75% RH, Sea Level 3-4 (contd) Ps = 2.34 kPa; Pv = 0.75 x 2.34 = 1.755 kPa

W=

0.6219 x 1.755 = 0.0110 kgv / kga (101.325 - 1.755)

i = 1.0 t + W(2501.3 + 1.86t) i = 20 + 0.0110(2501.3 + 1.86 x 20) = 47.92 kJ / kga (b) 20C, 75% RH, 1525m P = 99.436 0.01 x 1525 = 84.186 kPa Ps = 2.34 KPa; Pv = 0.75 x 2.34 = 1.755 kPa W=

0.6219 x 1.755 = 0.0132 kgv / kga (84.186 - 1.755)

i = 20 + 0.0132(2501.3 + 1.86 x 20) = 53.51 kJ / kga 3-5 English Units t = 72 Fdb; = 50 %; P = 14.696 psia

Pv or Pv = Ps ; Pv = 0.5(0.3918) = 0.196 psia Ps

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 Air dewpoint = saturated temp. at 0.196 psia = 52.6 F Moisture will condense because the glass temp. 40 F is below the dew point temp. 3-5 SI Units t = 22C ; 50% ; P = 100 kPa Pv = Ps ; Pv = 0.5(2.34) = 1.17 kPa

3-5 (contd) Air dewpoint = sat.temp. at 1.17 kPa = 9.17 C Glass temp. of 4 C is below the dewpoint of 9.17 C, therefore, moisture will ccondense on the glass

3-6 English Units (a) At 55F, 80% RH, va = 13.12 ft3 / lba and a = 0.0752 lbma / ft3

ma = 5000 (0.0762) = 381 lbma / min = 22,860 lbma / hr


(b) Using PSYCH a = 0.0610 lbma / ft3 or va = 16.4 ft3 / lba

m a = 5000 (0.061) = 305 lbma / min


3-6 SI Units (a) t = 13 C and relative humidity 80%

= 18,300 lbma / hr

then va 0.820 m3 / kga; ma = 2.36 / 0.82 = 2.88 kga / s (b) Assuming same conditions
v a = 0.985 m3 / kga ; ma = 2.36 / 0.985 = 2.40 kga / s
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

13

3-7 English Units t = 80F, 60% RH (a) Pv = Ps = 0.6 (0.507) = 0.304 psia

t dp = (t sat @ Pv ) = 64.5 F
(b) Same as (a) above 3-7 SI Units (a) 27 C, 60% RH, Sea Level Ps = 3.57 kPa; Pv = 0.6 x 3.57 = 2.14 kPa

t dp =(t sat at Pv ) 18.4 C


(b) Same as (a) above 3-8 t dp 9C (48F)

42% ;
Chart 1a & 1b

W 0.0071 kgv / kga (lbv / lba)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

14

ASHRAE PSYCHROMETRIC CHART NO.1


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55
R

60

90
50
.028

AMERICAN S OCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS, INC.

1.0
0 .8

SEA LEVEL
0. 6
0 .5

60
1 .0

85
15
-2 00 0 -1 00 0

.026

0. 3

0.2

0 .1

IR

PO

ER

Problem 3-8
PE U -B T Y AL P TH
25

TU

30

TE

TI O

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

SA

TU

15

40 35
35

45
40
1 3.

DR Y BUL B T EMPERAT UR E - F

10

48 (9)

15

72 (22)

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-9

(a,b,d) Using the Properties option of PSYCH: Relative Humidity = 0.59 or 59% Enthalpy = 30.4 Btu/lbma Humidity Ratio = 0.0114 lbu/lba (c) Again using the Properties option At W=0.0114 lbv/lba; RH = 1.00 or 100% The dew point = tdb or twb = 59.9 F

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

3000

5000

.0

2. 0

SENSIB LE HEAT TOTAL HEAT


0. 4

Qs Qt
-2.

4 .0 8 .0

-1.
-0 .5 - 0.4 -0.3

-8 -4 .0.0 0

45

85

WE T

.024

BU

LB

TE

50 0

80
40

MP E

55

RA TU

RE

-0 .2

-0 .1

- F

.022

20

15 00

80
h W

1 000

.020

ENTHALPY HU MIDITY RATIO

35

75
50

14 .5

.018

75

70

.016

70

.014

45

65

.012

60

65
% 90

1 4 .0 LU VO ME

55

80

%
60

.010

40

-C

% 70

42 %
Room
13 .5

U.F T. P RY .D LB ER

dp
45

50

55
60 %

.008

50

W=0.0071

% 50

A IR

.006

4 0%

35
.004

30 %

20 %
1 2. 5

.002

Y I VE H UMIDIT 10% RE LAT

30

15

3-9 (contd) (e) Using the Density of Dry Air option: Mass Density = 0.070 lba/ft3

3-10

Using program PSYCH (a) tdb = 102.6; twb = 81.1F 75 Fdb; 65 fwb; 14.2 psia (b) m = 58.7 lbm/hr

Q 2 = 1027 cfm
3-11 t1 = 80 / 67 F; t2 = 55 F and sat.; assume std. barometer (a) W1 W2 = 0.0112 0.0092 = 0.002 lbv / lba (b) ql = 31.5 - 29.3 = 2.2 Btu / lba (c) qs = 29.3 23.2 = 6.1 Btu / lba (d) q = ql + qs = 8.3 Btu / lba 0.6219 (0.3095) = 0.0134 kgv / kga (14.696 0.3095)
0.24 (65 - 80) + ( 0.0134 x 1056.5) = 0.00993 lbv / lba (1096 - 33)

3-12

* (a) W2 =

W1 =

also W1 = 0.6219 Pv1 / (P Pv1)


Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

16 Pv1 = (0.00993 x 14.696) / ( 0.6219 + 0.00993) = 0.231 psia 3-12 (contd)

1 =

0.231 = 0.46 or 46% 0.507

(b) P = 29.42 (0.0009 x 5000) = 24.92 in.Hg. or P = 12.24 psia


* W2 =

0.6219 x (0.3095) = 0.01613 lbv/lba (12.24 - 0.3095)

W1 =

0.24(65 80) + (0.01613 x 1056.5) = 0.01265 lbv / lba ( 1096 - 33) or kgv / kga

Pv1 = 0.01265 x 12.24 / ( 0.6219 + 0.01265) = 0.244 psia

1 =
3-13

0.244 = 0.48 or 48% 0.507

(a) Sea Level Wet Bulb, F 60 59.6 65.1 70 85.8 Dew point F 40.6 49.2 60.1 60.9 81.7 Humid. Ratio, lba/lbv 0.0053 0.0074 0.0111 0.01143 0.0235 Mass Enthalpy Rel. Density Btu/lba Humid., % lba/ft3 26.6 21 0.072 26.1 40 0.073 30 60 0.073 33.8 40 0.071 50 56 0.068

Dry Bulb, F 85 75 74.6 88.6 100

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

17 (a) 5000 ft. Dry Bulb, F 85 75 71.2 102.7 100 Wet Bulb, F 60 58.6 61.6 70 81.3 Dew point F 45.1 49.2 56.7 55.8 76.1 Humid. Ratio, lba/lbv 0.0076 0.0089 0.0118 0.01143 0.0235 Mass Enthalpy Rel. Density Btu/lba Humid., % lba/ft3 28.7 25 0.060 27.7 40 0.061 30 60 0.061 37.3 22 0.058 50 47 0.057

(c) Note effect of barometric pressure.

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

18 3-14
ASHRAE PSYCHROMETRIC CHART NO.1
R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6
0 .5

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2.0

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt
-2.

4 .0 8 .0

0.2

0 .1

IR

PO

ER

Problem 3-14
PE U -B T Y AL P TH

TU

30

TE

TI O

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45
40

DR Y BUL B T EMPERATUR E - F

10

52 (11)

15

72 (22)

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-15

Use Chart 1b, SI (a) td = 10 C; SHF = 0.62 (b) q = m (i1 i2 ) =


2.4 (57.1 - 34) = 63.95 kJ / s = 63.95 k W 0.867

qs = 63.95 (0.62) = 39.65 kW


3-15 Use Chart 1a, IP (a) td = 52 F; SHF = 0.63

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-1 .0
-0 .5 - 0.4 -0.3

-8 -4 .0.0 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENTHAL PY HU MIDITY RAT IO

35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

.012

60

65
% 90

55

80

%
60

Max RH=49.6 %
ME -C U.F

14 .0 V U OL

.010

40

% 70

50

dp
50

55
60 %
13 .5

Room

W=0.0083
R B. D RL PE IR YA

T.

.008

45

% 50

.006

4 0%

35

.004

30%

1 3. 0

20 %
1 2. 5

.002

10% RE LAT

Y IVE H UM IDIT

30

19 3-15 (contd) (b)

q=

5000(60) (32 - 22.6)= 203,317. Btu/hr 13.87

ASHRAE PSYCHROMETRIC CHART NO.1


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6
0 .5

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2.0

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt
-2.
-1.
-0 .5 - 0.4 -0.3

4 .0 8 .0

0.2

0 .1

PO

ER

TU

Problem 3-15
PE U -B T Y

IR

30

TE

TI O

TH

SA

25

1
60
65
% 90
1 4 .0 LU VO

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

AL P

TU

15

40 35
35

45
40
1 3.

DR Y BUL B T EMPERAT UR E - F

10

52 (10) 55 (13)

15

80 (27)

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

qs = 203,317 (0.63) = 128,089. Btu/hr


3-16 (a) i1 = 30 Btu / lba; v1 = 13.78 ft3 / lba; W = 0.0103 (b) i1 = 51.6 kJ / kga v1 = 0.86 m3 / kga
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

lbv ; 1 = 50% lba

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-8 -4 .0.0 0

45
85 WE T
.024

BU

LB

50 0

80
40

TE MP E

55
RA TU RE - F
.022

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENT HAL PY HU MIDIT Y RAT IO

35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

.012

ME

55

80

%
60

.010

40

-C U.F

ADP
50

% 70

T. P L B. ER

55
60 %
1 3 .5

.008

DR

45

50

IR YA

% 50

.006

4 0%

35

.004

30%

20 %
1 2. 5

.002

10% RE LAT

Y IVE H UM IDIT

30

20

3-16 (contd) W1 = 0.0103

kgv kga

1 = 50%
3-17 Use the Heat Transfer option of program PSYCH:

q = 148,239 Btu/hr
qs = 102,235 Btu/hr
SHF = 0.69

3-18 Use the Heat Transfer option of program PSYCH for sensible heat transfer only:

qs = 178,911 Btu/hr
Negative sign indicates heating.

3-19 Use the program PSYC to compute the various properties at 85/68 F; sea level and 6000 ft elevation. Elevation ft 0 6000 Enthalpy Btu/lbm 32.2 36.3 Rel. Hum percent 42 45 Hum. Ratio lbv/lba 0.0107 0.0144 Density lba/ft3 0.072 0.058

At sea level: ma = 5000 x 0.072 x 60 = 21,600 lba/hr


Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

21 3-19 (contd) At 6000 feet:: ma = 5000 x 0.057 x 60 = 17,100 lba/hr Percent Decrease at 6000 ft:

PD =
3-20

(21 ,600 17,100)100 = 20.8% 21,600

Use the program PSYC to compute the heat transfer rates at 1000 and 6000 feet elevation: (a) at 1000 ft, q = 200,534 Btu/hr (b) at 6000 ft, q = 190,224 Btu/hr (c) PD =

(200,534 190,224)100 = 5.1 % 200,543

3-21 (a) English Units


PB = 29.92 in.Hg. ; q = 0

i = iw = 180.2 + 0.8 (970.2) W


iw = 956.4 Btu / lbv From chart 1a; t2 = 91.5 F

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

22

ASHRAE PSYCHROMETRIC CHART NO.1


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6
0 .5

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2.0

SENSIB LE HEAT TOTAL HEAT


0.4
0. 3

Qs Qt

4 .0 8 .0

0.2

0 .1

IR

PO

ER

Problem 3-21
PE U -B T Y AL P TH

TU

30

TE

TI O

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

TU

15

40 35
35

45
40

4 0%

DR Y BULB T EMPERATUR E - F

10

15

20

91.5 (32) 98 (38)

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-21 (a)

SI Units PB = 101.325 kPa

i = iw = 419.04 + (0.8 x 2257) W


iW = 2224.6 kJ / kg From chart 1b; t2 = 32 C (b) Use Humidification (adiabatic) option to obtain 91.5 F db. PB = 29.92 in.Hg.; q = 0 (a) Using chart 1a
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

3-22

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-8 -4 .0.0 -2.0
-1. 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5 - 0.4 -0.3

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENT HAL PY HU MIDITY RATIO

35

75

2
50
14 .5
.018

75

70

60 %

.016

70

.014

45

65

.012

60

65
% 90

14 .0 V U OL ME

55

80

%
60

.010

40

-C U.F

% 70

T. P RY .D LB ER

50

55
60 %
13 .5

.008

45

50

% 50

A IR

.006

35

.004

30%

1 3. 0

20 %
1 2. 5

.002

10% RE LAT

Y IVE H UM IDIT

30

23

3-22 (contd)

i = iw = 1090 Btu / lbm W

From table A-1

x=

i-if 1090 - 196.1 = ifg 960.1

x = 0.931 or about 93 % (b) x will be the same

ASHRAE PSYCHROMETRIC CHART NO.1


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55
R

60

90
50
.028

AMERICAN S OCIETY OF HEATING , REFRIGERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8

SEA LEVEL
0. 6
0 .5

60

1 .0

85
15
-2 00 0 -1 00 0

.026

0. 3

0.2

0 .1

IR

Problem 3-22
PE U -B T Y AL P TH

TU

30

PO

ER

TE

TI O

SA

25

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45
40
1 3.

DR Y BUL B T EMPERAT UR E - F

10

15

80

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

50 00

.0

2.0

SENSIB LE HEAT T OTAL HEAT


0. 4

Qs Qt

-1.
-0 .5 - 0.4 -0.3

4 .0 8 .0 -8 -4 .0.0 -2. 0
0

45

85

WE T

.024

BU

LB

TE

50 0

80
40

MP E

55

RA TU

RE

-0 .2

-0 .1

- F

.022

20

15 00

ENT HAL PY HU MIDIT Y RATIO

1090
1 000

80
h W

.020

35

75
50
14 .5
.018

75

70

.016

b
70
.014

45

65

.012

60
55

60

65
% 90

1 4 .0 LU VO ME

80

.010

60

40

-C U.F

% 70

T. P L B. ER

50

55
60 %
13

.008

DR

45

50

% 50

.5

YA IR

.006

4 0%

35
.004

30%

20 %
1 2. 5

.002

10% RE LAT

Y I VE H UM IDIT

30

24

3-23 Assume PB = 101.325 kPa; q = 0

i 272.1 = iw = kJ / kg W 1000
iw = 0.272 (on scale) t2 = 22.6 C
ASHRAE PSYCHROMETRIC CHART NO.1
R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 101.325 kPa Copyright 1992

11 0
R

12

0
30

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

10 0
28

1.0
0 .8
10 .0

SEA LEVEL
0. 6
0.5

30
0 .9
1 .0
1 .5 2. 0

12 0
-5. 0

0.7

90
30 WE TB UL BT

26

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt
-4.0 -2 .0

4 .0

-2.0

0.0

0.272
80

EM

-1 .0

PE R

24

0.2

0 .1

AI R

O F

IL O G

EM

ER

Problem 3-23
R E P J -K LP Y A TH

AM

50
T

TU

TI O

TU

40

80 %
15
90 %

20

HUMI DITY RATIO - GRAM S M OISTURE PER KI LOGR AM D RY AIR

SA

20
10

5
40 %
0 .8

10

D RY BU LB TEMPERA TU RE - C

25

10

15

20

30

35

40

45

10

20

22.6

30

38

40

50

3-24

For adia. humidification (a)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

4. 0

5.0

AT

UR

1 .0

E-

C
22

-0 .5

11 0

-0.2

0 .9 2

3 .0

2 .0

70

25
20

ENTHALPY HU MIDITY RAT IO

2.5

h W

10 0
25

60
0 .9 0

18

16

20

20

90

2
0 .8 8

14

12

80
10

30

% 80
0 .8

15

6V

70

U OL

10
% 60

1
IC M

ME -C UB

70

4 0. 8

0%

ET ER R gD Rk PE

3 0%
0 .8 0

60

YA

20 %

IR

0 .7 8

IVE 10% RE LAT

HU MID ITY

50

ENTHALPY - KJ PER KILOGRAM OF DRY AIR

i = iw = 1131 Btu / lbw W

25

3-24 (contd)

qc = ma (i2 - i1)

m = 2000 x 60 / 13.14 a
m a = 9132 lba / hr

i1 = 18.1 Btu / lba ; i2 = 29.7 Btu / hr


qc = 9132 (29.7 - 18.1) = 105,931 Btu / hr
m w = m a (W3 - W2 ) ; W3 = 0.0167; W2 = 0.0032 lbv/lba

m w = 9132 (0.01 67 - 0.0032) = 123.3 lbw / hr

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

26

ASHRAE PSYCHROMETRIC CHART NO.1


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6
0 .5

50

.028

60

1 .0

85
1 5 .0
-200 0 -1 00 0

.026

2.0

SENSIB LE HEAT T OTAL HEAT


0.4
0. 3

Qs Qt

4 .0 8 .0

0.2

0 .1

IR

PE

TE

Problem 3-24
-B T Y AL P N TH E

PO

ER

TU

30

TI O

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

TU

15

40 35
35

45

DR Y BULB TEMPERATUR E - F

10

60 (16)

15

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

110 (43)

(b) Solution similar to (a)

3-25 English Units See diagram for construction on chart 1a.

32 2000 Q1 2 = = = 12 3000 Q3 3
Layout 2L/3 on the chart and read: W3 = 0.007 lbv/lba
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-8 -4 .0.0 -2.0
-1. 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5

- 0.4 -0.3

-0 .2

-0 .1

20

15 00

ENTHALPY HU MIDIT Y RAT IO

1131
1 000

80
h W

.020

35

75
50
14 .5
.018

75

3
.016

70

70

.014

45

65

.012

60

65
% 90

1 4 .0 LU VO ME

55

80

%
60

30 %
T. P DR L B. ER

.010

40

-C U.F

% 70

50

55
60 %
1 3 .5

.008

45

50

IR YA

% 50

.006

4 0%

35

40

.004

30%

1 3. 0

20 %
1 2.

2
.002

10% REL ATI

Y VE H UM IDIT

30

27 I3 = 22.2 Btu/lba
ASHRAE PSYCHROMETRIC CHART NO.1
NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6
0 .5

50

.028

60

1 .0

85
1 5 .0
-200 0 -1 00 0

.026

2.0

SENSIB LE HEAT T OTAL HEAT


0.4
0. 3

Qs Qt

4 .0 8 .0

0.2

0 .1

IR

PO

Problem 3-25
PE U -B T Y AL P N TH

TU

30
ER

TE

TI O

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

TU

15

40

45 40

DR Y BULB TEMPERATUR E - F

35
35
35

40 (4)

10

58.4 (15)

15

20

100 (38)

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-25

SI Units

Same procedure as above, read:

i3 = 34 kJ / kga
W3 = 0.007 kgv / kga
3-26 English Units Layout the given data on Chart 1a as shown for problem 3-25.

ma1 = 2000(60) 12.66 = 9,479lba hr


Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-8 -4 .0.0 -2.0
-1. 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5

- 0.4 -0.3

-0 .2

-0 .1

20

15 00

77
h W

80

1 000

.020

ENTHALPY HU MIDIT Y RAT IO

35

75
50
14 .5
.018

75

70

.016

2
70
.014

45

65

.012

60

65

1 4 .0

% 90

LU VO ME

52
50 45

55

80

%
60

.010

40

-C U.F

% 70
55

T. P DR L B. ER

.008

3
50

60

%
1 3 .5

IR YA

% 50

.006

4 0%

35

.004

30%

1 3. 0

1
1 2. 5

20 %
10% REL ATI Y VE H UM IDIT

.002

30

28 3-26 (contd)

ma2 = 1000(60) 14.44 = 4,155lba hr


ma1 32 9479 = = = 0.695 12 ma1+ma2 9479 + 4155

Layout distance 32 on line from 1 to 2 to locate point 3 for the mixture. Read: i3 = 21.5 Btu/lbm W3 = 0.0067 lbu/lba For W, % Error =

(0.007 0.0067)100 = 4.5 0.0067

For I, % Error =

(22.2 21.5)100 = 3.3 21.5

3-27 SHF =

250,000 = 0.8 200,000

or SHF =

59 = .81 73

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

29

ASHRAE PSYCHROMETRIC CHART NO.1


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

0.8
300 0

0 .8

.026

0. 3

0.2

0 .1

IR

PE

TE

Problem 3-27
U -B T Y AL P N TH E

PO

TI O

28.2
A SA TU R

ER

TU

30

25

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

15

40 35
35

45
40

DR Y BULB T EMPERATUR E - F

10

53 (12)

15

75 (24)

20

25

ENTHALPY - BT U PER POUND O F DRY AIR

3-28

Refer to diagram for 3-27 (a) q = ma (i1 - i2 ); i1 = 28.2; i2 = 21.5

ma = 250,000 / (28.2 - 21.5) = 37,313 lba / hr


Q = ma v 2 = 37,313 x 13.09 / 60 = 8,140 ft 3 / min
(b) similar procedure; Q = 3.85 m / s
3

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

50 00

2. 0

0 .5

SENSIB LE HEAT TOTAL HEAT


0. 4

Qs Qt
-2.
-1. 0

4 .0 8 .0

-8 -4 .0.0 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5 4 - 0. -0.3

-0 .2

-0 .1

21.5
20

15 00

80
h W

1 000

.020

ENTHALPY HU MIDITY RATIO

35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

60

65
% 90

50 %
1

.012

1 4 .0 LU VO ME

55

80

%
60

.010

40

-C U .F

% 70

T. P DR L B. ER

50

55

.008

2
45
50

60

%
1 3 .5

IR YA

% 50

.006

4 0%

35

.004

30%

1 3. 0

20 %
1 2. 5

.002

10% RE LAT

Y IVE H UM IDIT

30

30 3-29 (a) Use the AirQuantity option of program PSYCH, iterating on the relative humidity and setting the minimum outdoor Air Quantity to 0.01, NOT ZERO. Use the properties option to find the entering wet bulb temperature of 62.6F. Then

= 0.852
ts = 56F

(iterated)

Qs = 9,360 cfm
(b) Proceed as above

= 0.882
ts = 56F

Qs = 10,014 cfm
3-30 Proceed as in 3-29 above.

= 0.92
ts = 56.1 56 F

Qs = 11,303 cfm
3-31 (a) SHF =
500,000 = 0.91 550,000

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

31

3-31 (contd) (b)

q = ma (i2 -i1)

or ma = q/(i2 -i1)
ma = 550,000 (34.3 22.8)

ma =47,826lba hr
Q2= m a v 2 47,826 = x 14.62=11,654 cfm or 5.5 m3/s 60 60

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

32

ASHRAE PSYCHROMETRIC CHART NO.1


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS, INC.

1.0

SEA LEVEL
0. 6

50

.028

60

1.0

85
1 5 .0
-2000

0.91
300 0

0.8

.026

0. 3

0.2

0 .1

IR

Problem 3-31
U -B T Y AL P N TH

PO

ER

TU

30

TE

PE

TI O

SA

25

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45
40
1 3.

1
4 0%

DR Y BULB TEMPERATUR E - F

10

15

72 (22)

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

115 (46)

3-32 q = ma (i2 -i1)

i2 =

q +i1 ma

ma
i2 =

1400 x 60 = 5,915.5 14.2


-5 x 12,000 +38.5 5,915.5

i 2 = 2 8 .3 6 Btu/lba
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

5000

2. 0

0 .5

SENSIBLE HEAT TOTAL HEAT


0.4

Qs Qt
-2.
-1. 0

4 .0 8 .0

-1 00 0

-8 -4 .0.0 0

45
85 WE T
.024

BU

LB

50 0

TE MP E

55
RA TU RE - F
.022

-0 .5 4 - 0. -0.3

80
40

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENTHALPY HU MIDITY RATIO

34.3
35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

22.8
55

.012

60

65
% 90

1 4 .0 LU VO ME

80

%
60

30 %
DR L B. ER

.010

40

-C U.F

% 70

T. P

50

55
60 %
1 3 .5

.008

45

50

IR YA

50 %

.006

35

.004

30 %

20 %
1 2. 5

.002

Y IVE H UMIDIT 10% RE LAT

30

33 Then from Chart 1a, t2= 67F


ASHRAE PSYCHROMETRIC CHART NO.1
NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2. 0

0 .5

SENSIB LE HEAT TOTAL HEAT


0. 4
0. 3

Qs Qt
-2.

4 .0 8 .0

0.2

0 .1

IR

Problem 3-32
R PE U -B T Y AL P TH

28.4
TI O A SA TU R

PO

ER

TU

30

TE

25

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

15

40 35
35

45
40
1 3.

DR Y BULB T EMPERAT UR E - F

10

55

15

67

20

90

25

ENTHALPY - BT U PER PO UND O F DRY AIR

3-33 Use Adiabatic Mixing option of PSYCH with the Properties option to enter requested data. Assume volume flow rates of 3 to 1 to obtain. Tmix,db = 84.2 F Tmix,wb = 71.3 F

3-34 Use Program PSYCH at Sea Level elevation Iteration on the supply volume flow rate is required. This is the same as the leaving air quantity for the coil.
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-8 -4 .0.0
0

45
85 WE T
.024

-1.

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5 - 0.4 -0.3

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENTHALPY HU MIDIT Y RAT IO

35

75
70

75
50
14 .5
.018

75

.016

70

.014

45

65

.012

60

65
% 90

14 .0 V U OL

2 ADP 55
50
55
60 %
13 .5

ME

80

%
60

.010

40

-C U .F

% 70

T. P R .D LB ER

.008

45

50

IR YA

% 50

.006

4 0%

35

.004

30%

20 %
1 2. 5

.002

10% RE LAT

Y I VE H UM IDIT

30

34 3-34 (contd)

(a) Supply air quantity is 9,384 cfm. (b) The outdoor air quantity is 938 cfm. (c) Air enters the coil at 74.6 F db, 60.5 F wb at a rate of 9,740 cfm (d) The coil capacity is 248,256 Btu/hr. The amount of air returned is: (9,740 939) = 8,802 cfm.

3-35 Use Program PSYCH at 5,000 ft elevation Iteration on the supply volume flow rate is required. This is the same as the leaving air quantity for the coil. (a) Supply air quantity is 11,267 cfm. (b) The outdoor air quantity is 1,127 cfm. (c) Air enters the coil at 74.6 F db, 62.1 F wb at a rate of 11,697 cfm (d) The coil capacity is 334,143 Btu/hr. The amount of air returned is: (11,697 1,127) = 10,570 cfm.

3-36

Q 0 = 1000 cfm
(a) From Chart 1a

t s =120 / 74 F
ms = q 200,000 = (is -ir ) (37.2 22.8)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

35

= 13,889 lb/hr = m1

Qs = msv s = ms (14.78)/60 = 3,421 ft 3 / min


(b) mo = Qo /v o = 1000 x 60 / 12.61 = 4758 lb/hr
mr 13,889 4758 = = 0.66; From Chart 1a t1 = 61/ 47 F m1 13,889

t 3 - t1 = (119 61)
(c) mw = ms (Ws -W2 ) = 13,889 (0.0075 - 0.0036) = 54.2 lbm/hr (d) qf = m1(i3 -i1) =13,889 (32.8 18.6) = 197,224 Btu/hr

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

36

ASHRAE PSYCHROMETRIC CHART NO.1


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

0.8
300 0

.026

2.0

0 .5

SENSIB LE HEAT T OTAL HEAT


0.4
0. 3

Qs Qt

4 .0 8 .0

-8 -4 .0.0 -2.0
-1 .0

45
85 WE T
.024

BU

0.2

0 .1

IR

PE

TE

Problem 3-36
-B T Y AL P N TH E

PO

ER

TU

30

TI O

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45
40
1 3. 0

r
4 0%

DR Y BUL B T EMPERAT UR E - F

40

10

61

15

72

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

120

3-37

(a) t s = 120 / 71.4 F

Use Chart 1Ha

ms = 200,000 /(38.7 24.0) = 13,605 lba/hr = m1


Q s = 13,605 x 17.85 / 60 = 4048 cfm

(b) m 0 = (1000 / 15 .2) x 60 = 3947 lba/hr


mr 13,605 3947 = = 0.71; t1 = 62.8 / 47 F m1 13,605

t 3 -t1 = (119.5 62.8)


(c) m w =ms (w s -W1) = 13,605 (0.0088 - 0.0046) = 57.14 lbw/hr
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5 - 0.4 -0.3

-0 .2

-0 .1

20

15 00

ENT HAL PY HU MIDIT Y RAT IO

1150

80
h W

1 000

.020

35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

.012

60

65

14 .0 V

% 90

U OL ME

55

80

%
60

30 %
DR IR YA

.010

40

-C U.F

% 70

T. B. RL PE

47
45

50

55
60 %
13 .5

.008

50

% 50

.006

35

1 1

.004

30%

3
.002

20 %
1 2. 5

10% RE LAT

Y IVE H UM IDIT

30

37 (d)

qf = 13,605 (33.8 - 20.2) = 185,028 Btu/hr

3-38

Assume fan power and heat gain are load on the space
ms = 9384 x 60 = 42,915 lbm/hr; Prob 3-34 13.12

Wfan + qduct = ms (is ic )


= (4 x 2545) + 1000 = 11,180 Btu / hr
ic = 20.8 11 ,180 = 20.54 Btu/lbm 42,915

State c is required condition leaving coil Part a, b, and c are same as prob. 3-34; (d) qcoil =m1(i1-ic ) = 42,915 (26.8 - 20.54) = 268,648 Btu/hr

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

38

ASHRAE PSYCHROMETRIC CHART NO.1


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2.0

0 .5

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt
-2.
-1 .0
-0 .5 - 0.4 -0.3

4 .0 8 .0

0.2

0 .1

IR

PO

ER

TU

Problem 3-38
R PE U -B T Y

30

TE

TI O

TH

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

AL P

TU

15

40 35
35

45

DR Y BULB T EMPERAT UR E - F

10

55

15

72

20

100

25

ENTHALPY - BT U PER PO UND O F DRY AIR

3-39

qr = m s (i r i s ); W fan = m s (i s i c )

(a) ic = 28 Btu/lbm; ir = 33.7 Btu/lbm Using Chart 1Ha

qr = 1,320,000 Btu/hr

Wfan = 30 x 2545 = 76350 Btu/hr

Wfan = 30 x 2545 = 76,350 = ma (is -ic )

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-8 -4 .0.0 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .2

-0 .1

20.54
20

15 00

0
80
h W
1 000

.020

ENTHAL PY HU MIDITY RAT IO

35

75
50
14 .5
.018

75

70

.016

70

65

50 %
14 U OL .0 V

.014

45

.012

60

65
% 90

55

80

%
60

ME -C U.F

.010

40

% 70

T. DR B. RL PE

50

c s 50

55
60 %
13 .5

.008

45

YA

% 50

.006

IR

4 0%

35

40
30%
1 3. 0

.004

20 %
1 2. 5

.002

10% RE LAT

Y IVE H UM IDIT

30

39

qs = 1,320,000 = ma(ir -is )


ASHRAE PSYCHROMETRIC CHART NO.4
NORMAL TEMPERATURE
R

55
85
R

60

BAROMETRIC PRESSURE: 24.896 INCHES OF MERCURY Copyright 1992

50
.028

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
50 00

5000 FEET
0 .6
0 .5

60

1 8 .0

80
1 .0

0.8

0 .8

2. 0

-2 000

.026

45
80 W ET

SENSIBL E HEAT TOTAL HEAT


0. 4
0. 3

Qs Qt

-1

4 .0 8 .0 -8 -4.0.0 -2. 0
.0

-1 000

0.2

0 .1

AI R

RY

AT

UR

ND

ER

TU

RA

TI O

Problem 3-39
-B LP Y A TH EN

PO

TE

PE R

SA

TU

25

s
60

c
55
% 90
% 80

HUMIDITY RATIO - POUNDS MOISTURE PER PO UND DRY AIR

15

35

40
35

DR Y BUL B T EMPERATUR E - F

10

62.5 (17)

15

80 (27)

20

90 (32)

25

ENTHALPY - BT U PER POUND OF DRY AIR

Two unknowns & two equations

Solve simultaneous:

W fa n + q s = m a (ir -ic ) ma= 1 ,3 2 0 ,0 0 + 7 6 ,3 5 0 (3 3 .7 -2 8 )

m a = 2 4 4 ,9 7 4 lb a /h r
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

BU

LB

TE MP

.024

ER

75
50 0

AT U

40

RE

55
- F
.022

-0 .5 -0 .4 - 0.3 -0 .2

-0 .1

15 00

17 .5

75
10 00

.020 h W

ENTHALPY HU MIDIT Y RATIO

35

70
50
.018

70

30

65
17 .0

.016

65

50 %
r

59 (15)
60

.014

45

.012

16 .5 V

20

.010

50
70 %

55

40

U OL ME -C

45

50

.008

% 60
16 .0

U .F T. P ER

40

45

50

R .D LB

.006

4 0%

35

IR YA

30 %

.004

1 5 .5

20%

.002

I TY TIV E HUMID 10% RELA

30

40

is = ir - ( qs ma )
is = 33.7 1,320,000 =28.3 Btu/lba 244,974

Locate points on the condition line on Chart 1 Ha and point c is on cooler process line horz. to left of points. Read ts = 62.5 F, tc = 61.6F. (a) Qs =

244,974 x16.2 = 66,143cfm 60

(b) Qs = 31.2 m 3 s

3-40

English Units Tucson, Arizona, Elevation 2,556 ft.

imin =i0 =31.1 Btu/lba and sat. air ; t min =64.5 F; PSYCH
Shreveport, Louisiana, Elevation 259 ft.
imin =i0 = 42.5 Btu/lba and sat. air ; tmin = 76.8 F; PSYCH

SI Units Tucson, Arizona

imin =i0 = 51.5 kJ/kga ; tmin =18.1 C; Chart 1b


Shreveport, Louisiana
imin =i0 =75.5 kJ/kga ; tmin =24.8 C; Chart 1b

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

41

ASHRAE PSYCHROMETRIC CHART NO.4


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.642 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

259 FEET
0 .6

50

.028

60
1 .0

85
15 .0
-2 000

.026

2.0

0 .5

SENSIBL E HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt

4 .0 8 .0

-1 000

0.2

0 .1

AI R

TE M

ER

Problem 3-40 Shreveport, LA


TU -B Y LP TH A N E

- F

PO

PE

AT U

30

O N

AT I

25

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

AT

15

40 35
35

45
40

DR Y BUL B T EMPERATUR E - F

10

15

76.8

20

95

25

ENTHALPY - BT U PER PO UND O F DRY AIR

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

45
85 WE TB UL
.024

-1

-8 -4.0.0 -2. 0
.0

BT EM

50 0

80
40

PE R

55
AT UR EF
.022

-0 .5

-0 .4 - 0.3

-0 .2

-0 .1

15 00

80
.020 h W

10 00

ENT HAL PY HU MIDIT Y RAT IO

75
35

TLO
50
.018

75
14 .5

70

SL

.016

70

.014

45

65

60

65
% 90
1 4.

.012

20

55

80

.010

UM OL 0V

60

40

70

E-

50

55
% 60

.008

CU .FT DR LB . ER .P

45

50
50

1 3. 5

.006

4 0%

35

IR YA

.004

30%
1 3 .0

20 %

.002

IVE 10% RE LAT

HUMIDITY

30

42

ASHRAE PSYCHROMETRIC CHART NO.4


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 27.259 INCHES OF MERCURY Copyright 1992

85
50
.028

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

2556 FEET
0 .6

60

5 16 .

1 .0

85
-2 000

.026

2. 0

0 .5

SENSIBL E HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt

-1

4 .0 8 .0 -8 -4.0.0 -2. 0
.0

-1 000

45

0.2

0 .1

O U

EM

ER

Problem 3-40 Tucson, Arizona


R PE TU -B LP Y A

IR

O F

30

TU

TI O

TU

TH

25

65

EN

60
90 %

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

SA

15

DR Y BUL B T EMPERAT UR E - F

35
35

10

64.6

15

20

102

25

ENTHALPY - BT U PER PO UND O F DRY AIR

3-41

q = m s (ir i s )
(a) ms = 12,000 /(28.2 19.1) = 1,319 lba/hr ton
Qs = 1319 x 15.6 = 343 cfm/ton 60

mo r1 13 = = = 0.55 or 55% ms r0 23.5

(b) Qs 0.046 m3 / s - kW

m0 /ms 55%
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

80
0

.024

55
50 0

-0 .5 -0 .4 - 0.3

40

80

WE

-0 .2

-0 .1

TB

UL

.022

20

15 00

BT

75
10 00

EM P

ER A

TU

1 6 .0

RE

- F

.020

ENT HAL PY HU MIDIT Y RAT IO

h W

35

75
.018

50

70

.016

70

65

TLO

.014

45

1 5 .5

.012

55

60
% 80

.010

40

1 5.

50

% 7 055
% 60

UM OL 0V

.00 8

45

E-

50

CU

40

45
40

% 50
1 4.

. LB ER .P .FT

TA

.00 6

4 0%
30 %

35

DR IR YA

.00 4

1 4 .0

20%

.00 2

ITY TIV E HU MID 10% RELA

30

43

ASHRAE PSYCHROMETRIC CHART NO.4


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 24.896 INCHES OF MERCURY Copyright 1992

55
85
R

60

50
.028

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8
50 00

5000 FEET
0 .6
0 .5

60

1 8 .0

80
1 .0

2.0

-2 000

.026

45
80 W ET

0.7
0 200

SENSIBL E HEAT TOTAL HEAT


0. 4
0. 3

Qs Qt

-1

4 .0 8 .0 -8 -4.0.0 -2. 0
.0

-1 000

0.2

0 .1

AI R

DR

PE RA

TU

RE

UN

PO

TU

AT

Problem 3-41
AL PY EN TH

TE

PE R

IO

-B

UR

SA T

25
60

55

% 90
% 80

40 %
1 6 .5 LU VO

HUMI DITY RATIO - POUNDS MOISTURE PER POUND DRY AIR

15

35

40
35

DR Y BUL B T EMPERAT UR E - F

10

50 (10)

15

75 (24)

20

100 (38)

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-42 q = m2 (i2 i3 ); m2 =
m 2 = 26,042 lba/hr

500,000 (41.1 21.9)

Q 2 = 26042 x 14.55/60 = 6315 cfm m 0 = 0.25 x 26,042 = 6511 lba/hr m 0 / m 3 = 0.25; t mix = 67.5 / 49.5 F

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

300 0

BU

LB

TE MP

.024

ER

75
50 0

AT U

40

RE

55
- F
.022

.5 -0 -0 .4 - 0.3 -0 .2

-0.1

15 00

17 .5

75
10 00

.020 h W

ENT HALPY HU MIDIT Y RAT IO

35

70
50
.018

70

30

65
17 .0

.016

65

.014

45

60

.012

20

.010

50
70 %

55

40

ME -C

45

50

.008

s
40
45

% 60
16 .0

U.F T. P ER

50

10 %
0

L B. DR

.006

4 0%

35

IR YA

30 %

.004

1 5 .5

20%

.002

IVE 10% REL AT

HUMIDI TY

30

44 3-42 (contd) Preheat Coil:

qph = m0c p (t 4 -t 0 ) = 6511 x 0.24 (60-6) = 84,383 Btu/hr

Heat Coil:

qh = m2 (i5 -i1) = 26,042 (28.4 - 20) = 218,753 Btu/hr


Humidifier:

m w = m2 (W2 -W5 ) = 26,042 (0.0144 - 0.0035)


= 283.9 lbw/hr
(b) Q2 = 2.98 m3 / s; qph = 24.7 kW; qh = 64.1 kW;

m w = 0.036 kg/s

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

45
ASHRAE PSYCHROMETRIC CHART NO.1
R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 000

.026

2.0

0 .5

SENSIB LE HEAT TOTAL HEAT


0.4
0. 3

Qs Qt

4 .0 8 .0

-1 00 0

0.2

0 .1

IR

PO

ER

Problem 3-42
PE U -B T Y AL P TH

TU

30

TE

TI O

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45
40
1 3.

DR Y BUL B TEMPERATUR E - F

10

60 (16)

15

70 (21)

20

105 (40)

25

ENTHALPY - BT U PER PO UND O F DRY AIR

3-43

Use Chart 1a; qd = ma (ir is ) or m a = q d /(ir i s ) (a) m a = 150 x 12,000 / (28.4-22) = 28,125 lbm/hr

Qd = 28,125 x 13.25/60 = 61,211 cfm


Qm = 0.20 Qd = 1,242 cfm

mm = 1 ,242 x 60/13.5 = 5,521 lbm/hr [vm assumed]


im =ir 1.8 x 12,000/5,521 = 24.5 Btu/lbm; tm = 62 / 57 F

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

-8 -4 .0.0 -2.0
-1. 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5 - 0.4 -0.3

-0 .2

-0 .1

20

15 00

ENT HAL PY HU MIDITY RATIO

1153

80
h W

1 000

.020

35

75
50
14 .5
.018

75

70

.016

2
70
.014

45

65

.012

60

65
% 90

1 4 .0 LU VO ME

55

80

%
60

.010

40

-C U.F

% 70

30 %
IR YA

T. P

50

55
60 %
1 3 .5

.008

DR L B. ER

45

50

50 %

.006

4 0%

3 1 5

35

.004

30%

20 %
1 2. 5

.002

10%

H UM IDITY REL ATI VE

30

46 (b) Qd = 2.93 m3 /s; Qm = .59 m3 /s; tm = 17/14 C


ASHRAE PSYCHROMETRIC CHART NO.1
NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

0. 3

0.2

0 .1

IR

PO

Problem 3-43
PE U -B T Y AL P N TH

ER

TU

30

TE

TI O

SA

25

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45 40
1 3.

DR Y BUL B T EMPERAT UR E - F

10

60 (16)

15

75 (24)

20

25

ENTHALPY - BT U PER PO UND O F DRY AIR

3-44

(a) ma =

15.0 x 12,000 = 29,508 lba/hr (31.2 - 25.1)

Qd = 29,508 x 16.0/60 = 7,869 cfm; Qm = 0.2 x Qs

= 1,574 cfm

mm =1 ,574 x 60/16.2 = 5,829 lba/hr (v massumed)


im = 35.7 1.8 x 12,000/5,829 = 27.5 Btu/lba;
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

0.6

300 0

50 00

0.8

1.0
0 .8

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2. 0

0 .5

SENSIB LE HEAT T OTAL HEAT


0. 4

Qs Qt

-1.

4 .0 8 .0 -8 -4 .0.0 -2. 0
0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .5 - 0.4 -0.3

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENT HAL PY HU MIDIT Y RAT IO

35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

.012

60

65

14 .0 V

% 90

U OL

55

m 80 % s
% 70

r
60

ME -C U.F T. P L B. ER

.010

40

50

55
60 %
1 3 .5

.008

DR

45

50

IR YA

% 50

.006

4 0%

35

.004

30%

62 (17)
20 %
10% RE LAT Y IVE H UM IDIT

.002

1 2. 5

30

47

tm = 62.5 / 58 F
(b) Q s =3.7 m3 / s; Qm = 0.74 m3 /s; tm = 17 /14.4 C 3-45 Use Chart 1a;

mr 10 = 0.8 = m1 0r

[Both design and min. load condition] is = ir - qm / ms

ms =

Qd 50 x 12,000 = ir i s (29.35 - 22.3)

m s = 85,106 lba/hr; m s is constant for all conditions i s' = 29.35 25 x 12,000/85, 106 = 25.83 Btu/lba
(a) From Chart 1a; t s' = 64 F (b) m s i s + m b i1' = (m c + m b ) i s'
m b (i s i s' ) 24.2 25.8 = = 0.271 = m c (i s' i1' ) 25.8 31.7

(b) From chart 1a; t d = 49 F for both cases

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

48

ASHRAE PSYCHROMETRIC CHART NO.1


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

0. 3

0.2

0 .1

Problem 3-45
O N D U PO R PE U -B T

IR

ER

TU

30

TE

TI O

TH

SA

25

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

AL P

TU

15
40 35
35

DR Y BUL B T EMPERAT UR E - F

10

55 (13) 64 (18)

15

77 (25) 85 (29)

20

95 (35)

25
ENTHALPY - BT U PER POUND OF DRY AIR

3-46

Refer to problem 3-45. Results are similar.

3-47 (a) It is probably impossible to cool the air from 1 to 2 in one process. The extension of line 12 does not intersect the saturation curve. (b) Cool the air to state 1' and then heat to state 2.

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

50 00

0.9

1.0
0 .8

SEA LEVEL
0. 6
0 .5

50

.028

60
85
1 5 .0

1 .0

2.0

SENSIB LE HEAT T OTAL HEAT


0. 4

Qs Qt

-1.

4 .0 8 .0 -8 -4 .0.0 -2. 0
0

-2 00 0 -1 00 0

.026

45
85 WE T
.024

BU

LB

TE

50 0

80

MP E

55
RA TU RE - F
.022

-0 .5 - 0.4 -0.3

-0 .2

40

-0 .1

20

15 00

80
h W

1 000

.020

ENT HAL PY HU MIDIT Y RATIO

35

75

50

0'
75

14 .5

.018

70

.016

50 %
70
.014

45

65

1'

.012

60

65

1 4 .0

% 90

LU VO

s'
55
80

ME

%
60

.010

40

-C U.F

% 70

T. P L B. ER

50

s
50

55

.008

60

%
1 3 .5

DR

45

IR YA

% 50

.006

45 40

4 0%

35

.004

30%

1 3. 0

20 %
1 2. 5

.002

10% RE LAT

Y I VE H UM IDIT

30

49

ASHRAE PSYCHROMETRIC CHART NO.1


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2.0

0 .5

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt

-1.
-0 .5 - 0.4 -0.3

4 .0 8 .0 -8 -4 .0.0 -2. 0
0

0.2

0 .1

IR

Problem 3-47
PE U -B T Y AL P N TH

PO

ER

TE

67
65

TU

30

TI O

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45

DR Y BUL B TEMPERATUR E - F

10

52 (11) 60 (16)

15

80 (27)

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-48

(a)

mc sh = =.837 ms ch

mh cs = = 0.163 ms ch
mc 0.837 = = 5.14 mh 0.163
q = ms (ir is )
ms = 50 x 12,000 = 93,750 lba/hr (28.2-21.8)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENTHAL PY HU MIDIT Y RAT IO

35

75
50
14 .5
.018

75

70

.016

90 %
70
.014

45

60

65
% 90

.012

14 U OL .0 V ME

54
50

55

80

%
60

.010

40

-C U .F

% 70

T. RY B. D RL PE

1'
50

55

.008

45

60

%
13 .5

% 50

A IR

.006

4 0%
1 3.

35

40
30%
0

.004

20 %
1 2. 5

.002

10% RE LAT

Y IVE H UM IDIT

30

50

Q s = 93,750 x 13.2/60 = 20,625 cfm

(b) Qs = 9.7 m3 /s
ASHRAE PSYCHROMETRIC CHART NO.1
R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2.0

0.65
0 200

0 .5

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt

4 .0 8 .0

0.2

0. 1

IR

PO

ER

TU

Problem 3-48
PE U -B T Y AL P

30

TE

TI O

TH

SA

25

HUMIDITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

TU

15

40 35
35

45
40

DR Y BUL B T EMPERAT UR E - F

10

52 (11)

15

75 (24)

20

90 (32)

25

ENTHALPY - BT U PER POUND O F DRY AIR

3-49

See diagram of problem 3-48 (a)


mc mh 10.1 36 = = 0.9; = = 0.10 ; ms 46.3 ms 46.3

mc 0.9 = = 9.0 mh 0.10

ms =

50 x 12,000 = 83,333 lba/hr (30.1 - 22.9)

Q s =83,333 x 15.67/60 = 21,763 cfm


Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

300 0

-1.
.5 -0 - 0.4 -0.3

-8 -4 .0.0 -2. 0
0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENT HAL PY HU MIDIT Y RAT IO

35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

90 %
65
14 .0 V U OL

.012

60

% 90

ME

55

80

%
60

.010

40

-C U.F

% 70

T. P R .D LB ER

50

55
60 %
13 .5

20 %
h

.008

45

50

s
% 50

IR YA

.006

4 0%

35

.004

30%

1 3. 0

20 %
1 2.

.002

10% REL ATI

Y VE H UM IDIT

30

51

(b) Qs =10.3 m3 /s 3-50 (a) See diagram for problem 3-48


mc = 0.837; qc = mc (ir -ic ); mc = 0.714 x ms = 0.837 x 93,750 ms

mc = 78,469 lba/hr ; Qc = 78,469 x 13.04/60 = 17,054 cfm

qc = 78,469 (28.2-20.6) = 596,364 Btu/hr


(b) Qc =8.1 m3 /s; qc = 175 kW

3-51 SI Units (a) On the basis of volume flow rate using Chart 1b:

Q2 =

13 Q3 = 0.69 x 1.18 = 0.815 m3/s 12

and Q1= Q3 - Q2 = 1.18 0.815 = 0.365 m3/s

(b)

q34 = ma3 (i4 -i3 ) = q34 =

Q3 (i4 -i3 ) v3

1.18 (47.8-41.0) = 9.6 kW 0.835

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

52
ASHRAE PSYCHROMETRIC CHART NO.1
R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 101.325 kPa Copyright 1992

11 0
R

12

0
30

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

10 0
28

1.0
0 .8 0. 7

SEA LEVEL
0. 6

30
0 .9
1 .0

4
12 0

1 .5 2. 0
SENSIB LE HEAT T OTAL HEAT Qs Qt
-2
-1 .0
0. 3

-5.0
-2.0

90
30 WE TB UL BT E

26

0.2

0 .1

Problem 3-51
D O F AM R IL O G R K E P J

AI R

EM

ER

50

TU

TI O

LP Y

TU

20

TH

40

SA

HUMIDITY RATIO - G RAM S M OISTURE PER KILOGR AM D RY AIR

-K

20

5
40 %
0 .8

10

D RY BU LB TEMPERA TU RE - C

25

10

15

20

30

35

40

45

10

12

20

17.2

24

29

30

40

50

English Units

(a) Q1= 640 cfm; q34 = 33,684 Btu/hr

3-52 (a),(b) From Chart 1b, states 1.4 and ADP are known. Based on approx. 11.8 C db, 11.2 C wb, and 90% RH locate state 2. Then for full load design condition air is cooled from 1 to 2 and the room process proceeds from 2 to 4.
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

4. 0

5.0

10 .0

Problem 3-51
0.5

4 .0

-4.0
.0

0. 4
-0 .5

0.0

MP ER

24

1 .0

80

AT

UR

E-

C
22

11 0

-0.2

0 .9 2

3 .0

2 .0

70

25
20

ENT HAL PY HU MIDIT Y RAT IO

2.5
h W

10 0
25

60

18

0 .9 0
16

20

50 %
0 .8 8

90
14

12

14.7
15
30

90

80
10

% 80 3

15

0 .8 6V

11
10

70

U OL ME

% 60

70

-C UB

4 0.8

10

IC M

50

ET ER g Rk PE

3 0%
0 .8 0

DR IR YA

60

20 %

0 .7 8

IVE 10% RE LAT

HUM ID ITY

50

ENTHALPY - KJ PER KILO GRAM O F DRY AIR

53 For the high latent load condition, the air at 2 is reheated to state 3 where it enters the space and the process proceeds to state 4. (c) q24 = ma (i4 -i2 ) =
Q2 (i4 -i2 ) v2

Q2 =35 x 0.817 (47.7-32) ;

Q2 = 1.82 m3/s

q12 = ma (i1-i2 ) = q12 = 63.7 kW

1.82 (60.6-32) 0.817

q34 = ma (i4 -i3 )= q34 = 18.5 kW

1.82 (47.7-39.4) 0.817

q23 = q24 - q34 = 35-18.5=16.5 kW

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

54
ASHRAE PSYCHROMETRIC CHART NO.1
NORMAL TEMPERATURE
R

11 0
R

12

0
30

BAROMETRIC PRESSURE: 101.325 kPa Copyright 1992

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

10 0
28

1.0

Problem 3-52
0.7

SEA LEVEL
SENSIB LE HEAT T OTAL HEAT Qs Qt
-2
-1. 0

30
0 .9
1 .0

0 .8
10 .0

12 0
1 .5 2.0
4 .0
-4.0
.0
-5. 0
-2.0

90
30 WE TB UL BT E

26

0. 6
0.5

0. 4
0. 3

0.0

MP ER

24

0.2

0 .1

AI R

AM

IL O G

EM

ER

50

TU

Problem 3-52
E P J -K LP Y

O F

TI O

TU

20

TH

40

17
15
90 %

HUMIDITY RATIO - GRAM S M OISTURE PER KILOGR AM D RY AIR

SA

20

5
40 %
0 .8

10

D RY BU LB TEMPERA TU RE - C

25

10

15

20

30

35

40

45

10

11.8

19

20

23

27

30

40

50

3-52

English Units (a),(b) See above (c) Q2 = 4103cfm ; q12 =221,243 Btu/hr

3-53 English Units (a)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

4. 0

5.0

1 .0

80

AT

UR

E-

C
22

-0 .5

11 0

-0.2

0 .9 2

3 .0

2 .0

70

25
20

ENTHALPY HU MIDIT Y RAT IO

2.5

h W

10 0
25

60
0 .9 0

18

21
20

16

90
14

1
0 .8 8

12

80
10

30

14 11
ADP
10

% 80

15

0 .8 6V

70

U OL ME

2
10

% 60

3
4 0 .8

70

-C UB IC M

% 50

ET ER R gD Rk PE

3 0%
0 .8 0

60

IR YA

20 %

0 .7 8

IVE 10% RE LAT

HU MID ITY

50

ENTHALPY - KJ PER KILO GRAM O F DRY AIR

q34 = 67,498 Btu/hr; q23 = 52,502 Btu/hr

q=ms (ir -is ); ms = 5000 x 60/13.2 = 22,727 lba/hr


(specific volume value of 13.2 ft3/lbm is assumed.)

55

is = ir - q /ms =28.2 10 x 12,000 / 22,727 = 22.9 Btu/lba

t s = to = 57.5 F; Ws =Wo = 0.0083 lbv/lba


(b)

mr 0m m = = 0.462 r mm 0r ms

mr =0.462 x 22,727 = 10,500 lba/hr mo = 22,727 10,500 = 12,227 lba/hr


Qr = 10,500 x 13.68/60 = 2,394 cfm
Qo = 12,227 x 12.11/60 = 2,468 cfm
(c)

mr 0'm' = =0.578 mm' 0'r

mr =0.578 x 22,727 = 13,131 lba/hr; mo' = 9,596 lba/hr


Qr =13,131 x 13.68/60 = 2,994 cfm; Q o' = 9,596 x 13.48/60
= 2,156 cfm (d) qc = ms (im' -is ) = 22,727 (28.4 - 22.8) = 127,271 Btu/hr

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

56

ASHRAE PSYCHROMETRIC CHART NO.1


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

0. 3

0.2

0 .1

ER

TU

Problem 3-53
PO R PE U -B T Y

IR

30
P

TE

TI O

SA

TH

25

0'
60
65
% 90

HUMIDITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

AL P

TU

15

40 35
35

45 40

DR Y BUL B TEMPERATUR E - F

40 (4)

10

57.5 (14) (18) 65

15

75 (24)

20

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-53 SI Units (a) ts = 14.2C; Ws = 0.0083 kgv/kga


3 3 (b) Qr =1.13m s ; Qo =1.17m s

(c) Qr =1.41m

s ; Qo' =1.02m3 s

(d) qc = 37.3 kW 3-54 (a) Any combination that will yield an enthalpy less than 57.0 kJ/kga or 33 Btu/lba
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

0.8

2.0

0 .5

SENSIB LE HEAT T OTAL HEAT


0. 4

Qs Qt

-1.
-0 .5 - 0.4 -0.3

4 .0 8 .0 -8 -4 .0.0 -2. 0
0

45
85 WE T
.024

BU

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .2

-0 .1

20

43 (6)
0

15 00

1150
ENTHAL PY HU MIDITY RAT IO

80
h W

1 000

.020

35

75
50
14 .5
.018

75

70

.016

90 %
65

70

.014

45

.012

14 U OL .0 V

m'
60

50 %
r

ME

55

80

.010

40

-C U.F

% 70

T. P DR L B. ER

50

s
50

55

.008

60

%
13 .5

ADP

45

YA

% 50

.006

IR

4 0%

35

m
1 3. 0

.004

30%

20 %
1 2. 5

10% RE LAT

Y IVE H UM IDIT

70 (21)

.002

30

57

(b) m s = 5 / 0.84 = 5.95 kga/s = mr

mo mr = =0.36 mr 0r

mo = 0.36 x 5.95 = 2.14 kga/s


Qo = 2.14 x 0.852 = 1.82 m3 /s = 3,857cfm
(c) tad = 15.4 C or 60F (d) qo /qn = (im -is )/(ir -is ) = 1.0 (Essentially, no difference)
ASHRAE PSYCHROMETRIC CHART NO.1
R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 101.325 kPa Copyright 1992

11 0
R

12

0
30

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

10 0
28

1.0
0 .8
10 .0

SEA LEVEL
0. 6
0.5

30

0 .9

1 .0
1 .5 2. 0

4
12 0
-5.0
-2.0

0.7

90

26

SENSIB LE HEAT TOTAL HEAT


0. 4
0. 3

Qs Qt
-4.0 -2 .0

4 .0

30

0.2

0 .1

AI R

AM

IL O G

EM

ER

50

TU

Problem 3-54
E P J -K LP Y

O F

TI O

TU

m2

TH

40

HUMIDITY RATIO - G RAM S M OISTURE PER KI LO GR AM D RY AIR

SA

20

40 %
0 .8

10

D RY BU LB TEMPERA TU RE - C

25

10

15

20

30

35

40

45

10

18 (64)

20

25 (77)

30

40

50

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

4. 0

0.6

0.0

WE TB UL BT

EM

-1. 0
-0 .5

PE R

24

5.0

1 .0

80

AT

UR

E-

C
22

11 0

-0.2

0 .9 2

3 .0

2 .0

70

25
20

ENT HAL PY HU MIDIT Y RATIO

2.5
h W

10 0

25
60

18

57

0 .9 0
16

20
14

90

0 .8 8

12

15
30

90

% s

80
10

% 80
0 .8
15

6V

70
10

U OL ME

% 60

70

-C UB

4 0. 8

10

IC M

0%

ET ER gD Rk PE

3 0%
0 .8 0

60

RY

20 %

20 (68)
HUM ID ITY

A IR

0 .7 8

IVE 10% RE LAT

50

ENTHALPY - KJ PER KI LO GRAM O F DRY AIR

58 3-55

SHF =

424,000 = -4 530,000 424,000

Construct condition line on Chart 1a with preheat and mixing processes. (a) qsen = -424,000 = m sc p (t r -t s )
ms = 424,000 = 88,333 lba/hr 0.24 (75 95)

Q s =88,333 x 14.07/60 = 20,714 cfm or 9.8 m3 /s


(b)

mr hm = =0.33; mr = 0.33 x 88,333 lba/hr mm hr

mr =29,150 lba/hr; Qr = 29,150 x 13.68/60 = 6,646 cfm or 3.14 m3 /s


mh =1 0.33 = 0.67; mh = 0.67 x 88,333 mm

mh = 59,183 lba/hr; Qh = 59,183 x 13.1/60


Qh = 12,922 cfm or 6.1 m3 /s (at heated condition)
(c) qph =mhc p (th -t o ) = 59,183 x 0.24 (60-35)

q=355,098 Btu/hr or 104 kW


(d) qm =88,333 x 0.24 (95 - 65) = 635,998 Btu/hr or 186 kW
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

59

ASHRAE PSYCHROMETRIC CHART NO.1


R

NORMAL TEMPERATURE BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

55

60

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

2.0

0 .5

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt

-1.

4 .0 8 .0 -8 -4 .0.0 -2. 0
0

0.2

0 .1

IR

PO

ER

Problem 3-55
PE U -B T Y AL P TH

TU

30

TE

TI O

SA

25

HUMI DITY RATIO - POUN DS MOISTURE PER POUND DRY AIR

TU

15

40 35
35

45 40
1 3. 0

DR Y BUL B T EMPERATUR E - F

0
40 45 50 55

35 (2)

10

60 (16)

15

75 (24)

20

95 (35)

25

ENTHALPY - BT U PER POUND OF DRY AIR

3-56 Refer to chart 1a. (a)

q34 = ma3 (i4 -i3 ) = Q3 x

60 (i4 -i3 ) v3

Q3 x

q34v 3 (1750 x 13.23) = 60(i4 -i3 ) 60(28.1-23)

Q3 = 75.7 or 76 cfm = 0.040 m3 /s

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

65

70

95

0 200

300 0

45
85 WE T
.024

-4
50 0

BU

LB

TE

80
40

MP E

55
RA TU RE - F
.022

-0 .5 - 0.4 -0.3

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENT HAL PY HU MIDIT Y RAT IO

35

75
50
14 .5
.018

75

70

.016

70

.014

45

65

.012

60

65
% 90

1 4 .0 LU VO ME

50 %
r

55

80

.010

60

40

-C T. P U.F

% 70

50

55
60 %

20 %
IR

.008

DR L B. ER

1 3 .5

45

50

YA

50 %

.006

4 0%

35

m
30%

.004

s
20 %
Y IVE H UM IDIT

.002

1 2.

10% RE LAT

30

60 (b) t3db = 58.5 F and 80% RH or 15 C (c) Q2 =

31 ; Q3 = 0.754 x 75.7 = 57 cfm or 0.028 m3 /s 12

Q1= 76 - 57 = 19 cfm or 0.012 m3 /s


ASHRAE PSYCHROMETRIC CHART NO.1
NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8 50 00

SEA LEVEL
0. 6
0 .5

50

.028

60

1 .0

85
1 5 .0
-2 00 0 -1 00 0

.026

0.8
300 0

2.0

SENSIB LE HEAT T OTAL HEAT


0. 4
0. 3

Qs Qt
-2.

4 .0 8 .0

-1.
-0 .5 - 0.4 -0.3

-8 -4 .0.0 0

45
85 WE T
.024

BU

0.2

0 .1

Problem 3-56
R D F O N D U PO R PE U -B T

IR

ER

TU

30

TE

TI O

AL P

TU

TH

SA

25

62
60
% 90

1
65
1 4 .0

HUMI DITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

15

40 35
35

45
40

DR Y BULB T EMPERAT UR E - F

10

50

58.5

15

75

84

20

25

ENTHALPY - BT U PER PO UND O F DRY AIR

3-57 (a)

Refer to Chart 1

A reheat system is required. Process 1-2 is for the coil. Process 3-4 is defined by the SHF = 0.5 Process 2-3 represents the required heat.
Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

LB

TE

50 0

80
40

MP E

55
RA TU RE - F
.022

-0 .2

-0 .1

20

15 00

80
h W

1 000

.020

ENT HAL PY HU MIDIT Y RATIO

35

75
50

90 %
75

14 .5

.018

70
70
70

.016

50 %
.014

45

65

.012

LU VO ME

55

80

%
60

.010

40

-C U.F

% 70

T. P L B. ER

50

3 2
50

55
60 %
1 3 .5

.008

DR

45

IR YA

% 50

.006

4 0%

35

.004

30%

1 3. 0

20 %
1 2. 5

.002

10% RE LAT

Y I VE H UM IDIT

30

61 State 3 is defined by the intersection of the reheat and space condition lines.

(b)

q34 = ma3 (i4 -i3 ) =

Q3 x 60 (i4 -i3 ) v3

Q3 =

q34 v 3 100,000 x 13.4 = 60(i4 -i3 ) 60(28.2-23.9)

Q3 = 5,194 cfm or 2.5 m3 /s


(c)

q12 = ma (i1-i2 ) =

5,194 x 60 (34.2-20.2) 13.4

q12 = 325,594 Btu/hr or 95.4 kW q23 = 5,194 x 60 (23.9-20.2) 13.4

q23 =86,050 Btu/hr or 25.2 kW

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

62

ASHRAE PSYCHROMETRIC CHART NO.1


NORMAL TEMPERATURE
R

55

60

BAROMETRIC PRESSURE: 29.921 INCHES OF MERCURY Copyright 1992

90

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8
50 00

SEA LEVEL
0. 6

50

.028

60
85
15

1 .0

2.0

0 .5

SENSIB LE HEAT TOTAL HEAT


0. 4
0. 3

Qs Qt

-1.

4 .0 8 .0 -8 -4 .0.0 -2. 0
0

-2 00 0 -1 00 0

.026

.0

0.2

0 .1

Problem 3-57
F O N D U PO R PE U -B T

IR

ER

TU

30
P

TE

TI O

TH

SA

25

62
60
65
% 90

AL P

1
1 4 .0

HUMI DITY RATIO - POUN DS MOISTURE PER PO UND DRY AIR

TU

15
40 35
35

DR Y BULB TEMPERATUR E - F

10

45 51

15

66

75

85

20

25

ENTHALPY - BT U PER PO UND OF DRY AIR

3-58 Assume room temperature humidity of 50% and layout the state & processes on required from point c to s.

Supply Air:

qsen = 120,000 x 0.5 = 60,000 Btu/hr = msc p (t s -tr )

ms =

60,000 = 53,192 lba/hr 0.24 (75-70.3)

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

0 200

300 0

45
85 WE T
.024

BU

LB

TE

50 0

80

MP E

55
RA TU RE - F

-0 .5 - 0.4 -0.3

-0 .2

-0 .1

40

.022

20

15 00

80
h W

1 000

.020

ENT HALPY HU MIDIT Y RAT IO

35

75

50
14 .5
.018

75

70
70
70

.016

50 %

.014

45

65

.012

LU VO

56
55 50
55

ME

80

%
60

.010

40

-C

U.F

% 70

T. R B. D RL PE

.008

ADP 45

2
50

60

13 .5

YA

% 50

.006

IR

45
40

4 0%

35

.004

30%

1 3. 0

20 %
1 2. 5

.002

10% RE LAT

Y IVE H UM IDIT

30

63

Q s =53,192 x 16.33/60 = 14,477 cfm or 6.8 m3 /s


Mixed Air:

mo = 53,192 x 0.333 = 17,703 lba/hr


Qo = 17,713 x 17.2/60 = 5,078 cfm or 2.4 m3 /s

mr = 53,192 17,713 = 35,479 lba/hr


Qr =35,479 x 16.5/60 = 9,757 cfm or 4.6 m3 /s
Reheat:

qrh = mc c p (t s -t c ) = 53,192 x 0.24 (70.3-55.2)

= 192,768 Btu/hr or 56.5 kW


Coil:

qc =mm (im -ic ) = 53,192 (34.4 - 24.2) = 542,558 Btu/hr or 159 kW


( 200,412 190,109 )100 = 5 .1 % 200,412

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

64

ASHRAE PSYCHROMETRIC CHART NO.4


NORMAL TEMPERATURE
R

55
85
R

60

BAROMETRIC PRESSURE: 24.896 INCHES OF MERCURY Copyright 1992

50
.028

AMERICAN S OCIETY OF HEATING , REFRIG ERATING AND AIR-CONDITIO NING ENGINEERS, INC.

1.0
0 .8
50 00

5000 FEET
0 .6
0 .5

60

1 8 .0

80
1 .0

2. 0

-2 000
-1 000

.026

45
80 WE T

SENSIBL E HEAT TOTAL HEAT


0. 4
0. 3

Qs Qt

0.6 0.5
0 200

-1

4 .0 8 .0 -8 -4.0.0 -2. 0
.0

0.2

0 .1

AI R

RY

AT

UR

PO

TE

Problem 3-58
TU -B LP Y A EN

ND

ER

PE R

RA

TI O

TU

SA

25
60

HUMIDITY RATIO - POUNDS MOISTURE PER PO UND DRY AIR

TH

15

35

DR Y BUL B T EMPERATUR E - F

10

55 (13)

15

75 (24)

20

90 (32)

25

ENTHALPY - BT U PER POUND OF DRY AIR

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in courses for which the textbook has been adopted. Any other reproduction or translation of this work beyond that permitted by Sections 107 or 108 of the 1976 United States Copyright Act without the permission of the copyright owner is unlawful.

12 0

100

105

110

115

60

75

80

85

90

35

40

45

50

55

65

70

95

300 0

BU

LB

50 0

40

75

TE MP

.024

ER

75

AT U

RE

55
- F
.022

-0 .5 -0 .4 - 0.3 -0 .2

-0 .1

15 00

17 .5

75
10 00

50 %
0

.020 h W

ENTHALPY HU MIDIT Y RATIO

35

70

50
.018

70

30

65

90 %
65

.016

17 .0
.014

60

45

.012

55

% 90
% 80

r
55

16 .5 V

20

.010

50

c
70

40

U OL ME -C

45

50

.008

% 60
16 .0

U .F T. P ER

40

45 40

50

R .D LB

.006

4 0%

35

IR YA

35

30 %

.004

1 5 .5

20%

I TY TIV E HUMID 10% RELA

70 (21)

.002

30

Exerpts from this wrk may be reproduced by instructors for distribution on a not-for-prort basis for testing or instructional purposes only t students enrolled in courses for which the textbok has been adopted. ny other reproduction or trnstin ofthis work beyond tht permitted by Sections ]07 or ]08 of the 1976 United Sttes Copyright ct withut the permissin of the copyright owner is unwful. Requests for permission or further informtion should be ddressed to the Permission Deprtment, John Wiley & Sons, nc, ] ] Rier Street' Hoboken, NJ 07030'

Chapter 4

4-1

(a) comfortable
(b) too warm

(c) comfortabe
(d) too dry

4-2

(a) comfortable
(b) too warm

(c) comfortable
(d) too dry

4-3

(a) Assume sedentary dry


using equation 4-4a,

bulb of 78 75

F,

clo

o.5, met. = 1 .8,

to,act =

5.4(1 + 0.5)(1.8

.2) = 71 F

Relative humidity should be less than 50%


(b) Should wear a S\/eater or light jacket and slacks.

(clo = 0.8)

4-4

Use fig 4-1

(a) Summer,

to =

76 F or 24 C; Winter,
\/ith

to =

72 F or 22 C

(b) Use equation 4-4a aS a guide,


met =

clo = 0.2,

3.0,

tdb

:76

o/

to =76

-5.4 (1+0.2)(3-1.2) = 64 F [winterorSummer]

4-5 4-6 4-7

From fig 4-3 temperature can rise about3.2 F.(j.g C)

t=68 +3.2=71.2 Fort=20+ 1.8= 21.8C


From fig 4-3 @200 fpm, temp rise 5.3 F (2.9 C) with t,,"-t _ 9 F (5 c), temp rise 6.5 F (3.6 c)
to = (t,

+t^r)|2, then using Eq.

4-1

T,fn

='6* C\l2

g _Tr) = (53s)4 +(O.103 x 109) (4o)12(78_74)

tmft:82For27'8C
to=(74+82)2 = 78F or25.6C

4-8

Compute the operative temperature,


,xn

to

= 4q4

(O.103 x 1o911eo11/'(o _76)= 83.5 F or 28.6 C

to = (84

+76)12= 79.8 F or 26.5 C


=

From Fig 4-1, to

79'8 F and 50 % R.. is out of the comfort

zone. Recommend lowering to to about 77 F or 25 C.


tu

x72 F

4-9

Use Eq. 4-4 to estimate a value of the operative temperature

to, active, assuming to for sedentary activities is 78 F (25.6 C)


with met = 2.0. to, active = 78

5.4 (1 + 0.5) (2

1.2) = 71.5 F, (22C)

Exerpts fiom this work may be reprdued by instrutors for distribution on a not-1br-proit basis for testing or instrutiona puoses only to students enrolled in urses for whih the textbook has been adopted' ny ther reproduction r trnstion of this wrk beynd ha permited by Secions 107 r ]08 ofthe 976 Unied Stqes CopriPh cwithou he oermission fthe cpyrigh wner is unlful.

s an approximation
Tmrt = 2To

_,

and

Tflx =

Tno

* ci121Tg

_ ,

Eq '

(4-1)

eliminating Tmrt between the 2 equations

2(o_T3)4

= Tno

*CV1/21n _Tr)

where all temperatures are absolute

Solve by trial and error with T, =72+ 460

532 R

and Te =(71.5+460)=531.5 R, C=0.103 x 1Oe, V=30

ta=85F(30C)
Cold surroundings require high ambient air temperature
for comfort, even with high activity level.

4-10

(a) Most occupants will be uncomfortable because the relative


humidity is more than 60%, even with

trx

t,

(b) The lightest weight possible. Short sleeves, shorts,


open neck, etc.

(c) Lower relative humidity

if possible by adjusting the cooling

system to remove more moisture. Coud also increase the


relative air motion to highest values, perhaps use fans.

4-11

(a) Even

if the suit

was heavy weight, many executives would be

Xcets from this work may be reprodued by instuctors for distribution on a not-for-pro1'it basis for testing or instructional purpses ony to students enrolld in ourses for which th tetbook has been adpted. ny other reproducion or trnstion f his rk beyond ht permitted by Secions ] 07 or 108 o{ the ] 97 6 United Sttes Copyrigh c ithout the permissin of the coyright oner is unfu.

cool if sedentary.

(b) Would definitely be cold, especialy hands and feet.

(c) Probably would be comfortable

in typical work cothes

(d) Probably would be comfortable since they would keep


their coats on and would be walking around.

(e) Cold to very cold

4-12

Determine relative temperatures difference between inside and outside.

68 - 45 23 = 7 4 _ 45 29 Costs
74 68

are79o/o of that for increased setting, or

- 45 29 - 45 23

Costs are increased by

26o/o if

thermostat is raised.

4-13

Too much air motion in the cold winter months tends to cause drafts and make people uncomfortabe. Air velocity just sufficient to prevent large
temperature gradients from floor to ceiling is best for winter. he opposite
is true for hot summer months. Higher air velocity tends to compensate for high temperature and humidity.

4-14

(a) Raising the chiled water temperature will cause the cooling coil to
operate with a higher surface temperature and the relative humidity in the space will tend to rise if the latent heat gain is signifcant such as would be the case with many occupants, this could lead to
u

ncomfortable cond itions.

(b) Yes, during the unoccupied hours the space load may be almost totaly
erpts from thrs work may be reproduced by instructors for distribution on a not-fr-profit basis for testing or instrutional puoses only to students enrolled in ourses for whih the textbok has been adopled' ny other reproducion or rnsion of this rk beynd h permied by Sections ] 07 or 108 f the 97 6 United Sttes Copyright c ithu he permissin f the cpyright oner is unlful.

Sensibe heat gain and the load is much less than the design value. ln this case the chiled water temperature may be increased.

4-15

hese fans may bring air down in the Summer, increasing the
velocity of air in the occupied zone and providing improved comfort.
ln the winter, air may be drawn upward, pushing the warm air at the

ceiling downward where it can increase the temperature in the

occupied zone without increasing significantly the air motion below


the fan.

4'16

(a) able 4-2 gives a minimum required amount of ventilation air


of 15 ft3 /min per occupant. this is the minimum amount of
outdoor air that should be used under any circumstances.

Therefore, (Qo)rin = 15(30)

450

ft3/min

(b) on the basis of floor area, the occupancy woud be 25 and the
minimum ventilation requirement would be

Q,

15 (25) = 375 ft3 /min. lt would be better to design for

floor area if lowest air flow is desired. With 30 actua student air flow is such a case woud be insufficient.

4-17

Use Eq. 4-5, Solving for C, Cs


=

(QtC"

N)/Qt

C"

(N/at)

= (2001196 + (O.25l9o)

478 x 1o-6 = 478 ppm

XctS from this work may be reprduced by instrutors for distribution on a not_tbr-profit basis for tosting or instrutional purposes only to students enoled in courses for which the textbook has been adopted. ny her reprduction or rnsin of his ork beyond ha permied by Secions ] 07 or 1 08 of he 97 6 Unied Stes Copyrigh c w ithul the permission of the cpyrigh oner is unlful.

or using Sl Units

c,
=

(2oo / 106)+ (0. 118 t 0.472x 9OO)

(2OO /

106) + (278 t 106):478 ppm

4-18

n = number of people to occupy a room

N=n(5.Oml/s)
Solving Eq. 4-5 for
N = Qt (C,
n

- C") = n (5.0) ml/s-Person


/ (5.0)

: Qt (C, - C")

2.8 (1000-280) / 5.

n = 403 persons or 0.0069 m3 /s

- person

For English Units:


n=

6000 (1oOO - 28Ox 10-6) / O.O107 or 14.8 cfm/person

= 404 persons

4-19

Use the M-100 media of fig. 4-8. From table 4-3, select a

12x24 x 8

unit; 650 cfm, P = 0.4 in. wg

At P = 0.25 in. wg. each unit will handle Q


=

Ql |o'25 o.40]1l2

650 [O.25 t o'4oJ1l2


of units
permied

:514 cfm/unit. Then the number

Studnts enroed in ourses for which the tetbook has been adopted. ny oher reproduction or rnston f his ork beyond ht by Secions 1 07 r 1 08 of he 976 Unied Sttes Copyrigh c lithu he permission f the copyright oner is unful.

Ecerpts fiom this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructinal puoses only to

;g =(2000

514) = 3.89 or

4. This

is a satisfactory number.

4-20

Use the M-100 media from Tabe 4-3 select a O.3 x O.6 x-O.2 unit. This is rated at 0.3 m'/s with 1oo pa pressure drop.

t P

60 pa the alowabte flow rate for each unit would be Q = (0.3) (60/1 OOf tz = 0.23 m3/s
=

require 1'Oolo'23 = 4'34 units. This requires at east 5 filter units, but since this is an odd number, recommend
1.OO m3/s woud

using six units. Trying the 0.6 x 0.6 x 0.2 filter the allowable flow per unit would be

0.48 This would require more than two units of this size. conomies would determine the best choice.

= (0.62) (60/1}q1t2 =

4-21

Solving q' 4-1O for Q


Q
=

Qr [P / P,]1'2

= 9OO

[o'1 l0'15]1|2 =735 cfm/module

N = ss00/235 =
Ve = Q/ =

T.4g [must be integer] Use g modules


'|-

= 344fpm (2)(8)

5.7 fps

4-22

Solving q' 4-1O for Q


Q = Qr [P

P,J1l2 = (o'42) |24

l 37

'4]1t2 =

0.336

m=(2.8)/0.336=8.3
Use 9 modules, a 3 x 3 arrangement.

Excets from this work may be eprodued by instructors for'distribution on a not_1br-proit basis for testing or instructiona purposes only t students enrolled in courses for which the textbook has been adopted. ny other ,rpr:orl'u"on or trnsion of this work beyond th permilec by Sectins 1 07 or 108 f the ] 976 t]nied SteS Copyr?ht c w-ithut thi permis'" oj n, copyrigh wner i unlful.

/3

VelocitY

FAc AREA

(2.8)m3

/s

(0.3)(0.6)(e)m2

=1.73m1s

4-23
P
=

M-200; 0.6x0.6 xO.2;

O.4Om3

/s/module

Use Eq. 4-10

ta / Q.]' :1OO
=

lO,4OtO.42l2 =90.7 Pa

Velocity

0.4 =2.22m1s (0,3)(o 6)

4-24

No solution exists due to the fixed air quantity for the unit. This part of the problem is intended to show the student that typical direct expansion equipment cannot be used in this \May. lt also shows that the load due to outdoor air is very large.

4-25

exhaust

sHF= 0.7

ho

o'25 rh"; Locate point 1 on psychrometric Chart at82'4 F db and

66.8 F wb
it = 31.4 Btu / lbm and v1 = 13.9 ft3 /lbm
fbr tSting o instructional puosS only to Exerpts from this wrk nay be reproduced by instructors fo distribution on a nt-for-proftt basis or rnstion f his wrk beynd h permited students errrolled in courses fbr whih the textbook has been adopted. ny other reprodicrion is unlful' by Sectins 107 r ]08 ofthe t976 Llnited Sttes Copyrilht ctv,ithut he pemissin ofhe copyright oner

74

Q1, =

rhi (ii - is) = at

/V

(60)

(i1

is)
(i1

35 12,ooo Qls
is = 31

= (350 l 12'000) (6 / v1)

_i.)

.-

''''J8?r;

''

23'46 Btu / lbm

Locate on psychrometric chart' ts = 65'6 F db' 55'5 F wb


Q.r =

lil,

(ir.

- is) = 36'000;

ir =27

'6 Btu / lbm


lb / hr

tr, O,

= il1

(27 .6

^ - 23.46)
=

:8695'7

rh, (vr,

(13.4)

1940 cfm

Qt" = 8695.7 (31.4 -

23.46) = 69,000 Btu / hr = 5.75 tons

Qr

5.75 (350) = 2014 cfm


of fig 4-8.

() Design filters for 2014 cfm, use M-200 media

Try the 24x24x8 units of table 4-3. 920 cfm @0.4 in. wg.

For max. P of 0'125 in.wat.


Q = 920 [0. 125 tO.4O]
1t2

=514 cfm / module;

n = 2014 I 514 = 3'92, use 4 modules

4-26

Use the M-15 media,

93 % from fig' 4-3'

From table 4-2,60 cfm / person is required, outdoor air.


purpses only to on a not-for-profit basis for testing or instrutional Excerpts tiom this work nay be reproduced by instructors fr distribution or trnslionf ths work beyond th permied ny oher reprduction students enrolled in ourses for which tl-e textbook -,u, ..n uopt"J ' c \,'ithout thi permission ofhe copyright oner is unlwfu' by Sectins ] 07 r 108 o7 he-|97|6 tJnited Sttes Copyrigh

75

-A fresh air balance on the filter gives QrEt


+

Qo

Qs

where Q,. is recirculated air, Qs is outdoor air and

Q. is supply

air.
=

8, = (60 - 20) 10.93 = 43.0; Q,

43.0 +20

63.0 cfm / person

or the total amount of air supplied is

63.0 x 55 = 3465 cfm; Try the 12x24x8 unit of table 4-3

Q/unit=9oO[O'1 /O.35]12=481 cfm; n =4755 l481


= 7 .2

modules

Use 8 modules [Note: The M-24 media could also be used]

4-27

Q, = (25 - 15) / 0.S = 12.5 cfm / person

= 15 +

12.5 =

27 .5 cfm / person

4-28

Filter location is B, figure 4-9

Use Eq. 4-12, solve for RQ.. since


RQ = { -QoEv[C,

_(1_Et)Co] + N}/ (EvEfcS)

RQr={-2OOxO.85[180-(1-0.8)0.0]+(10x150x35'32)]l
(0.85 x 0.8 x '180) where Co
=

0.0

RQr

185 ft3 / min or cfm

for-testing or instrutional puoses only t Exerpts from this work may be reproduced by instructors for distribution on a not-ibr-profit basis h permitted the textbook has been adopted. ny other reprodiction or rnslin of this ork beyond students enroed in ourses fr which c iithout the permissin of he copyrigh oner is unl.ful' by Sectins 07 or 1 08 f the 976 tJnited Stes Copyrght

76

Qo

= 2OO

cfm, Qs

(1S5 + 2OO) = 385 cfm

4-2g

Solve q' 4-11 for RQ,


RQr
=

(_Qo)(Eu)(cr)+ N / rEiC,

RQr = [ (-20) (0.65) (220) + (125) (35.32 ft3/m3)] (0.65X0.7)(220)

RQ.

-9-*_!1!5^, ' =(0.65)(0.7)(220)

= 15.53 cfm/person

4-3o

For filter location A, use q. 4-1 1, solving for RQ,

RQr

(-QoEvCs

N) / (EvEfCs)

RQr = t (-2OO (0.85) 180) + (10 x 120 x 35.32 ft3/m3


(0.85 x 0.8 x '180
)

)l

RQr

183 cfm, Qo

= 2OO

cfm;

d,

383 cfm

4-31

(a) This type of space will require a high ventilation (supply air)

rate to handle the load, air cleanliness is not the main criterion.

Therefore, a low efficiency filter with low pressure drop is acceptable. From table 4-2, assume occupancy will be about 30 persons / l
OOO

ft2. So the total design occupancy is 90

persons. he design will be based on this occupancy although


the cooling requirements may dictate a larger supply air rate.
Excets from this work may be reproduced by instrutors
1br distribution n a not-fr-prfit basls for testing r instructinal purposes only to ht permitted students enroled in courses or which the textbok has been adopted. ny ther reprducion or trnstion of his ork beyond by Secins 1 07 or ] 08 of the 97 6 [Jnied Sttes Cpyright c thout the permissin f he copyright oner is unlful.

77

A ''fresh air'' balance on the filter


d," = (20

gives

(Q" _ Qo) / Ef

-15) / 0.5 = 10 cfm / person recirculation rate

4-31 (continued)

, :

1O +

5 =25 cfm / person supply rate

Q = 25 x 90 = 2250 cfm total supply rate


Net face area,
(b)

= 2250

/ 35o

= 6'43 ft2

A higher efficiency would reduce the total amount of air and

reduce the required face area. However this is not desirable in this case. First the filter system would have to be enlarged to handle the greater amount of air. A lower filter efficiency could be used and still maintain the required air quality. For example, suppose the load dictates 4000 cfm instead of 2250 cfm, then for 90 PeoPle

4ooo / 90 = 44'4 cfm / person

Using a minimum of 15 cfm / person of outdoor air.


Qr. = 44.4

15 = 29 '4 cfm / Person

8.
Et

29.4: (20 - 1s) / Er = 5 29'4 : 0'17 or 17o required


=

4-32

(a)

l5x

Q=

(Q, / v) 60

(i|.

-ir)

225 people

75F

xerpts frm this work may be reprodued by instructors for distribution on a not-for-profit b studes enrolled in courses for which the textbook has been adopted. ny oher reprduction by Sections ] 07 or ] 08 of he 1976 Unied SteS Copyrigh c )ithou he permission fhe cop;

RH=5%

125,0

78

x13 ft3

/ ba
[

. = (125,oOo x13)

60 x (28 - 1e.4

)]

Qs
(b)

3,149 cfm

, ,

= o
=

= 15 x225

3,375 cfm

-D
(c)

50 52
Supply air condition

Q. must be 3,375

cfm, find

ne\/

125,000 = (3,375 I 13) 60 (28 - i.)

i'

= 28

(125,000 x 13 ) / ( 3,375x 60)

20 Btu i lba

Locate new condition on chart aS Sho\/n' Coil must cool oDA


down to this new condition.

Excets frm this work may be reprodued by instrutors or distribution on a not-tbr-profit basis for testing r instructional purposes only to students enroed in courses for which the textbook has been adopted. ny her reproduction or rnsation of his work beyond th permitted by Sections 107 r ]08 ofhe )976 Unied SeS Cpyright ct withut the permissin fhe cpyright o]ner unl:wful.

Exets from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional purposes only to students enrlled in courses for which the textbook has been adopted. ny other reproduction or trnsltin of this work beyond tht permitted by Sections 07 or ]0B of the 976 United Sttes Copyright ct without the permission of the copyright owner is unlwful. Requests for permission or further informtion should be ddressed to the Permission Deprtment' John Wiley & Sns, nc, ] ] ] Rier Street, Hoboken, NJ 07030.

Chapter 5

5-'1
5-2

(a) (b)

k = Cx =0.2

4 =O.8 (Btu

in) / ( hr - ft2

F)

k = 1 .14 x 0.1 = 0.114 W / (m-C)

(a)

x=o.3o / 5.5 = o.o55 Btu / 1ft2-nr_ (b) C = O.O43 / . 14 = .307 W/ (m2 _ C)

C=k

11

5-3

(a)

R = 1lC= 1/0.055 = 18.3 (ft'R' = R l A= 1 l CA= 18.3/ 10

hr- F)/
=

Btu

0.183 (

hr-F)/Btu

(b) R ='1 I .307 = 3.26(m'-C)/W R'=3.26l9.3=0.35C/W


5-4 R=

Ri , Rgyp =1C=1l3'1=o'32 Rbtd = !0.33 = 3.03; Rair = 0.68


+

R-0.68

R=0.68 R=0.32

R = 0.68

0.32+ 3.03

0.32+ 0.68

R = 5.03 (hr- ft2- F) / Btu

5-5

+ R'= 2k| 2koL


AssumeL=1ft

tnb 2

n2

k:0'2

Btu - in' t(ft2

_hr_F);

kp =314 Btu-in

te _hr_F)

81

lnside Surface (7 m/s

0120

overalI hermal Resis.

0.652 m2clW

5-10

Between Frame Outside Surface 4 in. Face Brick Sheathing


lnsulation
0.17 0.65 1.32
1

t Framinq
0.17 0.65 1.32

1.0

2x4 stud

4.27 0.32 .68


14.14 0.32 0.68
7.41

Gypsum board
lnside surface
otal

UA:U1; +U11, U = UiAi


r

/ + U11/A

14'5

16 16^nd A =lan

A'

=L R
/ (r',..-tt'

, = "14.14) " +1= 0 o77Btu 110 " : -)- 116 7.41J


5-11

-r)
A

An ordinary walt with


highIy reflective wall,

= =

O.9 has a unit resistance of 0.68.

O.05, has a unit resistance of 1'70.

Assume radiation heat transfer is zero for reflective wall. hen


the resistance due to convection alone is approximately

Rc=1.7; hc=1/Rc=0.59; h.*r:1/0'68 = 1'47


Frac. Conv. = ha lh. *,
=

0.59 I 1'47 = 0'4

xerpts from this work may be reprodued "'.;.;;;1l;l,,.o,rr.r'r-

by instructors fr distribution on a not-for-profit basis for testing or instructional purposes only t the texibook has been adopted' ny ther reprcluclin *nh

o^:.:::Ei::::":!,::i:,i'''y''o"!:*!

-,

82

5-12

RzQ x 4\ Rr (2 x 6) wind. 0'17 0'17 1. Outside surface, 15 mPh 0'79 0'79 2. Siding 1'32 1'32 3. Sheathing 11'0 19'0 4. lnsulation, 4'27 2x4 6.7 2x6 0'32 0'32 5. GYPsum wall board 0'68 0.68 6. lnside surface 18'55 28.98 Total
ssume 15 mph
Ut
=

0.035 Btu / (hr - ft2 - F)

2 __O.o54 Btu / 1lr - ft2 - F1


% DiffereC = [o'O5-4r_0-035) '' )'

5-13

0.0s

ool = 35'2

Air space will be near the indoor temperature with small


t across the air Space.

Use t."rn
R
=

50 F and t

10 F and read [Tabte

1.oz(rrr

-f( -r) I Atu


=

S-3a]

or 0.18

m2clW

5-14 5-15

Assume tr"rn
R
=

50

F;

t = 10 F

3.55 (hr - ft2 _F) /

Btu

or 0.62

(.2

_c/W)

[abte 5-3a]

qc/ = U"t
Find U for highly reflective surfaces because radiation will be minimal. This will give a good approximation for the convection
component. From Table 5-2a,l1orz', heat flow down

83

Uc=1/R = 1l(2x4.55) =
q./
or
U^ _

0'11

" --l' (2x0

= o.625; q.

0.625(63 - 43) = 12'5 W/m2

Q/A..

='n l( 'L1oO]

, _ '4 |l

_[ l' l _1o]

/ a '.4l 'l

l'

for 1= t2=O'9, (q/A),.


= O.1

E : 0.82,

-]'

'
o

713 x9.s2 t635

_s.ol

Radiation heat transfer is about 10 times greater'

5-16

U*

= O.O7 Btu / (hr - tt2

11

Ud = O.4O Btu / (hr - ft2

- F) - F)
20'
g'

Uwin = O'81 Btu / (hr - ft2

Ad

17 '78 ft2; Awin =25'0 ft2;

*
U
I I_

= 117 '2

f(
+

Parallel heat flow Paths


=

U*A*

U66

U*;n*in

(o.O7 x117'2) + (O.4 x 17.78) + (0'81 x25'0) 117.2

O.3O Btu /(hr -

f( _F)

or about

'72\ t(m' _

c)

5-17

q/

= U(ti _to)

a not-for-profit basis fo testing or instructiona] purposes ony to Exerpts from this work may be reproduced by instrutors for distribution on penitted uJo|t.. ny her reprucion or rnstion of his work beyond h students enrolled in courses tbr wbich the texibook has been : : -'-.41-^ ^^^'',.:/a! ^''''av;" "'-6!$

84

From Table 5-4b, construction 2, R = 8.90 (hr

ft2

F) / Btu

Assume insulation does not

fitl the

airspace'

Remove R for metal bath and plaster of 0.47 (f''. - tt' - f)/Btu and ) \"' add R for acoustical tile and insulation' Ceiling, R" = 1 / 0'8; insulation'
R1e61=20.68; U = 1/R =
R='1

1'00;

0'048 Btu / (hr - ft2

-Fi

q/ = o'o48 (72 - 5) =

3'22 B / (hr _ ft2)


1

5-18

From Table 5-4a, Construction

Uw=

9!+=oe71wr(m2-c) \ 0.1761
Wl(m2

Ud = 2.27
Uwin =

-a)'

Table 5-8 Table 5-5b

4'62w1(m2 -

")'
+

w U

= =

35 m2;win =8m2;d = 2m2

U*A*

U6
+

35

Uwinwin
+

1x35) u _ Q.e7

(2.27x2)

(4'62x8)

-_

2.16 w

(m2

- c)

5-19
U = O.14 Btu / (hr
_

ft2 _ F1able5 _ 4a, Construction No. 2

R=1O.14 = 7'14, Rn =7'14_(1 to'44) + (1/0.55) =6.69


Un = 0.15 Btu/(h r

ft2

- F) or about .85 W

1m2-c1

5-20

ssume ardwood, k = 1.25 (Btu-in) / (hr - ft2 - F) Winter Summer


R =

0.68

Ri = 0.68

not-for_profit basis for testing or nstructiona purposes only to Excts from thts work may be reprodued by instrutors for distribution on a reprouction or rfistion of his ork beyond th permied students enolled in courses for which the tetbok has been adopted. ny ther

85
R =
'1

0.25 R, = 2.03
Ro =

'375

1.25 -F)
ft2

R = 1 '375

1'25

Ro = 0.17

R* = '1.95

U, =0.49 Btu / (hr-ft2

U* =0.51 Btu /(hr-ft2-F)

Both values are greater than the value given in

able 5-8 of O.39 Btu / (hr _

F), but acceptable.

5-21

Computed: Ri
Ri

= 0.68, Rs = 0.03 (estimate); Ro = 0.25

+RgaRo=0.96=R

U = 1.04 Btu / (hr - tt2


Utub

-r);

or 5.92 wl(m2

-c)

computed

1.O4 Btu / (hr - t2


\

_r);

Table 5-5a

or 5.91

l(m2

_c);
/'

Table 5_5b; Same result

5-22 (a)

From Table

5-5

U=1.08 Btu / 1nr - ft2 - F) 10 F

(b) ssume tr"rn : 50 F; t =


Ras = 1.ol (nr
Rn

-f( -r)
1

r atu

=U-R',= ++ ' ., 1.og


=

.O1

= 1'94, Un = O.52 Btu/1lr-ft2-F)

5-23 (a)

Uw
l l,.Jfl

o.o89 Btu /(hr - tt2 _

11

or O.51 W/(m2 _ c)ale 5-9


Jlv'l\J vYl1l or O'16 W/

_ .o29 Btu / (hr - ft2 -L lJur\ll -'L)

_F) _| l

(-'_c) -)

ante 5-1o

(b) Q=U(ti _tg); tr= t"ur-A

xerpts from this work may be reprodued by instrutors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in ourses for which the textbook has been adopted. ny ther reproducion or trnsltion f his ork beyond tht permited
..-_''r-] ^_':'_^'!

^'.'. ^'.4'

86
tavg

A
5-23 (continued)

:22

=35'8

(2'44

(12

C)

C) Table 5-11}Chicao.lllinois
Figure 5-7

tg__35'8-22 = 13.8;
q*
=

t:72re2c)

0.89 (4 x 20 x7) (72 - 1 3'8) = 2,900 Btu / hr or 0.85 kW

qn = 0.029 (20

x20) (72 - 13.8) = 675 Btu /hr or 0.2 kW

5-24

R"

R1,

Un =

0.029 Table

5-10

Rrin =

1l 0.48 Table 5-1a (Fibrous Pad)


2.08
=

Re

#"+

36.6

U" 5-25

0.027 Btu / (hr - ft2 - F) or 0.16 Wl(m'z - C)


(1 t \

(a) R*=: +11+ "0089


Rf

g.1) =

22.6

U* = 0.044 Btu/(hr-ftu-F) or 0.25 w1m2-c)


=

-: + (1 tO.4s): 0029
\

36.6

Un = 0.027 Btu/(hr - tt2

-f)

or 0.155

Wl(m'z-c)
Btu / hr or 0'42k\^

(b) Refer to problem solution 5-23 Q* = 0.044 (4 x20 x7) (72 - 13.8) = 1434
Qn =

0 027 (20 x20) (72 - 13.8) = 629 Btu / hr or 0.18 kW

5-26

Rins =

4'1z

(rrr

_f( _r)l

tu

O.24Btu/(hr

-'f(

-F) or 1.36 Wl(m'z - c)

Excerpts fom this work may be reproduced by instrutors for distribution on a not-for-prfit basis for testing r instructional purposes only to bSecti.s1[]7ny nn{t]o 1076'b;l.)l-l-"/-^4'-')-"}

studentsenrolledincoursesforwhichthetextbokhasbeenadopted. 'l-''':'''

nyherreproductionrrnstionofhisrkbeyondhpermied
:"'''.^'''

/ .*'

87

Then from Fig. 5-8, U'


Q=

0.85 Btu/(hr

-f(
=

-F) or 1.47 W(m-C)

U'P

(ti

- to) = 0.85 x 300172 -101

15,8'10 Btu/hr or 4.63 kW

5-27

t =

72 F (22 C) Assumed
= R5 +

R"

R1, Ub

o.52 Btu / 1nr -tt2 _

11 Table

5-9

Rfi,.,,

=R1

+Ru6*Rqyp=(5.0) + 0.0 +(1 12.22) = 7.22

R^- 1 +7.22=26.5 - 0.052


U"
=

o.o38 Btu / (hr -ft2 _F) or o'22l(m'z_c)


from Table 5-9
O.7 + (1

5-28

Ub

: 1.14
=

Rn

++ 1.14

12'6)= 1.66 (m2-c)//, Un = 0.60 W(m2-

c)

or

Un = O'1OO Btu / 1nr -ft2

-F)

This does not account for the walls above grade.

5-29

U = 0'16 able 5-'10 (no finish)

Rn:++(t69)+ ' 0.16 \


Un

(1 t4.6) =6.611m2-c1
-ft2

lw

= 0.15 W/(m2-C) or 0.027 Btu / (hr


Un(ti

- r)

5-30

q/A=
tl

-ts)=

(ti

-tt)/Rt=(tt-t)lR2
(112.6)+ 0.7 +0.12=
0.90

Rl=Rgyp+R1nr+R1, R1 =
= ti _UnR1(ti

_tg) =20 - [1.05 x 0.9 (2 - 10)]

Ecerpts frm this work may be reproduced by instructors for distribution on a not-for_pofit basis fr testing or instrutional purposes only to students enolled in courses for which the textbook has been adopted . ny ther reproduction or trnsltion of his rk beynd ht permied '.''-:-' ^'"-^-:' "'-5{i ' hi 9"};.-" a ^'' ]9 ^.}L- oaA L-;.^) c'-''^'

. . .

88

t1= 14.6 C or 58F


R2
=

Rrr, +Ri

I 12.6) +0'12='20

tz = 20_ [O.60 x O'2 (2o-1)] = 18.8

or 65.8 F

5-31

q/A=Un

(ti

_tg)=(t _t'')/R1; Rl=Ri +Rc

= 0.12 + (1 I 4.6) -- 0.34 t=20_ (O.15) (O.34) (20-10) = 19.5 c or 67 F

5-32

= 0.2 Btui(hr-ft2-F);

Figure 5-8

8=

U'P
=

(t1

_to);

Ui, = 0.81 Btu/ (hr-ft-F) or 1.a

W(m-C)

U'ni

1.37 Btu / (hr - ft -F)


Btu / (hr - ft) or 50.7 W/m Btu / (hr - ft) or 85.6 W/m

(a) q/P = 0.81 (70 - 5) = 52'7 (b) q/P = 1.37 (70 - 5) = 89'1

5-33

Q=

t / R'

Eq. 5-25; L>>'

L=

100ft

R'=

2kL

_'nL-o--@J _3"10012)
R'
= 8.

. zoo x121^ tn(12x1OO/2x3o)l

12

1O-3 thr - F) / Btu

Which neglects the resistance

of pipe wall.

purposes only to for distribution on a not_for-profit basis for testing or instrutional Excerpts from this work may be reprodued by instructors ht permited ork "., uJo|i"a. ny oher reprucin r rnslioi f this '1-"4' beyond hu, '' : Students enollod in courses fbr h'ih the textbook "' ^'
L- Q.nl;n-" n ^.' '

6- 70-42 - =3,4488tu ' 8.12 x 1O-'

/ hr;

q/L

= 34.488tu/(hr-ft)

orq=1.01 kW; 9=33 1W/m L


5-34

Q=t /R'

R'g

2 (1.4) 100

=4.98x10-3 C/W

film and the tube wall' Neglect resistance of the inside


O=

'

----------c =11.04kw 4.98 x 10--

60-5

5-35

Moisturewillmovetowardtheinside.Locatethevapor

insulation' retardent on the outer side of the retardent is placed on the The insulation will beome wet if the plywood would probably \/arp inside or left out entirely and the

and rot.

5-36 (a) Q/A = Uo(ti


Ro = O'68
Uo
=
+

_to)=(t _t1)/R1 =(ti


1+

_t)lR2

O'45 +1

1'O +O'8 + O'17 = 14'1

_F1 O'o71 Btu /( rr - ft2


0'68
O'68
+ +

Rr
R2

=
=

O'45 = 1'13( hr O'45 +11

f(

-F) / Btu
- ft2

-12'13(hr

-F)

/ Btu

tt=t_R1Uo(t_to)=7O_(1.13xO'O71)(7O-1O)=65.2F
purposes only to basis for esting or instructiona' for distribution n a no-for-prol yt.pern:ted lnay be reproduced by insructors Excerps rom his \rk j:*tbook has *9,i'"l'Ji."o"'i,-:';;;;;;;;;;;"ii"111i117; ,:y::'::'|"*o students enrolled in courses fo ^: lh.

90

tz=70-(12'13 x 0.071) (70-10) = 18'3 F

(b) At 70 F, 3O%o R.. and possible leakage


or 2-

of air to surfaces

tdp=37F<65F-ocondensationexpected
(c)Since|z=lS.3Fismuchlessthanthedewpoint,condensation
would ocur'
1' Place vapor retardent at the location of interface

5-37

Assume infiltration is negligible ufAf (ti - t") = UwA*(t. - to)+ U'P(t. - to)

rilcp(tc - to)
to =

* _ UrAtt, c _

+(U** +U'P+rhcp)to',ti=72F; (UtAt + U** + U'P + rhc, )


Rwoo =

1o F

ssume 1.5 in. of wood floor, Pine;


U,

'1'5l0'8 =1'88

=1; 'Rf

Rt =O'92+1'88+O'92 =3'72;Ut=0'27

Ur= 0'27 x 30 x 60 = 484 Btu/(hr-F)

rr -a'R* "*_Rw

=0.68+(6/15)+ O'17 =1'25',U*

O'80

U*A* = O.8O x 2(30 + 60)2 -- 288 Btu/(hr-F)

U'P=1.8x(30+60)2=324
,h.p
=

20 x 0.075 x 60 x o '24
+ (288 + 324 +

= 21

'6 Btu/(hr-F)
=

+ -484 x72 c_-

21'6)10

484+288+324+21'6

36.85 F

5-38

(a) Q/A = U(ti -to) = (tr-to)/R1;

(construction 2) + Uz=0.112', Rr=O.17 + 0.33 + 4'17 2'22 = 6'89

only to basis fo 1e^sting or lnstructional purposes ' by instructors for distribution on a not-for-pofrt Excrpts from this work may be rproduced of his ork beyond ht permited t.d. ,-ny otlr", ,rproEu.in r rnslio -'", "* students enolled in courses fr whih the textbo"t "J"p

91
t1 =

(6.89 x 0.112) (72-0) = 55.6 F

(b) U :
Rr

0.211 (construction 1) +2'22


=

= 0.17 + 0.33

2'72

ti =to+R1U(ti

-to)=O + (2.72x0.211)(72-0) = 41.3F

(c)

lf room air leaks into the air space for the case of no roof deck

insulation (b) there could be some condensation since would be exPected.

t6p =

50

F at72 F and 45% R. With the insulation, no condensation

5-39

(ti

-to) / Rr

= (ti

-ti)

/ R1

R, = 4'5 or O.79 1m2-cyw ; able 5-4a (Const. No.1)


R
=

0.68

O.45 + O.94 =2.O7 1nr-tt2_F1/Btu or 0.365 1m2-cru

Between Furring and block

tl

= ti _

ft,'

_ to) = 22_

ffir'+17)

= 3.98 C or 39

tdp = 9.5

C, Assuming room air can diffuse into the air space,

condensation likely will form on the concrete block surface.


Therefore, place vapor retardant on inside surface of gypsum

board. Use foil backed retardent. Retardent must not touch


concrete blocks!

purposS ony Exerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instrutional ,.,-r.':'!!i|',?! .o,,'",'to. *ni:| j:;bo has been adopted.

;;#;;;;ln

lh

o'l

to

"!!1:

":::::i:::::":!,*r::!''n! 'y,'o**o

92

5-40

U1A1(ti-tn) + Ua+(ti-tn) = 2U33(tn-to) + lJzAzftn-to)


,^

_ (UlAl + Uzz )ti + 2Uggto + Uzzto '' 2sg + UzAz * Ull * UqA

UrAr

0.09 x 8 x 20 = 14.4', 0.09 x 8.54 x20 = 15.4',

U33

0.09x3x8

= 1.08

UzAz

UA=0.09x3x20=5'4

r _(4.4+15.4)70+(2 x 0.8 x o) + (15.a x o) -S5.8F L6= " (2 x 1.08) + 15.4 + 14.4 + 5.4
Place water pipes in this space with some caution.
5-41
Uf

f (ti-tb ) = (U** + Utt

)(t -tg ) ; ti =

72 F

tg = turg

- - 37.6 _23
;

= 14'6 F or B C
+

Ut =

Carpet and Fibrous pad assumed, Ur = 0.172 Btu/ (hr U*

&

Rf

(2 x 0.92) + (1 5/0.8)

2.1 = 5.82
ft2 - F)

=.164 Table

5_

9;

Uot =

0.029 able

_ 1o

tb=

ltrti

+(

U**

+ Ubf f )tg

U11

+ U** *Urr
+ (.1G4 x 80 x 7 + 0.029 x 4OO)1a.6

r, _(0.172x400 x72) l'bto = 30.3 F or -0.95 C

Exerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instrutional purposes only to students enrolled in courses fr whih the textbook has ben adopted. ny oher reproucion or rnslii qf his ork beyond h nermied by Seins 07 r ! 08 n! n." t o7A t r;lDs <}-t-^ .^^',-]-Ll t 1: ^^...'- -

basis fr by instructr9 jor distribution on a not-for-prrt Excerpts frm this work may be reprodued textbook has been enrlled in ourses for whih the testing or instructinal purposes on1y to studes ]07 or of this work beyond tht permitted by Sections adopted. ny other reproduction or trns,ltion is unlwfu' ct withut the permission of the copyright owner 0B f the ]976 Unitei Sttes Copyright John should be'ddressed ti the Peimission Deprtment' Requests fr permissioln or furthir"infrmtion iiria son, nr, ] 1 ] Rier Street, Hoboken' NJ 07030'

CHAPTER

6-1

PSYC may be used to find the Refer to Table B-1 . The computer program R' humidity ratio from t66 and assumed 100%
Wind Direction, deg. CCW from N
(a) Pendleton,

OR L

11

6 13 4 12

140

0.0 0.0 0.0

(b) Milwaukee, Wl
(c) Anchorage,

-2 -9

290
10

(d) Norfolk,

VA

24
18

340 360 20

0.003
.0

(e) lbuquerque, NM
(f)

I
7

Charleston, SC

28

0.003

6-2 possible condensation on inside Design relative humidity is determined by (which is the maximum dewof glass. Find glass surface temperature poi;t temperature of the inside air allowed)' q/A = U(t' - to) = Cr(tr - b) t= 72"F; t., = glass Surface temperature U = 0.65 Btu/(hr-ft2-F)' Table 5-5a

c1 uhi
C = 1'172

111

, hi = 1.46 Btu/inr-ft2-f) Btl (rrr-ft2-F1

94

tr=

Uti + to (Cr

cl

- U)

City
(a) Caribou, ME (b) Birmingham, (c) Cleveland, (d) Denver,

lndoor
T, oF

Outdoor
, oF

tr=
top,

Design or

oF

RH-%
26.2
46.1

Max.

72

-10

35.5
50.2

72 72 72

23
b
3

o
C

42.6
41.3 57.3

34.6
32.9
59.9*

CO

(e) San Francisco, (g) Boise, lD

72 72 72

39
-'16

32.8 44.0

23.6 36.5

Rapid City
*

RH = 60 o/o would probably be uncomfortable R = 40 to 50% would be more realistic

6-3

Assume that the weather strip does not change the convetive heat loss. From Figure 6-2, Cp = 0.3. Using Eq. (6-7b) with the air density of 0 'F, the pressure difference due to wind is

:
P. =

[o

.086!\'( ls*ot * |.467 fi

z.(y.rrbm_ ft)

ft')\

l'\

mph) (o.rnr.o

lbf_s')

t"'tt ) lbf l ft')

P* =

0'037in'wg
^y

ssuming slight stack effect, P


Using Table 6-1 and Fig. 6-1,

0.04 in. water

puoses only to Excets from this work may be reprduced by instrutors for distibution n a not-for-profit basis or testing or instructional

nytherreproducionorrnslionofhisrkbeyondthtPermied studentsnrolledincursestbrwhichthetextbookhasbeenadopted. by Sections 07 or 08 ofthe ]976 United Sttes Copyright ctthout the permssin ofhe copyrigh oner is unlaful-

95

Loose fit with non-\/eather-stripped, K - 6; a lL = O.75 cfm/ft Loose fit with weather-stripped, K= 2; Q/L = O'24 cfmtft
Total length of crack, = [(3 x 3) + (2 x 5)] x 9 = 171 ft Using Ll2for calculation, then Q,, = 0.75 x 17112= 64.1 cfm, Q, = 0'24x17112= 2O'5 cfm

I
Now Q, =
rh cr(t1

to)

cp(t;

tr)

Q,r-8,,

Q,,

-At-4, Qt

64.t-20.5
64.r
= 0.68

or a reduction of 68% in sensible heat loss.

Also, (Kl
6-4

- K)l1=

-2)16 = 0.67 or 670/o Reduction.

From Fig. 6-2, Cp = 0'52tor windward wind' Assuming standard sea level air density, the pressure difference due to the wind speed of 13 m/s is

P., =

z.( .okg

t i/-s'

ry] s) _*

_ 53.6P

(a) From Table 6-2, K = 1 for tight-fitting. Then, from Fig. 6-1, Q/L = 0.60 L/m-s Q = 0.60 x (0.9 + 2'0) x2 = 3l8_L

ssuming that the wind speed and wind direction are the Same as the given conditions for the bank at Rapid City, SD, the heating load (at -20'6
basis for testing or instructional puoses only to Ecerpts from this work may be reprodued by instructors fo distibution on a not-fbr-prfit f his rk beyond ht permited in ourses fbr which the textbook has been adopted. ny oher repriucion or rnslion students enol1ed rJnited States Copyright cilhou he permission fhe copyrigh owner is unlwful' ]08 ofthe 976

by Sections

107

or

--6.C outdoor temp. and 72'C indoor temp.) due to the door infiltration can
be calculating using Eq. (6-2b) as:

a,

(:

. o

('

.#l

r,

* }r)rr,

1_zo.o1)"

c=

393.tW

(b) From Table 6-2, = 2 for average-fitting' Then, from Fig. 6-1, Q/L = 1'25 L/m-s

'1

.25x (0.9

+ 2.0)

x 2=7-25--Lls

, _(', .zs* 0

OO'+)

('.rrfil rrrn?)o,
x2 19f2-Lls

e20.6))" C = 819 0W

(c) From Table 6-2, K = 6 for average-fitting' Then, from Fig. 6-1, Q/L = 3.40 L/m-s

= 3.40

x (0.9

+ 2.0)

=(l

2*

('.#l rr, *}a)o'_e20.6))"C '001c)

_2227'6W

6-5

From Figure 6-2, C = 0.52' Using Eq. (6-7b) with the standard air density, the pressure difference due to wind is

p _ \-

o'sz (o

s#)

( b^_f) z.| z.17':::-_!lbf _s'z)


|

(zz-en-

r2

#)'

o.rnro :n:

^\ lbflft')

r,

P'

0't35in'wg

Neglecting stack effect and pressurization, P - 0.135 in' water From Table 6-1, K = 2 for average-fitting with non-weather-stripped. From Fig. 6-1, Q/L = 0.60 cfm/ft. L" = [(3 x2.5) + (2 x 4)]x3 = 46.5 ft

puoses only t on a not-for_profit basis for testing or instrutronal Excerpts from this work may be reproduced by instrutors for distribution

studentsenrlledinourses1brwhihthetextbookhasbeenadopted. nyotherreproduc'onorrnsionfthisrkbeyondhtpermited permisiin ofhe cpyrigh oner is unlwful' by Sectins 107 or ]08 oftnn isri {Jnied SeS Copyrigh chu ie

= 0.60 x

46.5 = 27.9 cfm.

b-b (a) The wind effect is assumed to be independent of height and pressure differences due to wind are the same as those given in Ex. 6-1.
3'd

Windward 0.03
Sides
Leeward
gth

orientation P,

Floor: P"/C

= 0.037;

P,

0.03 0.03

P* 0.066 -0.066 -0.033


-

= 0.037 x 0.8 = 0.03 in.

water

P .96 -0.036 -0.003

P, 0.066 Windward -0.08 -0.066 -0 08 Sides -0.08 -0.033 Leeward


orientation P.

Foor:

P./Co _ -0.100; P,

-0.100 x 0.8 = -0.08 in. water P -0.14


-0.'146 -0.1 13

(b) For Bitlings, MT, design conditionS are to = -7oF, t= 72"F, = 28o/o. From Table 6-3, K = 0.66 for conventional urtain wall.

ir will infiltrate on windward side only on 3'd floor. Windward - 3E floor QiA = 0.15 cfm/ft2; Q = 0.15(120 x 10) = 180 cfm Then 9 = (1 80 x 60/1 2.4)(0.24)(72 - (-7)) = 16,514 Btu/hr " Q,. = (180 x 60/12.4)(0.005 - 0.000)1060 = 4,616 Btu/hr Qt = Q, + 8r. = *1-3oBtu1h [3'd Floor]
gth

Floor

- All exfiltration
Qt
=

otur

on this floor.
19th

Floo

puoses only t EXerptS from this wrk may be reproduced by instructors for distributioIr on a not-for-pro1it basis for testing or instrutional h permitted students enrolled in courses tbr which the textbok has been adopted. ny her reprotluctin r trnsltion of this ork beyond by Secions 07 or ] 08 of he 976 t'Jnited Stes Copyrigh c 1ihou he permission f the cpyrigh lner is unrful.

986-7
(a) Windward

Doors: Double vestibule type P = o.146 in' water, assume 1/8 in' racks Q/L = 16 cfm/ft tFg. 6-7] , L -- 32 ft [Ex' 6-2] Q = 16 x 32 x0'7 = 358 cfm (Assume30o/oreductionforvestibuledoors)

6-7 (Cont.)

Side Doors: Double vestibule tYPe P = -o'o52 in' water' 1/8 in' cracks Q = O.O (negative pres' dff')
(b) Windward: P = O146 in' water' K Q/A = o.2o cfm/ft2 [Fig. 6-6]
=

0'66 lable 6-3]

A=120x10=1200ft2
Q
= 0.29(120) =

240 cfm

Sides: P

in' water' K = O'66 [Table 6-2] = O.O (negative pres' dff')


= -O'O52 = O'66

UULeeward: P = O'047 in' water, K Q/ = O.1Oo cfm/ft2, A = 1200 ft2

[Fig' 6-6]

= O.1O(1200) = 120 cfm;

Total infiltration for the walls is 8* = 240 + O.O + 120 = 360 cfm
(c) Totat infiltration is sum for doors and walls' From x.6-2'for leeward door' Q = 179 cfm' Then the total door filtration is

Qo=358+179=537cfm(neglectinfil.duetotraffic). Andthetotalwallinfiltrationis360cfm,thenQ=897cfm
only to basis for testing o instructional puoses instuctors fo dlstribution on a not-for-profit xcerpts tiom this wk may be reproduced by ork beyond hct permied textbook has been uaot,i 'ny ornr, ,rprort|uron'o''trnston-ths students enolled in ourses t. *-'}, the per-ission of he cpyright oner is unfu' Cpyrgh' ''i"rii'i"'' Sectins 1 07 or ] 08 o7 n' to:ii'inir-d Ses by 'i"

9V

70oF For Charleston, WV: to = 1 1oF' ti = q, = (897 x ll \ 'z)(o'z4)(70-11) = 65'25 Btu/hr q. = (897 x 60/1 1'72)(1060)(O'OO5 - O OOO) = 24'338 Btu/hr q = q" + 9. = 89,363 Btu/hr

6-8

to the wind sPeed of 20 m/s is


(

pressure difference due (a) Assuming standard sea level air density, the

o.o,urt\'(zo*pt *1.461L:\ /
|.9/+ tbfl

,,_

fi,J

=o 197in,water

UUWindward: P*=O197xO25=ooo: Leeward: P* = O"197 x (-0'5) = -0'099 in


AssumPtions: _ 40oF 1) temperature differenc, t to' = zi tle neutral pressure level is at floor 9' 3) the floor height is 12 ft', and 4) C = 0'80' Then, from Fig.6-5,

- } E:l, n*l:

Floor Floor Floor Floor

P" = O'13 x O'8O = 0'104 in' water 1: h = 108 ft., Pr/Co = O.13, and in' water 5: h = 60 ft., P, = 0'065 x O'8O = 0'052 -0'068 in' water 15: h = 72ft., P, = -O'O85 x 0'8O = -0j28 in' water 20: h = 132ft., PS = -Q'160 x O'80 =

puoses only to basis fr testing r instructional by instrutos fo distribution on a not-for-profit h permtted Excerpts tiom this work may^b reprodued the textbook *' 119iJ]1'^"'i";:i:j!i::;:;:;:':""":jfi,':i:,i{:x:x#,.beyond students enrolled n couSes tor whih he coyrigh owner is unlwful of

Windward

Leeward
i,.'i-n

;}i::j;fii,Z'i'"f!"in:ii'ini,a s**,

copy,ign,'a;,\iiio"i'',

& r *--,-,

100

Flnr
1

15 20
(b)

P* 0.049 0.049 0.049 0.049

P" 0.1 4 0.052 -0.068 -0.128

P 0.1 53
0.101

-0.019 -0.79

P* -0.099 -.099 -0.99 -0.099

P" 0.104 0.052 -0.068 -0.128

P 0.005 -0.047 -0.167 -0.227

6-8 (Cont.)

.*

& \d tl

-o.2

-.1

0.0
R.
ilt. lrate
".-,t

.1

.2

*E*-lfi$ffard

LErard

lnfiltration

- Windward Sides,

from 1't to 13th Floor Leeward Sides, 1't Floor onlY

Foor Exfiltration _ Wind\/ard Sides, from 14th to 2oth Leeward Sides, from 2nd to 2Oth Floor
1rt floor, lnfiltration on all sides windows

(c)

through doors, walls and fixed

for tight fitting. Windward Walls: from Table 6-3, K = 0'22 f rorn f ig. 6-6, Q/A = O.OB cfm/ft2'

A=(1+60)1 2=1920f(

= O.O8

x 1920 = 154 cfm

puoses only to basis for testng or instrutional by instructrs for distributon on a not-for-profit Ecets fom this work may be reproduced r*rin-hs ork beyond h Permied textbook ,u, ..n uipi"J . ny other reproa|ur'r,in-o, students enrolled in courses for whih the of he cpyright owner is unlful' Sttes Copyrght ct ithou ie permision by Sections 07 r ] 08 o7 rnr'i 9ii'i'ie

11

for tight fitting' Leeward walls: from Table 6-3, K = 0'22 From Fig. 6-6, Q/A = O'OO5 cfmlft2' A = (1OO + 60)12 = 1920 f(

Q =0.005x1920= 10cfm

for 1/8 in' crack' windward Doors: from Fig. 6-7, Q/L = 17 cfm/ft 6-8 (Cont.) For vestibule doors, assume a 35% reduction' Q/L = 17 x 0.65 = 1 1'05 cfm/ft L = (3 x 6.75) + (2 x 6) = 32'25 ft Q = 11.05 x 32.25 = 356 cfm
cfm/ft for 1/8 in' crack' Leeward Doors: from Fig. 6-7, Q/L = 1.5 or vestibule doors, assum e a 35o/o reduction' Q/L = 1.5 x 0.65 = 0'975 cfm/ft = O.975x32'25 = 31 cfm

Then,totalinfiltration(neglectingtrafficeffect)is + 551 cfm' Qtot = 154 + 1O + 356 31 =


the 1Sth and 2th floors'
6-9

negative pressure differentials for (d) and (e) lnfittration rate is zero due to

For Minneapolis, MN:

to = -1

1oF'

t1

= 70"F

'

[Note:t=70-(-11)=81oFisinconsistentwithProblem6-8where to be minor]
error is assumed t = 40"F was used; however, an floor' (a) From Prob. 6-8, Q = 551 cfm for 1't Btu/hr q, = (5s1 , dotl 2'15)(0'24)(70 - (-11)) = 52'896 o.ooo) = 11,537 Btu/hr o, = lbSt x 60/1 2.15)('1060)(0.O04 Qt= Qr* Qr. =64,433 Btuihr
(b) and (c) qt = O'O due to zero infiltration
puoses only to basis fo'testing r instrutional by instrutos for distribution on a not-for-profit his wrk beyond ht permied Excets frm this wrk may be reproded o' oon'otionf the ,.o" oi i'"r'i""n uopt.a. ,q"y "rn}')ir"ai.iion is unl:wful' students enrol'ed in courses for whih tie permsion of the copyrigh owner f the 97 6 t]nited SeS "iyriii by Sectins 107 r 1 08 'i,thout

ii

102
6-10

For Des Moines, lA:

to =

-4oF, ti = 70oF'

windows, doors, Transmission heat loss (negtecting infiltration) through walls, and roofs can be determined by Eq. 5-19 as: q = UA(t -to)

Windows: A

From Table 5-5a, U = 0.55 Btu/(hr - ft2 -'F1; q = 0.55(144)(70 - (-4)) = 5,861 Btuihr

= (3 xa)1

2= 144ft2;

Doors:

2=243ft2', From Table 5-8, U = O'28 Btu/(hr - ft2 - 'F); (assume panel with metal storm door) q = 0 28 (243)(70 - (-4)) = 5,035 Btu/hr
= (3 x 6.75)1

wails:

64)21- 144- 60.75 = 1395.25ft2', From Table 5-4a, U = 0.14 Btu/(h r -ftz - 'F);
= 8[(36 +
O.

Q=

14(1 395. 25)(70

(-4)) = 14,455 Btu/hr

Roof/Ceilinq: A = 36 x 64 = 2304 ft2', rorn Example 5-3, U = O.83 Btu/(hr _ ft2 _ 'F1; q = 0.083(2304)(70 - (-4)) = 14,151 Btu/hr

can be determined Transmission heat loss through the slat-on-grade floor bY Eq 5-23 as:
Q = U'P(ti -to)

Floor:

p = (36 +64)2=200ft; R-value u' = o.8o Btu/(hr - ft - F), from Fig' 5-8 (assume insulation of 5.4 (hr - ft2 -'F)/ Btu and d = 2ft)' q = 0.8(2OOX7O - (-4)) = 11'840 Btu/hr
heat losses; Finally, total transmission heat loss is the sum of all
for testing or instrutional puses only to instrutors for distribution on a not-for-profit basis Exerpts tiom this work may be reproduced by ork beynd h permited ui.J . ny oher reproa'o" or trnstion his t'u, ."n students enrolled in urses t win the txtbok tie per.isiion of he copyrgh oner is unlful' copyrgnt by Secions ] 07 or ] 08 o7,n, i o)i inted Stes

iriiiiiou

103 qt
6-1
1

5l.Btut

standard air density, From Figure 6-2, Cp= 0'52. Using Eq' (6-7b) with the the pressure difference due to the wind of 15 mph is
(0

LP,

5[ 0.0765y\fr' )

z.(nllbry__s2 _

lbf

P*

0.058 in. water

pressurization' thus For a low-rise building, neglect stack effect and P1 = 0.058 in. water
and doors' From TabIes 6-'1 and 6-2, = 1 for tight-fitting windows From Fig. 6-1, Q/L = O.'13 cfm/ft' ft L" = [(3 x 3) + (2 x a)]x3 + (3+6.75)x2x3 = 109'5 e = 0.13 x 109.5 = 142 dm,
9s
=

Qr=

Qt=

('zx60/12'15)(16OX.O5_0.00)=372Btulhr Q, + Qr. = 1,617 Btu/hr

(14.2 x 60/1 2.15)(0'24)(70

(-4)) = 1,245 Btu/hr

6-12 For alifax, Nova Scotia:


to = 2oF, ti =

70oF'

Refer to Problem 6-10 for other data'

Windows: q

wails: *r,

Doors:q=0.28(243)(70-2)=4'627Btulhr

= 0.55(1 44)(70

2) = 5'386 Btu/hr

13,283 Btu/hr Q = 0.14(1 395. 25)(70 - 2) = ootrcuno: q = O.083(23O4)(70 -2)= 13'004 Btu/hr q = O.8(2OX70 _2) = 10'880 Btu/hr
or instructional puoses only to for dlstribution n a not-fbr-profit basis for testing Ecets from this work may be reproduced by instrutrs th permitted . ny other repro3''o' or rnsltion his ork beyond t u, .", ui.J students enrolled in ourses fbr which the textbok per*isiion of he copyrigh wner is unwful' /ii i"i.d Sror", copyrsnt ii 'iiiou i" by Sectins ] 07 or 1 0B q 'n""i

Total:
6-13

104
qt =

4loBtu/hr

oF; ti 70"F = Memphis, TN; to = 21 R*= 0.92+ 1.55 + 0.99 + 1.77 +0.17 = 5.4 (Tables 5-1 a'5-2a) U* = 115.4 = O.'185 Btu/(hr - ft2 - 'F) Us = 0.81 Btu/(hr - f( - "F) (Table 5-5a) s = 6xax3 = 54 ft2 n* = (40xl O)-54 = 346 ft2 q,= 0.185 x 346 x (70 - 21) = 3,136 Btu/hr qs = 0.81 x 54 x (70 - 211= 2,143 Btu/hr
Qtotrl =

5z auk!

6-14

Concord, NH; to = -2F, ti = 70oF R*= 5.4-0.99+ 3.0=7.41 U* = .135 Btu/(hr _ ft2 - "F) Us = 0.81 Btu/(hr -f( - 'F) (From problem 6-13) q* = 0.135 x 346 x [70 - (-2)]= 3,363 Btu/hr qn = 0.81 x 54 x (72) = 3,149 Btu/hr
Qtotr =

1Buer

6-15

lnstructor suPPlies solution.

6-16

(a) q=9s vs

(i'

iu)

puoses only to for distibution on a not-for-profit basis for testing or instructional Excets from this work may be reprodued by instuctrs repriuctn or trnstion f his ork beyond th permited udo|ted ' Any other students enolled in ourses tbl which the textbook t-'as b"en Act ithou tie permisiion of he cpyrigh oner is unlcnful' by Secins 07 or ] 08 7 *e l ol i ined Stotn, Copyrght

(280'00)(14.6) . _ q":-=:-_ ^= v! _21.8)60 =^251 i._iu


19(S

105 cfm

2.7
=

(b)

q = rh cp(t, -

t..)

9
vs

cp(ts

tr)

Q'

;r==

q,

5'633 cfm (O24X1 15_7O) =

(250,00)(14.6)

6-17

SHF

4st Q./(9. + ")

Locate states, and ondition line and heating pocess on psychometric


chart. _ t') Q. = rh cp(t, _ tr) or h . = q '/cr(t, h. = 100,000/(0'24 x20) = 20,833 lbm/hr Q. = h. X vr/6O = 20,833 x 14.05/60 Q" = 4,878 cfm or about 4,900 cfm

-100'999 = 33, ooo - oo, ooo) = -3.O3 ===,


(1
1

EetS frm this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional puoses ony to permied students enolled in ourses for whih the textbok has been adopted. ny other reproduction or trnslion of this work beynd ht by Secions 107 or ] 08 of the 97 6 Unied Sttes Cpyright c ,ithout the permission f he copyrigh oner is unlnful.

106

p
i
n

ffi

Excerpts frm this work may be reprodued by instrutors for distribution on a not-for-profit basis for tSting or instructional puoses only to
by Sections

nyotherreproductionortrnsltionfthisorkbeyondthpermitted studentsenlledinoursesforwhichthetextbookhasbeenadopted. ] 07 or 108 of he 976 [Jnited SteS Cpyright ct ihout the permission of the copyright oner i3 unlful.

Exets from this work may be reproduced by instrutrs for distribution n a not-for-profit basis for testing or instructional purposes only to students enrled in courses for which the textbook has been adopted. ny ther reproduction r trnsltion fthis wrk beyond tht permitted by Sections ]07 or 0B of the 976 United Sttes Cpyright ct without the permissin f the copyright owner is unlwful. Requests for permission or further informtion should be ddressed to the Permission Deprtment, Jhn Wiley & Sns, nc, ] ] Rier Street, Hoboken, NJ 07030'

Chapter 7
7-1

First, find longitude from Table B-1a

Then, convert Daylight Saving Time to Local Standard Time using Eq. 7-5 Next, determine the equation of time from Table 7-2 Finally, determine Local Solar ime using Eq. 7-6 he following table Summarizes the solutions of the problem.

Location
Lincoln, NE Casper, WY Pendleton, OR London, UK
Norfolk,

Longltue'
76.2 96.75 106.47 118.85 0.45

Standard Meridian, o

VA

75 90 105 120 0

Daylight Savings ime


9:00:00 M 1:00:00 PM

^.-"":' tanarEouation o -' llme


ilme
:

Local

LocalSolar llme

12:00:00

10:00:00 M 3:00:00 PM 7:00:00 PM

M -2'41 min 7:52:47 A|' PM -2.41min 11:30:35M 9:00:00 AM -2'41 min 8:51:43 M 2:00:00 PM -2'41min 2:02:11P 6:00:00 PM -2.41min 5:55:47 PM
8:00:00

7-2

our angle (negative for morning and positive for afternoon) can be determined by

h:5* (LST _l2)


(a) h = 15*(8.19 -'12:00) = 15*(-3.683) = -55.25 deg. (b) h = 15*(10:03 - 12'.00) = '15*(-1 .950) = -29.25 deg.

(c) h = 15*(15:46- 12:00)= 15*(3.767)= 56.50deg.

107

(d) h = 15"(12.01 - 12:00) ='15*(0.017)= 0.25 deg'

7-3

t sunset and sunrise, =0"; sin(B)

From Eq. 7-8; os(/)

os(h). os()

- _sin(/).

sin()

os(h,,) = os(ft,,) = _ tan(/)' tan()

The following table summarizes the solutions of the problem.

Location
MT orlando, FL Anchorage, AL Honolulu, l
Billings,

Latitude,'N

'i"J;::',3" Cos(h)
20.6 20.6 20.6 20.6

45.8 28.43 61.17 21.35

^ffi::. -0.3865 112.7


-0.2035 101.7 -0.6829 133.1 -0.1469 98.4

',|1:ff ',t''i
4:29 5:13

AM AM 3:07 M 5:26 AM

7:30 AM 6:46 AM
8:52 AM

6:33 AM

Note earlier sunrise at greater latitudes


7-4
/=

33.0 deg. N

h = 15.(9-12) = -45.0 deg.

on Sep 21,

= 0.0 deg.

From Eq. 7-8; sin(B) = 36'37 deg'

: os(/).

os(ft). os()

sin(/). sin()

= 0.593

From q' 7-11

cos{ = s ;

sin os/ _ cos sin / os h

= -0.478

= 118.57 deg. (clockwise from north)

-"o,

nn a nnt-fnr_nrnfit hqqis fr testin or instructional puoses only to Exerpts from this work may be reDroduced bv instnlctrq f'r rliqtrih,lfinn

108

7-5

At sunris e,

_ 0"; sin(B)

From Eq. 7-8; os(/)


os(h,. )

'

os(h)

'

os() _ _sin(/)

' sin()

_tan(/)' tan()

(a)

June 21'' -- 23'45 deg; / = 58 deg'

-8'93 hours cos h = -O'6942; h = -133'96 deg' or

Sunrise is at 3:04 AM (Solar Time)


From Eq. 7-11;

^^^ "oo

_ sin _

cos /

os sin / os h
cos

= O.751

north) = 41.33 deg. (clockwise from

(b)
cos h

Dec21'' = -23'45 deg;


=

= 58 deg'

0.6942; h = -46'04 deg' or -3'07 hours

Sunrise is at 8:55 AM (Solar Time)

. sincos/ os=" From q'7-11;

_ossin lcosh

=-0'751

from north) = 138.67 deg. (ctockwise

7-6

Maximumsolaraltitudeangle,willoccuratsolarnoon,h=0

]09From Eq.

7-1O,
CO:

_ ^u*:90 _ Min\, u,)

From Table 7-2, |'u"l = 23.45

(a)

Denver,

= 39.75 deg. N.

For north latitude, / is positive and greater than |rrr| so we need largest positive value of .
From Table 7-2, 'u" = 23'45 deg. and hence '", = 73.70 deg. Therefore, maximum solar altitude angle occurs at solar noon on June 21.

(b)

Lansing, Ml: l= 42.77 deg. N.

For north latitude, / is positive and greater than |rrr| so we need largest positive value of . From Table 7-2, 'u"= 23.45 deg. and hence 'u"= 70.68 deg. Therefore, maximum solar altitude angle occurs at solar noon on June 21.

(c)

Sydney, ustralia:

/=

33.95 deg. S.
|/|

For south latitude, / is negative and largest negative rralue of .

is greater than l'u"l So

\/e

need

From Tabe 7-2, 'u, = -23'45 deg. and hence '", = 79.50 deg. Therefore, maximum solar altitude angle occurs at solar noon on Dec 21.
7-7

Longitude'. Lt= 100 deg. W

Local Standard Time. LCT = 3:30 pm

on Nov 21, Eo

= '13.8 min

instrutional puoses nly to Excerpts from this orktnay be reproduced by instrutors for distibution on a not-fr-profit basis for testing or

l . _-__t!^lj.-^^''-^^^

''^'^-^).'^1:^'"^-|-^aclntinnnfthj.srkbeondhDermied

110

Using Eq. 7-6,


pm.

LSf

= 15.50

(100-90).4 /60+ '13.8/60 = 15.063 Hr or 3:04

Latitude: l = 37 '5 deg.

our ange: h = 15-('15.063-12)

45.95 deg.

on Nov 21,

= -19.8 deg.

Using Eq' 7-8 to calculate solar altitude, = 21.36 deg. Then using q.7-11 to calculate solar azimuth; from north) Surface azimuth;
= 12+180 = 192

226'56 deg. (clockwise

deg. (clockwise from north)

Finally, using q.7-12 to calculate wall-solar azimuth

y= 1226.56-1921= 34.56 deg. 7-8 Using q' 7-13b to calculate angle of incidence for a vertical surface
= 39.92 deg.

Using q' 7-13a to caIculate angle of incidence for an inclined surface


For surface tilt = 70", = 32.30 deg'

7-9
For Ottawa, Ontario on July 21,

Longitude. Lt= 75.67 deg. W


Latitude: = 45.32 deg. N

XetS from this work may be reproduced by lnstrutors for distribution n a not-for-profit basis fr testing or instructional purposos only to studerrts enroled in curses for whih the tcxtbook has been adopted. ny her reroductio or r1fisin f his work beyond ht ermited

Equation of ime: oT

= -6.2 min

Dec|ination: = 20.6 deg.


(a) Eastern Daylight Savings Time:

EDSI

4:00 pm

Using Eq. 7-6, LS7- = 14.852 Hr or 2'.51 pm.


Hour ange: h = 15*(14'852-12)
=

42.78 deg'

Using Eq. 7-8 to calculate solar altitude, = 47"16 deg. Using q'7-13c to calculate angle of incidence for a horizontal surface, = cos-1(sin(47.16)) = 42'84 deg.
(b) At

sunset,
cos(fr

0 and sinp

=Q

):

_tan(/). tan()

Hour angle: h = 112.34 deg.

Solar time at sunset:

LSf

= 12 + hl15 = 19.49 hr or 7:29 pm.

astern Daylight Savings ime can be calculated by DST


=

LST

(L'

_ S(4min/deg-t4l)

- oT

+L
=

EDS
7-10

= 19.49 +(75.67-75)-(4/60)-(-6.2/60)+1

20.638 hr or 8:38 pm.

For Philadelphia, PA on July 21, Longitude'' L= 75.25 deg. W Latitude: / = 39.88 deg. N Equation of Time: oT = -6.2 min Declination: = 20.6 deg. Eastern Daylight Savings Time: EDSI = 10:30 am
xerpts from this work may be reprodued by instrutors for distribution on a not-for-profit basis fr testing or instrutional puoses nly to students enrol]ed in courses for which the textbook has been adopted. nyl other renro,l1ft;h ^v lf.l^i^,^ ^{lL]d 'l^yL o1'^') t1nt ^trmtted

112

Using Eq. 7-6, LS7 = 15.852 Hr or 3:51 pm.


Hour angle: h = 15-(15.852-12) = 57.78 deg.

Using Eq. 7-8 to calculate solar altitude, = 49'42 deg.

Using q' 7-11 to find solar azimuth;

= 114.30 deg. (clockwise from north)

(a) Using q' 7-13c to calculate angle of incidence for a horizontal surface,
= cos-1(sin(49.42)) = 40.58 deg.

(b) For vertical surface facing southeast, Surface Tilt; = 90 deg., and Surface azimuth; = 135 deg. (clockwise from north)'

Using q' 7-12 to calculate wall-solar azimuth , y= |114'3-135

20.7 deg'

Using q' 7-13b to calculate angle of incidence for a vertical surface,


=

cos-l(cos(49.42)cos(20 7)) = 52'52 deg'

(c) For inclined surface faing south, Surface Tilt; = (90-40) = 50 deg., and Surface azimuth', = 180 deg. (clockwise from north)'

Using q' 7-12 to calculate wall-solar azimuth, y= l114.3-180|

65.7 deg.

Using q.7-13a to calculate angle of incidence for an inclined surface,


d = cos-1 (cos(49.42)cos(65.70)sin(50)+sn(+g.42)cos(50))
=

46.'t 1 deg.

7-11
7-12

7-13

For Calibou, M on July 21,

instructional puoses only to . Exerpts from this work may be reprodued by instrutors f,or distribution n a not-or-profit basls for testing or hl permted enrolled in courses for which the texook has been adpted. ny other rerlu"',--:':::':::!*::::]'-g:,od students

113

Longitude' Lt= 46.87 deg. W Latitude: l= 68.02 deg. N Equation of Time: EOT = -6.2 min

Declination: = 20.6 deg. Solar Parameters; = 346'4 Btu/hr-ft2 or 1093 Wm2, B = 0.186, and C = 0.138 Eastern Daylight Savings Time: DSr = 2:00 pm Surface Tilt; = 60 deg. Surface azimuth, SW; / = 225 deg' (clockwise from north)

Using Eq. 7-6, LSI = 14'72 r


Hour angle: h = 15.(14.72-12)
= 41

.58 deg.

Using Eq. 7-8 to calculate solar altitude, = 36.04 deg.

Using q'7-11 to find solar azimuth;

__

230.2 de9. (clockwise from north)

Using q.7-12 to calculate wall-solar azimuth, y= 5'2 deg' Using q' 7-13a to calculate angle of incidence, = 7.45 deg.

Using q' 7-15 and clearness number of 1, 796.75 Wm2

Gry =

252'51 Btu/hr_ft2 or

Using q' 7-16a, G = 250.28 Btu/hr-ft2 or 790'03 Wm2 Using Eqs, 7-18 and 7-2O, G= 26'13 Btu/hr-ft2 or 82'46 Wm2
Therefore, total clear sky irradiation is276.51 Btu/hr-ft2 or 872.49 Wm2 7-14

Given lnformation: Date: June 21 Longitude' Lt= 96'0 deg' W Latitude: / = 36.0 deg. N quation of ime: oT = -1 .4 min Declination: = 23.45 deg.

puoses only to Eerpts fiom this wrk may be reprdued by instrutors for distribution on a not-for-profit basis or testing or instructional f his wrk beyond h permited students enrolled in ourses fb whih the textbook has been adopted. ny ther rerucion r rJ'lsalion

114

Solar Parameters; = 346.1 Btu/hr-ft2 or 1092 Wm" ' B = 0' 1 85, and C = 0.137 Central Daylight Savings Time: CDSI = 8:00 pm Surfae ilt; = 90 deg. Surface azimuth, SW; / = 225 deg' (clockwise from north) Reflectance from water; Ps = 0'25
Using Eq. 7-6,

LSf

= 18.58 Hr

Hour angle: h = 15-(18.58-12) = 98'65 deg'

Using Eq. 7-8 to calculate solar altitude,

= 7 '02

deg'

Using q' 7-15,

G, =

76'24 Btuihr-ft2 or 240'5 Wm2

lrradiation reflected from the ground can be determined by

Gn: PrF.r(sin +C)G'o


where F'ncan be determined from q'7-24'
Therefor, G = 2'47 Btu/hr-ft2 or 7'8

Wm'

7-15

Given lnformation: Date: lar 21 Latitude: / = 56.0 deg. N Equation of Time: o = -7'5 min Declination: = 0.0 deg. Solar Parameters; = ao.g Btu/hr-ft2 or 1164\Nlm', B = 0'149' and C = 0.109 Local Solar Time: LSf = 12:00 Pm Surface Tilt; = 90 deg' Surface Azimuth, S; = 180 deg' (clockwise from north) Clearness number; CN = 0'95 Diffuse Reflectance from Sno\/; n = 0'7
Hour angle: h = 0.0 deg.
puoses ony to distribution on a not-for_profit basis for testing or instrutional Excerpts from this work may b reprodued by instructors for of his rk befrr] .hot nermiti has been adopted. 'qn thei ,eroucion or rnstion students enrolled in courses for which the textbok

115

Using Eq. 7-8 to calcuate solar altitude, = 34'0 deg' Using q' 7-11 to find solar azimuth;

= 180.0 deg. (clockwise from north)


7r=

Using q' 7-12 to calculate wall-solar azimuth,

0.0 deg. 34.0 deg.

Using q' 7-13b to calculate angle of incidence, Using q.7-15, Gtv Using q'
7

268.5 Btu/hr-ft2 or 847 '1 \lm2

-16a, G = 222'6 Btu/hr-ft2 or 702'3


= 33.O Btu/hr-ft'

Wm'

Using qs' 7-21 and 7-22, G

or 104. 1 \lm2

lrradiation reflected from the ground can be determined by

G^: PrF'r(sln+C)G'o
where F*n can be determined from q.7-24' Therefore, GR = 62'8 Btu/hr-ft2 or 198.1 \lm'

7-16

Given lnformation: Date: Aug 2'1 Latitude: I = 32.0 deg. N Equation of Time: oT = -2'4 min Declination: = 12.3 deg. Solar Parameters; = 350.9 Btu/hr-ft2 or 1107 \llm2, B = 0'182, and C = 0.134 Local Solar Time: LSf = 10:00 am Surface Tilt; = 45 deg. Surface azimuth, SW; / = 225 deg. (clockwise from north) Diffuse Reflectance from ground; n = 0.3
Hour angle: h = -30.0 deg.

Using Eq. 7-8 to calculate solar atitude, = 56.1 deg.


Exerpts from this wrk may be reprodued by instrutors for distribution on a not-for-pofit basis for testing or instructional puoses only to students enrolled in ourses for which the textbok has been adopted. ny her renrdcin or trnstion f thi't yk hcn] thl nPrmitt/]

116

Using q.7-11 to find solar azimuth; = 118.7 deg. (clockwise from north) Using q.7-12 to calculate wall-solar azimuth, r= 106.3 deg. Using q.7-13b to calculate angle of incidence, Using q' 7-15,
Gruo = =

61.5 deg.

281'8 Btu/hr-ft2 or 889'1 Wm2

Using q'7-16a, G = 134'4 Btu/hr-ft2 or 424'0 Wm2


Using Eqs. 7-18 and 7-2o, G= 32'2 Btu/hr-ft2 or
10'1

'7

\m"

Using Eqs. 7-23 and7-24, GR = 11'9 Btu/hr-ft2 or 37 '7

\'lm2

',11.9) = 178.6 Btu/hr-ft2 or Using Eqs. 7-25 , Gt= (34.4 + 32.2 + = (424.0 + 101 .7 + 37.7) = 889.1 Wm'z

7-17

The following results are determined from a computer program employing equations in the book from Eqs. 7-6 to 7-26' Following tables summarize input and output data calculated for southwestfacing vertical window at32 deg. N latitude, 90 deg. W longitude, for all daylght hours of a clear day on July 21with ground reflectance of 0.2 and clearness number of 1.

Longitude 90 Standard Meridian 90 -6.2 EOT 32 Latitude Declination 20.6 225 Surf Azimuth 90 Surf Tilt 346.4 A 0,186 B 0,138 c cN1 0'2 RoG

lnput Data

deg deg
min

deg deg deg deg


Btu/hr-ft2

to on a not_for-profit basis for testing or instructional puoses only Exerpts from this work may be reprodued by instructors for distribution nr trn'ntinn n{1|1jq anr' holn'] th' 29;fio) textbk has heen adonted. n othcr fn/^.h'"tinn students enrlled in courses tbr vhich the

117

Output Data

cDsr 7.00 8.00 9.00


12.00 13.00 14.00 15.00 16.00 17.00 18.00 19.00
1

LsI 5.90 6.90 7.90 10.00 8.90 1.00 9.90


1

*Unit

of lrradiation is Btu/hr-ft,

Gruo* Go* Ga* G* G,* 153.43 151.90 112.19 O.OO 6.97 3.40 10.37 -76.55 21.78 78.63 146.37 140.64 209.84 o.OO 13.03 10.68 23.71 -61.55 34.38 85.69 139.31 128.74 249.18 o.OO 15.47 17.51 32.98 -46.55 47.09 93.60 131.40 116.76 268.71 o.OO 16.69 23.39 40.07 -31.55 59.65 104.24 120.76 104.98 279.23 o.OO 17.34 27.g5 45.2s 10.90 -16.55 71.33 123.59 101.41 93.63 284.65 o.OO 20.57 30.90 51.46 1 .90 -1.55 78.52 172.69 52.31 83.01 286.52 34.88 24.03 32.03 90.94 12.90 13.45 73.44 229.79 4.79 73.4s 285.30 81.05 27.54 91.28 139.87 13.90 28.45 62.18 252.83 27.83 65.62 280.70 115.85 30.36 28.70 174.91 14.90 43.45 49.71 264.52 39.52 60.08 271.44 135.41 31.69 24.45 1g1.54 15.90 58.45 37.00 272.79 47.79 57.55 254.30 136.46 30.69 18.81 185.97 16.90 73.45 24.37 279.93 54.93 58.44 220.69 115.51 26.33 12.15 153.99 17.90 88.45 12.00 286.94 61.94 62.60 141.60 65.16 1s.97 4.90 86.03
h,

. ,. -91.55 9.50 71.57


,

"

7-18
Using the developed program, following tables summarize input and output data caculated for south-facing Surface tilted at 45 deg. on Apr 21 in Louisville, KY.
lnput Data

Longitude Standard Meridian

Eo

Latitude

Declination
Surf zimuth Surf Tit

358.2
0.1

85.73 90 1.1 38.18 1.6 180 45


1

deg deg
min

deg

deg
deg

deg

Btu/hr-ft2

CN RHOG

64 0.12
1

0.2 Output Data

tSI
1.0

h,

'.
-38.3 -32.9 -24.8

2.0
3.0

-165.0 -150.0
-'135.0

," 18.8 35.7 49.8

," Gruo* 161.2 164.4 0.0 144.3 150.0 0.0 130.2 135.4 0.0 ,"

JD

G*

JR* ^

ra ^*

0.0 0.0 0.

0.0 0.0 0.0

0.0 0.0 0.0

0.0 0.0 0.0

Exerpts from this work may be reprodued by instructors for distributin on a not-for_profit basis for testing or instrutional purposes only to students enrolled in courses for whih the textbok has been adnted. nll nthy "o^.^)"

118

*Unit

4.0 -120.0 _15.1 61 .5 5.0 -105.0 _4.3 71.6 6.0 -90.0 7.1 80.8 .0 -75.0 18.9 s9.9 8.0 -60.0 30.6 99.7 9.0 -45.0 42.0 111.3 10.0 -30.0 52.3 126.8 11 .0 -15.0 60.2 149.3 12.0 0.0 63.4 180.0 13.0 15.0 60.2 210.7 14.0 30.0 52.3 239.2 15.0 45.0 42.0 248.7 '16.0 60.0 30.6 260.3 17 .0 75.0 18.9 270.1 18.0 90.0 .1 279.2 19.0 105.0 -4.3 288.4 20.0 120.0 -15.1 298.5 21 .0 135.0 _24.8 310.2 22.0 150.0 _32.9 324.3 23.0 165.0 -38.3 341.2 24.0 180.0 _40.2 360.0
7 7

118.5 120.7 18.4 106.0

108.4
1

90.1 80.3 68.7 53.2 30.7 0' 30.7 53.2 68.7 80.3 90.1 99.2
18.5

o.o o.o o.o o.o 99.2 91.4 95.7 o.o

of lrradiation is Btu/hr-ft,

130.2 144.3 161.2 180.0

76.8 215.8 49.2 22.1 62.5 259.6 120.0 26.6 48.4 280.3 186..1 28.7 35.1 291.1 238.3 2g.8 23J 296.5 271.5 30.4 18'4 298'2 282.9 3o.5 23.7 296.5 271.5 30.4 35.1 291.1 238.3 2g.8 48.4 2S0.3 186.1 28.7 62.5 259.6 120.0 26.6 76.8 215.8 49.2 22.1 91.4 95.7 o.o 9.8 106.0 o.o o.o o.o 120.7 o.o o.o o.o 135.4 o.o o.o o.o 150.0 o.o o.o o.o 164.4 o.o o.o o.o 175.2 o.o o.o o.o

o.o o.o 9.8

0.0 0.0 0.7 2.8 4.8 6.5 7.8 8.6 8.9 8.6 7.8 6.5 4.8 2.8 0.7 0.0 0.0 0.0 0.0 0.0 0.0

0.0 0.0 10.5


74.1 151.4

221.3 275.9
3,10.5

322.3 310.5

275.9 221.3 1s1.4


74.1

10.5 0.0 0.0 0.0 0.0 0. 0.0

7-19
Using the developed program,.following tables summarize input and output data calcuated for an east-facing windw, 3 ft. wide by 5 ft. high, with no set bak on a clea r Jul21 day in-Boise, lD.
Longitude
nput Data

Standard Meridian

oT

Latitude

Declination
Surf Azimuth Surf Titt

A
B

116.22 120 -6.2 43.57 20.6 90 90


346.4
38
1

deg deg
min

deg

deg deg deg

Btu/hr-ft2

CN RHOG

.'186
0.1

0.2

LSr 5.0 -,105.0 6.0 -90.0


ilffi;;;;;l#;':il;:'r;

h, o

Output Data

,.
3.8
14.0

,'
65.0 74.8

,"
25.0
15.2

o Guo* Go" 25.3 21.5 19.5 20.6 160.9 .150.6


,

G*

3.6

27.4

GR* Gt* e 0.4 23.5 352.4 6.'1 184.1 2761 .3


to

Exerpts from this work may be reproduced by instructors for on a not-for-profit basis for testing or instruionalmosesonl}, rnich the texthn.. hqc h-.- ".1l'_':9*':'

119

*Unit

7.0 8.0 9.0 10.0 1.0 12.0 13.0 14.0 15.0 16.0 17 .0 18.0 19.0
1

-75.0 -60.0 -45.0 -30.0 -15.0 0.0 15.0 30.0 45.0 60.0 75.0 90.0 105.0

oE

of lrradiation is Btu/hr-ft2

24.7 35.6 46.2 56.1 63.8 67.0 63.8 56.1 46.2 35.6 24.7 14.0 3.8

213.3 237.0 253.1 265.2 275.6 285.2 295.0

84.4 94.8 106.9 123.0 146.7 18.0

5.6 4.8 16,9 33.0


56.7

90.0
123.3

147.0
163.1 175.2 195.2

.185.6

205.0

281.6 283.0 104.0 281.6 117 '9 276.8 131.4 267.7 144.2 251.6 154.7 222.0 159.4 160.9 154.7 21.5

25.3 35.8 48.6 62.1 76.0 90.0

222.0 251.6 267.7 276.8

200.7 203.9 177.2 129.6

36.8 38.5
36.1

68.2 0.0 0.0 .0 0.0 0.0 0.0 0.0 0.0

31.4 26.2

21.5
17 .5

17 '2 .15.6

16.6

13.8 10.0
1.3

26.8 29.2 30.0 29.2 26.8 23.0 18.1 12.3 6.1 0.4

12.3 249.9 18.1 260.6 23.0 236.3


187.8 123.6

3747.9 3908.9 3544.7 2817.2

51.4 46.6 44.0 39.7 33.7 26.1 16.1 1.8

18s3.6
771.7 699.7

659.8
594.8 505.9 391.9 241.6 26.7

is the rate at which solar energy strike the window in Btu/hr

-20

Given lnformation:
Latitude:

Windowwidth;W=4ft. Windowheight; H=6ft. Setbackdistance; b=1 ft.


(a) On

Surface azimuth, S;

l= 32.47 deg.
z-=

180 deg. (clockwise from north)

April2l

Declination: = 12.3 deg. Local Solar ime: LSr= 9:00 am

Hour angle: h = 15.(9-12) = -45.0 deg.

Using Eq. 7-8 to calcu|ate solar altitude, = 43'82 deg' Using q' 7-1'1 to find solar azimuth; = 106'27 deg. (clockwise from north) Using q' 7-12 to calculate wall-soar azimuth, y= 73'73 deg. Using qs. 7-28 to 7-30 to calcuate shaded dimensions,
= (1 ft.)-tan(73.73) = 3.43 ft. y = (1 ft ).tan(43.82)/cos(73.73) = 3.42 ft.
! t

r6'
4'

Shaded area can be calculated by

x.erpts from- this work may be reproduced by instructors 1br distribution on a not-or-profit basis for testing or instructional puoses only t students enrol1ed in courses fbr which the textbook has been adopted. ny other reprducion or rnsl.tii of his wrk beyni th permied

bySections]07r]08ofhe976UniedlqaeC-apyrighcw,ihouheDern&1!!Mf1hecwlrjsh1

oue-r

j'9g!!-g+&!.

."!:'.''' a

'-7

120

,h =W

_ (W

x)

(H _ y) = 22'52

ft2

7-20 (Cont.) Therefore, the percentage of the window that is shaded is 93"8%.
(b)

On July

21

Declination: = 20.6 deg. Local Solar Time. LSl. = 12:00 pm

Hour angle: h = 15*(12-12) = 0.0 deg.

Using Eq. 7-8 to calculate solar altitude, = 78.13 deg. Using q.7-11 to find solar azimuth; = 180.0 deg. (clockwise from north) Using q' 7-12 to calculate wall-solar azimuth, r= 0.0 deg. Using Eqs. 7-28 to 7-30 to calculate shaded dimensions, x = (1 ft.)*tan(0.0) = 0.0 ft. y = (1 ft.)*tan(78.13)/cos(0.0) Shaded area can be calculated by
4.76 ft.

,h=W*H_(W _x)*(-_y)

= 19.03ft2

herefore, the percentage of the window that is shaded is 79.3%.


(c) On Sep 21

Declination: = 0.0 deg. Local Solar Time: LSl. = 5:00 9m

Hour angle: h = 15*(17-12) = 75.0 deg.

Using Eq. 7-8 to alculate solar altitude, = 12.61 deg. Using q'7-11 tofind solarazimuth; =261.81 deg. (clockwisefrom north)
Excerpts from this work may be reprduced by instrutors for dlstribution on a not-for_profit basis for testing or instrutiona] puoses only

to

studentsenrolledincoursesforwhihthetextbokhasbeenadopted. nyotherreproducionortrnsionfthisrkbeyondthpermted ;a ''"^''t\'1 by Secions 07 or ]08 ofhe 976 [JnitedSesCnriqhl '| \ithn1t th hovh'i'Ci' n{tho '^---:not '1lv'-

121

Using q' 7-12 to calculate wall-solar azimuth , y= 81.81 deg.


7

-20 (Cont.)

Using q.7-28 to calculate the horizontally shaded dimension,


x = (1 ft.).tan(81.81) = 6.95 ft.

X,

Since x is greater than W, the window is completely shaded.


Therefore, the percentage of the window that is shaded is 100%'

7-21

Given: Problem 7-20 with a tong 2 ft overhang located 2ft above the top of the window.
For this problem, bo for overhang is the sum of the overhang depth and the setback; hene, bo = /+] = 3 ft.
(a) he vertically shaded dimension on the window due to the overhang can be calculated bY:

lo=botanlcosy_!o-.
where 1rr-, is the distance of the overhang above the window. Therefore,
o = (3 ft.)*tan(43.82)/cos

(73'73) - 2 _ 8'27 ft'

Sine

is greater than H, the window is completely shaded.

Therefore, the percentage of the window that is shaded is 100%.


(b) Similafly, yo= (3 ft.)- tan(78.13)/cos(0.0)

- 2=

12'27 ft'

Since y, is greater than H, the window is completely shaded'


'100%' Therefore, the percentage of the window that is shaded is

basis 1br testing or instrutional puoss ony to Exets from thls work may be reproduced by instrutrs for distribution on a not-for-profit | this ork beyond ht permied in courses fbr whih the texibook has been aJopted. ny her reprucJio or rnslin students enrolled l^'-!'1 ^ ' '1 b,ySectins 07 r 08of the 1q76-ito)-qf'''"?""";*13

122 the setback' there is no (c) Since the window is completely shaded due to need to calculate Yo'
-22

setback' Given. Problem 7-2owith 6 in. setback instead of 1 ft'


(a) Using Eqs. 7-28 to 7-30 to calculate shaded dimensions,

x = (0.5 ft.)*tan(73.73) = 1'71 fL , = (o.s ft.)-tan(43.82)/os(73'73) = 1'71 ft'

Shaded area can be calculated bY


,n =W
*

_ (W

_x)* (H _ y) = 14.19 fi2

is 59'1%' Therefore, the percentage of the window that is shaded


(b) Using Eqs. 7-28 to 7-30 to calculate shaded dimensions,

= (O.5 ft.)-tan(0'0) = '0 ft' , = (.s ft.)*tan(78.13)/cos(0'0)

_-

2'38 ft'

Shaded area can be calculated bY


,l, =W
*

_ (W _'T )

(H _ y) = 9'52

ft2

shaded is 39'7%' Therefore, the percentage of the window that is

(c)UsingEqs.T-28to7-3Otocalculateshadeddimensions,
x = (0.5 ft.).tan(81'81) = 3'48 ft' , = (O.S ft.)-tan(12.61)/cos(81 'S1) = 0'79 ft'

Shaded area can be calculated


,h =W
*

bY

H _(W _.)* (H

y)

21'27

ft2

or instrutional puoses ony to for djstribution on a not-for-profit basis or testing Excets from this work may be reproduced by instructors

studentsenrolledinoursestowhichtnetexookhasbeen o7Abi+^)c'-!"^^f''";..1'! h'Srtinnrl07nrl0Rn{t1o

^l"i'r'i ''',.'"''^""i'-''""'''''-"'^-^{i"^^^'^'';-^1

iy'nrrrrprour^o-o,rnsliiofhisorkbeyondthtermitted
'''-''"i"-^'{"l

123 Therefore, the percentage of the window that is shaded is 88'6%'

-23

as described in Problem 7-20, the following table summarizes the calculated data.

on December 21, Declination: = -23'45 deg. Using the same procedure

Solar :"^::j Hour Solar Azimuth,Surface- '"Jlff#:"' Solar Angle, ltitude, :,ol1' ""; o o Time, f\Zllul Azimuth,' Dimension '' " 1x1, ft hr 1'37 8.OO -6O.O0 9.98 126.22 53 78 ',136.52 43 48 o'95 9.OO -45.00 1g.4g 0'60 1o,oo -3o.oo 27.17 148.96 31'04 o'29 1.OO -15.00 32.27 163.69 16'31 o oo 34.08 18o.OO O'OO 12.00 O.OO 0 29 13.00 15.00 32.27 196.3',1 16'31 o 60 27.17 211'04 31'04 14.00 3O.OO 0 95 43'48 15.00 45.00 19.49 22g 48 1'37 23g.78 53'78 16.00 60.0O 9.98
'1

Dimension Area,
(y)' ft

"#::
o'30 o'49 0'60 0'66 0'68 0'66 0'60 0 49 0 30

Shaded

ft2

%Shaded

rea
37

8'98 7 '18 5'65 4'20 2'71 4'20 5 65 7 18 8 98

29'9
17
1
',1

'4

23',5

'5
',3

17

23'5
29',9
37

'5

'4

-24

This problem is similar to ProblemT-21 but the overhang depth is 3 ft in instead of 2ft. Since the window in ProblemT-21 is completely shaded all all cases. he window in this problem is also completely shaded in cases since the overhang depth is greater in this problem'

-25

-26

-27

Eqs' First, we need to know angle of incidence and solar irradiation. Using problem), 7-8 to 7-26 (or a computeiprogr developed for previous
puoses only to on a not-for-profit basis for testing or instructional Exets 1iom this work may be reproduced by instructors for distibution

studentsenroledincoursestbrwhichthetextbookhasbeen

adopted' nyotherreproucinrtrnslioofthisworkbeyondhpermited

124

incidence angle and solar irradiation on a southwest-facing window for Boise, lD on a clear July 21 day at 3:00 pm solar time are Angle of Incidence = 52.4 deg', Direct Solar lrradiation: Gp = 163'4 Btu/hr-ft2' Diffuse Solar lrradiation: Ga + G = 34'5 + 23'0 = 57 -3 Btu/hr-ft', and Total Solar lrradiation: G1 = 163'4 + 57 '3 = 220'9 Btu/hr-ft2'
Then, the area of the glazing and of the frame is calculated to be 12'44 and 2.56 ft2, resPectivelY.
ft2

From Table 7-3, solar heat gain coefficients for the glazing system lD 21c are SHGGgo(52.4") = 0.548 and SHGGg= 0'52'
be From Table 5-2, the outside surface conductance may be estimated to 4.0 Btu/hr-ft2-'F.

From able 5-6, the U-value for the fixed, double glazed window having aluminum frame with thermal break utilizing metal spacers is 1.13 Btu/hrft2-'F.

From Table 7-1, solar absorptance of the aluminum frame (assuming the window is not a nev/ one) is 0.8.

ssuming the window with no setback (Ar,u'" = frame can be calculated using Eq' 7-31 as: SHGGr = 0.8*(1 '1314'0) = 0'226'

Aru),

the SHGC for the

Then, using q.7-32, the total solar heat gain is


Qsnc = (0.548.1 2.44 + 0.226*2.56)*163'4 + (0.52*1 2.44 + 0.226*2.56)-57.5 = 1613'68 Btuihr'
7

-28

glazing From Table 7-3, the glazing transmittance and absorptances for the system lD 21c are

puoses only to distribution on a not-for-prfit basis for testing or instrutional Excerpts from this work may be reprodued by instructors for of hs wrk beyond h permitted the tx;book has .", uJopt". ny oher reprouction or rnsti students enrl]ed in ourses for whih

125
7

-28 (Cont.)

T6(52'4") = O.+1 56, tw2) = O'140, fz2'4) = 0'1524' Ta= O'40, -Af = o.'13, and fza= O.15.

Using Eq. 7-35, total transmitted solar heat gain is


Qrru"', = (0'4156-163.4 + 0.4*57.5)-12'44 = 1130.9'1 Btu/hr.

Using Eq. 7-36, total solar heat gain absorbed by the glazing is
8 oroo,, =
=
[1

63'4*(0"1 4+0'

524) + 57'5*(0"1 3+0' 1 5)]-1 2'44

794.64 Btu/hr.

From Table 5-5a, the U-value for the center of glass is 0.42 Btu/hr-ft2-"F. Similar to the previous problem, the outside surface conductance may be estimated to be 4.0 Btu/hr-ft2-'F. Then, the inward flowing fraction for glazing layer 1 can be calculated by:

Nt=0.42 14.0=0.105
From Table 5-2a, the inside surface conductance may be estimated to be 1.46 Btu/hr-ft'-"F.

The conductance from the inner pane to the outdoor air can be calculated
by:

flo'2=

,11

U hi 0.42

1 1=-1

1
.46

=o'59Btu/hr-ft2-'F

Then, the inward flowing fraction for glazing layer 2 can be calculated by:
Nz= 0.42 / 0.59 = 0.71

puoses only to Exerpts 1iom this work rnay be reprodued by instrutors for distribution on a not-for-profit basis for testing or instructional permitted students enrolled in ourses fbr which the textbok has been adoted' ny oher reproduction r lrnsltin of his wrk beyond th

126 7-28 (Cont.)

Using q. 7-38, the inward flowing fraction of the gazing system is


N=
[1

= 0.122

63.4*(0.'1 0S*0. 14+0.7 1*0.1 524) + 57.5*(.'1 05*0. 13+0.71-0. 1 5)] l 220 '9

Using Eq. 7-39 and the SHGGr calculated from the previous problem, the solar irradiation absorbed by the frame is
Qoroo,f = (163.4 + 57.5)*2.56*0.226 = 127 .80 Btu/hr.

Using q' 7-40, the total absorbed solar heat gain of the fenestration system is
Quruo,ur =

794.64*0.122 + 127 .80 = 224.75 Btu/hr.

The total solar heat gain is then


Qsrc = 1130.91 + 224.75 = 1355.66 Btu/hr.
7

-29

From Table 7-4, lAC for a lighted-color Venetian blind installed on a residential double-pane window is 0.66.

Using q' 7-41, the total solar heat gain is


Q

suc = '226-2'56-220'9) + [0.548*12.44*163.4 + 0.52* 12.44*57 .5]*0.66 = 1108.48 Btu/hr.

-30

From Table 7-6, for a ighted-color Venetian blind, shade transmittance, reflectance, and absorptance are 0.05, 0.55, and 0.40, respectivey.

Using q' 7-42, the transmitted solar heat gain is

127

7-30 (Cont.)
Qrroo = 0.05*1130.91 = 56.55 Btu/hr.

Using q' 7-43, the absorbed solar heat gan is


4or"" = 224.75 + 0.40*1 130.91
=

+ 0.55*1 130.91 *0.122*(0.'13+0.I S)

698.36 Btu/hr.

7-31

From Table 7-3, solar heat gain coefficients for the glazing system lD 5b are

SHGGgo(52'4")

0.6256 and SHG Gg = 0.60.

Similar to Problem 7-27 , SHGGr = 0.226.

Then, using q'7-32, the total solar heat gain is


Qsc = (0.6256-12.44 + 0'226*2.56)*1 63.4 + (0.60.12.44 + 0.226*2.56)*57.5 = 1828.64 Btu/hr.

-32

From Table 7-3, the glazing transmittance and absorptances for the glazing system lD 5b are
TD(52'4") = 0.5332, 'Af ,o2'4) = 0.1924, 1fro2'4) = O'12, Ta= 0.51, -Atro= 0.19, and -Arzd= 0.11.

Using q. 7-35, total transmitted solar heat gain is


Qrsac,g = (0.5332*'163.4 + 0.51*57.5)*1

2.44 = 1448.64 Btu/hr.

Using Eq. 7-36, total solar heat gain absorbed by the glazing is
Q

llc'g =

[1

63.4*(0.1924+0'12) + 57.5-(0.

9+0.

1)1-12.44

-32 (Cont.)
=

-===
849.60 Btu/hr.

From Table 5-5a, the U-value for the center of gtass is 0.55 Btu/hr-ft2-"F.

similar to the previous problem, the outside surface conductance may be estimated to be 4.0 Btu/hr_ft2_.F. Then' the inward flowing fraction for glazing layer 1 can be caculated by:

Nz=0.SS /4.0=0.1375
Simiar to the prevous probtem, the inside surface conductance may be estmated to be 1.46 Bt/hr-ft2-"F.

The conductance from the inner pane to the outdoor air can be calcuated by.

ho,z=t\ =T-] 1 (]_ O55 - 1-46


/vz=0.55/0.gg=0.625

= 0.88 Btu/hr-ft2-"F

hen' the nward flowing fraction for gtazing layer

2 canbe

calcutated by:

Using q. 7-38, the inward flowing fraction of the glazing system is N = []-63 4-(O.1375-. 1924+o.625*0'12) + 1375*0' 19+0'625*0' 1 1 l 22o'g )]
=

'Jr';''

he solar irradiation absorbed by the frame is the Same as the previous probem, and is equa to 127 .80 Btu/hr'

Using q' 7-4O, the totat absorbed solar heat gain of the fenestration system is

7 -32 (Cont.)

+ 127 '80 = Qo'"o'gt = 849'60*0'1OO

212j6 Btu/hr'

The total solar heat gain is then


+ Qwc = 1448'64

212J6

= 1661'4 Btu/hr'

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instrutiona purposes only to students enrolled in courses for which the textbook has been adpted. ny other reprduction r trnsltion of this wrk beyond tht permitted by Sections ] 07 or ] 0B of the 1976 United Sttes Copyright ct without the permission of the cpyright owner is unlwful. Requests for permission or further infrmtion should be ddressed to the Permission Deprtment, Jhn Wiley & Sons, nc, ] ] Rier Street, oboken, NJ 07030.

Chapter 8
B-1

a) The heat gain is generally geater than the cooling load during the morning hours M/hen sunlight first strikes a building and the internal loads first begin. Heat is being stored in the building structure, furnishings, etc. b) Late at night when occupants are not present, lights and equipment are off and solar radiation is zero, the building gives up stored heat to the air, which the equipment removes as cooling load. The heat gain may be quite small, zero, or negative. c) At some time during the day, probably early evening, as heat gain is

decreasing, and equilibrium condition can be established when heat gain and cooling load are equal. Or, some interior zones, where the cooling load is driven only by internal heat gains may reach equilibrium if the heat gain remains constant for a number of hours.

8-2
Multipe design conditions should be checked, including peak dry bulb along with mean coincident \et bub, and peak wet bulb along with mean coincident dry bulb temperature.

8-3

SHRE 90.1 specified the2'5% design conditions, which roughly

corresponds to the 1% design conditions in the current Handbook of Fundamentals and the textbook.
Location Norfolk, VA

Outdoor

DB.'F
91

Outdoor

WB,'F
76

DB.'F
75

lndoor

lndoor RH. % 50

Elevation, ft
30

Latitude,
ON

36.90

131

8-4
into the tayer library' The select materials; some may need to be entered here' (Note that not resulting wall construction ,pp"rrt as shorrun using a density of 120 everything is specified exacity, .o that a student it1yt"i iic wi get a different set of CTF coefficients')
-"..-"...-ns1]
0 3

130 "18
3.

5]

5n

for room mode, we After running the HvacloadExplorer program in execute obtain the following CTF coefficients for this wall.
n

xn, Btu/h-ft2-"F

Yn, Btu/h-ft2-"F

zn,

Btuih-ft2-"F

0
1

4.276507
-5.36497

0 0445
0.1 1581 0.01 1845

0.642344
-0.98287

0.638772
-0.02179

2
3

1.141149
-0.027 59
-7

0.376555
-0.01 101

0.001 134

.7-05

0.00017

-5E-06

B-5

except that the RThis problem is solved in the Same \/ay aS Problem 8-4, 13 insulation is changed to 5.5" thick R-19 insulation.
or instructional puoses only to for dtstribution on a not-for-profit basis for testing permed xerpts fom this work may be reprodued by instutrs iny oh* up-iurrn-o, onstionf his work beynd th t,u, "., uai-pt.' students enrolled in courses tor whih the tetbook of the cpyrigh owner is unlful' copyrg|rt 'a| rr"iiu n, prr^''n by Secions 107 or ] 08 o7 ne ii;i' initid Sror^

132

The folowing CTF coefficients are obtained:


n

xn, Btu/h-ft2-"F

Yn,

n,

tu/h-ft2-'F 0.000071

Btu/h-ft2-"F

0
1

4.277384
-5.95084 1.847897 -0.16027 0.001331

0.644513
-1.08666
0.510931 -0.05401

0.004622
0.008936 0.001835 0.00004

0.779066 -0.10021 0.001435

2
3

0.000734

8-6

gain, this problem follows the procedure of the last two problems. The thickness of the roll roofing must be estimated, and the conductivity chosen to match the overall conductance. (k=thickness*conductance)

The following CF coefficients are obtained:


xcets from this work may be reproduced by instrutors for distibution on a not-for-profit basis for testing or instrutional puoses only to students e'rolled in courses for whih the textbook has been adopted. ny oher reproduction or rnsion of this ork beyond h permited by Secins ] 07 r 1 08 of he 97 6 Unied Stes Cpyrigh c w ithu he permissin f he copyrigh oner is unlful'

133

xn, Btu/h-ft2-'F

Yn,

Btu/h-ft2-'F

n,

Btu/h-ft2-'F

0
1

1.014657 -1.09939

0.006092 0.029838 0.006044


0.000071

0.644513
-0.6816 0.150594

2 3

0.126521
0.000256

0.079104
0.00003

8-7

ln this case, a reasonable value for the resistance of the air-space must be selected. For the air^-space, an R-value of 1 is chosen; thus conductivity is set to '12 Btu-in lhr- ft2- F, and the thickness s set to 12 in Density an bp are set to zero and 0.24, respectively.

nt: ayers listed fnm tp t bfiom :epr*s*ni {r:n thg nutsiJ* t inside ot lhe sur{ce

The following CF coefficients are obtained:


n

xn, Btu/h-ft2-'F

Yn,

Btu/h-ft2-'F

zn,

Btu/h-ft2-'F

0
1

1.014651

0.00468 0.027234 0.00674 .00016

0.654471
-0.71129 0.095526 0.000053
0.1 781 59

-1.12785
0.1 51 609

2
3

0.000351

Exc-erpts from this work may be reproduced by instrutors for.distribution on a not-for_profit basis for testing or instrutional puoses only to students enrolled in courses or which the textbook has been adopted' ny ther reprocion or trnsl(]in of his rk beyontl th permied by Sectins ]07 r ]08 ofhe 1976 Unied SteS Cpyrigh cw'ithou hi permissn fhe cpyrigh ner i unlful'

134

8-8

Again, reasonable values must be assumed for the density of the acoustical tile and the specific heat of the limestone concrete.

The folowing CTF coefficients are obtained:


n
CI

xn, Btu/h-ft2-'F

Yn,

Zn'

3.162792
-3.76069

Btu/h-ft2-'F 0.002232

Btu/h-ft2-'F 0.2851 '16

0.01895

-0.38995
0.137 459

0.71366

2
3

0.633425
-0.00642

0.007779
0.000149

-0.01912

-0.0352

8-9

First, app|y the exterior onvective heat transfer correlation, Equation 818a, to determin h"' Assume the 15 mph wind is windward on the surface, which results in h" = 2.3 Btu/(h-ft2-F). Estimate the sky temperature as 10.8 R below the outdoor ambient temperature = 546.87 R. Then estimate the effective sky temperature for a vertical surface from quation 8-25
tsky,o=

cos (90/2)ry +(1-cos(90/2))f,

550.0 R

EXcetS from this work may be reprodued by instructors for distibution on a not-for_profit basis for testing or instructional puoses only to students enrolled in urses for which the textbook has been adopted. ny oher reproduction or trnsion of this wrk beynd h permited by Sectins 07 r 08 f the 1976 tJnited Sttes Copyr1h c \itlout he permission of the copyrigh oner is unlfu.

136
Declination
Surf zimuth Surf Tilt

346.4
86 0.1 38
0.1
1

20.6 270 90

deg

deg
deg
Btu/hr-ft2

RoG

CN

0.2 Output Data

MDST LSI h, o 1 .00 23.79 176.83 2.00 0.79 -168.17 3.00 1.79 -153.17 4.00 2.79 -138.17 5.00 3.79 -123.17

"

,'

,o

,o

* r/vD 0.00 0.00 0.00 0.00 0.00 0.00

JD* ^

rd* ^

JR* ^

rt ^*
0.00 0.00 0.00 0.00 0.00 0.00 9.93 23.08 32.24 39.29 44.53

-34.27
-33.23

-28.80 -21.65
-12.54

*Unit

12.00 13.00 14.00 15.00 16.00 17.00 18.00 19.00 20.00 21.00 22.00 23.00 24.00

4.79 -108.17 -2.11 5.79 -93.17 9.19 6.79 -78.17 21.05 7.79 -63.17 33.22 10.00 8.79 -48.17 45.49 11.00 9.79 -33.17 57.51
10.79 11.79 12.79 13.79 14.79 15.79 16.79

6.00 7.00 8.00 9.00

356.41 86.41 87.03 13.26 256.74 101.06 28.82 241.18 114.99 42.20 227.80 128.63 53.39 216.61 141.58 62.87 207.13 152.80

of lrradiation is tu/hr-ft2

20.79 '131.83 21.79 146.83 22.79 161.83

-3.17 75.28 11.83 72.19 26.83 62.36 41 .83 50.63 56.83 38.41 71 .83 26.17 17 .79 86.83 14.15 18.79 101 .83 2.58 19.79 1 16.83 -8.27

-18.17

68.46

-18.00 -26.06 -31.74

269.56 0.44 277.71 7.71 285.45 15.45 293.49 23.49 302.43 32.43

218.87 51.13 245.60 24.40 259.78 10.22

107.55 162.45 127.34 142.66 168.24 101.76

79.02 190.98 86.89 183.11 95.77 174.23

71

.22

198.78

159.17 156.37 146.65 134.23


120.81

106.97 92.97 78.94 65.01 51.37 38.42

108.07 206.38 246.69 266.87 277.85 283.62 285.80

27.20 20.83 23.63


33.35 45.77 59.19 73.03

284.93 54.68 280.80 1 18.63 272.32 170.01 256.78 201.20 227.20 202.07 161 .85 151.27

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

12.82 10.26 15.32 16.92 16.57 22.71 17.25 27.27 17.61 30.29 47.91 20.83 31.59 52.42 25.38 31.06 111.11 30.63 28.75 178.01 35.51 24.81 230.32 38.43 19.50 259.13 37.19 13.16 252.42
27

0.00 0.00 0.00 0.00 0.00 0.00 6.71

0.00 0.00 0.00 0.00 0.00 0.00 3.22

312.83 42.83 325.24 55.24 339.93 69.93

5.53 0.00 0.00 0.00 0.00

5.07 0.00 0.00 0.00 0.00

.51 0.93 .00 0.00 0.00 0.00

6.19 0.10 0.00 0.00 0.00 0.00

184.97 6.10 0.00 0.00 0.00 0.00

The hourly dry-bulb temperature is calculated using Equation 8-2. Here, the hour nearest to the local solar time has been used to determine the temperature. A spreadsheet is used to obtain the solution. lteration is accomplished by simpy pasting the calculated values of Io" back into the " Io", estimated" column.
lnput Data U-Value Solar absorotivitv Ihermal emissivit
0.1

Btui(h-ft2-F)

0.8

0.9

Excets from this work may be reproduced by instrutors for distrrbution on a not-for-proit basis for testing or instructional puoses only t students enrolled in courses for whih the textbook has ben adopted. ny other reproducion or trnstion f his wrk beyond th permitted by Secions 107 or ]08 ofthe 976 United Sttes Cpyriqht ctlihu he permissin fthe cpyright oner is unlful.

137
is Peak temperature Dailv Ranqe Mean Wind Soeed
72.O
F

96.0 25.4 10.0

F F mph Output Data

Clock
Time
1.00

Local Time

Outdoor
Dry-bulb Temp.
(F)

Solar

emp. (F) 64.4


63.1

skv

Effective
Temp.
(F)

skv

To",

hc

hrsky

hrg..o

estimated (Btu/(h(F)

(Btu/(h

(Btu/(h-

ft'-F)) 1.58 1.58


'1.58

-fr-F))
0.46 0.46 0.45 0.45 .45 0.45 0.45 0.46 0.47 0.48 0.49 0.5
0.51

ft'-F))
0.47 0.47 0.46 0.46 0.46 0.46 0.46 0.47 0.48 0.49 0.50
.51

calculated from 8-24


(F) 73.14 71.93 70.72

To",

9conduction

(Btu/(htt')) 0.1
1

2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.0 11.00 12.00 13.00 14.00 15.00 1 6.00 17 0 18.00 19.00 20.00 21.0 22.00 23.0 24.00

23.79 0.79 1.79 2.79 3.79

4.79
5.79 6.79 7.79 8.79 9.79 10.79 11.79 12.79 13.79
14.79 15.79

75.2 73.9 72.6 71.6 70.9 70.6


71.1

61.8 60.8
60.1

67.5 66.3 65.0 64.0


63.2

74.60 73.15 71.94 70.72

-0.01

-0.13
-0.23

1.58
'1.58

59.8

72.4 74.7 78.0


8'1.8

60.3 61.6 63.9


67.2
71 .0

63.0 63.5
64.7

69.75 69.03
69.'18

1.58 1.58
1.58

69.75 69.02 68.78


72.34 77.55 82.47 87.66 92.76 97.77 102.84 122.43
142.11

67.0
70.3
74.1

86.1

90.2 93.2 95.2


96.

16.79 17.79 18.79 19.79 20.79 21.79 22.79

o?

95.2

90.7 87.4
84.1

81.3 78.7 76.7

75.3 79.4 82.4 84.4 85.2 84.4 82.7 79.9 76.6 73.3 70.5

78.5 82.5 85.6 87.6 88.4 87.6 85.8 83.0 79.7 76.4 73.6
71 .1

74.55 78.99 83.53 88.42 93.24 98.33 109.05 131.23 148.77 159.92 162.49 153.00 118.72
84.81

1.58 1.58 1.59


'1.59

1.59 1.59
1.61

1.62 1.62
1.62 1.62

67,9 65.9

69.1

81.65 78.97 76.55

1.60 1.58 1.58 1.58 1.58

0.53 0.57 0.60 0.62 0.62 0.60 0.54 0.49 0.48 0.47 0.47

0.52 0.54 0.58


0.61

-0.30 -0.32 0.03 0.56 1.05 1.57 2.08 2.58 3.08 5.04
7.01

.63 .63
0.6'1

155.98 162.15
158.51

0.55 0.50 0.49 0.48

138.39 86.48 81.63 78.96 76.54

8.40 9.02 8.65 6.64


1.45

0.48

74.60

0.96 0.70 0.45 0.26

8-11

This problem uses the same solution procedure as Problem 8-10.

Longitude 116.22 Standard Meridian 105 EOT -6.2 Latitude 43.57 Declination 20.6

lnput Data

deg
deg min deg deg

Excets from this wok may be reproduced by instructors fbr distrrbution on a not-for_profit basis for testing or instructional puoses only to students enrolled in ourses for whih the textbook has been adopted. ny other reproduction r trnstion of this rk beyond h permitted by Secions ] 07 or ]08 of he 976 United Sates Cpyright c ,ithout he permission of the cpyrigh oner is unlwfu.

138
Surf zimuth Surf Tilt

346.4
0.1 0.1
1

180 90
86 38

deg
deg
Btu/hr-ft2

CN RHOG

0.2 Output Data

MDST LSr h, " , " 1.00 23.15 167.23 -24.77 2.00 0.15 -177 .77 -25.80 3.00 1.15 -162.77 -23.91 4.00 2.15 -147.77 -19.34 5.00 3.15 -132.77 -12.59 6.00 4.15 -117.77 -4.21 7.00 5.'15 -102.77 5.31

"

o '68

346.83 166.83

*Unit

13.00 14.00 15.00 16.00 17.00 18.00 19.00 20.00 21.00 22.00 23.00 24,00

8.00 6.15 -87 .77 9.00 7.15 -72.77 10.00 8.15 -57 .77 .0 9.15 -42'77 12.00 0.15 -27 .77
1 1
'1

15.60 26.32
37 .17

47 '76
57 .42

12.15 2.23 13.15 17.23 14.15 32.23 15.15 47 .23 16.1 5 62.23 17 .15 77 .23 18.'15 92.23 19.15 107 .23 2015 122.23
21.15 137.23 22.15 152.23

11.15 -12.77

64.68 66.95
62.91 54.71

44.67

33.95
23.10 12.48

2.38
-6.85 -14.79 -20.95

of lrradiation is Btu/hr-ft'z

254.61 22.70 269.45 58.92 277.79 87.76 281.98 105.54 185.34 5.34 283.00 1 10.30 217 .50 37.50 281.09 101.56 239.78 59.78 275.81 80.22 255.07 75.07 265.88 48.70 266.84 86.84 248.28 11.34 277.01 97.01 215.64 0.00 286.67 106.67 106.26 146.49 0.00 296,51 116.51 116.49 3.97 0.00 307 .11 127.11 126.80 0.00 0.00 318.90 138.90 136.76 0.00 0.00 332.16 152.16 145.67 0.00 0.00

96.42 83.58 108.99 71.01 125.92 54.08 151 .07 28.93

0.00 0.00 17.66 162.34 0.00 31.94 148.06 0.00 44.76 135.24 0.00 56.15 123.85 0.00 66.47 113.53 0.00 76.20 103.80 103.29 173.45 0.00 85.92 94.08 93.66 227.72 0.00 2.32
177

" 152.14 154.11 150.59 143.20 133.87 123.75


,

Gr*

Go*

G*

JR ^

Lz1

^*

0.00 .00 0.00 0.00 0.00 0.00 113.42 46.47


84.88 77.37 71.58 68.02 67.06 68.82 73.09 79.44 87.38 96.45

0.00 0.00 0.00 0.00 0.00 0.00

2.89
10.77 16.45 20.78

24.56 27.57
29.47

29.99
29.04 26.78

13.24 18.90 23.67 27.24 29.38 29.95 28.90


17

0.00 0.00 0.00 0.00 0.00 0.00 1.07 7.06

0.00 0.00 0.00 0.00 0.00 0.00 3.96 17,83 29.69

62.38
107.15 142.58 164.39 170.24 159.50 94.57

23.50
19.55
15.02

22.36
11,44

26.32'133.31

.29

48.18
26.46 14.28 0.32 0.00 0.00 0.00

9.10 0.25 0.00 0.00 0.00

5.19 0.07 0.00 0.00 0.00

lnput Data U-Value Solar absorptivitv hermal emissivih Tis Peak temoerature Dailv Ranqe Vlean Wind Soeec
0.1

Btu/(h-ft2-F)

0.9 .9 72.0 96.0 30.3


1

F
F

1.0

mph Output Data

Excets from this work may be reprodued by instructors fbr distribution on a not-for-profit basis for testing or instructional puoss only to students enrolled in courses for which the textbok has been adopted. ny other reprducion or rnsltin of his work beyond th permied by Sectins ]07 r 08 ofhe 1976 Unied Sttes Cpyright ctihout the permission ofhe cpyright oner is unwful.

139
Outdoor
Dry-bulb Temp.
(F)

Clock
Time
1.00 2.O0

Solar
Time

Local

Temp.
(F)

skv

Effective
Temp.
(F)

Skv

estimated (Btu/(h(F)

To"'

h"

hrsky

(Btu/(h
-ft'?-F))

(Btu/(h-

hrgr

To.,

calculated
(F)

Qconduction

ft'-F))
1.72 1.72 1.72 1.72

tt'-))
0.46 0.46 0.46 0.45 0.45 0.45 0.45 0.45 0.46 0.47 0.50 0.53 0.56 0.58 0.59 0.59 0.58 0.55 0.53 0.52 0.50 0.49 0.48 0.47

fromS-24
71.15 69.41

(Btu/(hft2))

23.15 0.15
1.15

73.0 71.2

3.00

69.6
68.'1

4.00
5,00 6.00 7.00 8.00 9.00
10.0 1 1.0

2.15 3.15

62.2 60.4 58.8 57.3


56.'1

65.3

63.5
62.0 60.5

71.15 69.41

67.96
66.51 65.35 64.48
64.1

4.15
5.15 6.15 7.15 8.15 9.15 10.15 11.15 12.15 I 3.15 14.15 1 5.15 16.15 17.15 18.15
'19.15

66.9 66.0 65.7 66.3 67.8


70.5

oa

74.5
79.0 84.2 89. 92.7
95.1

12.00 13.00 14.0 15.00 1 6.00 17.00 18.00 19.00 20.0 21.00 22.00 23.00 24.00

96.0
95.1

20.15
21 15

22.15

93.0 89.6 85.7 81.8 78.4 75.4

55.2 54.9 55.5 57.0 59.7 63.7 68.2 73.4 78.2 81.9 84.3 85.2 84.3 82.2 78.8 74.9
71 .0

58.4
58.1

58.7 60.2 62.9 66.9 71.4 76.5 81.4

68.60
74.15
81.31

99.67 116.02
129.01 137.21 '139.67

85.0
87.5 88.4

136.52
127.91

87.5 85.3
82.0
78.1 74.1

67.6 64.6

70.8 67.8

114.37 100.24 93.64 85.63 79.56 76.37 73.47

1.72 1.72 1.72 1.72 1.72 1.73 1,74 1.74 1.75 1.75 1.75 1.75 1,74 1.73 1.73 1.72 1.72 1.72
1.72 1.72

0.45 0.45 .45 0.44 0.44 0.44 0.44 0.44 0.45 0.46 0.49 0.52 0.55 0.57 0.58 0.58 0.57 0.54 0.52
0.51

67.96
66.51

65.35
64.48
65.5'1

70.67
75.96

-0.09 -0.26 -0.40 -0.55 -0.67 -0.75 -0.65 -0.13 0.40


1.71

89.08
106.51

3.45

121.05 131.75 137.47 137.47 132.07 121.67 107.09 98.57


91.61

4.90
5.97 6.55 6.55
6.01

4.97
3.51

2.66 1.96

0.49 0.48 0.47 0.46

83.43 79.56 76.37 73.47

114
0.76 0.44 0.15

B-12

This problem is solved in the same manner as Example 8-2. The results (conduction heat fluxes for each hour in Btu/(hr-ft2)) may be summarized in tabular form as:
Hour
1

Day

Day

0.312
0.463 0.508

2 3

4
5

0.494 0.454
0.410

6
7
B

0.387

0.402
0.473

2 1.126 0.954 0.804 0.673 0.56't 0.475 0.426 0.426 0.487

Day 3

1126
0.954 0.804 0.673
0.561

0.475

0.426
0.426 0.487

Excets from this work may be reprodued by instructors for distrrbution n a nt-for-profit basis for testing or instructional puoses only t students enrolled in courses for whih the textbook has been adpted. ny ther reproduction or trnsltion f his ork beyond h permied by Secins 07 or 08 fhe 976 Unied Stes Cpyright ct wihou the permission ofthe copyrigh oner is unlful.

140
10
11

0.612
0.820
1.089 1.399

12 13 14 15 16 17 18 19

0.620 0.825 1.092


1.401
1

0.620
0.825

1.092
1.401
1

1.715
1.998

.716

.716

1.999

2.223

1.999

20
21

2.362 2.405 2.352 2.215


2.016
1.786
1.551

2.223

2.362 2.405
2.353

2.223

2.362 2.405
2.353

2.215 2.016
1.786
1.551

22 23 24

2.215 2.016
1.786
'1.551

1.327

1.327

1.327

Because the wall is ightweight, the results converge rapidly.


8-13

This problem is soved in the Same V/ay aS the previous problem. Note that the additional insulation substantially reduces the conduction heat flux, as expected. The resuts (condution heat fuxes for each hour in Btu/(hr-ft2)) may be summarized in tabular form as:
Hour
1

Day

0.203 0.329

0.379
0.380 0.356 0.323 0.298 0.296 0.328 0.407 .535
0.711

4
5 6 7

Day 2 0.915 0.778 0.659 0.554

Day 3
0.915 0.778 0.659 0.554

0.464
0.390 0.340 0.322

0.464
0.390

0.340
0.322

I
10
11

0.344
0.417

0.344
0.417

12

0.542 0.715
0.927
.156 1.374 1.559
'1

0.542
0,715
0.927 1 .156 1.374 1.559

13 14 15 16 17 18 19

0.925

1.154 1.373
1.559
1.691

1.757

1.754
1.685

20
21

'1.685 '1.406

1.692 1.758 1.754

1.692 1.758 1.754


1.685

22

1.562 1.406

1.562

1.562 1.406

Exc-erpts from this work may be reproduced by instructors for.distribution n a not-for-profit basis for testing or instrutional purposes only to students enrolled in ourses fr which the textbook has been adopted. ny other reprdCion or rnsltion of his lork beyond th permied (Jnied Ses Cpyright c ithou thi permissn 7 he by Sections ] 07 r ] 08 f he 1 976 copyrigh ner i unlwfut'

141
23 24 1.237

1.070

1.237 1.070

1.237

1.070

8-14

The solution to this problem is similar to that of Problem 8-9, except that to estimate the maximum possible surface temperature, the surface may be assumed to be adiabatic, and U is then zero. Also, the surface-to-ground radiation coefficient is zero, and no correction is necessary for the sky temperature, as the surface is assumed to be horizontal. Assume the wind is windward, h"= 1.3 Btu/(h-ft2-F). Then, the final converged answer for the surface temperature is:
hr,sky=

1.361

Btu/(h-ft2-F)

fr"=

201.0 F

B-'15

From Table 8-2, heat gain for occupants that are "Seated, very light work" have 245 Btulhr (72 W) sensible heat gain, and '155 Btu/hr (45 W) latent heat gain. The sensible portion is assumed to be 70% radiative/ 30% convective.

The sensible heat gain from people is72 Wperson x 30 people The radiative portion is 0.7 x 2160 = 1512 he convective portion is 0'3 x2160
=
'

2160 W.

648 W.

The latent heat gain from people is 45 Wperson x 30 peoPe = 1350 W. The sensibe heat gain from lighting is '1 .5 ft2 x 4OOO sq. ft. = 6000 W; 20o/o is assumed to enter the plenum space directly, leaving 4800 W which is assumed to be 59% radiative I 41% convective. The radiative portion is 0.59 x 4800 = 2832\'t. The convective portion is 0.41 x 4800 = '1968 W.
The sensible heat gain from equipment is 1 fi( x 4OOO sq. ft. = 4O0O W, which is assumed to be 20o/o radiative I 80% convective. (Note this
xcerpts fiom this work may be reprodued by instrutrs for distribution on a nt-fbr_profit basis for testing or instrutional puoses only to students enroled in courses for which the textbook has been adopted. ny her reproductn r trnsltin of this work beynd ht permitted by Sectins l07 r 108 ofhe 976 Unied Ses Copyrigh clithoul the permission ofthe copyright wner is unlwfu.

142

assumption is based on the assumption that most of the equipment is fancooled. Students are likely to make varying assumptions.) he radiative portion is 0'2x 4000
=

800 W.

The convective porton is 0.8 x 4000 = 3200 W.


The total sensible heat gain is 2160
+

4800

4000 = 10960 W.

The radiative portion is 1512 + 2832

800 = 5144 W. 3200


=

The convective portion is 648 + 1968


The total latent heat gain is 1350 W.
8-16

5816 W.

From Table 8-2, heat gain for occupants that are involved in "Sedentary \/ork" is275 Btu/hr (81 W) sensible heat gain, and 275 Btulhr (81 W) latent heat gain. The sensible portion is assumed to be 70o/o radiative/ 30% convective.

The sensible heat gain from people is 81 Wperson x 35 people he radiative portion is 0'7 x 2835 = 1984.5 W. The convective portion is 0.3 x 2835 = 850.5 W. The latent heat gain from peope is 81 Wperson x 35 peoPle
=

2835 W.

2835 W.

he sensible heat gain from lighting is '15 \,lm2 x 75O m' = 11250 W; 50% is assumed to enter the plenum Space directly, eaving 5625 W that is assumed to be 59% radiative I 41% convective. The radiative portion is 0.59 x 5625
=

3319 W.
=

The convective portion is 0.4'l x 5625

2306 W.

The sensible heat gain from office equipment is 7000 W, which is assumed to be 20o/o radiative I 80% convective. (Note this assumption is based on
EXetS from this work may be reprduced by instrutrs for distribution on a not_for-profit basis for testing or instrutional purpses only to students enrolled in ourses fr which the textbok has been adopted' ny oher reproduction or rnscin ofhis work beyond h permitted bySectins 07 r ]08f the 976UniedSesCopyrighcy,ithouthepermissionof hecopyrighwnerisunlful.

143
the assumption that most of the equipment is fan-cooled. Students are likely to make varying assumptions.)

The radiative portion is 0.2x 7000 = 1400 W. The convective portion is 0.8 x 7000 = 5600 W.
The total sensible heat gain is 2835 + 5625 + 7000 = 15460 W.

The radiative portion is 1984.5 The convective portion is 850.5


The total latent heat gain is 2835 W.
8-17

3319 + 1400 2306 + 5600

6703.5 W. 8756.5 W.

Heat gain to the space = 0.8 x 6000 W

4800 W

Problem 8-18
At 4.00 p.m., 70 people are present. Assuming "seated, light offie \Mork", the sensible heat gain per person is245 Btu/hr (72) and the latent heat gain per person is 200 Btu/hr (59 W).

Sensible heat gain

245 Btu/hr/person x 70 people = 17150 Btu/hr.

Latent heat gain = 200 Btu/hr/person x 70 people = '14000 Btu/hr. t 6:00 p.m., no one is present; sensible and latent heat gains are O Btu/hr.

8-19

Excerpts fiom this work may be reprodued by instructrs for distribution on a not-fr_prfit basis for testing or instrutional purposes ony to students enrolled in courses for which the textbook has been adpted. ny her reproduction or trnsion of this work beyond tht permitted by Sectins 1 07 or ]08 of the 1 976 United Stes Copyright c ithout he permission of he cpyrigh ner is unlfu.

144 First, compute the properties of the corresponding fictitious surfaces, using Eqns 8-35, 8-36, 8-37. Resuts are shown in the shaded table entries,
beow.
Surface
1

Area (ft')
639.7 639.7
84.0 0.9 0.9 0.9 0.9 0.9

A-
575.8 575.8 75.6 75.6 1058.4

T(F)
122

orth roof

2 3

4
5

South roof West wall East wall ttic floor

143 102
92

70241.8 82332.6
7711.2

A--T

1983.7 1983.7 2539.4


2539;4,
1'4;47.',4'

l]f

;lF)
,

0',9
0.9 0.9 0.9 0:9

1,10.6

13.9 113,8
114.1

84.0
1176.0

6955.2
100548.0

95

128,4

hen, compute the radiant interchange factor and radiation heat transfer coefficient using Eqns. 8-38 and 8-39. Using Eqn. 8-40, estimate the radiative heat flux from each Surface (Q,.u), then determine the radiative heat transfer from each Surface (Q,"r). Then, compute the total radiative heat transfer from all surfaes = -69,769.5 Btu/hr. Divide by the total Surface area, 2623.4 ft2, to get the baancing factor, -26'6 Btu/(hr-ft'1, which must be subtracted from the previously caculated heat flux from each surface to determine the "balanced" radiation heat flux from each surface (q,rlbal). Multiply by the area to determine the radiation heat transfer from each Surface (Q,"/bal)' Chek to see that they nov Sum to zero.
Su"face
I

Fit

Trus (R)

hri

(Btu/
(hr-ft2))

Qra

Q,uo

qr"6/bal

(Btu/hQ

North roof

0.872 .897 0.897 0.832


0.872

576.0
583.1

11.4

2 3

4
5

South roof West wall East wall ttic floor

11.9
1

567.6 562.7 571.4

11.2 1.0

10.6

129.7 463.7 -132.6 -242.5 -355.3

82950.9 296624.7
-11140.0 -20368.1 -417837.0

(hr-ft')) 156.3

(Bt

Q,u6lbal (Btu/hr)

99964.1

490.3
-'106.0

313637.9
-8906.1 -18134.2

-215.9
-328.7

-386561.8

8-20 First, compute the properties of the corresponding fictitious surfaces, using Eqns 8-35, 8-36, 8-37. Results are sho\Mn in the shaded table entries, below.

Surface
1

Area
(m2)

A-
.9 108.7

T(C)
43

--
4672.9

A,

t1
0.:,9,

Ti(e)
38.3

North roof

120.7

'

372:7,

Exerpts from this work may be reprodued by instrutors for distribution on a not_for-profit basis for testing or instructional puoses only to students enro]led in courses for which the textbook has been adopted' ny other reproducin or rnslion of his ork beyond ht permited by Sectins l 07 r 08 of the 976 Unied Stes Copyrigh c withu he permission of he copyrigh olner is unlavfu.

145
2
2

4
5

South roof West wall East wall


Attic floor

120.7 18.0 18.0 216.0

0.9 0.9 0.9 0.9

108.7
16.2 16.2

194.4

50 36 38 32

5433.6
583.2

372.7
475t.:5

0.9 ,0.9
0.;9 .,9

36.0
39;6 39.5 45,3

615.6
6220.8

45.5
277.5

hen, compute the radiant interchange factor and radiation heat transfer coefficient using Eqns. 8-38 and 8-39. Using Eqn. 8-40, estimate the radiative heat flux from each Surface (9,"r), then determine the radiative heat transfer from each Surface (Q,"). Then, compute the total radiative heat transfer from all surfaces = -3027.9 W. Divide by the total surface area, 493.5 m2, to get the balancing factor, -6.1 Wmz, which must be subtracted from the previously calculated heat flux from each surface to determine the "balanced" radiation heat flux from each surface (q,u6lbal). Multiply by the area to determine the radiation heat transfer from each surface (Q,"/bal). Check to see that they no\M Sum to zero.
Surface
1

Fir

Tuus (K)

hrt

(Wm'\
^

Qra

Q,"o

(il4

qru6/ba

(Wm')
34.8 93.4 -15.8 -3.2
-70.1

Q,,/bal

2
J

4 5

North roof South roof West wall East wall Attic floor

0.872

0.897
0.897 0.835

0.872

313.8 316.2 310.9


31 1.9

6.'1

b_J
6.1

28.6 87.2 -22.0


-9.4

6.2

31 1.8

57

-76.2

3459.0 10534.5 -395.4 -168.4 -16457.6

(w) 4199.9 -285.0

11275.4 -58.0 -15132.3

8-21

The solution procedure is identica to that of Problem 8-19, except the emissivities for surfaces 1 and 2 are 0.1. Fictitious surface properties are shown in the first table.
1

J
4
5

Surface Area (ft') North roof 639.7 South rool 639.7 West wall 84.0 East wall 84.0
Atti floor 1176.0

0.1 0.1

64.0 64.0
75.6 75.6 1058.4

A-

T(F)
122

A--T
7804.6 9148.1 7711.2

At 1983.7
1983:7,

:1

T^,(F)

0.9 0.9 0.9

143 102
92

0.6 .6

2539;4

0'5 t 0,2
.5

6955.2
100548.0

2539.4
14:47.'.4

97.6 96.6 98.6 99.2


11'3.3

he total radiative heat transfer from a|l surfaces = -3476.1 Btu/hr. The balancing factor is -1. 3 Btu/(hr-ft2).

Surface

Fir

*s (R)

hri

(Btu/

9rao

(Btu/hr)

Q,r

Qrr/bal

(Btu/

Q,,a/bal (Btu/hr)

Excets from this work may be reproduced by instrutors for distributin on a not-for-profit basis for tsting or instructional puoses only t students enrolled in courses or which the textbook has been adpted. ny other reprducion or rnslion of his ork beyond thc pemitted by Secions ]07 or ]08 fhe 976 Unied Ses Copyright ctihut the permission ofhe cpyrigh wner is unlcrful.

146
(hr-ft'))
1

(hr-ft'))

North roof

0.098
0.098

2 3

4
5

South rooi West wall ast wall Attic floor

0.874
0.874
0.222

569.5 579.5

1.2
1.3

560'
555.3 563.8

10.5 10.3 2.7

30.3 60.8 35.5


-74.1

19378.4

31.6
62.1

38903.3
2984.3 -6220.9 -58521.2

-49.8

36.9 -72.7 -48.4

20226.0 39751.0 3095.6 -6109.6


-56963.0

Note that the radiative heat fluxes from surfaces 1 and 2, and to surface 5 are significantly lower. (The heat flux incident on surface 5 has been reduced by s5%.) he catch is that "in real life", everything else does not remain the same. ln particular, the temperatures would change significantly.

8-22 The solution procedure is identical to that of Problem 8-20, except the emissivities for surfaces 1 and 2 are 0.1. Fictitious surface properties are shown in the first table.
Surface
1

Area
(m2)

A-
0.1 0.1 12.1 12.1

r(c)
43 50

A--T
519.2 603.7 583.2

,
372'7'
372,7 .475.5
,475,,5'

',

T(c)
33;6
,,33.9 41.1

North roof

2
J

4 5

South roof West wal East wall Attic floor

120.7 120.7 18.0 18.0

.6

0'6
0,5 0.5
o'.2

33'2

0.9

0.9
0.9

16.2 16.2

Jb
38 32

615.6
6220.8

33,8

216.0

194.4

277,,5

The total radiative heat transfer from all surfaces = -341.5 W. The balancing factor is -0.7 Wm2.
Surface
1

Fy

Trrs (K) 311.4 314.8


308.1

hrl

/Wm')
^

9ra

Q," (h4

qru6/bal

(Wm')
7.0 12.3
12.8

Q.,a/bal

(w)

North roof

J
4
5

South roof West wall East wall Attic floor

0.098 0.098
0.870 0.870
0.241

309.0 309.7

0.7 0.7 5.8 5.8


1.6

117
12.1

6.3

765.2
1407.1

848.7 1490.7

217.6
443.7 -3175.0

230.0
456.1

24.6
-14.7

25,3
-14.0

-3025.6

8-23

Exerpts frm this wrk may be reproduced by instrutors 1br distribution on a not_for-prfit basis for testing or instructional puoses ny to students enolled in courses for which the textbook has been adopted. ny lher reprducin or rnslion f his ork beyond h permilted by Sections ] 07 or 1 08 f the 976 Unied Stes Copyrigh ct thout the permissin ofhe copyright ner is unful.

147

Convective heat transfer coefficients are determined from Table 8-8. Coefficients for the pitched roof surfaces are based on the "Sloping - 45 degrees" surface position. more sophisticated approach would involve interpolation. The resuts are summarized below.
Surface
1

Area

(ft2)

(F)
122

North roof

639.7
639.7 84.0 84.0 1 176.

2 3 4 5

South roof West wall East wall Attic floor

143 102
92 95

Surface Position Sloping 45 deqrees Sloping 45 derees Vertical Veftical Horizontal

Direction of

Heat Flow

h" Btu/(hr-ft2-F)

(Btu/(hr-ft"))

9""onu""tion

Downward Downward

o.42 0.42 0.56 0.56 0.18

15.54

24.36
9.52 3.92 1.80

Horizontal Horizontal
Downward

8-24

Convective heat transfer coefficients are determined from Table 8-8. Coefficients for the pitched roof surfaces are based on the "Sloping - 45 degrees" surface position. A more sophisticated approach \Mould involve interpolation. The results are Summarzed below.
Surface
1

Area

(m2)

r(c)
43 50 36 38 32

orth roof

120.7 120.7 18.0 18.0 216.0

2
J

South roof West wall ast wall Attic floor

4
5

Surface Position Sloping 45 deqrees Sloping 45 deqrees Vertical Vertical Horizontal

Direction of Heat Flow


Downward Downward

(wm2-K)
2.39 2.39
3.18 3.18 1.02

hc

Qt'"onu""1on

r//m')

33.46
50.1 9

Horizontal Horizontal
Downward

22.26
28.62 3.06

B-25
Excets from this wrk may be reprodued by instructors for distribution on a not-or-profit basis for testing or instructional puoses only to students enrolled in ourses for which the textbook has been adopted. ny ther reprducin or rnsion of his wrk beyond ht permtted by Sectins ]07 r ]08 fthe 976 United Stes Copyrigh cll,ihout he pemission ofhe copyrigh lner is unlcrful.

r_
148 First, the solar irradiation on the window is obtained in the same manner as the solution for Problem 7-17. The following tables show results for the west-facing window.

Longitude 101.7 deg deg Standard Meridian 90 -6.2 min Eo Latitude 35.23 deg Declination 20.6 deg 270 deg Surf zimuth deg 90 Surf Tilt A 346.4 Btu/hr-ft2 0.186 B 0.138 c cN1 RHOG 0.2
Output Data

lnput Data

cDSr Lsr

o , " G," Go* Ga* Gr* " , , " , " 15.00 13.12 16.75 69.25 229.59 40.41 74.35 283.92 76.59 27.06 30.47
h,

G,*

134.12

The layer absorptances of the double-pane (lD5a) can be found from able 7-3 as:
GDirect,outer: 7f ,774 dg)
Direct,inner

\Mindo\/

v/ith '1l8 in. sheet glass

:'dr(7 4deg)

: O.13 : 0.06

(diffuse,outer:
aciffuse'inne,

.fiyarn_ 0.11
.fz'aixur,

0.07

Then, the solar radiation absorbed by each pane of the double-pane window may be determined by (neglecting incident solar radiation from the
inside):
Q"itob,o,b,d,outer,

j,:

Q"itob,o,b,d,n*',,"

0.13(76.5g) + O.11(57.53) : 16.29 tu/(hr_ft^2) :0.06(76.5g) + 0.07(57.53) : 8.62tl(hr-ft2) i,

8-26
Exets 1iom this work may be reproduced by instrutors for distribution on a not-for-profit basis for testing or instructional puoses only to students nrolled in courses for which the textbook has been adopted. ny oher reproducion or trnstion f this ''ork beyond ht permited by Secions ]07 r ]08 ofthe 976 (Jnied SteS Cpyright cwithu he permissin fhe copyrigh owner is unlful.

149
First, the solar irradiation on the window is obtained in the same manner as the solution for Problem 7-17 ' he following tables show results for the west-facing window.

Longitude 108.53 deg deg Standard Meridian 105 -6.2 min EOT 45.8 deg Latitude Declination 20.6 deg 270 deg Surf zimuth deg 90 Surf ilt 346.4 Btu/hr-ft2 A 0.186 B 0.138 c cN1 0.2 RHOG
Output Data

lnput Data

MDST LSr h, " ,' , o , o Grvo* G" Gd* G* ,' 15.00 13.66 24.92 57.57 227.35 42.65 66.77 277.89 109.60 29.57 27.29 The layer absorptances of the double-pane (lD5a) can be found from Table 7-3 as:
&Direct,outer:

Gt*

166.46

\/indo\M \/ith

1/8 in. sheet glass

.ir(67 deg) : 0.L27

aDirect,inner: 7t1167 deg)

: 0.073

ddffise'outer:
c]iffuse,inner:

-f,a1urr: 0.11 .lz,ar, : 0.07

hen, the Solar radiation absorbed by each pane of the double-pane window may be determined by (neglecting incident solar radiation from the
inside):
Q"
it ob,o,bnd,outer'

Q"t ob,o,bud,inner,

j, : 0.27 (|0g.6) + 0. 1 1 (56.s6) j, : 0.073(109.6) + 0.07(56.86)

: :

20.1 7

Btu/(hr-ft2) 1 1.98 Btu/(hr-ft2)

8-27

RsULTs BY ts D UsG T}*| VCXpLORR pRBR AR l-{lcl-lR -.| R$UL$ Y f; RS ETl*iD


Usl G l-t spRD$*| H. 8-28
xcerpts ftom this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional puoses ony to permied students enrolled in ourses or which the textbook has been adopted. ny ther reprducin or rnsltin f his ork beyond th by Secions ] 07 or 1 08 of he 976 United Stes Cpyrilht ct without the permissin ofthe cpyright oner is unful.

150

The RTS method is used to obtain the cooling load results for this problem. The following table shows total cooling loads and cooling loads due to window heaigains for both low-e and regular double-pane windo\/S' l cooling loads due to other heat gains are the same as those shown in Example 8-16.
(from ExamPle 8-16) Window Window Total

Low-E Windows

Regular Windows
Windw Conduction
(Btu,&r)

Hour

Window

Condution (Btu,hr)
1

SG
364

(Btu,&r)

(Btu/hr)

SG
420
345

(Btu,4lr)

(BtuAr) 4516
3921

Total

186

2
2

146
110 79 58 52
61

299 246

4418 3843
3352

228 179
135 97 72 63 75

284
234
193 159

4
5

203
167

2940
2623

3414 2989

2662
2452

6
7 8 9

tJo 254
465

2419 2465
2737
8'190

293
537

92

145

710
978
1247

10
11

215
300
389

9562
1

toc
JOO

112 178

2518 2829
8333
9761 11141

820 1129
1437 1720
1

12

1492
1694 1 833 1897
188'1

13 14 15 16
17 1B

469
533 577 593

0883 12143 13275

14250
1 1

477 574 654


707 726 717

12458
I

951

3637

2111

585
553 503

1787

1624
139'1
1

5007 5486 15701 1 0635

2185
2167 2060
1

14648 15425
1

19

20
21

444 386
327

089 839

22 23 24

674
546

9550 8460 7477 6588


5777 5057

677 616 544 472


401 336

873

'1604

1256
968 777

5905 16105 11008 9877 8727

7692
6765 5922 5176

274 228

629
513

445

279

As shown in the above table, usng the regular \indo\ Would resut in slighily higher cooling loads than using the low-e window. The following 'hcrease in cooling loads due to changing the type of figure illustrates the
w]ndow from the low-e window to the reguar window.

puoses ony to on a not-for_profit basis fr testing or instrutional Excets from this work may be reprodued by instrutors for dlstributin or rnsltionf hs ork beynd th permited ny olher reprodc'ilon students enrolled in courses tbr which the textbook has been "p" permission ofhe copyrigh wner is unlwful' ]07 or 108 ofhe 976 Unied Stes Copyright ctithout th
by Sections

151

Cooling Load Comparison


18000
'15000

d
o
cr)

12000 9000 6000 3000 0

o o )

't0 '13
Tirne, Hour

'16

8-29
Soluton to be provided by an instructor. 8-30 First, the solar irradiation must be determined and is the same as that shown for Problem 8-10. hen, the hourly dry bulb temperature is calculated using quation 8-2. Here, the hour nearest to the local solar time has been used to determine the temperature. Finally, the sol-air temperature is calculated using quation 8-63 with the therma radiation correction term being zero for a vertical surface.

Local lnsolation Outdoor Solar (Btu/h- Drybutb Clock Time Time ft2) emp (F) 1.00 23.79 0.00 75.2 2.00 0.79 0.00 73.9 3.00 1.79 0.00 72.6 4.00 2.79 0.00 71.6 5.00 3.79 0.00 70.9 6.00 4.79 0.00 70.6

Sol-air Temp
(F)

75.2 73.9 72.6 71.6 70.9 70.6

Excets from this work may be reprodued by instrutors for distribution on a not-for-profit basis fr testing or instrutional puoses only to students enrolled in courses flr whih the ttbook has been adopted. ny oher reprduction or tr.nsltion f this ork beyond ih permied by Sectins ] 07 or ] 08 of the 1 976 tJnited Sttes Copyright ct y'ihou the pemission of he copyright ner ii untwful.

152
7.00 8.00 9.00 10.00
1

5.79

9.93

71.1

73.1

6.79
7.79 8.79 9.79 10.79 11.79 12.79 13.79 14.79 15.79 16.79 17.79 18.79 19.79

23.08
32.24 39.29 44.53 47.91 52.42
111 .11

72.4 74.7 78.0


8'1.8
86.'1

77.0
81 .1

1.00

12.00 13.00 14.00 15.00 16.00


'17.00 '18.00

178.01

230.32 259.13

252.42
184.97
6.'10

19.00 20.00

90.2 93.2 95.2 96.0 95.2 93.5 90.7 87.4


84.1

85.8 90.7 95.7 100.6 115.4 130.8


142.1 147.1

143.9 127.7 88.6


84.1

21.00 22.00 23.00


24.00

20.79 21.79 22.79

0.00 0.00 0.0 0.00

81.3 78.7 76.7

81.3 78.7 76.7

8-31

This problem uses the same solution procedure as Problem 8-30. Note that the solar irradiation is the same as that shown for Problem 8-1 1.
Clock
Time
1.00 2.00 3.00

Local Time
0.1 5

Solar
23.15 1.15

(Btu/h-ft2) Temp

nsolation

Outdoor
Drybulb
(F)

4.00
5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00
14.00

2.15
3.15

4.15
5.15

6.15
7.15
8.1 5

15.00 '!6.00 17.00 18.00 19.0

9.15 10.15 11.15 12.15 1 3.15 14.15


15.'1 5

16.15 17.15 19.15

20.00 21.00
22.00

'18.15

20.15

0.00 0.00 0.00 0.00 0.00 0.00 3.96 17.83 29.69 62.38 107.15 142.58 164.39 170.24 159.50 133.31 94.57 48.18 26.46 14.28 0.32 0.00

Sol-air Temp (F)


73.0 71.2

73.0 71.2

69.6
68.1

69.6
68.1

66.9
66.0 65.7 66.3 67.8 70.5 74.5 79.0 84.2 89.0 92.7
95.1

66.9 66.0 66.3 69.0 72.3 79.9 90.6 100.4 108.8 114.6 1 16.6
115.1

96.0
95.1

93.0 89.6 85.7 81.8

110.2 102.3 96.9 91.8 85.7 81.8

Exerpts from this work may be reprodued by instrutrs for distributin n a not-for-profit basis for testing or instrutional puoses only to students enrolled in ourses or which the textbook has been adopted. ny other reproduction r rnstion of his ork beyond th permied by Sectins ] 07 r ] 08 f he 97 6 Unied Stes Copyright ct ithou the permission of the cpyright oner is unfu.

153
23.00

24.00

21.15 22.15

0.00 0.00

78.4 75.4

78.4 75.4

8-32 This problem uses the simiar Solution procedure as Problem 8-3O. First, the solar irradiation is determined for the flat roof using the procedure described in Chapter 7. The resuts are shown below.
nput Data

Longitude Standard Meridian

EOT
Latitude

Declination
Surf Azimuth Surf ilt

Apar
Bpar

106.62 105 -6.2 35.05 20.6 0 0


346.4
1

deg deg min deg deg deg deg

Btu/hr-ft2

Cpar CN RHOG

86 0.1 38
0.1

0.2

Output Data

o MDST Lsr h, o ,. , " , 1.00 23.79 176.83 -34.27 356.41 356.41 2.00 0.79 -168.17 -33.23 13.26 13.26 3.00 1 .79 -153.17 -28.80 28.82 28.82 4.00 2.79 -138.17 -21.65 42.20 42.20 5.00 3.79 -123.17 -12.54 53.39 53.39
4.79 -108.17 -2.11 5.79 -93.17 9.'19 6.79 -78.17 21.05 7.79 -63.17 33.22 10.00 8.79 -48.17 45.49 1.00 9.79 -33.17 57 51
1

Gruo* Go* G* G*

Gt*

6.00 7.00 8.00 9.00

12.00 10.79 -18.17 15.00 16.00 17.00 18.00 19.00 20.00


21

11.79 -3.17 14.00 12.79 11.83


'13.00

22.00 20.79 131.83 23.00 21.79 146.83

.00 19.79 16.B3


1

26.83 41.83 56.83 71.83 17 .79 86.83 18.79 101 .83


13.79 14.79 15.79 16.79

68.46 75.28 72.19 62.36


50.63
38.41

127.34 168.24 218.87 245.60 259.78 269.56


277

79.02 79.02 68.95 206.38 74.12 86.89 86.89 56.78 246.69 135.17 95.77 95.77 44.51 266.87 190.31 107.55 107 .55 32.49 277 .85 234.37
21.54 283.62 263.81 14.72 285.80 276.42 17.81 284.93 271.28 27.64 280.80 248.75 39.37 272.32 210'52 51.59 256.78 159.55 277 '71 63.83 227 .20 10.20 285.45 75.85 '161.85 39.s6 293.49 87.42 5.53 0.25 302.43 98.27 0.00 0.00 312.83 108.00 0.00 0.00 325.24 116.06 0.00 0.00
127.34 168.24 218.87 245.60 259.78 269.56

0.00 0.00 0.00 0.00 0.00 62'87 62'87 92'11 0.00 71 .22 71.22 80.81 108.07
124.27 123.23 1 18.80 111.65 102.54

0.00 0.00 0.00 0.00 0.00 0.00 17 .26

26.17 14.15

2.58
-8.27 -'18.00

-26.06

285.45 293.49 302.43 312.83 325.24

'71

14.91 28.48 34.04 36.83 38.34 39.14 39.44 39.32 38.75 37.58 35.44

0.00 0.00 0.00 0.00 0.00 0.00

22.33

31

.35

0.76 0.00 0.00 0.00

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.0 0.00 0.00 32.17 0.00 102.60 0.00 169.21 0.00 227.14 0.00 272.71 0.00 302.95 0.00 315.86 0.00 310.60 0.00 287.50 0.0 248'10 0.00 194.98 0.00 131 .56 0.00 61.90 0.00 1.01 0.00 0.00 0.00 0.00 0.00 0.00

Excerpts from this work may be reproduced by instrutors for distribution on a not-fbr-profit basis 1br testing or instrutional puoses only to students enolled in courses or which the textbook has been adopted. ny other reprducin or trnslion f his work beynd ht permited by Secions ]07 r 08 of he 976 Unied Sttes Cpyright c1.ithut he permission f the copyrigh oner is unll.

154
*Unit of lrradiation is tu/hr-ft2

24.00 22.79 161.83 -31.74 339.93 339.93 121.74

0.00

0.00

0.00

0.00

0.00

Then, the sol-air temperature is determined using Equation 8-63 with the thermal radiation corretion term being 7 "F for a horizontal surface.

Clock Time
1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.0 9.00 10.00 11.00 12.00 13.0 14.00 15.0 16.00 17.00 18.00 19.00 20.00 21.00 22.00 23.00 24.00

Local Solar Time 23.79 0.79 1.79 2.79 3.79 4.79 5.79 6.79 7.79 8.79 9.79 10.79 11.79 12.79 13.79 14.79 15.79 16.79 17.79 18.79 19,79 20.79 21.79 22.79

lnsolation
(Btu/htt2) 0.00 0.0 0.00 0.00 0.00 0.00 32.17 102.60
169.21

227.14
272.71

302.95 315.86 310.6 287.50 248.10


194.98 131.56

61.90
1

.01

0.00 0.00 0.00 0.00

Outdoor Drybulb emp (F) 75.2 73.9 72.6 71.6 70.9 70.6 71 .1 72.4 74.7 78.0 81.8 86.1 90.2 93.2 95.2 96.0 95.2 93.5 90.7 87.4 84.1 81.3 78.7 76.7

Sol-air Temp
(F)

68.2

66.9 65.6
64.6

63.9 63.6
70.5 85.9 101.5 116.4 129.3 139.7 146.3 148.3 145.7 138.6 127.2 112.8 96.0 80.6
77.1

74.3 71.7 69.7

8-33

For hour 15, Equation 8-64 is used to find the conduction heat flux.
Q"conduction

= .0052 x (151 '2-74) + .001 44 x (138'1-74)

.00645 x (120.3-74)...

2.897 Btu/(hr-ft2)

Excrpts from this work may be reprodued by instrutors for distributin on a not-for-profit basis for testing or instrutional purposes only t students enrlled in courses for whih the textbok has been adopted. ny ther reprducion or rnslin of his ork beyond th permed by Secins 107 r 108 ofthe 976 (Jnied SeS Copyrigh c|)ihou the permission ofhe cpyright oner is unlful.

155 8-34

Equation 8-64 is used to find the conduction heat flux for each hour.
Hour
1

q" (Btu/(hrft2))

Hour
13

q" (Btu/(hrft2))

1.835

0.828 0.798

1.824
1.772 1.693 1.595 1.486
1.372

14
15

J
4 5

0.791
0.810
0.861

16 17
'18

6
7

0.948
1

19

.071

1.259 1.149
1.047 0.956 0.882

20
21

1.225 1.396 1.563

10
11

22 23 24

1.704
1.797

12

8-35

For hour 12, qation 8-64 is used to find the conduction heat flux.
Q"conduction

= 0.0061 92

x (143.9-72) + 0.044510 x 0.047321 x (1 21 .4-72)...


7

(1

34.3-72)

.028 Btu/(hr-ft2)

8-36 Equation 8-64 is used to find the conduction heat fux for each hour.
q" (Btu/(hrft2)) q" (Btu/(hr-

our
1

Hour
13 14 15 16

ft2))

0.674 0.401
0.1

1.050

1.544

3 4

99

2.012 2.409

0.051

Excets from this work may be reproduced by instrutrs for distribution on a not-for-profit basis for testing or instructional purposes only to students enolled in ourses fr which the textbook has been adopted. ny oher reprclucn or trnsnf hs work beyond iht pemiect by Sections 07 or ] 08 f he 1 97 6 tJnited SeS Cpyrigh c 4,ithout the permission f the copyrigh oner i unlwful.

156
5

-0.058 -0.138 -0.197


-0.232

17 18 19

2.694
2.841

6
7

2.834
2.671 2.361
1.936 1.466
1.031

8
9 10
11

20
21

-0.209 -0.075

22

0.194
0.583

23
24

12

8-37

Equation 8-64 is used to find the conduction heat flux for each hour with so-air temperatures calculated in Problem 8-31.
q" (Btu/(hrft2)) q" (Btu/(hrft2))

Hour
1

Hour
13
14

3.492
3.147

-0.055
0.1

2 3 4 5

65

2.758 2.348
1.937 1.536

15 16

0.563

1.112
1.754 2.417 3.026 3.510 3.823 3.958
3.931

17
18 19

6 7

1.154
0.796 0.472
0.1

I
9

20
21

10
11

99

22 23

0.00 -0.098

12

24

3.765

8-38

Using the simplified approach, the solution procedure is the same as that of Probem 7-27. First, we need to know ange of incidence and Solar irradiation. ssuming a west-facing window, the incidence angle and solar rradiation for Albuquerque, NM on a c|ear July 21 day at 3:OO pm solar time are (see solution in Problem 8-10 for reference)

Angle of lncidence = 65.0 deg., Direct Solar lrradiation. G = 1 18.6 Btu/hr-ft2,


Exerpts from this work may be reproduced by instructors for distribution on a not-fr-profit basis for testing or instructiona purposes ony to

studentsenrolledincoursesforwhichthetextbookhasbeenadopted. nyotherreprdicionrrnstion1hsorkbeyoidihpermied by Secions ]07 or 108 of he 976 United Ses Cowrigh c withu thb permissn of the copyrigh oner ii unlful.

157

Diffuse Solar lrradiation: Ga a G = 30.6 + 28.9 = 59'4 Btu/hr-ft2 Then, the area of the glazing and of the frame is calculated to be 27 .2 and 4.8 ftz, respectively.
ft2

From Table 7-3, solar heat gain coefficients for the glazing system lD 5b are SHGG9(65") = 0.515 and SHGGs = 0.60. From able 5-2, the outside surface conductance may be estimated to be 4.0 Btu/hr-ft2-'F. From Table 5-6, the U-value for the fixed, double glazed window having aluminum-clad wood/vinyl frame with insulated spacers is 0.48 Btu/hr-ft2-"F. From able 7-1, solar absorptance of the vinyl frame painted white is 0.26.

ssuming the window with no setback (Ar,r'" = frame can be calculated using Eq. 7-31 as: SHGG1= 0.26*(0.4814.0)
= 0.031.

Asu),

the SHGC for the

For an unshaded window, the total solar heat gain is calculated using Eq. 7 -32 as
Qsc = (0.51 5*27 '2 + 0.031-4.8)-'1 '18.6 + (0.60-27 '2 + 0.031*4.8)*59.4 = 2657 '2

Btlhr'

B-39

This problem uses the same solution procedure as the previous problem. Assuming a south-facing window, the incidence angle and solar irradiation for Boise, ]D on a clear Jly 21 day at 3:00 pm solar time are (see solution in Problem 8-1 '1 for reference) Angle of lncidence' = 68.8 deg., Direct Solar lrradiation: G = 101.6 Btu/hr-ft2, Diffuse Solar lrradiation: Ga + G = 29'0 + 28.9 = 57 '9 Btu/hr-ft2, and
Exets from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional puoses only to students enro11ed in courses for hich the textbook has been adopted. ny oher reproducion or rnslion of his work beynd h permitted by Secions ]07 r ]08 fthe 976 Unied Ses Copyright cwihout he permissin fthe copyrigh o'ner is unlfu.

'158

The area of the glazing and of the frame is the same as that calculated in Problem 8-38. From Table 7-3, solar heat gain coefficients for the glazing system lD 29a are SHGG,(68.8") = 0'408 and SHGGs= 0.57. From Table 5-6, the U-value for the fixed, triple glazed window having aluminum-clad wood/vinyl frame with insulated spacers is 0.44 Btu/hr-ft2-"F. The outside surface conductance and solar absorptance of the frame are assumed to be the same as those in Problem 8-38.

Assuming the window with no setback (Ar,u'" = frame can be calculated using Eq. 7-3'1 as: SHGGr = 0.26*(0 .4414.0)
= 0.029.

Asu),

the SHGC for the

For an unshaded window, the total solar heat gain is calculated using Eq. 7-32 as.
Qsuc = '408-27 '2 + 0.029-4.8)*101.6 + (0.57*27.2 + 0.029*4.8)-57.9 = 2047.4 Btu/hr.

8-40

First, determine conduction heat gain by multiplying fluxes from Problem 833 by the surface area, 8OO ft2. Then, from Table 8-20, select the radiative/convective split to be 63%137o/o Apply the split to determine the convective and radiative heat gains. Then, apply Equation 8-67 to the radiative heat gains to determine the radiative cooling load. Sum the radiative cooling load and the convective heat gain to get the cooling load.

Excerpts rom this work may be reprodued by instructors fr distribution on a not-for-profit basis for testing or instrutional purposes only to students enrolled in courses for whih the textbook has been adopted. ny other reproducion or rnstion f this ork beyond ht permied by Secions ] 07 or ] 08 of he 976 United SteS Cpyrigh c ithut he permissin of the copyright owner is unlful.

'159
Conduction Heat Gain
(Btu/h0 5462.3

Hour
1

Convective

HG

Radiative

HG

Radiative Cooling Load


2903.7 2813.1

Cooling Load 4924.7


4625.9 4306.7 3987.7

2021.0
1812.8 1603.8 1404.7 1221 2 1056.0 910.4

3441.2

2 3 4
5

4899.6
4334.5 3796.4 3300.5 2854.1 2460.6

386.7
2730.7 2391.7 2079.3
1798.1

2702.9
2583.0 2460.2

b
7 8 9

2123.8
1854.2 1673.6 1598.0 1629.0 1759.4 1983.0

785.8
686.1 619.2 591.3 602.7

10
11

12

13 14 15 16 17 18 19

2318.0
2803.7 3450.5 4215.9 5016.0 5741.3

651.0 733.7 857.6


1037.4 1276.7 1559.9 1855.9

1550.2 1338.0 1168.2 1054.4 1006.7 1026.3 1 108.4 1249.3 1460.3 1766.3

2339.0 2222.4
2113.0 2014.0
'1930.6

3681.4 3395.0
3132.9

2898.9
2700.1 2549.9

1868.0 1829.3
'1815.8

2459.2
2432.1 2466.8 2561.5

2173.8 2656.0
3160.1

1827.8 1868.9 1947.4 2068.9

2726.6 2984.8 3345.5


3790.2

2230.3
2419.2 2614.7 2789.4 2913.3 2969.4 2961.2

4275.2
4739.0

20
21

2124.3
23'18.6

3617.0
3947.9 4078.5 3997.4
376'1.9

22
ZC

6266.5 6473.8
6345.1 5971.2

24

2395.3 2347.7 2209.4

5108.0 5308.6
5317.1

5170.6

Cooling Loads and Heat Gains


700.0 600.0
5000.0

4000.0
3000.0 2000.0
1

6)

000.0
0.0

Exets fiom this work may be reprdued by instructors for distributron on a not-fr-profit basis fr testing or instrutional puoses only to students enroled in ourses for which the textbok has been adopted. ny her reprductin or trnstion of this work beyond h permitted by Secions ] 07 r ] 08 of he 976 Lnied Sates Copyright c ithout he permission of he copyrigh lner is unlcrful.

16

8-41

First, determine conduction heat gain by multiplying fluxes from Problem 835 by the surface area, 1OOO ft2. Then, from able 8-20, select the radiative/convective split to be 84ol16o/o' Apply the split to determine the convective and radiative heat gains. Then, apply quation 8-67 to the radiative heat gains to determine the radiative cooling load. Sum the radiative cooling load and the convective heat gain to get the cooling load.
Radiative Cooling Load
4864.4

Hour
1

Conduction eat Gain


(Btuihr)

Convective

HG

Radiative

HG

Cooling Load
5220.7

2227.2
1338.2

356.4
214.1 100.4 9.2 -63.6 119.4 -149.7 -97.7 81.2 370.2 730.7 1124.5 1512.8 1857.6

1870.8
1124.1

2
J

627.7
57.3 -397.4 -746.0 -935.8 -610.8 507.2

4
5 6
7

o 9

527.3 48.2 -333.8 -626.7 -786.0 -513.1


426.1

4530.5 4222.8
3938.6 3676.2 3436.0 3228.9 3120.5 3179.7
3417.1

4744.6
4323.2 3947.7 3612.7 3316.7 3079.2

3022.8
3260.8 3787.2

10
11

2313.5
4567.1

12 13 14 15 16 17
'18

7028.4 9455.0
1169.7 13293.3 1 4350.1 14672.7 14222.5 1318.3 11142.9 8809.6 6593.1

19

2126.9 2296.0 2347.6 2275.6 2082.9


1782.9
1

1943.3 3836.3 5903.8 7942.2 9752.2 I 1 166.3


12054.1 12325.1
I

3808.3

4316.0 4893.4
5486.8 6042.8
651 1.5

4539.0 5440.6
6406.2

7344.4
8169.7 8807.6 9197.1 9300.4 9101.0 8607.3 7877.0 7097.7

20
21

409.5

1946.9 1935.4 9360.0 7400.1

6849.5 7024.8
7018.0 6824.5

6467.5
6042.8 5622.2 5228.0

22

154.9

s538.2
4017.6

z3
24

4782.8
3353.'1

765.3
536.5

6387.5
5764.5

2816.6

or instructional puoses only to Excts frm this work may be reprdued by instructors for distribution n a not-for-profit basis for testing permitted or trnsCion of thS work beyond ht students eno]led in courses for which the textbook has been adopted. ny oher reprducion fthe 976 Unied Sttes Copyrigh ctwihout he permission fhe cpyright oner is unlwful.

s;"i'n'

]07 r ]08

161
cooling Loads and eat Gains
1

6000.0 4000.0 2000.0

fl

'10000.0

(,
(! !

(!

8000.0

--r-- Conduction Heat Gain


(Btu/h0

6000.0

-*x* Cooling Load

911131517192123

8-42
First, determine conduction heat gain by multiplying fuxes from Problem 836 by the surface area, 1200 ft2 ' Ther , from able 8-2o, seect the radiative/convective Split to be 84oe% pply the split to determine the convective and radiative heat gains. Then, apply Equation 8-67 to the radiative heat gains to determine the radiative cooling load. Sum the radiative cooling load and the convective heat gain to get the cooling load.
Conduction Hour
1

Heat Gain (Btl/hr) 809.2 481.0

Convective

HG

Radiative G
679.7
404.1

Radiative Cooling Load


1

Cooling Load
1332.4 1182.3 1056.5
951.1

129.5

2
3

77.0
38.2 9.8
11 .1

238.5
61.2 -69.3

4
5

200.4 51.4
-58.2

6
7 o

-166.0
-237.0 -278.7 -250.9 -90.4

I
10
11

233.3
700.2

12

-26.6 -37.9 -44.6 -40.2 -14.5 37.3 112.0

-139.5 -199.0
-234.1

-210.8 -75.9 196,0 588.2

1203.0 105.3 1018.3 941.3 872.8 811.4 756.2 707.9 674.0 667.9

861.7 784.9 718.3

663.3 633.8 653.4


737.1

699.7
771.3

883.3

Excerpts rom this work may be reprodued by instructrs for distribution on a not_for_profit basis for testing or instrutional puoses only to students enrolled in ourses for which the textbook has been adopted. ny other reproducion or trnslion of this work beynd ht permited by Secions 107 r 108 ofthe 976 United Sttes Copyright cithut the permissin ofthe copyrigh oner is unlcrwful.

162
13
14

15
16 17

1260.3 1852.6 2414.9

201.6
296.4

386.4
462.5 517.3

1058.6 1556.2 2028.5

877.1

2890.5 3233.3
3409.7 3401.3

2428.0 2716.0
2864.2 2857.1 2692.2 2380.2
1951 .6

18 19

545.6
544.2 512.8 453.4 371.7

20
21

22 23 24

3205.0 2833.6 2323.3


1759.4 1237.6

281.5
198.0

1477.9 1039.6

1007.4 1149.7 1290.4 1416.6 1516.5 1580.7 1602.7 1579.7 1513.7 1417.5 1309.3

1078.8 1303.8
1

536.1

1752.9 1933.9

2062.0 2124.9
2115.5

2033.0
1885.5 1699.0 1507.3

Gooling Loads and Heat Gains


4000.0
3500.0 3000.0
t

2500.0 2000.0 1500.0


'1000.0 _--_ Condution Heat Gain

(Btu/hr)
*__*

Cooling Load

c
l1

500.0 0.0 -500.0

8-43

First, the hourly Soar heat gains are determined using the same solution procedure Sho1/n in Problem 8-38. The results are Sho\/n below. Note that the Sola irradiation on the window is the Same aS that shown in Problem 8-10. Also, note that the calculated Soar gain at 3:00 p.m. is slightly different from that shown in Problem 8-38 due to rounding errors.
lnput Data

Glass Area Frame rea

27.2 4.8

ft',
ft2

Excerpts from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instructional purposes nly to students enrolled in courses for whih th textbok has been adopted. ny her reproducin or rfiSlin of this work beyond th permied by Secions ]07 r ]08 ofthe 97 i United Sttes Copyrgh ct wihout the permission fhe copyright oner is unwfu.

163
Diffuse SHGC Angular SHGC - 0' Angular SHGC - 40' Angular SHGC - 50' Angular SHGC - 60" Angular SHGC - 70" ngular SHGc - 80" Frame sGc
0.6 0.7 0.67 0.64 0.58 0.45 0.23
0.03'1

Clock
Time
1.00

2.00 3.00

4.00
5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14,00 15.00 16.00 17.00 18.0 19.00

20.00 21.00 22.00


23.00 24.00

lnc. ngle, ' 87.03 101 .06 114.99 128.63 141.58 152.80 159.17 156.37 146.65 134.23 120.81 106.97 92.97 78.94 65.01 51.37 38.42 27.20 20.83 23.63 33.35 45.77 59.19 73.03

Dir

Btu/hr-ft2 0.00 0.0 0.00 0.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.68 18.63 170.01 201.20 202.07 151.27 5.07 0.0 0.00 0.00 0.00
1

lrradiation,

Output Data Diff

Btu/hr-ft2 0.00 0.00 0.00 0.00 0.00 0.00 9.93 23.08 32.24 39.29 44.53 47 .91 52.42 56.44 59.38 60.32 57.93 50.35 33.70 1.03 0.00 0.00 0.00 0.00

lrradiation,

Solar Heat Gain,


Btu/hr 0.00 0.00 0.00

0'00 0.00
0.00
163.51

380.04 530.96
647.01

733.28 788.98 863.28


1314.44 2657 .05

3940.06
4657.12 4594.55

3393.40
111.74 0.00 0.00 0.00 0.00

ln the original RS methodology, two types of radiant time fators v/ere utilized to convert So|ar heat gains into cooling oads. The Solar.-RTS was used to convert the beam transmitted solar gain whie the Nonsoar-RS V/aS used to convert all other Solar gains' However, to simpify the calculations, only one RTS (Nonsolar-RTs) is used in this edition. Since the calculated Solar heat gains include both transmitle ad absorbed Solar gains, the recommended radiative and convectivsplits shown in Table 820 would not be applicable. For this problem, it is assumed that the radiative fraction of the combined solar heat gain is about 0.9. Therefore,
Exets from this wrk may be reproduced by instructors fr distribution on a not-for-profit basis for tSting or instructional purposes only t

studentsenrolledincoursesforwhichthe textbookhasbeenadopted. nytherreproductionrtrnsltionfhisrkbeyondhpermied by Sectins 107 or ]0B ofthe 976 Unied Sttes Copyrigh cwhu he permissin ofhe cpyright oner is unlfu.

164 the radiative/convective split is 90%110%. Then, apply the split to determine the convective and radiative heat gains and apply Equation 8-67 to the radiative heat gains to determine the radiative cooling load. nd, finally, sum the radiative cooling load and the convective heat gain to get the cooling load.

Heat Gain

Solar

Hour
1

(Btu/hr)

Convective HG
0.0 0.0 0.0 0.0 0.0 0.0
16.4

Radiative

HG

Radiative Cooling Load


141 0 91.6 59.8 39.2 25.9
17.2

Cooling Load
141.0

2
3

4
5

I
9 10
11

12
13 14

15
16 17

0.0 0.0 0.0 0.0 0.0 0.0 163.5 380.0 531.0 647.0 733.3 789.0 863.3 1314.4 2657.1 3940.1
4657.1

38.0
53.1

0.0 .0 0.0 0.0 0.0 0.0 147.2 342.0

91.6 59.8 39.2 25.9


17,2

477.9
582.3

87.6 215.2 339.6

64.7 73.3 78.9 86.3 131.4

450.5
543.8

103.9 253.2 392.7 515.2


617.1

660.0
710.1

265.7 394.0
465.7

777.0 1 183.0 2391.3 3546.1 4191.4


4135.1

615.8 687.3
932.5 1661.8

694.7 773.6 1064.0 1927.5

2566.6
3304.7 3630.8 3261.0 1624.6
912.1

2960.6
3770.4

18 19

4594.6 3393.4
111.7 0.0 0.0 0.0 0.0

459.5
339.3
11.2

4090.3
3600.4 1635.8
912.1

20
21

22 23 24

0.0 0. 0.0 0.0

3054.1 100.6 0.0 0.0 0.0 .0

549.4 343.2 218.7

549.4 343.2 218.7

Exerpts from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instructional puoses ony to permied students enrolled in courses }or whih the textbook has been adopted. ny other reproducin or rnsion of his rk beyond th by Secions 1 07 or ] 08 of the 1 97 6 Uniecl Ses Copyrgh c |uithu the permissin f he copyright owner is unful.

-165

Cooling Loads and Heat Gains


5000.0

4500.0 4000.0
(!
I

3500.0 3000.0

2500.0
J.

_*x-

Soiar Heat Gain (Btu/hr)


Cooling Load

2000.0
1500.0
1

(!

000.0 500.0
0.0

B-44

This problem uses the same solution procedures as Problem 8-43. Note that the solar irradiation on the window is the same as that shown in Problem 8-11. Also, note that the calculated Soar gain at 3:00 p.m. is slightly different from that shown in Problem 8-39 due to rounding errors. Th radiative/convective split of 90%l10% is also used for this problem.

Area Frame Area Diffuse SHGC Angular SGc - 0" Angular SHGC - 40' ngular SHGO - 50' Angular SHGC - 60' Angular SHGC - 70' Angular SHGC - 80" Frame SHGC
Glass Clock
Time
1.00 2.00 3.00

lnPut Data

27.2 4.8
0.57 0.68 0.65 0.62 0.54 0.39 0.18 0.029

ft'
ft2

Angle,'
152.14
154.11 '150.59

lnc.

Dir lrrad,

ft2 0.00 0.00 0.00

Btu/hr-

OutPut Data

Diff lrrad, Btu/hrf1'

Solar Heat Gain,


Btu/hr

0.00 0.00 0.00

0.00
0.00 0.00

or instructional puoses only to EetS from this work may be reprdued by instructors fbr distribution on a not-for-profit basis for testing the textbook has been adopted. ny other reproiucon or trnslin f his ork beyond th Permied students enrolled in courses fbr which is unlful. by Sectins 07 or 08 f the ] 97 6 (]nied Sttes Copyright ct wihou the permission f the copyrigh oner

166
4.00
5.00 6.00 7.00 8.00 9.00 10.00
1

143.20 133.87 123.75 113.42 103.29 93.66

0.00 0.00 0.00 0.00 0.00 0.00

84.88
77.37 71.58

22.70
58.92 87.76 105.54 1 10.30 101.56 80.22 48.70 11.34 0.00 0.00 0.00 0.00 0.00 0.00

1.00

0.00 0.00 0.00 3.96 17.83 29.69 39.68 48.23


54.81

0.00 .00 .00


6'1.91

278.89 464.39 680.73


1139.73 1721.36 2140.21

12.00
'13.00

14.00 15.00 16.00 17.00 18.00 19.00 20.00

68.02 67.06 68.82


73.09 79.44 87.38 96.45 106.26 116.49 126.80 136.76 145.67

58.85 59.94 57.95


53.1 0

2255,35
2046.81 1551.04
978.1 5

45.86
36.84 26.46 14.28 0.32 0.0 0.00 0.0

592.46 413.94

21.00
22.00 23.00 24.00

223.45 4.97
0.00 0.00 0.00

our
1

Heat Gain (Btl/hr\ 0.0 0.0 0.0 0.0 0.0 0.0

Solar

Convective

HG

Radiative

Radiative Cooling Load


356.3 341.8 328.6 316.4 305.0
294.1

Cooling Load
356.3 341.8 328.6 316.4 305.0
294.1 303.1

2 3

4 5

o
7

I I

61.9 278.9
464.4

. 0.0 0.0 0.0 0.0 0.0 6.2

27.9
46.4 68.1

10
11

680.7
1139.7 1721.4 2140.2 2255.4 2046.8 1551.0
978.1

114.0
172.1

12
13

14
15

214.0 225.5
204.7
1

to 17 18 19

55.1 59.2

97.8 41.4 22.3 0.5 0.0 0.0

592.5

413.9
223.4 5.0 0.0 0.0 0.0

0.0 0.0 0.0 0.0 0.0 0.0 55.7 251.0 418.0 612.7 1025.8 1549.2 1926.2 2029.8 1842 1 1395.9 880.3 533.2 372.6
201.1

297.0 338.9 391.2 457.1 583.2 763.0 935.3 1046.5 1067.8


991 0

366.8

437.6
525.2 697.2
935.1

1149.3 1272.0 1272 4


1146.1

853.6 723.9

951.4
783.1

633.6
551.8 465.4

675.0
574.1

20
21

22 23 24

----

..--o.0

4.5 0.0 0.0

465.9
421.3 393.5 373.0

421.3
393.5 373.0

Excets from this wrk may be reprodued by instructors or distribution on a not-for-profit basis for testing or instrutional puoses only to students enrolled in courses for whih the textbok has been adoted' ny oher reprducion or rnslon of his ork beyond th permed by Secions ]07 or ]08 ofhe 976 Unied Sttes Cpyrigh clithout lhe permissin ofhe copyright oner is uncrful'

167

Cooling Loads and Heat Gains


2500.0

2000.0

500.0

E
(E

--l_Solar

eat Gain (Btu/hr) ,--x- Cooling Load


1

000.0

500.0

0.0

8-45
Hour
I

Heat Gain (w) 200.0 200.0 200.0 200.0 20.0 200.0 200.0 2000.0 2000.0
2000.0

lnternal

Convective

HG

Radiative HG
100.0 100.0 100.0 100.0 100.0 100.0 100.0 1000.0 1000.0 1000.0
'10.

Radiative Cooling Load


125.3

Cooling Load
(V

2
3

4
5

6
7

10
11

100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 1000.0 1000.0

225.3
216.6 211.0

116.6
111.O

107.3 105.0
103.4

207.3 205.0
203.4 202.4 1566.7 1753.8
1

102.4 566.7 753.8


85'1.1

851 .1

12 13 14 15 16 17 18 19

2000. 2000.0 200.0 2000.0


2000.0

10.
1000.0 1000.0 100.0 1000.0 1000.0 1000.0 1000.0 100.0

2000.0
2000.0

200.
200.0

1000.0 1000.0 1000.0 1000.0 1000.0 1000.0 1000.0 100.0

906.9 940.8
962.1

1906.9 1940.8
1962.1

975.6 984.3 990.0 993.6 996.0 532.6

1975.6 1984.3 1990.0 1993.6 1996.0

632.6

EXcetS from this wrk may be reprduced by instructors fr distribution on a not-fr-profit basis for testing or instructional puses only to students enolled in ourses for which th tetbook has been adopted. ny her reproduction or trnstion of this rk beyond h permitted bySectins 07 or 08of he ]976UniedSttesCpyrightctwithutthepermissinf thecpyrighownerisunlcrful.

'168
20
21

22 23 24

200.0 200.0 200.0 200.0 200.0

100.0 100.0 100. 100.0 100.0

100.0 100. 10. 100.0 100.0

346.2 249.2 193.6


159.9

446.2 349.2

293.6 259.9
238.7

138.7

Cooling Loads and Heat Gains


2500.0

'6

2000.0

1500.0

()

(!

+*x-

lnternal

l-1eat

Gain (W)
(\/)

Cooling Load

o
(

8-46
lnternal Heat Gain

Hour
1

rw)

Convective

HG

Radiative

HG

Radiative Cooling Load


405.'1

Cooling Load (w)


505.1

200.0

2
3

200. 20.
200.0

4
5

200.0
200.0

I
o

10
11

12
'13

14

200.0 2000.0 2000.0 2000.0 2000.0 2000.0 2000.0 2000.0

100.0 1.0 100.0 100.0 100.0 100.0 100.0 1000.0 1000.0 1000.0 1000.0 100. 1000.0
10.0

'100.0 100.0

100.0

100.0 100.0 100.0 100.0 1000.0 1000.0 100.0 1000.0 100. 1000.0 1000.0

392.9 381.7 371.2 361.3


352.1

492.9 481.7

471.2
461.3 452.1 443.3
15'18.9

343.3 518.9 562.8 59.6 612.3 630.8


647.1

1562.8 1590.6 1612.3


1

630.8

1647.1

661.9

1661.9

xets from this work may be reproduced by instuctors for distribution on a not-for-profit basis for testing or instructional puoses only to students enroled in ourses for which the textbook has been adopted' ny oher reprductn or rnsl(tion of his work beyond tht permied by Sectins 07 or ] 08 of the 1 976 Unied Sttes Copyrgh c'ihou he permissionbf the cpyrigh wner is unlful.

'169

15 16 17 18 19

2000' 2000.0
2000.0

20
21

22 23 24

2000.0 200.0 200.0 20. 200.0 200.0 200.0

100.0 1000.0 1000.0 1000.0 100.0 100.0 100.0 100.0 100.0 100.0

1000.0 1000.0 1000.0 1000.0 100.0 100. 10. 100.0 100.0 100.

675.5
688.2 700.0
711 .1

1675.5
'1688.2

1700.0
1711 .1

537.6 495.7

637.6
595.7 569.9 549.9 533.2 518.4

469.9
449.9 433.2 418.4

Gooling Loads and Heat Gains


2500.0

200.0

1500.0

----

lnternal Fleat Gain (W1 ooling Load (W)

1000.0

*-s*

500.0

;
0.0

:.

.::l

L-.*

&-x** *

cerpts tiom this ork may be reprodued by instructrs for distributin on a not_for-profit basis fr testing or instrutional puoses only to students enroled in ouses 1br whih the textbook has been adopted. ny oher reproduction or trnson of this work beyond h permied by Secins ]07 or ]08 fhe 976 Lnited SteS Cpyright c ihou he permiSSin fhe copyrigh oner is unlwful'

170

8-47 Gomparison of LW and


M/ 1

Zone Responses

o (!
o
:=

2000.0

, 1500.0

o
a'

o
o

_--.*

,
(,

--r-- lnternal Heat Gain ) MW1 Zone Clg. Ld v)

1000.0

-_.*- W Zone Clg. Ld. (W)

'6

-t)

(,

50.

--'. l)* ':'* ^__x


11
'13

*. \
\

5**+-

15

17

19

21

23

Hour

As shown in the figure, there is a signifrcant difference in the response of


the two Zones, with the W zone having substantiatly more damping and time delay.

Excets f?om this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instructional puoses only to students enrolled in courses fr whih th textbook has been adopted. ny oher reproclucin or rnsionbf hs work beyod ih permied by Sections ]07 r ]08 ofhe }976 United Stes Cpyright ctwithut the permissin fhe cpyrigh wner i unlful'

171

8-48

Assumptions applied to each heat gain are discussed in the solution to Probem 8-15. The equipment heat gain is assumed to be continuous. The total convective and radiative heat gains are determined in the folowing table. he atent cooing oads are equivalent to the latent heat gains shown in the last column.
Total Total Latent from

Name:

Radiative
Fraction:

99p]9_ Lihtino
0.7 0.59

Euipment
0.2

otal

Radiative

Convective

People

llor
1

eat Gain
(\/)

eat Gain /w)


0 0 0

Heat Gain (w) 4000 4000 400 4000 4000 4000 4000 4000 400 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 40 4000 4000

Gain (W)
4000 4000 4000 400 4000 4000 4000
0960 0960 1 0960 1 0960 1 0960 1 0960 1 0960 1 960 1 0960 1 0960 8800
1 1

Heat

Gain (W)
800 800 800 800 800

Heat

Heat Gain
r
320C)

Heat Gain (w)


0 0 0 0 0 0
n

0
U

2 3

0 0 0

4
5

6
7

0 0 0
0

I
10
11

2160 2160
2160 2160 2160 2160

12 13 14 15
16

2160
2160 2160 2160
0 0
U

4800 4800 4800 4800 4800 4800 4800


48CI0

17 18 19

4800 4800 4800


0 n 0 0

800 800 5144 5144 5144 5144 5144 5144 5144 5144 5144 5144
3632 800 80 800 800 800 800

320 3200 3200 3200 3200 3200


581 6 581 6 581 6
1

5816
581 6 581 6 581 6

350 350 1 350 1 350 1 350


1
1

350

5816
581 6

58l 6
5168 3200

35 350 1 350 1 350


1
1

0 0 0 0 0 0 0

20
21

0 0

22 23 24

0 0

4000 400 400 400 4000 4000

320 3200 3200 3200 320

The sensible loads are then determined from the radiative and convective heat gains using Equation 8-67 and the radiant time factors from able 821, as shown in the next table.
cets liom this work may be reproduced by instructors 1br dlsribltlon n a notbr-pofit basis for testing or instructiona] purposes ony to it- lrses fr hich the tebook has ben adptd. l;l er reprdction or trnslcio cf his 'ork beyond h erfrited by Sectils ] 07 r 08 f he 97 6 Unied SteS Copyrigh c ihou le ernission f the cpyrigh '!'ner iS unl.ful'
suderrts en:-olled

172

Hour
1

Heat Gain (w) 4000.0 4000.0 4000.0 400.0 4000.0 4000.0 4000.0
10960.0 10960.0 10960.0 10960.0 10960.0 10960.0 1096.0 10960.0
'10960.0

lnternal

Convective G
320.0 3200.0 3200.0 3200.0 3200.0 3200.0 3200.0 5816.0 5816.0 5816.0 5816.0 5816.0 5816.0 5816.0 5816.0
58 1 6.0

Radiative

HG

Radiative Cooling Load


2218.4

Cooling Load (w)


5418.4 5362.5

2
3

4
5

6
7 8 9 10
11

12
'13

14

15 16 17 18
'19

10960.0

20
21

22 23 24

880'0 4000.0 4000.0 4000.0 4000.0 4000.0 4000.0

5816.0 5168.0 3200.0 320.0 3200.0 3200.0 3200.0 3200.0

800.0 800.0 800.0 800.0 800.0 800.0 800.0 5144.0 5144.0 5144.0 5144.0 5144.0 5144.0 5144.0 5144.0 5144.0 5144.0

2162.5
2110.6 2062.1 2016.7 1973.8 1933.3 2782.4
2996.'1

5310.6
5262.1 5216.7 5173.8

5133.3
8598.4
8812.1

3131.2 3237.5

8947.2

9053.5
9144.0 9224.1 9296.7

3328.
3408.1 3480.7 3547.6 3609.6
JOO /. /

9363.6
9425.6 9483.7 8581.3 5999.1 5825.5

3632.0
800.0 80.0 800.0 800.0 800.0 800.0

3413.3 2799.1

2625.5 2512.4 2422.9


2346.8

5712.4
5622.9

5546.8
5479.4

2279.4

Cooling Loads and Heat Gains


1200.0 10000.0

'6

8000.0 6000.0 4000.0 2000.0


0.0

o
,

instructional purposs only to xets fiom this wok may be reproduced by instructofs for distrlbution on a not-for-profit basis for testing or ht permited enrolled in ouses fo which th textbok has been adopted' ny other reprducion or trnsion of this rk beyond students ]976 Jnited Sttel Cpyrigh ct\'ithout the permissin ofhe cpyrigh owner is unlfu. by Secions 07 or 08 fthe

173 8-49

Assumptions applied to each heat gain are discussed in the solution to Problem 8-'16. The equipment heat gain is assumed to be continuous; the lighting heat gain is assumed to occur from 8 a.m.-6 p.m. The total convective and radiative heat gains are determined in the following table. The latent cooling oads are equivalent to the latent heat gains shown in the last column.
otal

Name:

People
0.7

Liohtin .59

Eioment
0.2

Total

Radiative

Total Convective

Pete

Latent from

Radiative
Fraction:

Hour
1

Heat Gain (w)


0 0 0 0
U

Heat Gain (w)


0

2
3

0 0
0

4
5

6
7

0 0

0 0

9 't0
11

2835 2835 2835

2835
2835 2835 2835 2835 2835

12 13
14

15
'16

17 18 19

2835
0 0 0 0 0 0 0

5625 5625 5625 5625 5625 5625 5625 5625 5625 5625 5625
0 0
0

Heat Gain rw) 700 7000 7000 7000 7000 7000 7000 7000 7000 7000 700
7000

Gain (W)
70 7000
700

Heat

Gain (W)
1400 1400 1400 1400 1400 1400 140

Heat

eat Gain
/\

Heat Gain (w)


0 0

7000 700 7000 700


5460 1 5460 1 5460 1 5460 1 5460 1 5460 1 5460 1 5460 1 5460
1

7000
7000

7000
7000

20
21

22 23 24

7000 700 7000 7000 7000 7000 7000 7000

'15460

6703.25 6703.25 6703.25 6703.25 6703.25 6703.25 6703.25 6703.25 6703,25 6703.25
4718.75
1

12625
7000

400

7000 7000
7000 700

1400 1400
1

400

7000

1400 1400

5600 5600 5600 5600 5600 560 5600 8756.75 8756.75 8756.75 8756.75 8756.75 8756.75 8756.75 8756.75 8756.75 8756.75 7906.25 5600 5600 5600 5600 5600 5600

0 0
0 0

2835 2835

2835 2835
2835 2835 2835

2835 2835
2835
0

0
0 0

0
0

The sensible loads are then determined from the radiative and convective heat gains using quation 8-67 and the radiant time factors from able 821 , as shown in the next table.
EXcetS fm this work may be reprodued by instrutors for distribution on a not_for_prfit basis or testing or instructional puoses only to students enro|led in courses for whih the textbok has been adopted. ny her reproduction or rnslin f this ork beyond tht permited
by Secions ]07 or ]08

ofthe 976 Lnied

Sttes Cpyright ctlithut the permissin

fhe cpyright oner is unlful.

174

Hour
1

Heat Gain (w)


7000.0 7000. 7000.0 7000.0

lnternal

Convective G
5600.0 5600.0 5600.0 5600.0 5600.0 5600.0 5600.0 8756.8 8756.8 8756.8 8756.8 8756.8 8756.8 8756.8 8756.8 8756.8 8756.8 7906.3 5600.0 5600.0 5600.0 5600.0 5600.0 5600.0

Radiative

HG

Radiative Cooling Load


2888.2

Cooling Load (w)


8488.2 8430.6 8377,5 8327.8 8280.7

2
3

1400.0 1400.0
1

400.0

4
5

6
7

7000. 7000.0 7000.


15460.0 15460.0 15460.0 15460.0 15460.0 1546.0 15460.0 15460.0 15460.0 15460.0 12625.0 7000.0 7000.0

140.0 140.0
1

2830.6 2777.5 2727.8


2680.7 2635.8 2592.7 3814.6 4292.6

400.0

8235.8
8192.7 12571.3 13049.3 13296.5 13451.2 13563.6 13654.2
13732.1

140.0

8
9

10
11

12
'13

14 15

o
17
'18

6703.3 6703.3 6703.3 6703.3 6703.3 6703.3 6703.3 6703.3 6703.3 6703.3
4718.8 1400.0 1400.0 1400.0 1400.0 1400.0 1400.0

4539.8
4694.4

4806.9
4897.4 4975.3 5045.3 5109.7 5170.2 4754.8 3825.2 3446.7 3246.7 31 19.9 3027.2 2952.4

13802.0 13866.5

'13926.9

19

20
21

22 23 24

7000.0 7000.0 7000.0


7000.0

12661.0 9425.2 9046.7 8846.7 8719.9 8627.2 8552.4

Cooling Loads and Heat Gains


18000.0 16000.0

'6

14000.0
'12000.0

oE
IE

(!

10000.0 8000.0 600.0 4000.0 2000.0 0.0

---G- lnternal

Fteat Gain (W;

q)

*x*

Cooling Load ()

basis for tsting or instrutional puoses only to xcerpts tio this work may be reproduced by instuctors f distribution n a not-for-profit reprodc'tin or trnson of ths ork beyond ht permitted students enrolled in ourses tbr which the textbook has been adopted. ny other thecopyrightonerisunful' iysr,iton, 107 r ]0Bf the 1976JnitedSttesCopyrighctlithoutthipermissinof

175
8-50

Heat gain to the space = 0.8 x 6000 W = 4800 W, assumed 59% radiative, 41o/o convective, from able 8-20' The sensible loads are then determined from the radiative and convective heat gains using Equation 8-67 and the radiant time factors from Table 8-21, as shown below. here are no latent cooling loads.
Heat Gain (w)
0.0 0.0 0.0
0.0

lnternal

our
1

Convective G
0.0 0.0 0.0 0.0 0.0 1968.0 1968.0 1968.0 1968.0 1968,0 1968.0

Radiative HG
0.0 0.0 0.0 0.0 0.0 2832.0 2832.4

Radiative Cooling Load


79.8 52.4 34.7
23.1
'15.6

Cooling Load (w)


79.8 52.4 34.7
23.1 15.6

2 3
4

0.0

6
7 8 9

10
11

12 13 14

15 16 17 18
't9

4800.0 4800.0 4800.0 4800.0 4800.0 4800.0 4800.0 4800.0 4800.0 4800.0 4800.0 4800.0 480.0
0.0

1473.9

2832.0
2832.0

2060.5 2365.5
2540.5 2646.7

3441.9 4028.5

4333.5 4508.5
4614.7 4681.2

2832.0
2832.0

2713.2
2755.6

'1968.0

2832.0
2832.0 2832.0 2832.0

4723.6
4750.9 4768.5

20
21

22 23 24

0.0 0.0 0.0 0.0 0.0

1968.0 1968.0 1968.0 1968.0 1968.0 1968.0 0.0 0.0 0.0 0.0 0.0 0.0

2782.9 2800.5
2812.0

2832.0
2832.0 2832.0 0.0 0.0 0.0 0.0 0.0 0.0

2819.5
2824.3

4780.0 4787.5 4792.3


4795.5 1366.5 777.9

2827.5
1366.5 777.9

471.8
296.0 189.3 122.5

471.8 296.0
189.3 122.5

A plot showing the lighting heat gain and resuting cooling loads follows.

puoses ony toExcerpts frm this work may be reproduced by instructors for distribution n a not-for-pro1it basis 1br testing r instrutional this ork beynd ht permited students enoled in courses tbr hih the tsxtbook has been adopted. ny ther reproclucion or trnston f by Secion 107 r ]08 ofthe 976 United Saes Copyri?h c1|,ithou the permission ofhe copyrigh olner is unlful.

176

t6000.0 5000.0

Cooling Loads and Heat Gains

,6

4000.0 3000.0

--{-

|nternal Fleat Gain (\l)


(\/)

___x* Cooling Load

o l,

57

11 13 15 17 19 21
Hour

23

8-5'1

The schedule described in problem 8-18 is reduced to the number of peope present per hour in the table below. Assuming "Seated, light office *ork'', the sensible heat gain per person is 245 Btu/hr (72) and the latent heat gain per person is 2bO Btu/hr (59 W). lnternal heat gains from occupants are assumed to be 70o/o radiative. The latent cooling loads are equivalent to the latent heat gains shown in the table. The sensible loads are then determined from the radiative and convective 8heat gains using Equation 8-67 and the radiant time factors from Table 21 , as shown below.

As is readily evident from the plot, the heavyweight zone significantly


damps the response to the heat gains'

on a not-fr-profit basis for testing r nstructional purposes only to Exerpts from this work may be reproduced by instructors for distribution of his work beyond h permied fbr which the textbook t-,u, ..n uopt. . ny ther repriucon or rnslion Studnts enoled in courses cyithou hi permissin fthe copyrigh owner is unlful' by Secins ]07 or ]08 ofhe 976 United SeS Copyri?ht

177
Latent heat gain
(\/)

Hour
1

resent
0
0

People

Heat Gain (w)


0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

lnternal

Convective

HG

Radiative

HG

2
3

0
0

4
5

0
0

6
7

I
9

0
0

10
11

12
13

14
'15

40 40 60 60 60 70 70
70 10
0 0

2880.0 2880.0
4320.0 4320.0 4320.0

0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 864.0 864.0 1296.0 1296.0
'1296.0

0.0 0.0 0.0 .0 0.0 0.0 0.0 0.0

Radiative Cooling Load 20.6


12.5 7.8 5.0 3.4 2.5 2.0
1.6

Cooling Load (w) 20.6


12.5 7.8 5.0 3.4 2.5 2.0
1.6

0
0 0

0
0

2016.0 2016.0
3024.0 3024.0 3024.0 3528.0 3528.0 3528.0 504.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

1021.8 1484.5

2233.7 2593.8 2784.5


3143.9
33'17.9

1885.8 2348.5 3529.7 3889.8

16 17 18 19

5040.0 5040.0 5040.0 720.0


0.0 0.0 0.0 0.0 0.0 0.0 .0

20
21

0
0

22 23 24

0
0 0

1512.0 1512.0 1512.0 216.0 .0 0.0 .0 0.0 0.0 0.0 0.0

4080.5 4655.9
4829.9

3410.8
1931 .3

4922.8 2147.3
1010.7 552.7 309.2 175.8
101.1

2360 2360 3540 3540 3540 4't30 4130 4130


590
0 0 0 0

1010.7 552.7 309.2 175.8


101.1

0
0 0

58.8 34.6

58.8 34.6

Cooling Loads and Heat Gains


6000.0 5000.0

'

4000.0 3000.0 200.0 1000.0

--*-

lnternal Heat Gain (W1 Cooling Load (W)

*-s*

puoses only to Excets from this work may be reprodued by instructors fr distribution on a not-for-profit basis for testing or instrutional ht permited students enrolled in course s for which the textbook has been adopted. ny oher reproducin or rnsion of hs ork beyond by Secins ] 07 or ] 08 f the 97 6 (Jnitecl Ses Copyrgh c |ihu the permissin f he copyright wner is unlfu.

178

Solution to be provided by an instructor.

basis for distribution on a not-for-profit wrk may be reprduced by instru:lor:.fo, Excerpts from this for which the textbok has been i, purposes on1y stues enr1led "or.r"s by Sections ]07 or 10B testing or instrutional o}ths ork beyo'nd tht permitted owner is unlwful' adopted. ny other repiodction "y ""ititi" the permission-o/'u copyrgit ct of the 1976 (Jnitecl itotus Copyright 'iin, he Piimiision Deprtment, John nfrmtionilroua i" oaarrrruio h'uouurt, for permission or further

'';i,;;;'';:"{,-i", il l Riir

Street' Hoboken' NJ 07030'

CHAPTER 9
average degree day is 6283' From Table 9-1, the number of From Fig. 9-1, Co = 0'60 Using q' 9-2,

f-

gas Or F = 438.7 mcf of natural

_ tu l hr)(}'60) (24hr l dy)(6283' F dy)\2-^2-^1000 = 438,727 std ft3 (0 (7_ 12"tr)(10 \tu l stdff)

f-

(24hrldy)(6283'F_dy)(-^?5,000tulhr)(0'60) l kW _ hr) (1 J) ql o _z' r)aL2tu

= 102,867 kw-hr

0'287 $Elec = 102,867(0.1 O) = $1 $Gas = 438.7(4.5) = $1,974

Sec_$Gs
$Gs

|0287_974 914

4.2

5'2 times as much' or the electric cost is about Source energy using eec' Source energy using gas
=

@at)(000stdff
438'7 mcf
= 1063'6 mcf

_ (1 02,s 67 k-t4l

hD

!u_

kY-' hr)

lm

>_-

"o,"ff=-tiU 242% That is ele. heat uSeS


9-3

S,_SG

1063.6

_438'7

- more1.42 energy' Source


=

DU' The following are information for Washington' degree day is 4224' From Table g-l,1he number of average From Fig. 9-1 , CD= O'62' is 20 "F' From Table B-1a, the outdoor temperature

Forenergyefficientfurnace,assume85o/oeffiiencyfactor, Using q' 9-2,

Or F = 177 .5 mcf of natural gas

"

-, ,-, 04hr l d )(4224" F =


-10.85X7O_

_ dy)(|20'000t u

hr)(0'62\ 'o'=177,468stdft3

20"trX1O00tu l stdft3)

9-4
+5 Qro" = ato
1

Load Profiles
80000

120,OO0=a(20)+b g=2(gQ)+b

160000

toooo

t_ l z000

12,ooQ =(20 _60)a

lo
soooo 6oooo 4oooo
2OoOo
0

a = -3OOO, b = 180,000 3'000 to Q uo" = 180,000 -

E'

30

4o

Outdoor TemP, "F

9-5 8o. = Qrn - Qnt = 18O'oOO _ to o" = 160,000 3,000

3'Oo0

to

20'00

only to for testing or instructional puosS for distribution on a not-'br-pro'it basis *is wor-k beyond ht permited this work may be reprduced by instrutrs Exets from -ny oher *p-a""ri"]r'i,o^o*7 the txtbook r-,* *. studnts enrolled in courses to. w,-' ""pi.. of he copyright oner is unlful' copyrgn, 'a}i:i';;u' i'! irr'*i" l'oii'ii'ri,',r, by Secions ]07 or 108 o7 m,

186

9-6
Group

lll

ll

lVVVl

Sunday
Monday

Tuesday Wednesday Thursday Friday


Saturday

shift 2

shift

1481012162024

Hour

ssumes Sunday and Saturday in shift 2


See Table 9-2 shift 1 hrs in Group ea. qp
I

shift 1 Days in ea. qp.


0

Total hrs ea. qp


0 0

shift

Total hrs in ea. p.


28 28 28 28 28 28

Frac. of shift 1 hrs ea. gp


0.0 0.0

Frac. of hrs in ea. qp.


'1.0

0 0

il
t

0 5 5 5 5

1.0

0.36
0.71 0.71 0.71

0.64
0.29 0.29 0.29

IV

4 4

20 20 20

V
VI

instructional puoses only t Ecets from his wrk may be reprodued by instrutors for distribution n a not-for-profit basis for testing or has been adopted- ny other reprodiction or rcnsion f this wrk beyond ht permited students enrolled in courses for whrch the textbook hecopyrighowneriSunlfu. bySecins ]07 r ]08of the 976(JnitedSteSCopyrightcthoutthepermissionof

lo/

9-6 (Cont.)
Bin.

Temp
62 57 52 47 42 37 32 27 22
17 12

lII
0 0
0 0

Shift t hrs in each Group

III

IVVVI

shift
69 58 86 87 99 75 66 28 22
11
1

0 0 0 0 0 0 0 0 0 0 0

0 0
0 0 0

34 38 49 36 35 32 27
10

I
1

96 77 67 47 48 38 28 17
12
1

68 82 94 62 65 54 36 17
16

hrs 267

shift 2 hrs

255 296
232 247 199
157 72 58 22 2

375 346 388


337 420 422 347 157 113 73 16

4
0

Tota:
9-7

1807

2994

The procedure is the same as Problem 9-6. Use appropriate bin data from pp. B in last step as per Table 9-3.
9-8

Refer to xample 9-2, insert shift hours of Problem 9-6 in column 2 and 3 of Table 9-5 and recalculate.
9-9

Reconstruct able-9-3 for the appropriate city to obtain Shift A and Shift B hours. lnsert the hours in columns 2 and 3 of Table 9-5 and recalculate.

Exets from this work may be reproduced by instructors for distribution on a not_for-profit basis fr testing or instrutional purposes only to students eno11ed in courses for whih the textbook has been adopted. ny other reproduction or rnsltion of this work beyond h permtted by Secins ] 07 or 1 08 of he 1 976 Uned SeS Cpyrigh ct ithut he permission of the copyrigh lner is unlful.

188

9-10

Reconstruct Table 9-3 using the shift hour fractions from Problem 9-6 and bin hours and temperatures for the appropriate city. lnsert the shift hours in column 2 and 3 of Table 9-5 and bin temperatures in column 1 and recalculate.

9-1

Solution furnished by an instructor.

'/'''

Exets from this work may be reproduced by instructors for distribution on a not-for_profit basis for testing or instructional puoses only to students enrolled in courses for which the textbook has been adopted. ny ther reproduction r trnstion of this 'rk beyond ht permitted by Secions ] 07 or 108 ofhe 976 [Jnied Ses Copyrigh c ithout the permission ofthe copyrigh oner is unlful.

Exets from this work may be reproduced by instructors for distributin on a not-for-prfit basis fr testing or instrutinal puoses only to students enrolled in courses fr which the textbook has been adpted. ny other reproduction or trnsltion of this wrk beyond tht permitted by Sections 107 or 0B of the 1976 Jnited Sttes Copyright ct without the permission f the copyright ov)ner is unlwful. Requests for permission or further informtion should be ddressed to the Permission Deprtment, John Wiley & Sons, nc, ] ] ] Rier Street, Hoboken, NJ 07030'

CHAPTER

1O

1O-1. (a)

neglect

',*

o+ + _Pz+'
(!
iz;
Wp =

+
=

Zz+
-80 (ft

Wp +

tt, Vl

VziZ=z

-, g/g/"

lbf)/lbm

Pz = Pl + Wp = 20 + 62.4(80)1144 = 54.7 psig Ps = Pz - Ps_ U:)rg= 54.7 _ (62'4 X 50)/1 44 _ (20 x 62'41144)

Pg= 54.7 _ 3.3

24'4 psig
(1't)g+

P=Pz- PZ-((izg_
28.7 psig

=54.7

ffiX25)

(#)(20+

'15) =

(b) Neglecting the pump, the pressure or head required for this pipe is:

= 28'7 - 20

psi or P

8.7 psi

20.1 ft.

87I
I

lo tl l l) |

20

Note:

This is the characteristic for only part

of the total
system.

0L_

oa
= Hz

150
(.

10-2.

* +

trZz=

(8 x 2.31)

250 + 30 + 300

190

= 98.5 ft of water
=

42'6 psig 294 kPa

Jt
= -325ft: H^ = 325ft of head
(

'10-3.

l_z=Hp+ !,t+z=0
H^ =

('-2,

-25- 300

970 kPa

10-4.

100
+
)+ 12 + 1b

5o
75

10-5. (a)l=al+Z
Hz=zQz+z
Series Connection

H2
L

(
.)

z2
Hq

-c.

Ql=Qz;Sum

H=lr

xcerpts from this work may be reproduced by instructors 1br distribution on a not-for-proit basis for testing or instrutinal puoses only to students enolled in ourses for vhih the textbook has been adoted' ny her reproducion or rnsion of his rk beyond h permitted by Sections ]07 or 08 ofhe ]976 United Ses Copyrighctwithou the permissin fhe copyrigh oner is unfu.

H=Hl *Hz =Qz(a+Az)+G+zz)


Hl = z, =ZzorZ=0 Sum Q
Parallel Connection

191

Ql=
Q

^E,z= Yar
l
+Q

=Q

6ra*M)'
10-6.

r= JH_(Jil q * ^[- . )
+

^E Yaz

t=f!Y1 ; V = 6. 3ft/sec, L = 3OO ft, D = ' D2g

4.026
12

Referring to Figures 10-2a and 1 0-2b


62'4(1 .04)6'30(4'026 l12) Re = D _ = 75,696 (2'7 11490) = 0.00015 ft; Table 10-1

/d=o.ooo1

12 5" 4.026

/D = 0.00045; f = (,=

0'022 Fig.

10-1

/3OO) 0.022 \'

(6.30)2

(4.026 t 12) 2(32.17)

= 12.1 ft of 30o/o E.G.sol.

= 12.6 ft of water

38 kPa

-'.--Excerpts frm this work may be reprodued by instructors for djstribution on a nt-for-profit basis for testing or instrutional puoses only to students enrolled in courses or which the textbook has been adoped' ny ther reproduction or rnstion of his ork beyond h permitted by Secions ] 07 or 1 08 of the ] 976 United Stes Cpyright ct ithou he permission of he copyright wner is unlful.

192

10-7.

(a)
(
J-

so

925

100

125

150

gpm

(b)

Qn

48 gpm; Qs

24 gpm; Qc

= 32 gpm;

(c) (d)

28ft
60 gpm Qs = 32 gpm Qc = 41 gpm

Qn

_ 125 gpm

10-8.

Refer to Problem 10-7;

z _ 0
=O.9O8O

(a) Hn= uoQi, n=


Hs = auQ3, s = Hc = a.Q3, c =

9= + ai 50'
30'

9= a6

= +=+ aa 45'
a2

= o'o278
=o.O'148

H(^n/o!o8
+

02
645.06

Jt

oza + J.roua)2

= 0.001

55Q2

(b) Q

= 100 gpm; H = O.OO155 x (1OO),

1S.5 ft

Excerpts from this work may be reproduced by instrutors for distribution on a nt-for-prfit basis for testing r instructional purposes only to students enro]ed in courses for which the textbook has been adopted' ny other reproduction or rnsltion of this work beyoncl h permiedbySectins 07 or l08 of he ]976LlniedSalesCpyrightct]ihouhepermissionf he copyrighnerisunlfu.

Hn = Hs = c = 'l5.5 ft

193

Qn=
Qg=

J/r

=.,/l55/O.OO8 =44gpm
=

.'m

lo'o2?8

23'6 pm

Qc =

Jss/oJl4g
(a)

= 32.4 gom
= 0.001

(c) From

above. H

55(12q2 = 24.2 tt

Qn=
Qg =

=55qpm
=
=

J2lo278

29.5 gpm
4O.4 qpm

Qc = J%2to148

= 125 gpm

1o-9.

= CA

r|2g"(P, '--L

_Pr)l''''
-]

v'vv 'D1 =84.8 = O.55 154.1

D2

aSSume C = 0.638 using Fig. 10-9;

P_Pz
Q

Ar= (O.os4s)2 = O.00565 -4

m2

= O.O98(13.55)9.s = 13.O13 J/kg

= 0.63S(0.0056 5)t2(13,013)11/2 =

0.0184 m3/s x 292 gpm


= 1.98 x'105

V
C6

z=

3.26 m/s; Re

999(3'26)(0:085)
1.4x10-3
10-9.

^:

0.638 From Fig.

herefore the original assumption is satisfactory.


Excerpts from this work may be reproduced by instrutors for distribution on a not-for_profit basis for testing or instructional puoses only to students enrolled in courses tbr which the textbook has been adoped' ny ther reprduction or rnslaon of his ori beyond-th permitted by Secions ] 07 or 0B of he ] 976 United Ses Cpyrigh ct wihu the permissin of he copyrigh ner is unwful.

194

1o-1o. (a)V.. = 2g" (Po,


Table A-1a;

L-" [ )] L

= 59'83 lbm/ft3

_,ll"' _|z x s?'

x o.os x 144 0 +91x 144)

1t2

=3.97 ft/sec

(b)rir = VA(O. 821= 59.83 x 3.97

rh = 39 lbm/sec or 140,674 lbm/hr

r+][q''l2 4r 12 )

o.z

10-11

(a) 40

35

T2s

(b)

Read from Fig. 10-11a at 35 ft and '125 gpm, W. = '1.6 HP

(c) (d)

= 180 gpm, H, = 20 ft; 1.8 P

his is actually out of the operating range of the pump and the
efficiency is very low. ln situations like this there is a danger of overloading the pump motor; however, that does not appear to be a problem in this case since the motor is probably a 2HP model.

xcerpts from this work may be reprodced by instrutors for distribution on a not_fr-profit basts for testing or instrutional purpses only to students enrlled in ourses for whih the textbok has been adpted. ny other reprodctin r rnslion f his work beyond tht permied by Sections ]07 or 08 fhe 1976 Uned Stes Copyrightct1|ihout he permissin fthe copyrigh oner is unlcrlful.

195

10-12. NPSHR
NPSHA

= =

ft (Figure 10_1 1b) [e"e") -2,-r,- f&9"] \ g / g)


NPSH
=

20

to ( 20='u 13.55x62.4 -"_2_ t_l'sox 44


12

62.2

az.z

"=32'85_20_2_1'17
'10-13. (a) 231 gpm, p = 73'4% W, = 12* tlP

9.68 ft; (2.)rr, = 9.68 ft

200

(b) 225 gpm o = 73 '3o/o W, = 12- P

140
100

10-14.

(a) (b)

= 73.3o;

W,

= 11. 5

HP
185

225 gpm; '185 ft of head

149

r=73.5%;Ws=14P

(c)

o= 73o/o,

W.

= 14 P
gpm

225

231

10-15 From Problem 10-14b, the original system defined by 225 gpm and 149

ft of head and would operate at 242 gpm, 173 ft of head and require 14.4 HP with the 7in impellor. hen,

Ecerpts 1iom this work may be reprduced by nstrutors for distribution on a not-for-profit basis for testing or instrutinal puoses nly to students enrolled in urses for which the textbook has been adopled' ny her reproducion or rnsion f his wrk beynd th permited by Sections ] 07 or 08 of he 97 6 United Stes Copyrigh c ithou he permission of he cpyright lner is unlwful.
_. _

196

Pln= 35o[+.l =3o37


\242 )

H^ =

" 3 "
1

3500/

(go37

)'
=

= l3O ft

w^

The fficiency woud not Chan ge,74.2o

4.4(s037)' 3500,

e.4 HP

1o-16

Dn

"r(#)=
()'

7(o e7)

6 8 in

Hn = *,

173

(o'g44)= 163 ft

1.

.[)u

= 14'4(o'g17)

= 13 2

The fficiency would not Chan ge,74.2o

10-17. Uses Fig.

0-20 or program PIPE

(a) 25 gm; 1 % in., V < 4 ftlsec,2in dia. or less (b) 40 gpm; 2in. V < 4 fVsec,2in dia. or less (c) 15 gpm; 1in., v < 4 fUsec, 2in dia. or less (d) 60 gm;2% in', '(,'1< 4 pVsec; dia > 2 in. (e) 2OO gpm; g %in., .(,'1< 4 ftllOO pUsec; dia > 2in.
2ooo gpm; 8 in., /1 slightly
>

4 ftl1oo

ft

Exerpts 1iom this work may be reprduced by instructors fbr distribution on a not-fr-profit basis for testing or instructional puosos only to students enroled in courses tbr which the textbook has been adopted' ny her reproduction or trnsion of this ork beyond h permied by Secions ] 07 or 08 of he ] 97 6 Unted Ses Copyrigh c ithu the permission of he cp,'igh ner is unlwful.

1-18. (a) K = 30 ft, ft = 0.019; K = 0.57 (Table

197

10-2; Figure 10-22a) = 3.82 fVsec; ! r = 0'57(3'822l2.2x2)= O.13 ft

(b) K

= 340 ft, ft= 0.017; = 5.0

f/sec; !

= 5.78

= 5.78 x 5.02t132.2

x2)

2.24 ft

(c) K= 60ft, ft= 0.018; K = 1.08 V = 6.5 ft/sec; ! r= 1.08 x 6.52t(2x32.2)


'10-1e.
!r=

= 0.71 ft

2.31

(#)'

= 10.8 ft of water or 4.7 psi.

10-20. Assume com. stl. pipe Q


= O.O3

mt/s = 108 m3/hr, size pipe for about 4 mllOO m

From Fig. 10-20, use 5 inch pipe, lD = 130 mm


nt '

_ a, f - ..25 ml100 m; [1= (3'251100)200

6.5 m of water or 63.7 kPa

Pg = 35 kPa

For strainer. P"

' - | o-99-1' "


1 0.00722 J

'27

kPa

Then for the pump:


Pp = 63.7 + 35 +
'17

.3 + 3(1000)(9 .807)11000 = 145'4

kPa

p = 145.419'807 = 14.8 m

= O.O3 mu/s

30 L/s

10-21. Size the pipe using Fig. 10-20 or program PIPE. Fitting equivalent lengths found using Fig. 10-22a; 10-22b and able 10-2' Program PPE could be used to solve the complete problem including fitting losses. Data for hard calculations are summarized below:
xcerpts from this work may be reproduced by instrutors for distribution on a not-for-pro1it basis for testing or instrutional puoses nly to students enroled in ourses or whih the textbook has been adopted' ny other reproducion or rnstion of his ork beyond ht permitted by Sections ]07 or 08 ofhe 976 Unied SleS Cpyright clihu he permission ofhe cpyrigh oner is unful.

198

lO(3)

ro(3)

1ot3]
I

/o\

\:-/

o(3)

55)

Sec.
No.
1

qpm

stze
3

it
ft./'100 ft

Le
ft.

t
ft.

tn.

Valve

Con.
ft.

Coil
ft.

otal
ft.

120
70 2.5 40 2 40
2

3.38 3.64
3.'1 3.'1

45
'15

1.5

1.5

0.6 0.7 0.4


1.6 1.4
1

0.6
11.4
12.1

6 7

24
13

12.0

12.4
1.6 1.4

4
10 2 3

90 2.5 120
3

5.84 3.38 4.7 4.7


6.3 6.3

27

42
22

5
2 50 2 30 1.5 30 1.5

10.0 10.0
14.4

11.0 11.2 16.2

26 28
13

1.2 1.8

I
9

0.8

15.0

15.8

ch

120

20

Exerpts lrom this work may be reproduced by instrutors for distribution on a not-1br-profit basis for testing or instructional purposes only to students enrol]ed in courses or whih the tXtbook has been adopted' ny her reproducin or trisltin of his ori beyoncl h permitted by Secions ] 07 or 08 of he ] 976 (nted SeS Copyrigh ct wihut the peimission f he cpyrigh ower is uncnful.

199

same.

The head losses for the three parallel runs are approximately the

For run (1-5-6-Z-4-10), Hp = 49.6 ft For run (1-5-S-g-10), Hp = 55.5 ft For run (1-2-3-4-10), Hp = 46J ft Therefore, a pump should be selected to provide about 56 ft of head at
120 gpm.

10-22. 500 gpm, Use 5 inch pipe; !'f

4.17 fil1OO

ft

= 8.0

ftlsec

Length of pipe = 160 + 3O + 12 = 202 6-5 in elbows = ,lS

ft

ft

(Figure 10_22)

3-5 in gate valve = 12 ft


1-5 in gobe valve = 130 ft; Total equivalent length = 419 ft

. 4.17(41e\ /, = -_1}-J "/ =


For strainer: ! For cond

17

'5 ft of water

!
17

"o

2.31 = e.24ft of water "= = 20 ft of water

[#)'

hen Hp =

'5 + 9.24 + 20 + (3o

12) = 64.7 ft at 5OO gpm

10-23'Use q. 10-33

Exerpts frm this work may be reprodued by instructors for distribution on a not-or-profit basis fbr testing or instructional puoss only to students enrolled in ourses fr which the textbook has been adopted ny her eprdacton or rq'nsion of his ork beynd th permied by Sections ] 07 or 08 of he 1 976 United Ses Cpyright ct ihut he peimission of the cpy.igh owner is unlfu.

200
,,_

".

_ -

6oott*:;*g
I

-,l) - 3x6 sxlo-u (1,0


og.g ]

-oull

gz.g

= 19.4 9a1. = 74 L

10-24' Use Eq. 10-34 v,


Vr-_8.-gal
=

oo[[9

g L[ 0'10zz

_,'l _ 3x6.5x1

o_u (1,, o _

'-___-_-J

ou1l

33 L

'_ 69:%,

10-25. Use Eq.

10-33 tl = 60oF, P2= 50 psig, P1 = 20 psig, v1 = O.O1653 ft3/lbm

vz = O.O1 6772 ft3/lbm, tz = 220"F

V=

= _11_5_gal.

435 L

10-26

(a) Use Eq.

'10-16

P,+ PPz= Pzgzz +v+g

'g"9c
=

lL
9c

24o
t,

''

ff

(zz-z)+ w

P9n LE
-

9cl

Exerpts from this work may be reproduced by instrutors for distribution on a nt_for-profit basis for testing r instructional purposes only to students enrolled in ourses for which the textbook has been adopted,' ny other reproducton or ffion of his wori beyond-h permied by Secins ]07 r ]08 fhe 976 L]nied Ses Copyrightcthou he peimission fthe copyrigh ower is untful'

=
(b)

e4o)

#(60)

es1=Be psis or
61

2 kpa201

P,'+g!= P2+g2 9c - --gc


Pz=P-

(z-zz)=89.o
=

-effi
has a

Pz = -15 psig

-i03 kpa or about o absorute

(c) No, makeup water is not available to overcome a pressure of gg psig. However, the domestic water system probabry
booster pump.

10-27

(a)

Pz *

o* (zz-z) + * 9, gc 9c
62.4(60)

62.4(240) 5+ 144

144

62.4(25) 144

'n0.8

Pr = 93.8 psig or 647 kpa

(b) =Pz+
Pl

!9
9c

(zz-z)

5 *62|(,2ra0) = 5 + 104 =.t09 psig

= 109 psig or 752

kPa

Excerpts from this work may be repoduced by instructors for distributin n a not-for-profit basis for testing or instructinal puoses only to students enrolled in courses for which the iextbook t-,u. ".n permied by Sections ] 07 or 08 of the ] 976 1dj -l rir, rpr"a""ron or rnslion f his work beyond h United Stes copyrighi c withu he p,e1mison of he copyright ner is unlful.

202
(c) This location is at east workable. owever the pressure at the pump is still very high. The domestic service water

floor.

pressure would have to be boosted to a higher pressure at the 2oth

10-28

(oo , sz)
Qo

(a,

x +o)=

(ao x

*Q.

Q= 100

Solve Simultaneous
57Qb + (O x 1OO) - 4OQb = 100 x47

ab =
(b) (c)

17

= 41.2 say 41gpm 41 = 59 gpm

Q.

= Q.. = 1OO -

Size all pipe for 100 gpm


D = 3 in. from Fig.
'1

0-20 or PIPE

10-29. (a) Each chiller requires 600 gpm. Since chiller 2 is partially loaded
must have the full flow of 600 gpm. Therefore, Q"p = 1200 - 750 = 450 gpm

it

(b) (150 - 60)

+ (450

x 42)

600 ts, ts

46.5 F

(c) LR

= 150/600 = 0.25
stl.

(d) Main pipe to and from sec. Circuits: D = 8 in. com.

Excerpts from this work nay be reprodued by instructors for distribution on a not-for_profit basis fbr testing or instructional puoses only to students enlled in courses for whih the textbook has been adopted' ny ther reproductin or trnslion of this work beyond h permited by Sectins ]07 or 08 fhe ]976 United Snes Cpyrighcihu the permissin ofhe copyright oner is unlfu'

Dns = Dco = O in. com. sfl. (S in. a litile small)


D"p =

203

6 in. com. sfl.

in.)

Dsc = DRo = 6 n. com. stl. ( could be 5 in. but easier to make all 6
= PIl

(e) Rpm,

050l12oo)

= 35OO(75o/12o0) =

2188

( W
or

*#=1-ff

=,l_[ffiJ' =, (##)

= O 756

75o/o

10-30. (a)

Q"n = 12OO

-750

450 gpm

(b) Qrtr

(450x42)+ (750x60) = 53.3 F 1200 Both chillers receive the same temp. water
+ Qztz = Qsts; ,. =

(c) Load
LR=
10-31.

ratios are the same:

##=0628or63%

xcerpts from this work may be reprodued by instructors fr distribution on a not-for_profit basis fr testing or instrutiona puoses only to students enrolled in courses for whih the textbook has been adopted. ny her )eproclucion or rnslin of this rk beyoncl th permitted by Sectin's 07 or 108 of he ] 976 Jnitecl Sttes Cpyrgh c wthu he pession of the copyright ner is untful.

204
10

(13)

2(6) 3

*{s) **nt*if r
T'r^;n }iJJ' ^
!

u?

1*{S}

*{s} s 2(s) 8

Ba*n*s ve,v* {typi*aii

**rnnr** pip*

Note: Piping is type L copper ll |engths are total equivalent lengths

10-31.

Fow rate Coil opm (L/s) A 40(2.5) B 40(2.5) c 50(3.2) (continued) Dia.

Lost head ft (m) Coil Con. valve 12(3.7) 10(3) 15(4.6) 12(3.7) 18(5.5) 15(4.6)

Section
No.
1-2

gpm
130 90 50
3

ir
ftl10' 3.7 4.8 5.0

L"
ft

in.

!.r ft

2-3 3-4
^,^il

2% 2

60 20 30

2.2

r;

355

' he reproduced

by instrutors for distribution on a not_or-profit basis fortiting or instructionai puoses ony to -h hih the textbook has been adopted' ny oher eprduction r rislin of his wori beyond ''/ United Ses Cpyrigh c ithou he permission of he copyv.ight oer is unlful.

Con. C 4-5 Com. oi 2-6 Coil A Con. A


3-7

205
130
0 3 3

3.7 3.4

40
30

40

Coil B Con. B 7-8

40

3.4

10
10

15 1.5 0.0 39.2 1.0 12

ft

(tote

23

80

2%

3.9

20

0.8 28.3

0.5 15 12

ft
ft

(total)

(totat)

Circuit 1-2-3-4-5-1 is the path of greatest lost head. From Fig. 40 ftof head and 130 gpm the 7 in., 1750 rpm model which
ft of head.

choose at froduces about 43


1O-1 1

p^q 2 2 lbu] 2(r)3(r}


t p,ih-*:y +* PumP {12)l 4Q t1i
f

s*ianc* vxl* {typi*ai}

{}

*hill*r

p l ]$} $

*ntr*i . valv*
{

typi*xi}

10-32. Notes: Ppe is schedule 40, commercial steel. ll lengths are total equivalent lengths exc|uding control valves.

Circuit

Flow rate gpm (L/s)


60(3.8) 70(4.4\ 70(4.4\

'' be reprodued by instrutors for distribution on a not-for_profit basis for testing or instructional puoses on1y to "hih the textbok has been adopted. ny oh-er )eproducin or rhin o7 tn beyond th '976 United Sttes Cpyrigh c ithou the peission of he copyright ner 'or is unlwful.

Control valve head loss ft (m) 40(12) 5(15) 50(15)

206

Section
No.
1-2 2-3

Dia.

gpm

if
ft/'l00' 2.4 4.2 3.5 2.4 2.5

L"
ft

(.t

in.

ft

200
140 70

3-4 Con.
4-1

4 3 2% 4
2% 3 2%

200 200 240


400 240

4.8 8.4 8.4 50


o

200
60

2-5 Con. A 5-4


3-6

9.6
40

81 .2

ft tt ft

(total)

140 70

4.2 3.5

200 40

8.4

54.4 51.4

(total) (total)

Con. B

50

1.4

Circuit 1-2-3-4-1 has the largest head loss of al paths. Select pump for 2OO gpm at 81 ft of head. From Fig. 10-1 1, use: 5' in., 3500 rpm model. Will operate at 96 ft at 200 gpm. 10-33

(a)

qst = 20

x 12,000 x2= 480,000 Btu

/1

c, (t,.-t.)

gst

480000
62.4(1) (60-45)

512.8 ft3

orQ=3,8369a1

(b) Vol

= 513 ft3 10.2 ft

ora Space

ftx 8 ftx 8 ft ora cyindrical tank

8 ftdia. x

10-33. (continued) Solution - Sl:


(a)
Qg1

(352_280) (2)= 144k\^l-hr= mc, (trt.) _ Qcp(t-t.)


144 x3600 = 14 m3 980(4. 184) (1 6-7)

Qst , (t1ts )

' 1le reprodued

by instrutors for distribution on a not-for-profit basis for testing or instrutional purposes only to '.'hih the textbok has been adopted. ny oher reproduction r trnsltion of his wrk beyond tht ^76 (ned Ses Copyrigh chout he permission fthe cpyrigh oner is unlful'

207

(b) Vol.

2mx2.4mx2.4m
is:

10-34. Solutions may/can Vary. typical solution

(a)

Use 2 chillers of '15 tons total capacity in a reverse return system similar to figure 10-32. The piping would be routed overhead around the complex with supply and return running parallel, starting and returning to the equipment room.
Total flow rate is

(b)

Q =16 x2'25

36 gpm Using PIPE or Fig 10-21; Dia. = 2in'

(c)

Estimated length 3600 ft

=225x4x2= 1s00ft.

otal Eq. Length=2x 18OO

Assuming an average oss of about 2.5 ft1100 ft; The pump head required would be:
Hp = 2.5 x 3600/100 = g0 ft with flow rate of 36 gpm

'10-35 Solutions may vary


(a)Figure 10-34 is a schematic of what the system woud be. However, there would be 3 chillers and the secondary piping would be routed in a square fashion around the outside of the parking
garage in reverse return.
(b)he primary system would appear as in Figure 10-34 with the

common pipe as shown because of the expected variable and light


load at night.

(c)The tertiary circuits would be as shown in Figure 10-34 and piped in a reverse return manner. (d)For each building:
Excerpts rom this work may be reprodued by instructors or distribution on a not-fr-profit basis for testing or instrutinal puoses only to students enroled in ourses for whih the textbok has been adopted' ny other reprductin r rislion of his ork' beynd tht pemitted by Sections 07 or 08 of the ] 976 tJnited Ses Cpyrigh c 1ihou the permission of he cpyrigh owner is un:wful.

208

4x500(60-45) = Q=4x600 =2400 gpm


=

Qi

1500 x 't2000

600 gpm

(e) Dia. = 10
10-36.

in., Figure 10-20 or plpE

Y a_Air Vent (Typical) ,+9*4 Heating Device (Typical) r-


T<-TypicatTrap

;Contro valve (Typical)

IE

er--] < !- - -<-'-' -2


;-

o r--5

Possible

Vacuum Breaker on each Heatinq Device

10-37

'

ssume boiler pressure of 2'O psig with P/L = 2'O oz or 0'125 psi/1OO ft' (Tabe 10-4a). hen, P = o'125x 175l1OO = 3'5 ozor 0'22 psi P is about zthe alowabe from Table 10-4a'

Assume boiler pressure of 1.o psig with P/L 0'125 psi/1Oo ft. (Tabe 10-4a)' Then P = 0'125 x 175l1OO = 0'22 psi which is near the maximum in able 10-4a' Either boiler pressure could be used,
but select2.0 psig to be conservative.
xc-erpts fiom this work may be reproduced by instructors fr distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in curses for whih the textbok has been adpted. ny oher reproducin or rnsion of his wrk beyoncl tht permited by Sectins 07 or 108 of he ] 97 6 (]nitect Stes Cpyrigh} c ith'u he peimission of he cpyright er is untfu.

209

From Figure 10-48a at 850 lb/hr; P/L = 0.'125 sil100 ft, and boiler pressure of 2.0 psig: Pipe diameter = 4 in., with steam velocity of 4,00 ftlmin at zero psig. Correct velocity to 2'0 psig (Fig. 10-49a)

= 3,800 ftlmin

10-38. For each

ft.

unit at full load: = 283 lb/hr

Pipe size depends on slope of line, able 10-5a. For slope of 1/8 to in./ft, D = 1 in. nominal specify slope of % in./ft (conservative).

10-39. Refer

The available head is = 2 x'100/110 = 1'82ftl10 ft. Then at 850 lb/hr of condensate flow, D = 1 in. nominal is adequate.

to Table '10-5a.

10-40

(a)

q = rhcp(t,-t,) =

ga##(1)(6s
-..-

- 42)

' ^

1200x7'48 = 1'250 =1200x624(654 - ^F^ gpm 60 X

(b) ssuming no changes in the temperatures, the total flow rate would
., =

-P 9t 1l25O) 1200 \
'/

be:

937.5 or 938 gpm

he chillers could share the flow:

-=469gpm (J, ^-938

= '2

and be above their minimum flow of

70o/o.

Qmin

469 625

0.75 or or Ts%

Ecerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instrutional puoses only to students enroled in ourses for whih the textbook has been adopted. ny ther reproducin or rnslion f his ork beyond th permitted by Secions ]07 r 08 fthe E976 Lnied Sttes Copyright ct\ithout he pe'mission fhe copyrigh wner is unlvful.

210

flow and the parallel pumps coud operate at:

his is probably the best way to operate. here would be no bypass

RPM,

*x 625

35OO =

2,626

(c) At 6% full load, again assuming no change in temperature, the


tota flow rate would be:

Qp = 0.6(1 250)

750 gpm

This is too much flow for one chiler and not enough for two chillers at minimum flow of 875 gpm or 438 gpm each. herefore, both
chilers will have to operate at least at 438 gpm each and some ftow

bypassed equal to:

875 - 75O = 125 gpm

The pumps could both be slowed to:

RPMP = '

,9'? 1250
fu

35o) = 2'450

(d) t 25% of

capacity, again assuming the temperatures do not

change, the flow rate for the load is:

d,

= 0.25(1250) = 313 gpm

which is less than the minimum flow rate for even one chiller. herefore, shut down one chiller and operate the other at least its
minimum flow of 438 gpm. The bypass flow would be: Qop
=

438 - 3]3 = 125 gpm

One pump would be shut down and the speed reduced for the other
pump to:

RPM, '

*(3sOO) =2,453 625

Excerpts 1iom thrs work may be reproduced by instructors for distributin on a not-for-profit basis for testing or instructional puoses only to students enrolled in urses for whih the textbook has been adopted. ny other reproclucion r rislion of this work beynd'tht permitted by Sections ] 07 or 08 of the ]976 Unied Stes Cpyrigh c withu he permission of he copyright owner is unlfut.

Excerpts from this work may be reprodued by instructors for distribution on a not-fr-prfit basis for testing or instructional pulposes only to students enrolled in courses for which the textbok has been adopted. ny other reproduction or trsltion of this work beyond tht permitted by Sections ]07 or 0B of the 976 United Sttes Copyright ct without the permission of the copyright iwner is unful. Requests for permission r further informtion should be ddressed to thi permission Deprtm'ent, John Wiley & Sons, nc, ] ] Rier Street, Hobken' NJ 07030.

GHAPTR
11-1

11

(a) Using Eq.

'1-1b

1=L959ll-,

J"
1:

' s5 '-Ao = = O.353


=

ft2;

ssumed K

=6

X5o

' 50.,/0.353

-=ug-^o)

68.5 ft;

x1

= 34.2ft; xlso = 22.8ft

(b) Q,

CQov"/v,, C = 2; q. 11-2a

(Q,)so = 2(3OO)850/SO = 10,2OO ft3/min (Q,)loo = 6O(85O)/1OO = 5,1O0 ft3/min (Q,)rso = 6OO(850)/150 = 3,400 ft3/min

11_2'

Using q. 11-3
t, _ t, = 0.8(to _ t.)

(V,/Vo), t,

= 0.8(100-75)

V,ll'tO

(t,)so = 0.8(28)50l1100 = 1'02 F


(t*)loo =

2'04 F

(t )lso = 3.06 F

11-3.

50 ftlmin throw = 24

6 = 18 ft

212

From Eq. '1 1-'1 and Qo = Vo x o; Assume K

=6

;=1l3Kro'ffi

Qo_

Q"

*v* 18 x 5o =1.13K - .13x6


'1

= 132.7
D^

ny combination shown would


on the available total volume

be

acceptable. The size would depend


flow
rate of air and the size of the space.

29 39 49 59 118

ln.
a

ft.

J 4
5

0.25 0.33

0.4t7
0.500 1.00

t2

11-4.

Q,

Q oC V Q o/Ao

Vo=

= zstl Lr-

"lV,

Eg. 11=2a

V,= V"(1.13)Kl lx ; K=

L4 \z1

r9)'l=
1

s fVmin

6, x =

12ft

vr=

636 x 6(1 .i q'4 t12 = 159 ft/min ^l+x(O.S)2

'

Qr= 125x2x6361159
11-5.

= 1000 cfm

A ceiling type diffuser system has the ability to handle large


quantities of air because the air is discharged radially and

diffuses the high velocity jet in a short distance.


11-6. (a) A perimeter type system would be necessary to achieve a

satisfactory heating performance. ny other type of system would lead to a cold and drafty floor.

Exepts rom this wrk may be reproduced by instructors for distribution on a not-fr_proft basis for testing or instrutional puoses only to students enrolled in urses for which the textbok has been adopted. ny other reprduction or trns{ion f this work beynd h permited by Sections ]07 r l08 ofthe 976 tJnited Sttes Copyrighctihouthe permission ofhe copyrighneris unlllfu.

(b)

An overhead type system would be preferred because of the greater need for cooling during the summer and less need
for heat durng the winter.

213

11-7

'

system is required to do a good job of heating. spreading jet should be used when heating and a nonspreading jet should be used when cooling.

perimeter type system would be the best choice. This type

11-8'

Some kind of overhead system woud be preferable since cooing would be the dominant mode of operation. However,
ceiling diffusers with radial discharge woutd not be required due to a low volume of circuated air' high side walt type of system or ceiling diffusers with discharge in only one or two directions
with a arge throw would be preferred. This would give the maximum air motion with a smal amount of circulated air.

11-9.

10 in. round diffuser, Tabe 11-4;650 cfm

lnterpolation between 600 & zoo cfm is required

NC=0.5x(21 -17)+17=19
x5o = 0.5(1 1-10) + 10 = 10.5 ft

p=oo62(ffi)'=oo73in
11-10.

wq

For 150 cfm/ft, Po

= O.08

x (150116712 = O.65 in' wg.

Excerpts from this work may be reproduced by instructors for distributiol on a not-for-profit basis fr testing or instructiona puoses only to students enrolled in courses for which the textbk has been adopted ny oh,er aurton or rnslion f this wrk beynd th permitted by Secions ] 07 or 08 of he ] 976 ('|nited Ses Cpyright ct w ihu he p,e{m|sson of he copyrigh oner is untnfut.

214

Throw values are for a 4 ft active length then


X5 =

21 _ 0.6(4) = '18.6

ft;

he uncorrected NC for a 10 ft length is NC


For a length of 6 ft the correction is -2.

= 23

_ 0.6(5) = 20.

Corrected: NC
lnterpolate:

= 20

-2

= 18

11-11. Model 28, 4-48 T-Bar; Table '1 1-6, 270 cfm
NC
0.7 (36

32) + 32 = 34.8 or 35

xso =

0.7(11 -10) *
, ^-^'t2

l0

= 10'7 or 11 ft

p=O.r[

245

+l )

=o.13in.wq

11-12' From Table 11-1, L = 12 ft' Then


Q=

from able 11-2 at

40 Btu/(hr-ft21, lxuo/L1rr*

=1.3 and the range is1.2 - 1.8, and X5s = 1.3

x12= 15.6ft

A good solution would be to use the 4 in. size with


'150 cfm/ft. with uncorrected throw of 18 ft and

NC

= 19.

The corrected throw is:


Xso ='18 x 0.85 = 15.3 ft and

NC = 19 - 4= 15

0.057r)'
139

= O.066 in. wq

11-13. (a) Room char. Length


Range of xso/L

= 14 ft,

Table

1 1-'1

(x5/L)rr, = 0.8, Table 11-2


= 0.5

to 1.5; xso = 0.8 x 14= 11.2ft

Eerpts fom this work may be reproduced by instuctoS f distribution on a not-for-proft basis for testing or instrutional purposes only to students enrolled in courses for which the textbook has been adopted. ny other reprducon or rnsion f this ork beyond tht permited by Secions ] 07 or 08 f the ] 976 Jnied Sttes Copyrigh c l ihou the permission f the cpyrigh wner is unlwful.

The best choice would be a 12 in. size with 600 cfm

215

(b)

xso =

13.

--'-'--'- 14'3 :9 Q) = 14.3ft;x5e/L 80' 14

= 1.02(in the range)

Po = o.o81

(ffi)'

0.0g6 in. wg., NC =

22+ffol

=24.5

11-14.
(a)

Room char. Length is 26 ft,Table 11-2


(x5/L),,, = 1.6 (Table 11-2); range of (x5g/L) = 1'2
Xso = 1.6 x

- 2'3

26 = 41.6 ft; Q/diff = 60012 = 3OO fm From able 11-5, the 18 x 4, 14 x 5, or


= 31 ft

12 x 6 sizes may be acceptable athough the throw is

less than desired. Xso

Xso/L = 31.6126 = 1.2 (barely in the acceptable range)

(b)

Xso =

31- ft (zero defection)


22*,

NC =

^po:

o.o6e

(#)'=

0.065 in. ws.

11-15

lt is good practice to keep the core veocity below 5OO ftlmin.

solution is the 18 x '1 2; Table 11-7

Po- -o.O45

65 NC= 21 + fZl 135' =24


Note that static pressure and Po are negative.

[,)' 535/

= -O.O57 in. wg

11-16. Guidelines:
1-Place diffusers under or between double windows. 2-Select throw using the DPl procedure. Characteristic length
xerpts from this work may be reprdued by instuctoS for distribution on a not-for-proflt basis for testing or instrutional puoses only to students enrolled in courses for which the textbook has been adopted' ny oher reproduction or risltin of his wori beyond'tht permied by Seclins ] 07 or 08 f he 976 Unied Sttes Copyrigh ct ithout he permission f he cpyrgh ower is unlwful.

216
=

floor to ceiling.

3-Noise criteria (Nc) should usualy be less than 30. 4-Be Sure that the tota pressure required is compatible
with the pressure characteristics of the system. For example, a smal commercial system may have a fan that produces only

about 0.6 in. wg. total pressure while a large commerciat system may operated at2-5 in. wg. total pressure. The diffusertotal

pressure osses should be no more than abo ut 10% of the fan total pressure.
5- Use data from Table
11-17
1

1-3

'

Guideines:

1-center diffusers in square or nearly square spaces. Divide large or irregular spaces into imaginary square spaces and
pace a diffuser in each Space. Select throw using DPl procedure. 2-ry to obtain a balance between many small diffusers versus
a few very rarge diffusers to be cost effective.
?_ v

4_ t

See Problem 11-16

5- Use data from Table 11-4

11-18. Guidelines:
1-Locate diffusers about 12 in. below ceiling on inside wals. Setect
throw using ADpl procedure. 2-he jet may be spread with this type diffuser. However, more than one diffuser should be used where the room width is at least two times the room depth.
3-

Exerpts frorn this work may be reprodued by instructors for distributin on a not-fr-prfit basis for testing or instrutional purposes only t students enro]ed in courses for which the textbook has been adopted ny ol'r, rpioaun or rnslrin of this rk beyond h pemied by SeCionS 07 or 08 fhe ]976 (]nied Sqtes Copyrigh' clihu he peimssin fhe copyrigh ner is untful.

. I See problem 11-16

v&

45- Use data from Table


1

217
'1-S

Excerpts from this work may be reprodued by instrutors for distribution on a not-for-profit basis for testing or instrutional puoses ony to students enrolled in courses for whih the textbok has been adopted' ny other reproduction or trlion of this work beyond'th permitted by Secions ]07 or 08 ofthe ]976 (]nied Sttes Copyrighcithou the permission fhe cop7righ ower is unlful.

218
-ffi

11-19. Guidelines:
'1-Locate grilles in ceiling near the inside wall.

2-Noise criteria (NC) should be less than 30. 3-The negative static pressure should be held to minimum, especially for light commercial systems with small fans.

core velocities of less than 5oo ftlmin will usually yield a quiet system with a reasonably low-pressure loss. Higher
velocities and pressure ross may be tolerated with heavy commercial applications. 4- Use data from Tale 11-7.

11-20.

(a)

+l+

H-24, Mod 28 at 89 cfm each

<-l-+ +l-+

2'-windows

*l-+ +t-e +l-r

l+ +l-,

_+

(b)

X1oo=

89 cfm/diffuser; Po ote: other acceptable soutions also exist.

3ft; L =7

ft; X19/L

=3l7

= O.43; o.3 < (x19/L) < 1.o 0.06 in. V/g.; C = 20

11-21. Simiar to

11-2O - Diffusers shoud throw air towards the windows - Arrange to obtain uniform air motion - Might use diffusers with short throw around exposed walls with larger units in the interor.

11-22. L = 9 ft; Table'l i-1


Exepts from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional puoses only to stdents enrolled in courses for whih the textbook has been adopled,' ny othe, )eprocturton or trnstion of his ork beyond h pemied by Secions ] 07 or 08 f the ] 97 6 tJniez Ses Copyrgh' ct thut he peission f the cpyrigh oner is unlwful.

xso=0.9x9=8.'1
Po =

219 X59/L = 0.9; able 11=2, straight Vanes ( Assume light load for a secondary system)
ft
11

solution: 9-4 ft length diffusers with 50 cfm/ft, 2 in. size, able 11-3, x = 8.5 ft (no correction required); NC = 15 - 4 = Place 3 diffusers on each exposed wall
4-'12 in. size from able 11-4
=

0l4q2 x O.036

= O'047 in. wg.

11-23. Use

650 cfm/diffuser; L Room Load = 18

20

ft

80

Btu
78

= (hr _ ft )

x5sil

= 0.8,

Table 11-2

x = 16 ft (desired)
Xactual

F5

(650 - 630)
_

63i

(7 _ '15) + 15 = 15.5 ft
range)

xact_15.5_., -fl : = 0.78 (in acceptable ^


NC = 27;
Po=O 105

r]'= 630/

O.112 in. wg.

11-24' Use
=

14-H-48, Model 28 diffusers from able 11-6;


= 20 ft, xlse/L

229 cfmldif. as shown. L

0.3 and acceptable range is 0.3 to 1.0.

xcerpts 1iom this work may be reproduced by instrutors for distribution on a not-for-prfit basis fr testing or instructional puoses only to students enrolled in ourses for which the textbook has been adopted' ny ther reproductin or trnsion of his ork beyond-th permited by Secions ] 07 or 08 of he ] 976 United Stes Copyrigh c ithou he permissin of he copyrigh oner is unlrful'

220

Desired throw: xloo = 0.3 x 20 Actual throw:


Xact =

= 6 ft.
'1

6.5, Tabe

'1-6
80

Xr"t/L = 6'520 = 0.33,

o.K.

NC

29, Po = 0.095 in. wg.

ltLr
78

11-25. Refer to Problem 11-23, Q


return, limit NC to about

2600 cfm; refer to Table 11-7.


with

ssume a ay-in ceiling with 2 ftx 4 ft tiles. o assure a quiet

20. Use 2-24 in. x24 in. grilles

1300 cfm each. Nc < 25, Po = -0.048 in. wg.

11-26. Refer to Problem


Assume

11

-24,3200 cfm.

a2ftx4

ft lay-in ceiling.

Use 24 in. x 24 in. size from able 11-7


cfm/grille = 320013 = 1067; Nc < 2
Po = -0.033 + 0.006 = -0'027 in. wg.

'

Using three units,

Excerpts fiom this work may be reprodued by instrutors or distribution on a not-for-profit basis for testing or instrutional puoses only to students emlled in ourses for which the textbook has been adoted' ny her reproduction or trnstion of his work beyond h permtted by Secions ] 07 or 08 of the ]976 tJnited Stes Cpyright c ithou the ermission of he copyright oner is unlfu.

Exerpts from this wrk may be reproduced by instructors fr distribution on a not-for-profit basis for testing or instrutional puoses nly to students enrlled in courses fr whih the textbook has been adopted. ny other reproduction or trnsltion of this work beyond tht permitted by Sections ]07 or 0B of the t 976 United Sttes Copyright ct without the permission of the copyright owner is unlwful. Requests for permissi or further informtion should be ddressed to the Permission Deprtment, John Wiley & Sons, nc, ] ] ] Rier Street, Hboken, NJ 07030.

CHAPTER
12-1.

(a) W.

= rt (Pl

_ Pz)l ssume standard air


= o.60

(b) r,=
(c)

ffi
=

Q(Pl -P2) _ 2oo(1.9) 6350 6350

HP - O.45 kW

=#ffi+

= O 54 Pu =

or 54o
=

= 2Ooo/O

'84=2,381ft/min,
0.35 = 1.55 in wg

Q381l4ooq2

.35 in wg

P. = 1.9

W"

2000x'1.55 = 0.49 6350


=

s = Ws/Wrr,

0'4911'1 = 0'44 or
= 1.55 in wg

44o/o

(d) From

(c)

abovet P,

12-2

Qz =

a,
=

#ffi

2ooo

(ffi#)

=24oocrm

= 1,133 L/s

P,z

P.l

[Hffi)'

= 1.55

(ffi#)'

= 223in wg 555 Pa

Poz =

".[ffi)=
]'
=l

(pv")2

o( -*9\ =z'in -1Oo/


'1

wg

=682Pa

W,

\i, [RPM, RPM1

'

(12o0lu 1000/

l.9 HP = 1'42k\

221

12-3.

(a,b) Qz =

Q (750i900)

0.833 Q
P1

Poz= PO1(75ol9OO)2 = '694

HPz- P1(75oi9oo)3
80 RPM

= 0.579

HPl
7OO

RPM
Po

a
6,000 10,000 14,000 12-3
2.4
J

Po

HP
2.75
3.5 3.45

a
5,250 8,750

HP
1.84

2.3
1.87 1.15

1.76 1.43 0.88

2.34
2.31

12,250

6 5 (d)

2.0

'1.6

4
3 (L

1.2
U)

Po = 1-30 in. wg = 9625 cfm P = 2.34

E o

0.8

2
1

t- 0.4
0.0

02

468111214
cfm x 10-3

12-4. Since pressure in in. wg. is plotted on the ordinate instead of head the
pressure must be adjusted to reflect the barometric pressure at 5280 ft
elevation.
Po = (Po)rt(/P.t) = (Po).t(Po/Po,'t)

also, W = W.t(/Ps*o)=
Po,,t =

Wr16(P6/P5'r16)

14.696 psia; Po = O.491(29'42 _ 0.0009 x 5280); Eq. 3-4

or instrutional puoss only to Excerpts from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing of this work beynd ht enrolled in courses for wtrih the tixtbok has been adopted. ny other reproduction or trnslion students oner is unful' 08 of he 976 Lnitec] Ses Cpyrigh} c )ithou the permissin f he copyrigh permied by Sectins ] 07 r

222

Po = 12.112 psia

hen in Denver,

Co the

ne\M characteristics

may be obtained by
Wst.

computing Po and W at various volume flow rates from Fig. 12-8.


Po = (Po),ro(2.112t14.696) = 0'824(P6)916 ?d

W - 0-824
14,000

Q cfm
6,000
Po

'10,000

W
2.75 2.27

Po

W
3.5

Po

W
3.45 2.84

Sea Level
Denver

2.3 1.9

1.87 1.54

1.15

2.88

0.95

:. (w",0 - w)1oo _ 3.5 - 2.88 (b) W=ff= 35


.

= 18% (decrease) 12-4 for explanation.

12-5. Refer to Problem


P6 = (99.436

0.10 x 1618) = 83.256 kPa

Po = (Po)st = (83.256/101 '325) = 0.822(Po).16 \/ = Wst

x0'822

(a)

Q
125
Po

m3/min

155

180

W
1

Po

W
1

Po

W
2000

Sea Level
lbuquerque

400

350

320

600

260
214

329

1110

263

1315

1644

nly to Excerpts from this work may be reprodued by instrutors fr distribution on a not-for-profit basis for testing or instrutional puoses wrk beyond h students enrolled in ourses fr whih the textbook has been adopted. ny oher reproducion or rnsin of his permited by Sections ]07 or 08 ofhe 976 Unied Stes Copyrigh ctwihout he permission ofhe copyright oner is unlful.

(b)

(1600--1315) W = 10O = 17'ro/odecrease 1 600

223

12-6. (a)

This is at the limit of the good selection range. lt would be


better to choose a different fan.

(b) near perfect match with the fan capable of producing about
1.85 in. V/g. tota pressure at 10,000 cfm.

(c) A bad application and

out of the recommended range.

Would probably be unstable.

12-7

[From Fig. 12-9]

(a) No, fan (b) No,

is too small.

not a good application, fan is too large.

(c) YeS, near perfect appication; moderate fan speed,


high efficiency.

12-8.

150 m3/min, 4OO

Pa

[From

Fig 1 2-10J
W
= 2OOO ft/min

The fan would be acceptable and is reasonable.


1 =

55%; RPM = 85O;

W,

= 185o

12-9.

(a) At 1418 cfm = 1420 cfm, Ve


P" =

[+l' 4005,
-

o.zs

in. wg., Po =

P,

P,

= O.88 in. wg.

P.

= 0.88

0.25 = 0,63 in. wg.

518 in. wg.

Ecerpts from this work may be reproduced by instructors 1br distribution n a not-for-profit basis for testing or instructional puoses only to students enrolled in ourses for whih the textbook has been adopted. ny ther reproducion or rnslion of this rk beynd th permitted by Sections ] 07 r 08 of the ] 976 United Sttes Copyright c ithu he permission of he copyright ner is unlful.

224

(b) From able

12-1 in col. For 5/8 in. wg.

The rpm is 1092 and power is 0.39 P

0.94
O.BB

\o10e2

rPm

0.80

1240

1420 cfm

12-10' (a)
(b)

Po = 3.0 + 0.3 + 0'20 = 3.50 in. wg.


desired

fanr ,' . tP {z'

svstem with svstem eifect factor

3.
3.CI

'osystem wlthout system


effect fator

iffu"

setection without system effect factor

Q cfm

't3,500

15,00

(c)
12-11.

13,500 to 14,000 cfm

/2istem, actual

,,f-r whiih tl

r ]08 fthe ]9

225

System eff. Factor 12-12' D" = (4 x 12 x

610

- 430

.1gO

pa

16l)112 = 15.6 in = 0.7,

ssume blast area ratio

Table 12-3

\/ V = 400(1 2 x 161144) = 5333 fVmin " One eff. Duct length = 5.3 diameters, table 12_2 or L" = 5.3 x '15.6 = 83 in. % ff ' Duct length = 100 x 30/83 = 36

Elbow in position C, Fig. 12-13


Ebow loss factor = 0'79, able 12-5
Po = 0.79(5333l4o0q2 = 1.40 in. wg.

12-13' V

= 4OO

0l

x 142l14 x 1aa)]

4,276 ftlmin

Duct length = 28 in.; R/D = 10.5114 = o.7s; L/D = 29114 = 2.0 Elbow and duct loss factor = 1.O, able 12-6
Po

1'0(4276l4ooq2 = 1'14 in. wg.


=

12-14' Blast area ratio

0.7, Tabe 12-3

D" = (4 x 20 x 2Ol)1l2 = 22'6 in.

= 1O,OOO

1441(20 x20) = 3,600 fVmin

L" = 3.6 dia., Table 12-2


L/Le

(0122.6)13.6 = 0.12

Co = 0.4,

Table 12-4

Po = 0. 4(3600l4ooq2 = O.32in. wg.

12-15' D" = (4 x 12 x 12l)1l2 = 13.5 in.


Exerpts from this work may be reproduced by instructors fr distribution on a nt-for-profit basis for testing r instructiona1 puoses ony to students enrolled in curses for whih the textbook has been adopted. ny her reproductin or thfin f his wri beyond h permied by Seclions ] 07 r t 08 f he 1 97 6 Uni ed Stes Copyrgh c ihout the permission of the copyright oner is unlwful.

226

V"

= 25001(12x 121144) = 2500 ft/min


=

One eff. Duct length

2.5 diameters,Table 12-2

L = 2.5 x 13.5 = 33.9 or 34 in. 12-16. From Problem 12-15, Vr= Ve = 2500 ft/min (assumed)
Po = C"(v /4005)2; Co = O.16/(250O t400q2 = O'41

From able 12-6, LlH = 4'3 Length = 4.3 x 12 = 51.5 in.

12-17. (a) he design condition and the observed condition are on


nearly the same system characteristic. Therefore, it is probable that the fan is not running at the desired speed
of about 920 rpm but at a lower speed of about 6'10 rpm.

(b) The fan is operating near the 920 rpm characteristic


but something related to the duct system has changed.

Possibly a damper is closed, a duct has collapsed or some


other obstruction is present.

(c)

Both the system and the fan characteristic have

changed. The duct system has probably


become fouled or slightly damaged is some way while
the fan speed has decreased slightly due to \ear and tear.

1.5x5000 = 1.62 12-18' Wsn,l = 16 HP; Wsh,2 6350x0.73

Diff

= rco(16_,!62) 16

= +O%

[decrease from 1 to 2!

puoses only to xerpts from this work may be reprduced by instrutors for distibution on a not-for-profit basis lor testing or instrutional his work beyond tht students enrolled in courses for whih the textbook has been adopted. ny other reprductin or rnslion of permied by Sections ] 07 r 08 of he 1 976 United Ses Cpyrigh c |ithu he erfiissin f he cop1''igh oner is unfu.

227

12-19. (a) Assume 15,000 cfm is an equivalent value for the day.
Forfull load point 1: Wr
For part load cond.: Wp
= 16
= 6.7

x0.746x24=286.5 kwh
x

0]46 x24

= 120.Okwh

(28q'9_ ]20) x 286.5

'1OO

58o/o

(decrease)

(b) No, the fan would be forced to operate to the left of the maximum

pressure and would probably be unstable.

12-20' W l = 28.5 P; W z=

17

'5

HP

(static po\er used)

W =

(28'?:17 '5)
28.5

1OO

= 39o/o (decrease)

12-21. (a) Wr

28.5 x 0.746 x24 = 510 kwh

W,

= 27

W
(b) W,

=
=

'0 xO'746 x24 (510_:183)


510
1OO
=

483 kwh (vanes assumed " open)

= 5'3% (decrease) 483 kwh = 5'3% (decrease)

27 x0.746x24
(510_l_483) 51

W =

1OO

(a) and (b) essentialy the same.

12-22' The actual inside dimensions are 10 x 8 in. or D"

9.8 n., Table 12-7

For duct, unlined, Po/L = 1 .8 in. wg./100 ft (Fig. 12-21)

2ooox144 1 0x8

= 3600 fvmin

From Fig. 12-23, roughness corr. Factor = 1.51, then for the
Exerpts from this work may be reprodued by instrutors fr distribution on a not_for-profit basis for testing or instructional puoses only to students nolled in courses or which the textbook has been adoped' ny other reprduction or rnsCion of this ork beyond tht permied by Secions ]07 or 08 ofhe ]976 United Ses Cpyrightcwithou the permissin ofhe copyright olner is unlwful.

228
Po

lined duct, Po/L = 1 .8(1 .5'11 = 2'72 in' wg./100 ft. and

50 x2'72110 = '1.36 in. wg. or about 338 Pa

12-23. Po = (Po)rl X

P/P.l,

_]!}Ps P,rz

P = 0.491(29'42

0.0009 x 5000) = 12.236 psia

Po = 1.36(12'236114.696) = 1'13 in. wg. or about 282 Pa


12-24.

600 cfm

()
Dz = Ds = 10 in'', A2lA1= 0.6 = 3/Aa

|
tl

-=t'

Pd/L = 0.185 in. wg./100 ft; Fig' 12-21 Pzs = 0.1 85 x20l100 = .037 in. wg.

For contraction, AzlA = 0.6, Coz=

0'21

For expansion, A+/As = 1'67, Ca = O.80

Table 12-gA
=660ft/min

z=

Vs= - = 11OOfUmin; =Vgx ff (o1'


4112 )
= O.O16 in. wg.

600

'

Pz= 0'21(11}ol4oO5)2

Po = 0.80(660/4o05)2 = a'O22 in. wg.

Po = 0.037 + 0.016 + 0'022 = 0.075 in. wq.

Exerpts rom this work may be reprodued by instructors for distributin on a not_for_profit basis for testing or instructional puoses only to students enrolled in courses for which the textbook has been adopted. ny oher reprducon or rnsion of this ork beynd th permitted by Secions ] 07 or 08 f the ] 976 United Stes Copyrigh ct ithout he permission of the copyright oner is unlful.

12-25' (a)

229 Bellmouth, Co = 0'2i brupt, Co = 0.5; Table 12-109 & 10


Pos = O'2(1ooo/4oo5)2 = O.o125 in' W9.
Pon = O.5(1oOo/4oO5)2 = O.0313 in. wg.
o/o

- 3.1 Pa

x7'8Pa

Diff .

(0'0313 - 0'0125) (1oo) = lsoo/o 0 0125

(b) Poa

= O'2(40O0l40oq2 = O.2O in. wg.

50 Pa

Pon = O.5(4OOol4ooq2 = O.50 in. wg'


o/o Diff.

124 Pa

(0.5

o.2\/

- 0.2) (1oo) =

15Oo/o

12-26. Table 12-8a, Co = 0.25 = 1200l[(la)x(1 4ln)2! = 1122'5 ftlmin Po O.25(1122.5l4oO5)' _ O.O2 in. wq.
V
o

also

Vo = 0'6l|@l(0.35)2] = 6'24 mls


Po

0.25(6.2411.2q2 = 5.8 Pa
Co = 0.15, Table 12-8b

12-27. (a)

Vo
Po

= 25OO

1441(16 x 16) = '1406 ftlmin

o.15(1 40614005)2 = O.O'185 in. wq.


=

or

Vo = 1.21(0.4 x 0.4)

7.5 m/s

Po = 0'15(7 '5l1'2q2 = 5.1 Pa

(b) Co = 1 '2 able 12-8C


Po = 1.2(140614005)2 = O.148 in. wq.

or

Po = 1'2(7.5l1'29)'= 40.6 Pa

Excerpts from this work may be reprodued by instrutors for distribution on a not-for-profit basis for testing or instructional purposes only to students enrolled in ses for whih the textbook has been adopted. ny other reproduction or trnsltion of his rk beyond h permited by Sectins ] 07 r l 08 f he ] 97 6 Unied Ses Copyrigh c wihout the ermission f he cpyrigh oner is unlful.

230
12-28.

a/a

c=

25O18OO = 0.3125

A/Ac=(6112)2=O.25
Co = 0.345, able 12-11A

V = 25Ol|(l4)(6t2)2]= 1273 ft/min


or

V = 0'12[(ila)(.15)2]

6.8 m/s

Po = 0.345(1 273t4o05)2 = O.O35 in. wg.

or

Po = 0.345(6 '8t1'2q2 = 9.6 Pa

Qr/Q=55O/80O=0.6875
S/Ac =

(0112)'= 0.694

C" = 0.135, Table 12-11A

V.
or

= 550l|(la)(0l12)'! = 1o8 ftlmin


= o.26ll(ila)(0.25)21 = 5.3 m/s

V,

Po" = O.135(1oO8/45)2 = O.OO9 in. wq.

or

Po" = O.135(5.3/1 2972 = 2'3 Pa

12-29.

From Problem 12-28

a/a

= O.31 25;

A/A"= 0'25

Vo = 1273 fVmin or 6.8 m/s


C = 0.93, able 12-11F
Poo = 0.93(1 273l4oo5)2 = O.O94 in. wq.

or

Po = O.93(6.811'2q2 = 25.8 Pa

Qr/Qc

= 0.6875; r/A" = 0.694

C,

= 0.135;

Table 12-118

V,

= lOOB fVmin or 5.3 m/s

Po, = O.135(1oOs/4oo5)2 = O.OO9 in. wq.


Excerpts from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional puoses only to students enrolled in ourses for whih the textbook has been adopted. ny ther reproduction or trnstion of his ork beyond h permied by Secions ] 07 or 0B of he ]976 United Stes Copyrigh c wihou he permissin f he copyrigh oner is unl:lful'

or

Po, = o.135(5.3/1 29)2 = 2'3 Pa

231

12-30' (a) Ao/Al

= 6.0, = 180 deg., Co = 37'4,

Table 12-98

vr

o?9-0"'^!o = 2,ooo ft/min (18x18)


=

oVo

lVl,

Vo =

1,

x 2,O0O = 2000/6 = 333 fVmin

Po = 37.4(333l4o0q2 = 0.260 in. wq.

(b) Co = 14.35 (Table 12-98)


Po = 14.35(333t4ooq2 = O.O99 in. wq.

12-31.

ao/Q"

= 5OO/1OOO = O.5o

/A" = (812)'= o'444 S/c = (8/1 2)' = 0'444

Q,/Qc

= 500/1OOO = O'5

(a)

C = 0.755, Table

C" = O.2'15,

12-12A lnterpolation required 1 Table 12-12A l ASHRE Duct Fitting

or use Data

V = 50Ot|t4)(8t2)2]= 1432 ft/min

- v,

or or or

V= O.24l|(l4o.2)'] =7'64mls
Po = 0.755(1 4g2l4o05)2 = O.O97 in. w.

Poo = O'755(7 .64112972 = 26'5 Pa

Po, = O'215(1432I4OO5)2 = O.O28 in. wq. Po, = O'215(7.641129)2 = 7 '54 Pa

Excerpts f,rom this wrk may be reproduced by instructors or distributin n a not-for-profit basis for testing or instructional puoses only to students enrolled in courses fr which the textbook has been adopted. ny oher reproductin or trnstin of his work beyond h permied by Secons ] 07 or 08 of he ] 97 6 tJnied Ses Copyrigh c ithu the permission of he copyright ner is unlrwful.

55 72 20

0.'135

0.07 4

0.50
0.16 2.0

2(0.26) 2(0.26)
0.17

1020 630 550

0.032 0.004 0.038

0.034 0.013 0.003

0.140
0.057
0.051

233
35
14 13

2
3

0.055 0.050

0'40
0.010

12-33' L = D x Co/f; f

0.019, abe 12-13


ft

Bellmouth: L = 1 x0.210.019 = 10.5


brupt Int.: L = 1 x 0.5/0.019
=

26.3 ft

= 1OOO x l4 = 785 cfm; Po/L =

O.12in'wg'l1oo ft, Fig' 12-21


Pa
7'9 Pa

Pog = Pon =

0.12x 10'5l100
0.'12x26'3l100

= 0.0126 in. wg. or about 3.'1 = 0.0316 in. wg. or about

12-34' From Probem 12-26' Co = 0.25, D = 14 in'


Lu = DxC olfi f = 0.017 ,

Table 12-13

'= -

lx

12

0'25
0.017

= 17

'2ft

= 12OO cfm; P/L = 0.'13 in. wg./1OO ft

Po = 0.13 x 17 '2l100 = 0.022 in. wg. or about 5.6 Pa

Note: Most of following duct sizing problems can be solved with the computer
program, DUCT.

12-35. From Figure 12-36.

Excerpts frm this wrk may be reproduced by instructors fr distribution on a not_for-profit basis fr testing or instructional puoses only t students enrolled in ourses for whih the textbook has been adopted' ny ther reproduction or rnstion f his ork beynd h permed by Sections ] 07 r ] 08 f he 976 United Stes Cpyright c |'ithu the permissin of he copyright oner is unlful.

234

Estimate Tota] quivalent Length of Run 1-2-3 to be approximately


132 ft, able 12-14' Then Po/Le = (0.13 x 1 00)1132
= 0.'10 in.

wg./100 ft size ducts using Figure 12-21 and record the

actual Po/L from Figure 12-21'

Section
No.

Le ft

a
cfm

D
in.

P/L
in. wq.

Pn in. wg.

100 ft
1

45
16
71

300 220
100 80

2
3

I I
6
5

0.084 .090 0.083 0.14

0.38

0.014
0.059 0.077 0.069

4
5

55 55

120

0.125

Run 1-2-5 actually has the greatest lost pressure. Pl = 0.038 + 0'077 Plzs = 0.038
0.115 in. wg.;

Pzs = 0.038 + 0.014 + 0.059 = 0.121 in. wg.


+

0.014 + 0.059 = 0.1'1

'1

in.

\/g.

12-36. The design pressure loss is (0.25 1-2-3-4-5, Le = 185 ft

0.1 ) = 0.1 5 in. wg. (for supply ducts) is:

Assume the run with the largest equivalent length

hen for design: Po/Le

(0'15 _ 0'03) x 1OO = 0.065 in. wg./'1oO ft 185

Exerpts fom thls wrk may be reprodued by instructors for distribution on a not-for-profit basis for testing or tnstrutional puoses only to students enrolled in courses fr whih the textbook has been adpted. ny oher reproduction or trnsion of this ork beyond h permitted by Secns ]07 r ]08 fhe 976 United Ses Copyrightc,ihu the permissin fhe copy'igh ner is unlnful.

235 Section has a total flow of 845 cfm. herefore, the maximum velocity in section wjl! be about 800 fVmin if a 14 in. duct is used.

Exerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional puoses only to students enolled in ourses for which the textbook has been adpted. ny other repsluction or rnsion of his ork beyond th permitted by Sections ] 07 or 0B of the 1976 Unied Snrcs Copyright c wihout he permis\ o/*e copyright oner is unlwful.

236
12-36. (continued)
(a)

Section
No.

Le
ft

a
cfm

D
in.

P/L
in. w.

Pn in. wg.

100 ft
1

88
18 16 17

845
595 395 275 125

14
12 12
9

0.065 0.07 0.034 0.065 0.065 0.060 0.072 0.065 0.040

0.57 0.013 0.0054


0.0'1
1

2
3

4
5

46
51

0.030
0.031 0.031

6
7

250 200
120
150

I
8

43 49 49

I I

0.032 0.020

With the equal friction method, every branch should have a damper for

balancing purposes. ctual total pressure loss:


Po

P1 + P2 + P3 + Pa + Pu + Ps

Po = 0'146 in' wg'

Note that run 1-2-3-4-7 actualy has the greatest loss in total pressure
but the difference is not significant. Use Po = 0.15 in. wg.

(b)

Sizing of the longest run, 1 -2-3-4-5, is the same as (a) above where
Po/L = 0.065 in. wg./100 ft. Construct a new table as follows:

petmied by Secions 07 or 108 ofhe 976 Unied Ses Copyr4hc'!hou he permission fthe copyrigh oner is unrwfu.

Ecerpts fim this wrk may be reprodued by instructors tbr distribution on a not-for-pro1lt basis for testing or instrutional puoses only to students enrolled in ourses fr which the textbook has been adopted. ny oher reproducin or rnsltin of his work beyond ht

---------------MAIN DUCT RUN


(1)
(2)
Le
ft.

BRNCH DUcS
(6) (7) (8) (e) Br. (10)
(1 1)

237
(1

(3)

(4)

(5)

(12) Pi
L
('10)100 (11)

3)

(14) D"/wxh
in.

(1

5)

Sec
No.

cfm

DJwxh
in.

P
L

v
fpm

Po
(2)(5)

Po
(7)

P
Poot

Le
ft.

fm

v
fpm

Se
No.

100

-(8)* P

BB
'18

845 595

14
12 12

0.065 0.070
0.034

800 760 500 600 500

0.057 0.013

0.057 0.070

f)

0.39
0.036 0.035 0.020

51

0.076
0.084

250 200
120 150

550

43 49 49

I
7

570
500

J 4
5

16 17

?o
275 125

0.005
.01'1

.75 .086
0.116

8 9

0.071 0.041

I
7

0.065 .065

420

46

0.3

ffuser G 0.030

0,146

The left 8 columns are the same as (a) above. The branches, 6-7-8-9,
are sized to balance in the right hand 7 columns.

(c)

Equal Friction Method

-- Design Procedure -Sysem type: Supp}y Duct Sizing Method: Equal Friction
Rounding Method: Round Nearest

-- Ean Selection -Kno\n

Fan Parameter: F'an Tota ressure :

0.

250 in.

wg

Fan lrflow: Fan or Externa1 Total Pressure:

Coi1 Lost PreSsure: i1ter Lost Pressure: 0 . 000 in. Misc. Lost PreSSure: 0. in.
.25 in.

B45.0 cfm .25 in. . 0 in.

wg wg wg w wg
%

U AU

External Total Pressure:

AHU Pressure

Pressure for Supply System: 0.150 in. wg - or 60.0 for Return System: 0.10 in. wg - or 40.0

-- Lost Pressure from ir HandJ_ng Unit to Diffuser -Diffuser D Q Tota1 Delta P (cfm) (1n. wg) 71 125.0
A.L20
Excerpts from this work may be reproduced by instrutrs for distribution n a not-for-prfit basis for testing or instrutional puoses only to students etrrolled in ourses for which the textbook has been adopted. ny other reproducion or rnsion f this wrk beyond tht permitted by Sections ] 07 r 108 f the ] 976 United Stes Copyrigh c ''ihout he permission f he cpyrigh oner is unlful.

238
t6 30
34

22

120.a 200.0 250.A


B45.

150.0

0. 21

0. 130 0. t25

0.154

Total

-- Calculated Fitting D Fitt1ng Type

Vaues -Dia. ( in)


14. 14.

Q (cfm) 845.0 845.0 845.0 845.0 845.0 595. 250.0 B45. 595.0 395.0 20.0 595.0 395.0 215.0 L20.0 395.0 215.0 L25 .0 150.0 215.0 125 .0 L25 .0 L25 .0 L25 .0 15.0 1s0.0 15.0 15.0
15.0
]

Velocity (ftlmin)
'79.4

(in.

Delta

P wg)

(in.

AP

/L

wg)

1 2 3 4 5 6

Air andling Unit Straight Duct


lbow Elbow

0.0

0.0

.000

Conica Contraction
Tee / e
main branch

14. 72 .4
o

19A.4 '790.4 19A.4


565.

0.013
0. 13 0. 06 0. 05

0.06415

'75'7.6

0.006
0.018
0.

7 Straight Duct B Tee / wye


1 Tee

common

14.0

main branch

72 .0

9 Straight Duct / wye

conmon

10.0 8.0

main branch
comon

10.0 9.0
1

72 .0

11 Straight Duct 12 Tee / 13 14 15 16 17 18 19 20 21 22 23 24 25 26 21 28 29 30 31 32 33 34


lbow Elbow Elbow

,ye
Duct Duct

il?}l.n
conmon

Straight Straight

10.0 9.0 1.0 ?n 9.0 7.0


'7.0 1 .0

.0

19a.4 151 .6 124.2 573.0 151 .6 124.2 622.5 449.0 '724.2 622.5
461 .1 461 461 461 461

0.004
0.01_7

0.011_61

0.007 0.003
0. 16

0.08259

561.3 622.5
.1 .1
.'7

0.007 0.002 0.009 0.008 0.002 0.002 0.003 0.030 0.006 0.005 0.016 0.005 0.040 0.002
0. 11 0. 03

0.07138

0.05817
.05B17
. 8082 . B0B2

Diffuser / Grile Straight Duct Straight


Duct

7.0 1.0 7.0

.1

'1

Ebow

.0 1 .0

Elbow

bow

Diffser / Gr Straight Duct Diffuser,/ Gri11e Straight


Duct

561.3 561.3 561.3 561.3


449.0 449.a 449.0

?n 7. 7.0

L24.0 20.0 120.0


120 .0

0.05405

]-bo'

Elbow Elbow

Ebow

Diffuser / Grit Straight Duct Dlffuser / Gril

8.0 8.0 9.0 9.0 9.0

20.0 2AA. 20.0


20.0

573.0 573.0 573.0 565.9 565.9 565.9

.036

.03

250.0 250.0 250.0


250.0

0.010 0.005 0.040 0.003 0.013 0.004


0. 50

0. 7106

0.06004

(c) Balanced Capacity Method


-- Design Procedure --

Ecets from this wrk may be reproduced by instrutors for distribution on a not_for-profit basis for testing r instrutional puoses only to students enolled in ourses for whih the textbook has been adopted' ny other reproducion or rnstion of his rk beyond h permied by Sectins ] 07 or l 08 f the 1976 United Stes Copyright c withu he permissin of he cpyright oner is unlful.

____
System type: Supply Duct Sizing Method: Balanced Capacity Rounding Method: Round Nearest

239

-- Fan Selection -Known Fan

Parameter: Fan Total Pressure :

0.250 in.
in. in. in. in.
wg wg wg
^rq

wg

Fan irflow: Fan or External Total ressure:

Coi Lost Pressure: E'iter Lost ressure: Misc. Lost PreSSure :

.250 0.00 0.000 0 . 00

B45.0 cfm

HU AU HU

xterna1 Total Pressure:

.25 in.

wg
%
%

Pressure for Suppy System: 0'150 in. wg - or 60.0 Pressure for Return System: 0.10 in. wg - or 40.0

-- LoSt Pressure from ir and1ing Unit to Diffuser _Diffuser D Q Tta Delta P (cfm) (in. wq) L] 22 26 30 34 Total -125.0 150.0 720.0 200.0 250.0
845.0 0.138
.154

0.145 0.140 0.141

Cal cu-Lated

Fitting Values -Dia. (in) Q (cfm) 845.0 845.0 845.0 845.0 845.0 595 . 0 250.0 845. 595.0 395.0 200.0 595.0 395.0 215.0 720.0 395.0 215 '0 \25.0 150.0 21 5.0 Velocity (ftlmin) 0.0 '790.4 190.4 190.4 '190.4 '7 57 .6 116.2
'790.4
'751

D Fitting Type 1 2 3 4 5 6 Air Handling Unit Straight Duct Conicaf Contraction E}bow trlbow main Tee / Wye branch

Deta P (in. wg)


0.00

(in.

P/L

wg)

0. 14.0 14.0 14.0 14.0 1'2 .0 8.0 common 14. 72.a 7 Straight Duct 10.0 8 Tee / \Ne main branch 1 .0 common 72.0 10.0 9 Straight Duct 9.0 10 Tee / Wye main branch 6.0 common 10.0 9. 11 Straight Duct 6.0 L2 Tee / Wye main branch 1 .0 conmon 9.0

0.013
0.013
.006

.06415

0.006

0 . 005

0.016
0.07167

.6 124.2 1 48.4 15'1 .6 -124.2 622'5 6lL.2


124.2

.07
0.004 0.016
0.03 .013

0.007 0.07
0.003 0.009

0.08259

622.5 636.6 561.3


622.5

0.07138

Excets from this rork may be reproduced by instructors for distribution n a nt-for-profit basis for testing or instrutional puses only to students enrolled in courses for which the textbook has been adopted. ny ther reproductiol1 or trnsaton f his work beyond tht permitted by Sections ] 07 r 08 f the t 97 6 Unied Stes Copyrigh ct ||1thout he pemissin of the copyrigh oner is uncwful.

240

0.72304 L4 Elbow

13 Straight

Duct

6.0 6.0 6.0 6.0 7.0 /.u 7.0 1.0 6.0


6.

125 .0 L25 .0 L25 .0

636.6
636.6 636 .6 636 .6

0.016 0.004 0.005 0.007


.030

15 Sraight Duct 76 lbw l1 Diffuser / Grille


1

1r
1,25

0.72344

.0

8 19 2a 27 22 23 24 25 26

Elbow

Sraight
Elbow

Duct Duct

Straigh
Elbow

150.0 150.0
15.0

Diffuser / Grille
Elbow
El-bow

Straight Straigh
lbow

Duct

2"7

Diffuser / Grile
Elbow Duct

6.0

28 29 30 31 32 33 34

Diffuser / Grille
Elbow

1.4 1.0 7.0 8.0 8.0 8.0

Strarght Duct

Diffuser,/ Grille

150.0 1"20 .0 120.0 t2a .0 120.0 200. 200.0 200.0 200. 250.0 25.0 250.0 250.0

561.3 561.3 561.3 561.3 6tt .2 6L7.2 6L1.2 148.4


'1
"7

0.006 0.00s 0.016 0.005 0.040 0.004 0.023 0.006 0.036 .005

0.08082
.08082

0.L427

48 .4

0.009
0. 40
^ ^41

nT q

0.13629

'716.2 1L6 .2 ' 16 .2

0.005
0.007 0.050

0.10661

12-37. Pos + Pon = .70 _ 0.35 = 0.35 in. wg.

Pos = 0.65(0.35) = 0.23 in. wg. Po


^y

0.35 _0'23 = 0.12 in. wg.

he method of Solution is similar to Problem 12-36' An acceptable solution follows:


(a)

Longest run

-2-3-4-5-6-7-8-9-1

-13

The summation of equivalent lengths may vary v/ith designers.


Po/Le
=

(0.23

217

- 0.03) 100

0.092 in. wg./'100 ft

Size all Suppy ducts for this pressure loss per unit length.

basis for testing or instructional puoses only t Ecrpts from this work may be reproduced by instructrs for distibution on a not-for-profit his work beyond h in courses for whih the tXtbook has been adopted' ny other reproductin or rnsltion f students enrolled is unlful' 1976 Unied Sttes Copyrigh't ct ihout he peimission of he copyright oner pe,rmed by Sections ] 07 r l o7 ,r,

241

1200
1

16 14 14 12 12 12 10

150 100 100

2
3

050

850

4
5

750
650 550 475 225 175
50

75
100

b
7
8

200

I
7 5

9 10
11

125
50 75 50

6
5

12 13 14

6
5

basis for testing or instrutional puoses only xerpts frm this work may be reproduced by instructors for distribution on a not-for-profit of his work beyond th in courses for wt'ih the textbook has been adopted. ny oher reproducion or rnsl(tion students enrolled is unful' 976 United Stes Cpyrigh't ct lithou the peimissin ofhe copyrigh oner permied by Secins ] 07 or l i7 in,

----=12-42. (continued)

9,rE
ci.
cE -O
(/)

c) o o o o o o ...-

t*

(o

o c c{
o (o
c{

(o

-.l

N'

rf

f) ol l ^

o o c.l
(o

o o o

c)
--

la
.l

I; |
l(J

lcs

lo l-o
o

f, |

lo IO

()

l
!.t

o
)

ci

) C.l

c!
c)

\-

c;

c!

C.l

c.l

C.l

(
t-

t ]

.J o O )

C
.-

.t

.-

a)

(r)

*-*u{

-*

O
-l-

cj

c;

co

.-

o (o
ci

ci
)

ci
(\
c.l

ci

ci
c{

l> tt.lg l l= l l l ] lc l l IL
I()

l)

E o

lc

o 2

co

.l

c\l

\r

o
o

= o
(o
c -

ds
^l^

l-c l) l-c
I

ti-

c;

v O
)

(o

ci
(o

) (o

c)

o o o ci ci o v ) o c! o ( cf) o o $ o o I ci c;

(o

.l .l

lo lo lU)

o
I

*"3
t
t--

s )
o

<)

c;

o
ci
c{

ci
c)

= o o

c{

z !cr>a

O O cO

(o

o o o .c{

(o
.t

o
..-

$
(o

.c
o -

(
_

()

oXl ci.

cf) cO -i ci O ci

)
o

c;

) o

ci

c;

U) (

O
(

U'
()

c{

c!


o
$

(o

(o

_
(

!-

-o (
(

o o o

(o

()

u.
c{

--

C.l

c.l

c.l

()

f)

.c
cf)

o
t#

\r

f)

c{

.
J

(
(

c
o

U)

O
-

cr)

r,

cf)

E (

12-37. (continued)
Po for the longest run will be about 0'22 in. wg' for the above sizes"

herefore, size the return system for a pressure loss of (0.35 _0'22)
or 0.13 in. wg.

For the return system:

(L")r* x 230 ft,

('1

2r

3r)

then Po lL"= r0'13-__0'05'] ''oo = O.O35 in. wg./'1oo ft

230)

Using the equal friction method: Section


No.
1r

a
cfm

D
in.

L"
ft

P"/L

Po
in. wg.

1200 800 400

18
'16

115
70

0.038 0.033 0.36 0.036 0.036

0.044
0.023
0.0'16

2r 3r

12 12 12

44
14

4r
5r

400
400

0.005 0.010

28

Return system is the same for parts (a) and (b).


Po for return = 0.133 in.
\Mg.

(c) Equal Friction Method


-- Desiqn Procedure -System type: Supply Duct Sizing Method: Equal- riction Rounding Method: Round Neares

-- Ean Seection -Known an Parameter: an Total Pressure :

0.700 in.

wg

244
an Airflow: Fan or Externa Total Pressure:

0.700 in. Coil Lost Pressure: 0.25 in. F'iter Lost Pressure: 0 . 10 in. isc. Lost resSure: 0.00 in.

1000.0 cfm
wg wg wg wg
^rg

HU AU AHU

Externa1 Total Pressure:

0.350 in.

Pressure for Suppy System: 0.228 in. wg - or 65.0 Pressure for Return System: 0.123 in. wg - or 35.0

-- Lost ressure from ir and1ing Unlt to Diffuser -Diffuser D Q Total Deta (cfm) (in. wg) 2'7 30 34 38 56 60 63 61 12 15 Total 75. 75. 75.0 s0.0 75.0 100.0 100.0 100.0 200.0 150.0
1000.

0.221 0.201

0.272 0.171 0.158 0.171 0.L42 0.2a2 0.131

0.21

-_ Calculated Fittin Values -D itting Type

Dia. (in)

Q (cfm)

Veocity (ftlmin)

Delta P (in. wg)


0.000 0.011 0.061

(in. wg) ^P/L


0.08745

ir andling Unlt .0 Conical- Contraction 14.0 Straight Duct 14.0 Tee / wye main l2.a branch 1 .0 conon 14.0 5 Straight Duct 12.0 6 Tee / Wye main 12 .0 branch 1 '0 conmon L2 '0 7 Straiqht Duct l2.0 B Tee / vfrze main 10.0 branch 6.O common L2.0 9 Straight Duct 10.0 10 Tee ,/ Wye main 10.0 branch 6.0 conon 10.0 11 Straight Duct 10.0 L2 Tee ,/ Wye main 9. 0 branch 6.0 connon 10.0 13 Straight Duct 9. 0

1 2 3 4

1000.0 0. 1000.0 935.4 100.0 935.4 850. 082.3 15. 561.3 1000.0 935.4 850.0 L082.3 650 . 0 82'7 .6 2a0.0 1 48.4 B50.0 1082.3 650.0 B2'7 .6 550.0 1008.4 1OO.O 5O9.3 650.0 821.6 550.0 1008.4 450.0 825.! 100.0 509.3 550. 1008.4 450.0 825.7 350 . 192 .2 100. 509.3 450.0 825.L 350 . 0 1 92.2

0.007
O. O1O

.058

0 . 008*<10>

0.003

0.13819

.09 .37 0.

0.005 6

0.08429

O. O1O*<10>

0.15164

0.064

0.004
a.024
0.
O .

0.10485

014

0. 11082

Excerpts from this work may be reproducd by instrutors for distribution on a not_for-profit basis for testing or instructional puoses only to students enrolled in urses for whih the textbook has been adopted. ny ther reproductin of trnsltion of his ork beynd th permied by Secions 07 or l08 fthe 976 Unied Stqes Copyright c'|)ihout the permission ofthe cpyrigh oner is unlcrwful.

14 Tee 15 L7 18 19 20 27 22 2? 24 25 26 2'l 28 29 3 31 32 33 34 35 36 31 38 53 54 55 56 51 58 59 6 6L 62 63 64 65 66 61 6B 69 70 11 12 13 14 15 16

main 8. branch 5.0 common 9.0 Straight Duct B.0 bow B.0 Straight Duct 8.0 Tee ,i Wye main B.0 branch 4.0 common 8.0 Straight Duct B.0 7.0 Tee / Wye main branch 5.0 conmon B.0 1 .0 Straight Duct T / n1lzo main 5.0 branch 5. conmon 1.a lbow 5. Straight Duct 5. Rectangular Transition 5. Diffuser / Grile Straight Duct 5.0 Rectangular Transition 5. Diffuser / Grille Elbow 5.0 5. Straiqht Duct Rectanguar Transition 5.0 Dif fuser / Gril-le Elbow 4.0 4.0 Strarght Duct Rectangular Transition 4.0 Dif fuser ,/ cril1e Elbov 5.0 Straiqht Duct 5.0 Rectanguar Transition 5.0 Diffuser / cril1e 1bow 6.0 Straight Duct 6. Rectangular Transition 6.0 Diffuser / cri]e Straight Duct 6. Rectangular Transition 6. Diffuser / Gri1e E1bow 6.0 Straight Duct 6.0 Rectangular Transition 6.0 Diffuser / Gril]_e '7 .A Straight Duct 1.0 Elbow 1 .0 Straight Duct Rectangu1ar Transition 1 .0 Diffuser / Gritle Straight Duct 1 .0 Rectangular Transition 7.0 Dif fuser ,/ Grille Elbow 8.0
,/
f / li

Wye

215.a 75. 35. 215.0 215.0 215.0 225.a 5. 215.4 225.a 150.0 75.0 225.0 150.0 75.0 75.0 150.0 75.0 75.0 75.0 75.0 75.0 75.0 75.0 75. 75.0 75.0 75.0 50.0 50.0 5.0 50. 75.0 75.0 75.0 75.0 100.0 100.0 10.0 100.0 100.0 100.0 10.0 100.0 10.0 100.0 10.0 200.0 200.0 20. 20. 20. 150.0 150.0 150.0 215.0

.8 1B1.B 181 .B 644.6 573.0 l1i .B 644.6 561.3 550.


'7B1

192.2

.8 550.0
"781

0.019

. 05

245
0.7268'7 0.L268'7

0.013
a

0.08

0.06
.021

.09*<10> 0.

561.3 550.0 550.0 550.0 550.0 210.a 550.0 210.a 55.0 550.0 21a.0 573.0 573.0 180.0 550.0 550. 210.0 509.3 509.3 360.0 59.3 36.0 509.3 509.3 360.0 148.4 148.4 48 ' 4 120.0
"7

644.6

0.003 0.011 0.002 0.007 0.006


0.05 0.05 0.06

07

0.0880

0.018

0.08082

561.3

0.072

.11869

0.030 0.025 0.005 A.025 0.007


.010

0.07 .018 0.017 0.01B


0.005 0.030 0.004 0.003 0.045
.003 0.04

0.11869

0.11869

0.16916

0.020 0.006

0.11869

0.008

a.0122l
a.0B221'

0.072 0.008 0.02'7


0.001 0.045 0.001
.020
0

0.032
0.003
0. 45

a.08221-

0.013

0.l.3629
0.1-3629

.a21

561.3 54.0
181

0.032
0.005

0.08082

.B

* - De}ta P fas computed using

the fitt1ng

equivalent lenqth

Balanced Capacity Method


Exets from this wrk may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to students enlled in ourses or whih the textbook has ben adopted. ny ther reproduction or trnslion of his rk beyond tht pernied by Secions ]07 or l 08 f the ]976 Unied Sttes Copyright c hout he permissin f he cpyrigh owner is unlcrful.

246
-- Desiqn Procedure -Note that almost al branch ducts need a damper to increase the diameter and reduce ve1city.
System type: Supply Duct Sizing Method: Balanced Capacity Rounding Method: Round Nearest

-- Fan Selection -Known F'an Parameter: Ean Tta1 Pressure

0.700 in.
wg wg wg wq wg

wg

an irflow: Fan or xternal Total Pressure:

100. cfm

Coi Lost Pressure: Filter LoSt Pressure: Misc. Lost Pressure:

.7 in.

0.25 in. 0 . 10 in. 0.000 in. 0.350 in.

HU

External Total ressure:

AHU Pressure HU Pressure

for Supply System: 0.228 in. wg - or 65.0 for Return System: 0.L23 in. wg - or 35.0

-- Lost Pressure from ir Handling Unit to Diffuser -Diffuser lD Tota Delta Q (cfm) (in. wq)
P

2'7 30 34 3B 56 60 63 61 12 15 Tota

75.0 75.0 75.0 50.0 75.0 100.0 100. 100.0 20.0 150.
100.0

0.221 0.243 0.232 0.219 0.285


0.25'7

0.271 0.2L2

0.202 0.17

-- Cacuaed iting Vafues -D ltting Type 1 2 3 / ir and1ing Unit Conical Contraction Stralght Duct .aa / l.,o main branch counon 5 Straight Duct 6 Tee / wye main branch Dia. (in) .0 .0 14. 72.a 6. 14.0 l2.0 !2.a 1.a
14

Q (cfm) 100.0 1000.0 1000.0 850.0 15O . O 1000.0 850. 650.0 20.

Veocrty (ftlmin) 0.0 935.4 935.4 L082.3 1 63 .9 1-082.3 821.6 '748.4


935.4

Deta P
0.000 0.011 0.010
O. O57

(in. wg) (in. wg) ^P/L 0.007 0.03


0.08745

0.058

.O8*<1O>

0.13819

Excerpts from this work may be reprodued by instrutors for distribution on a nt_for-profit basis fr testing or instrutional puoses only to students enrled in ourses fr whih the textbook has been adopted. ny ther reProduction or rnsin of his work beyond h permied by Secins 07 or ] 08 f the 97 6 United SeS Copyrighl ct ihou he pemission of he cpyrigh olner is uncrful.

7 Straight Duct B Tee / wye 9 Straight Duct 10 Tee / Wye 11 Strarght


'r ^^ 99
/

conmon

72 .0
1_2

main

branch
conmon

10.0

.0

85.0 650.

082.3 145.9

247
0.005 0.009 0.039 0.006 0.08429

L2 .0

o
4.

main

branch
conmon
maln

10.0 10.0 10.0


1.0

650.0 550.0 450.0 100.0


55.

10.0

821 .6 1008.4 821 .6 10B.4 825 .7 1145. 9

/ r^ir7^ ly

Duct

branch
conon

13 Straight Duct main 74 Tee / Wye 5


L1
LB

branch

Elbow

Straight

Duct Duct

conmon

L9
20

Tee / Wye

Straight

main branch
a1n

2L
22

Straiqht

/ l1lr^ ]

Duct

conmon

branch
common

9.0 4.0 10.0 9.0 8.0 4.0 on 8.0 8.0 8.0 8.0 4. 8.0 8.0 7.0
o.u

450.0 350.0 10.0 450.0 35. 275.0 75.0 350.0 t1\ a

10B.4 825.L 192.2 1145. 9 825.1 -7q2 2 181 .8 859.4


1A) 181 181 181
'7

0.010*<10> a .062

0.15164

0.004 0.005 0.031 0.014 0.005 0.017

.104B5

0.11082

' tr

215.0 225.0 50.0

215 .0 aa tr

5.

23

Straight Duct Tee / Wye


Elbow

main branch
conon

24 25 26 21 28 29 30 31 32 33 34 35 36 31 38 53 54 55 56 51 58 59 60 67 62 63 64 65 66 61 68

1.4 4.0 5.0 ?n


5.

Rectangufar Transition

Straight

Duct

tr1bow

Diffuser / crille Straight Duc Rectangular Transition Diffuser / Gritle


Rectangular Transition
Elbow

5.0 5.0

150.0 75.0 225.0 15.0 75. 75. 150.0 75.0 75.0


?tr

4.0

4. 5.
tr

Straight

Ducc

75.0 75.0 75.0 75.

573.0 81 .8 644 .6 561.3 550.0 644 .6 561.3 859.4 550.0 561.3 55.0 550.0 210 .0 859.4 214 .0 550.0 214 .0
550.

.8 .8 644 .6

.8

0.006 0.008 0.013

0.L2681 0.!268'7

0.009*<10> 0 .021

0.07
0.003 0.011
0.007 0.007

. 880

0.018
.006

0.08082

0.at2
0.00s 0.030
0

0.11869 0.35266

9.02!
0.025
.006 .024

Diffuser / Grille

75.0 75.0
75.
5.

0.018
.05 0. 25 0. 7

0.11869

Elbow

Straight Duc Rectangular Transition Diffuser / Grille


Recangufar Trans1tion Diffuser / Gri1e
bow

4.0 4.0
\

Straigh Sraigh

Duct

4.4 4.0 4.0 4.0 4.4 4.0 4.0


ol

50.0 50.0 75.0 75.0


75.
'tr

50.

573.0 573.0 180.0


859.4 859.4 210 .0 1145.9 1145.9 360.0
L1_45

0.017
0.010 0.020 0.015
.424 0.03 0 .021
0

.16916

.053 0.060
0.042 0.045
0

0.35266

Rectangular Transition Diffuser / Gri]e


bow

Duct

10.0 10.0
10.

0.59144 0.59144

Straight Duc Rectanqular Transition Diffuser / Grille


Scraight Duct Rectangular Transition

4. 4.

Diffuser / crille Straight Duc

4.0

7.

100.0 10.0 10.0 100.0 100.0 10.0 100.0 100.0 20.

360.0
9

.9

0.090
0.032 a2'1
.042

1145.

7L45 .9

360.

0.06
0.042 0.045

0.59'744

148.4

a.021

0.!3629

Exerpts from this work may be reprduced by instructors for distribution on a not-fr-profit basis for testing or instrutional puoses only to students enrolled in courses for which the textbok has been adopted. ny other reprducin or rnstion f this ork beynd th permitted by Sections ] 07 r l 08 f the 1 976 United SteS Copyrigh c'withou he permission of the cpyrigh owner is unlful.

248 70 lt 12 13 14 15 16

']48.4 200.a 0.013 1.0 69 Ebow 148.4 0.02'1 0.1-3629 1 .0 200.0 Straight Duct 120.0 0.001 20.0 Rectanguar Transition 1 .0 0.045 200.0 Diffuser / Gril-le '7 150.0 0.069 0.17139 6. 63.9 Straight Duct 150.0 0.007 540.0 Rectangular Transition 6. .020 150.0 Diffuser / Gri1e '7B'7.B 0.05 2'75.a B.0 Ebow * - Delta was computed using the fitting equivalent ength

Return Ducts, Equal Friction Method


-- nj ^_ D:ocedure
vYl L ]

__

System type: Return Duct Sizing Method: qual Friction Rounding Method: Round Nearest

-- Fan Seection -Known an Parameter: an Tota1 Pressure

0.700 in.
wg wq wg wg wq

wg

Fan irfow: Fan or External Ttal ressure:

Coil Lost Pressure: iter LoSt Pressure: Misc. Lost Pressure:

1200,0 cfm .7 in' .25 in.

0.100 in. 0.000 in. 0.350 in.

AU AU U

xternal Tota1 Pressure:

Pressure for Suppy System: 0.228 in. wg - or 65.0 Pressure for Return System: 0.123 in. wg - or 35.0

% %

-- Lost ressure from ir andling Unit to Diffuser -Diffuser D Q Tota Delta P (in. wg) (cfm) 11 14 l"7 400.0 400.0 400.
0.125 0.113 0.096

Tota1 120.0 _- Cacu1ated F'itting Vaues -_


TD

Fitting Type

Dia. (in)
0. 18.0 1B.0 1'2.a 16.0 18.0 16. 12.0 \2.0 16.0

Q (cfm) 1200.0 72A0.0 L200.a 400.0 800.0 1200.0 800.0 4.0 400.0 800.0

Velocity (ftlmin) .0 679.1 619.1 509.3 573.0 0 509.3 509.3


573 '

LP/L Delta P (in. wg) (in. wg)


. 0

1 2 3 4

ir Handllng Unit Rectangular Transition Straight Duc main Tee / \ye branch colmon 5 Straight Duct main 6 Tee / wye branch conmon

0.001

0.002
0.026 0.026
0.0]-5

0.03512

679.1

0.006
0.013

0.03a24

573.0

Excets from this work may be reproduced by instrutors for distribution on a not-for-profit basis for testing or instructinal puoses only to students enrolled in ourses for whih the textbook has been adopted. ny other reproducion or rnslion of his rk beyond th permited by Sectins ] 07 or 08 of he 1976 United Stes Cpyright c ithou the permission f he copyright oner is unfu.

7 Stralght Duct 0. 3476 B Elbow 9 Straight Duct 10 Rectangular Transition 11 Diffuser / crile 72 Straight DucL 13 Rectangular Transition L4 Diffuser / Grile 15 Straight Dct 16 Rectangular Transition 11 Diffuser / Gri-1e
. 03

12 .0

400.0
4.0 40.0 40.0 40.0

12 .0

509.3 400.0 s09.3 l-00.0


59.3

0.007 509.3

249
0

L2 .0 L2 .0
L2 .0 L2 .0

400.0 400.0 400.0 400.0 400.0

100.0 509.3
100.

L2.A L2 .0

0.001 0.014 0.050 0.001 0.014 0.050 0.003 0.014


0.05

.034'7

0.03476 0.03476

12-38. The three branches from the plenum must be designed as close as

possibe for the Same preSSUre ]oss. Start \/ith B since it appears
to be more extensive than or c.
0.18

For B: Po/Le =[
For

145
142 0.18

- 0.025

'100 = 0.107 in. wg./100 ft '100 = 0.109 in. wg./10 ft

Po/Le

=(
=(

0.18-0. 025
0. 025

For

C: P"/L"

104

100 = 0.149 in. wg./100 ft

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instrutional puoses only to students enrolled in courses for whih the textbook has been adopted. ny other reproductin or trnstion of his wrk beyond h permited by SecioS ] 07 or ] 08 f the 97 6 United SeS Copyrigh ct ithou the pemission of he cop1',"igh oner is unlcrful'

250

12-38. (continued)
MA|N DUc RUN

BRNC DUCTS
(6) (7)
(8)

(1)

(2) Le
ft.

(3)

(4)

(5)

(e) Br.

(1

0)

(11)
Le
ft.

(12) Pi L
(1 0)1

(13)

(14)
De in.

(1

5)

Se.
No.

cfm

D"
in.

P
L

v
fpm

Po
(2)(5)

Po (7)

Pi
Po6+

cfm

v
fpm

Sec
o.

actual
*r"

100
1

-(8)+
-P

00

(1 1)

8 o

44 22 25
54

500

12 10
7

.057 .085
0.1
1

650
700 630

.025
.019

025 .044
.072 0.119

14
10

0.094

55

0.171

125

b
7

660
760 550

375
175
100

0.75
0.047

52 38

0.144
0.124

200
75

11

o28
.047

12

IJ

.87 P

520

Tot
1

145 50
19

.025
760 700 59 530

0 144
0.048 .ubb .086
.

40
300

10

.095 .92

.048
0.018 0.02 0.046 0.025

0.084

38

0.221
0.1

100 100
'100

b o

750
510
500

0.66
0.046

48
q7

38

Tot. 15 17 Tot.

25 48 142 56 48 104

200
100
o

8
.095 P

0.8'1

t5z
157

225
100

7
^

17

850 510

0.095
0.04'1

.095
'136 161

to

0.041

38

0.1 8

125

610

.085 P

0.025

Note that the resulting total pressures losses turn out to be:
(Po)a = 0.144 in.wg., (Po)n = 0.157 in. wg.; (Po)c = 0.161 in.
\g.

Within the accuracy of the calculation these are appoximately equal'


It

may be necessary to use a damper in branch B, sec. 8.

12-38. Branch A, Balanced Capacity Method


__
Jf

)q

- pocedure -Y11 ! l

System type: Supply Duct Sizing Method: Balanced Capacity Rounding Method: Round Neares __ an Sefection -_
Known an Parameter: Plenum Tota1 ressure

0.1B0 in.

wg

Fan irflow:

40.0 cfm

Excerpts from this work may be reproduced by instructors for distribution on a nt-for-profit basis fr testing or instrutional puoses nly to students enrolled in ourses 1br whih the textbook has been adopted' ny other reproduction or trnsion of this ork beynd ht permittec by Secions ]07 or 08 ofthe ]976 Unied Stes Cpyright cihou he permission ofhe cpyrigh owner is unlwful.

Fan or External Total Coil Lost E'iter Lost Misc. Lost


AU HU U

Pressure reSSure Pressure Pressure

.269 1n. 0.000 in. 0.000 in. 0.00 in. 0.269 in. 0.180 in. 0.089 in.

wg
1^rg

251

wg
\^rg

External Total Pressure:

1^rg

Pressure for Supply System Pressure for Return System

wg wg

or or

33 0%

6'7

0%

Lost re$-sure from ir Handling Unit to Diffuser -Diffuser D


15 19 23 29
1

(cfm) 100.0 100. 100.0


100.

r^-^1 Od-L

(in.

n^l -^ reLd

n r

wg)

0.171 0.155 0.141 0.187

Total

400.0

-- Calculated Fittlng D itting Type

Values -Dia.
(in
)

(cfm)
4.

Velocity ( ftlmin)
.0 905.4 905.4 905.4 905.4

Delta P (in. wg)


0.000 0.011 0.003 0.011 0.014 0.006 0.039

(in. wg) ^P/L

1 2 3 4 5 6

ir Handllng Unit Conlcal Contraction Straight Duct


Elbow

0.
9.

9. 9.0

40.

400.0
40.

0.

14157

Stralght Duct Tee / wye main

branch

7 Straight Duct 8 Tee / wye main

conmon

8.0 5.0
tr

qn

branch

8.0 1.4
'7.0

on

400.0 300.0 100.0 400.0 200.0 100.0 300.0 200.0 100.0 100.0
200. 30.0

Qo /

0.14157

733.4 on / 859.4

t48.4

0.018
0.005 0.020 0.016 0.004
0.
]_3

0.14878

9 Straiqht Duct 10 Tee ,/ Wye main 11 72 13 1'4 15 16 t'7 18 79 2A 2L 22 23 24 2- 28


E1bw

conmon

8.0

branch
conmon

Straigh Straight

Duct Duct

Recanguar Transition
Ebow

5.0 1.0 5.0 5.0 5.0 5.0

7?? I a o 1 148.4 133.4


1))

0.1_3629

100.0 100.0
10.

148.4 133.4
1aa 1))

1.0

Diffuser / Grille
Duct

10.0

360.
7??
a 1a

Rectanquar Transition 5.0


Efbow

Sraight

n
tr

Diffuser / cr1le
Duct

Rectanguar Transition 5.0 Diffuser / cri]_e

Straiqht

5.0

100.0 100.0 100.0 100.0


10.

0.020 0 .0!2 0.016 0.010 0.025


0.07

0.1_9911
0

.1997'7

36.0

5.0 Sraight Duct Butterfy Damper 5. RectanguJ-ar Transition 5.

100.0 100.0 100.0


10.

???
aa1

360.0
111 1" 1

0.016 0.010 0 .425 0.007 0.016


0. 10

0.99'71

0.L9911
0.3-991"7

10.

100.0

360.0

a.025 0.016 0.058


0. 10

Exets from this work may be reprodued by instrutors for distributin on a not_for_profit basis for testing or instructional purposes only to students enrolled in ourses for which the textbook has been adopted. ny ther reproducion or trnslain of his work beyond h permited by Secions ] 07 or 08 f the ]976 Unied SeS Copyrgh ct'wihou he permissin of he copyrigh oner is unlfu.

252

29 Diffuser / Grille

100.0

0.025

Branch B, Balanced Capacity Method


Desgn Procedure _-- -\.
System tye: Supply Duct Sizing Method: Balanced Capacity Rounding Method: Round Nearest
/ t"

-- an Sefection
nown Ean

__

Parameter: Plenum Total Pressur : 500.0 cfm .18 in.

0.180 in.
wg wg wg
Wg

wg

Fan irflow: Fan or xternal Total Pressure:

AHU AU AHU

Coil Lost ressure: i1ter Lost Pressure: Misc. Lost Pressure: External- Total Pressure:

000 in. 0.000 in. 0.00 in.


0.

0.180 in.

wg
% %

Pressure for SuppJ_y System: .18 in. wg - or 1OO.O Pressure f or Return System: 0 . 000 in. \^g - or .

-- Lost ressure from ir andling Unit to Diffuser -Diffuser D Q Tota De]ta P (crm1 (1n. wg) 13 L6 19 23 Total 10.0 75.0 200.0 125.a
50.0

0.185 0.179 0.\42


.15B

-- Calculated ittin Vaues -D itting Type 1 2 3 5 6 7 8 9


A1r andling Unrt Conica Contraction Straight Duct 'aa / ;l',o main

Dia. (in)

Q (cfm) 500.0 50.0 500.0 375.0 25.O 500.0 375.0 2.0 175. 375.0 175.0 175.0 75. 1.0 175.

Velocity (ftlmin) 0.0 916.1 976.1 848.8 636.6 B4B.B 1O18.6 891.3 891.3 891.3 859.4 '733.4
B91.3 84B.B 916.7

Delta P (in. wg)


. OOO . O11

(in. wg) ^P/L


0.72'723

0. 10.0 10.0 9.0 branch 6.O corrion 1.0 Straight Duct 9.0 Tee / wye main 6. branch 6.0 conmon 9. Elbow 6.0 Straight Duct 6.0 Tee / wye main 4.0 branch 5.0 conmon 6.0

0. 18 O.06

O.o42
.OO9

0.019
0.019
0.008

0.725"75

O.014
0.020
0.OO6

0.22175

xcets from this work may be reprodued by instrutors fr distribution on a not-1br-profit basis for testing or instructional puoses only to students enolled in ourses for which the textbk has been adopted. ny ther reproducion or rnslion of his ork beyond th permied by Sections ]07 r 08 fhe 1976 Unied Sttes Copyright chou he permission fthe copyrigh olner is unrwfu"

10 11 \2 13 L4 15 16 71 18 19 20 27 22 23

Diffuser,/ Gril1e Straight Duct Rectangular Transition Diffuser / Gri1e Straight Duct Rectanguar Transition Diffuser,/ Grile Straight Duct Butterfly Damper Rectangular Transition Diffuser / critle

n Straight Duct RectanguJ-ar Transition 5.0


4.0 4.0 6.0 6.0
b.u 6.0 6.0

El-bow

5.0

100.0 100.0 100.0 75.0 75.0 75.0 200.0 200.0


200 .0 125 .4

'733.4
1?2'

10.0

360.0
210 .0

859.4

1018

120 .0

.6

1-25.0
1o

L2s.A

636.6 636.6 450.0

0.007 0.028 0.010 0 .025 0 .028 0 .025 0 .025 0.041 0.014 0.025 0 .0L2 0.044 0.005
a

253
0.1_99'71

0.35266
0

.29022

0.72304

.02s

Branchffilanced Capacity

Method

-- Design rocedure -System type: Supply Duct Sizing Method: Balanced Capacity
Rounding Method: Round Nearest

-- an Se1ecion -Knotn Ean Parameter: Plenum


F.an

Total Pressure : 180 00 0 . 000 0.000


0.
.

0.180 in.
wg wg
\^g

wg

or External Total Col Lost Filter Lost M1sc. Lost

an irfw: Pressure: Pressure: Pressure: ressure:

225.0 cfm

in. in. in. in.


ln. in.

wg wq
\.^/g

AU HU AHU

Xterna1 Tota1 Pressure:

0.

18 in.
0

ressure for Supply System: Pressure fr Return System:

0.180
0.

wg

or or

10.0 z
.C)

-- Lost Pressure from ir andlinq Unit to Diffuser Diffuser D a Totat Deta (cfm) (in. wg)
1-4

1B

10.0 725.0
aatr

.191

0.186

Total

-- Ca1cu1ated Fittin

Values -Dia. (in


8.
)

D Fitting

Type

(cfm)
225

Velocity
(

ftlmin)
O. 644

Delta P (in. wq)


O. OOO

(1n.

AP

/L

wg)

O . OO5 Excerpts from this work may be reproduced by instrutors for distribution on a not-for-profit basis for testing or instructional puoses only to students enrolled in courses or which the textbok has been adopted. ny ther reproducion r rnslion of this ori beyond-h permied by Secions ] 07 or 08 of he 1 976 Jnited Sttes Copyrigh ct ihout he permissin of the copyrigh oner is untwfu'

1 Air Handling Unit 2 Conical Contraction

0.0

225.A .0

O .6

254

4 Butterfly Damper 5 Straight Duct 6 Elbow 7 Straight Duct 8 Elbow 9 Straight Duct 1 Tee / Wye main 11 72 13 74 15 71 18
Efbow

0.08800

3 Stralght

Duct

8.0 8.0 8.0 8.0 8.0 8.0 8.0 6.0 6.0


22\

225 .0

644

.6

0.003

644 .6 644 .6 644 .6 644 .6


644 .6

na tr n

225 .0 225 .0
C1

branch
co'mon

Straight

Duct

8.

6.0 6.0 6.0 6.0


6.

225.0
1.

.0 10.0
1_25

Diffuser / Grille Sraight Duct Rectangular Transition Diffuser / Grile

Rectanguar Transitj-on

100.0 10.0 100.0


14tr

644 .6 636.6 509.3 644 .6 509.3 509.3 360.0

0.003 0.011 0.003 0.003 0.02s


o.

0.003 0.004 0.006 .005


.006

0.!12

0.08800 0.08800 0.08800

oo7

o. 0822L

L25 .0 L25 .0

636.6 450.0

0.010
0.00s 0 .025

0.12304

12-39. Solution follows Example 12-14 closely. 12-40 Solution follows Exampte 12-14 closely

Excets from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional puoses only to students enrolled in courses for which the textbook has been adopted. ny her )eproducion or rhion of his wrk beyond h permied by Secins ] 07 or 08 of he 1976 (]nied Sttes Copyrigh c ihou he peission of the cpyrigh

oer ii

unw'ful.

12-41.

255

SF
2
1

F
M

Po=o
1

c
A

8,,
=

Supply fan: Po

4 in. wg.

Return fan: Po = 1.75 in. wg.


12-42.

SF

2 S
1

Space Pressure S

P=0
-1

-2

le

Fan, Po = 5.75 in. wg.


Exorpts from this work may be reprodued by instrutors for distribution on a not-for-profit basis for testing or instructional puoses only to students enolled in ourses for which the textbook has been adopted. ny other reproduction or trnsti()n f this work beyond h permited b) Sections ] 07 or 08 of the 1 976 Unied Sttes Copyright ct lihout he permission ofthe copyrigh owner is unawfu.

257 12-43.
4

RF
M

P=0
-1

-2

Supply fan: Po

4 in. wg.

Return fan: Po = 1.75 in. wg. 12-44.


6

SI 4

P=0
-1

-2

Excerpts from this work may be reproduced by instructors for distribution on a not-for-prfit basis for testing or instructional purposes ony to students enrolled in urses for whih th txtbook has been adopted. ny other reprduction or rnslion f his rk beyond th pemited by Secions ] 07 r ] 08 of he 976 Unied Sttes Copyright c ithout he permission of the cpyrigh oner is unw/ul'

258 Fan, Po = 5'75 in. wg.


12-45.

(a)

ssume a reasonable duct velocity of about '1200 fpm. Po/L


in. wg./100 ft. and D" = 18 in. (may be converted to

= 0.095

20x14

in. for

example) For the duct: P

(0.095 x 40)1100 = 0.038 in. wg.

For elbows: Co = O.15; P" = 2x o.15(118O/4OO5)2 = 0'026 in. wg. For damper: Co = O.52, P = 0'52(118o/4OO5)2 = 0.045 in. wg. For grille: P, = 0'25 in. wg For expansion: Vo = V.'(A.'/o) = 118Ol2 =59O fpm
Pu

1'2(59ol4oo5)2 = 0.026 in. wg.

overall: Po
Po

= 0.038 + 0.026 + 0.045 +

0'25

0.026

.385 in. wg.

(b)

For 18 in. duct with 1,00 cfm, P/L = 0'027 in. wg./10 ft
For duct: P6 = 0'027 x 401100 = 0.01 1 in. wg. For elbows: P" = 2x0'15(59ol4og5)2 = 0.006 in. wg. For grile: P, = O'25(1Qoo/2o)2 = 0.063 For expansion: Vo = 59012 = 295 fpm

P" = 1'2(295l4oO5)2 = O.OO7 in. wg.


xerpts frm this work may be reproduced by instrutors or distribution on a nt-for-profit basis for testing or instrutional puoses only to students enrolled in courses for which the textbook has been adopted- ny oher reproduction or trnsion of this ork beyond h permitted by Sections 07 r 108 fthe ]976 Uniled Stes Copyrigh cwihu he permissin fthe copyrigh oner is unlful.

For damper: P6 = 0.385 _ (0.01

259
'1 +

0.007 + .063 + 0.007)

P6 = 0'297 in' wg. = Co"(59O lAooqz

(c)

Co" = 0.29710.022 = 13.7

12-46. Equal Friction Method


Note that a damper has been inserted in duct 6 (N. 34 betow) to cause an increase in duct diameter from 8 to 9 1n. with a consequent decrease in velocity to an acceptable 1evel.

-- Deslgn Procedure -System type: Supply Dut Sizing Method: trqua1 r1ction
Rounding Method: Round Nearest

-- Fan Selection -Known Fan Parameter: E'an Tota1 Pressure

.900 in.
wg wq wg w wg

wg

an

or Ext.erna Total Coil Lost ilter LoSt Misc. Lst

Fan irflow:

Pressure: Pressure: Pressure: Pressure:

.500 in. 0.100 in. 0.050 in. 0.250 in.

845.0 cfm 0.9 in.

AU AU AU

External Total Pressure:

Pressure for Supply System: 0.150 in. wg - or 60.0 Pressure for Return System: .10 in. wg - or 40.0

% %

-- Lost ressure from ir and1ing Unit to Diffuser -Diffuser ID Q Tota Delta (cfm) (in. wq) 19 24 28 32 38 Total 150.0 L25.0 120.0 200.0 25.0
845.0 0.128 a.123 0.11s 0.143
.141

-- Ca1cu1ated Fittin Values -TD itting Type Dia. (in) Q (cfm) Velocity (ftlmin)
Delta P (in. \^/g) (in. wg) ^P/L

Eerpts from this work may be reproduced by instrutors for distributin on a not_fr_profit basis for testing or instrutional puoses only to students enrolled in courses fr which the textbok has been adopted. ny oher reproducin or rnslion of this work beyond h permitted by Seclins ] 07 or 1 08 of the ] 976 Unied Ses Copyrigh ct wihu the permissin f he cpyrigh ner is unlful.

260 1 2 3 4 5 6 ir anding Unit Conical Contraction Straight Duct


Elbow Elbow

Straight

Duct

14.0 14.0 14.0 14.0 14.0 2 .0


74 .0

L4 .0

0.0

845.0 845.0 845.0 845.0 845.0 845.0 845.0 595.0

190 .4 190 .4 190 .4

0.0

190.4 190 .4

0.000 0.008 0.003

0.005
.006

0.06

0.06415
0. 6415
. 6415

7 Straight Duct 8 Tee / vlye 9 Straight Duct 10 Tee / Wye

main

branch
comon

on

250 .0

15'7 . 6

190.4
56

0. 05

0.006

main

12.A
10. 10.

845.0

branch

11 Straight Duct: L2 Tee ,/ Wye main 13 Stralght Duct 1-4 Tee / Wye main 15 16 11 18 L9 20 22 23 24 25 26 21 28 29 JU 31 32 3 3 34 35 36 3'/ 38
bow

co]non

12 .0

8.0

branch
comon

9.0 7.0 10.0 1.0 1.0 9.0 1.0 1.0 1.4 1.0 1.4 1.0 7.0 1.0 1.0 7.0 7.0 8.0 8.0
B. 9.

12A.A 395.

215 .0

395.0 200.0 595.0 395.0

190.4 151 .6
' 573.0 -151 .6 '1 ' G22 '\ 124 .2 622 .5
46'7 .'7

0.018 0.004 0.017

1'

0. 07

.01 L61

0.07

449 .0

0.003 0.016
0.07
0.
3

0.08259

branch
conon

215.0 150.0
15.0 15.0

L25 .0

561.3 561.3 561.3 561.3 450.0


46'7

0.07138

0.011 0.006 0.005 0.016 0.004 0.040 0.013


0.08082
0.0B82

Straight

Duct

Strai ght Duct Rectangular Transition

21-

Straight Duc Rectanqular Transition Diffuser / Gri1e Ebow Straight Ducc Rectangular Transition Diffuser,/ crill_e Sraqh ]uct Rectaigular Transition Diffuser,/ Grille
lbow

Ebow

Diffuser,/ Grltle Sraight Duct

150.0 150.0
150. 125 .0 L25 .0

1atr . rZJ

12
T

n n

375.0
449 .0

461 .1 61 1

.1

120.0 200.0 240.A 200.0 250.0 250.0 250.0


250.
250 .0

72A.A 720 .0

L20 .0

449.A

36.0

20.

573.0 573.0 600.0

Stralght Duc Butterfly Damper Straight Duct Rectanguar Transition Diffuser / Gri1le

E]_bw

9.0 9.0 9.0 o


9.

565.9 565.9 565.9 750.0


6

0. 3
. 13
0

0.002 0.002 .030 0.002 0.011 0 .002 .036 0.003 0.010 0.000 0.04
.024

.02

0.05817 0.05817

0.05405

0.07106

0.0604

0.001 0.001
0.
5

0.06004

Balanced Capacity Method


Note that dampers have been inserted in ducts 6 and 7 (No. 31 and 36 below) to cause an increase in duct diameter and a consequent decrease in velocity.

-- Design Procedure -System type: Supply Duct Sizing Method: Balanced Capacity
Rounding Method: Round Nearest
Exerpts frm this work may be reprodued by instrutors for distribution n a not-for-profit basis for testing or instructional purposes only to students enoed in courses for which the tetbook has been adopted. ny ther reproducion or trnlslion of his ork beyond h permied by Secions ] 07 or 08 of he 1 976 United Sttes Cpyrigh c hout he permission of the cpyrigh owner is unl:lful.

261

_- an Selection -Known an

Parameter: Fan Tota1 Pressure :

0.9OO in.

wg

an Airflow: Fan or xternal Total Pressure:

Coil Lost Pressure: i1ter Lost Pressure: Misc. Lost Pressure:

0.900 . 500 0.100 0.50

845.0 cfm

in. in. in. in.

wg wg wg w wg
?
%

U AU AU

Externa1 Total ressure:

0.250 in.

Pressure for Supply System: 0.150 in. wg _ or 60.O Pressure for Return System: .100 in. wg - or 4O.O

_- Lost Pressure from ir andling Unit to Diffuser -Diffuser D Q Total De]ta P (cfm) (in. wg) 19 24 28 33 38 Total 150.0 725.0 720.0 200. 2s0.0
845.0 0.141 0.728 0.140 0.140 0.131

-- Calculated Fittlng Values -D itting Type 1 2 3 4 5 6 7 8


1r anding Unit Conical Contraction

Dia. (in)
0. 14.

Q Veocity (cfm) (ftlmin) O O O 0 845.0 B45.O 845.0 595. O 250.0 845. 595. 395. O 20.0 595.0 395. 21 5.O L2a.O 395.0 2']5.O 15O. L25.0 2'75.0 150.0
B45. B45. 845. 845.
O. O 19O.4 '79a.4 '7 90 .4 i90.4 190.4 19O.4 j5j .6 458.4

De1ta P

(in. wg)
O. OOO . O8 O. OO3
O.

(in. wg) ^P/L


O. 6415

Straight Duct 14.0 Elbow 14 . 0 straight Duct 14.0 bow 14.0 Straight Duct 14. Tee / wye main 72.A branch 10.0 conmon 14.0 9 Stra1ght Duct 72.0 10 Tee / Wye main 10.0 branch 8.0 counon 2.0 11 Straight Duct 10.0 12 'T / ',o main 9.0 branch 6. O co]non 10.0 13 Stralqht Duct 9. \4 ee / Wye main 1 .0 branch '7 .0 co]nmn 9. 15 Straight Duct 1 .a

O.OO6

o.oo5

OO6

0.06415
O.O6415

O.OO6
.020
O. OO5

151 .6

151 .6 j24.2 573.0

190.4

O. OO4 O. O17

O.7 OO7

0.0'716'7

622.5 561.3 46i .i 561.3


622.5

'724.2

124.2 622.5 6l.2

O.OO3

O.

O. O8259

O. O13 O. OO7 O. OO3 O. O713B

0.011
O.

OO6

. O8s2

xcets from this work may be reproduced by instructors for distribution on a nt-for_profit basis for testing or instrutional purposes only to students enrolled in courses for which the textbook has been adopted. ny other reprducion or rnsion of this work beynd h permited by Sectins 07 or a8 of the ] 976 Unied Stes Copyright c wthout he pemission f the copyrigh oner is unvful.

262

19 20 2 22 23 24 25 26 21 28 29 30 31 32 33 34 35 36 3-l 38

j 1-6 Elbow 1-1 Stralght Duct i .0 1B Rectangular Transj-tion i.0

.0

Reclangular Transit1on

Diffuser / Grilte Straiqht Duct 1bow Straight Duct Rectangular Transition Diffuser / erile El-bow Straight Duct Rectangular Transition Diffuser / Grill_e Elbow Butterfly Damper Straight Duct Rectangu1ar Transitin Diffuser / Gri11e E1bow Butterfly Damper Straight Duct Diffuser,/ critle

j.A

i.0
6. 6.

1.0
0

1.O

15.0 150.0 150.0 150.0 12 n 125.0 125.0


120.0 120 .0 200 .0 200. 200 .0 200.0 200.0 250.0 250.0 250.A 250. 250 .0
120 .0 120 .0 1t\ cl 725 .0

561.3 561.3 450.0


461 .'7 461 .'7 461 ."7

0.016 0.013 0.002 0.002


0.004 0.040

0.05

0.08082 0.05817
.05817

375.
G1

0.002
.030

6.0 8.0 8.0 8.0


8.

1 2 36.0

677 .2

573.0 573.0
?? n

0.007 0.036 0.003 0 .024


0.00
0

0.023

0.004

0.1\42-7

600.0
458 .4

0.010
.002

0.07106

1.0 10.

458 .4

0.040 0.0L6

10.0
1.0

750.

458.4

0.008
0.001 0.050

0.03599

Exets frm this work may be reproduced by instructors for distribution on a not-for_profit basis for testing or instructional puoses only to students enrolled in courses for which the textbook has been Moptd. ny ther reproduction or rislion f hN wri beyond h pemied by Secins ] 07 or 08 of the 1976 United Sttes Cpyrigh c ihut he peimission of the cpyrigh over is unlfut.

Excets from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instructional purposes only t students enrolled in ourses for whih the textbook has been adopted. ny other reproduction r trnsltion of this wrk beyond tht permitted by Sections ]07 or 0B of the 976 United Sttes Copyright ct without the permission of the cpyright o')ner is unlwful. Requests for permission or further infrmtion should be ddressed to the Permission Deprtment, John Wiley & Sons, nc, ] ] ] Rier Street, boken, NJ 07030.

CHAPTER
13-1. From q' 13-2

13

h-= tr* _
(C*

c-

lb*
_ t2 (l* , n,

r.,,.

ft'
_hr

ft2

Now C and W are related by

Eq

13-14

|% W" * = lba fto

lb*/ft3

he density of dry air must be used. Then from q. ,1 3-17


h =

hrP"' =

ftz _ hr--

-ft3 X9 =

ft3

ft2

]b, _hr

Consider Eq. 13-13 which is dimensionless

h
P3Cp,h
-z-

Btu
ftz _ hr _

F |b, Btu
^--^---;-

ft3 lb,F

ft2

- hr

ft3

Clearly dimensionless when C* is used.

13-2.

using Eq. 13-'18,

h Le2t3 1; h = = -- = ,,'9. = 41'7lba/(hr cpah = Cp, 0.24


= h/" = 41 .7lO'O75 = 555.6 ft3/1hr

ftr)

also h,
h6

_ ft')

: 0.057 kgal(m'0.61s p"oa7

s)

13-3. hd
k

0,075x100x60x(1 t14_

261

o44

= g52

k = 0.0147 Btul(ft-hr-F) (able A-4a) n=


Ot.O,::!,

x \ ' (1t12)0.61 5(852)047 = 2.S9Btu/(hr-ft2-F)

h6 = h/cpa

=2.5910.24= iO.B lba/(ft2-h11

h,

= h6/" = 1O.8/0 .O75 = 144

ff lt'-hr)
3

13-4. Nu

0.023 Re0.8 pro 3 0r h

0.023 (k/D) Reo.s pro


'1

and h6 = h/cpa, assuming Le = Re = V ol;


L=

= 600/ =

(il$

= 471 ft/min or 28,260 ftthr

0.044lbmlft-hr;

0.075 (Tabe A-4a)

Re =

0'075?8'260x1 = 48,170 0.044

Pr = 0.7; k = 0.01 47 btulhr-ft-F (Tabe A-4a)


h = O.O23

(48,17o)os(O.7)o., = 1.7 Btu/(hr-ft2-F)

h = 1'710'24 =

7'1 lba/(ft2-hr)

h* = h6/^=7'1l0'075 = 95 ft3/(ft'-hr)

13-5. 43,560

ft2 = 1

acre;

i'l

* = hd(Wr, - W-)

Use j factor anaogy, h/crh6 = Le2l3

ssume: Le

= 0.85; C + 0'24

Thenho-

o.24(o.8q2t3
=

'

=23.221bal(ft2-hr)

Using chart 1: WW*

0.013 bu/lba

- 0.0223lb"ilba

(assume sat. air at 80 F)

Excerpts from this work may be reproduced by instrutors fbr distribution on a nt_for-profit basis for testing or instructinal purposes nly to students enroled in ourses or rhih the textbook has been adopted. ny oher reproductin o, rootion of his rk beyond h pemited by Sections ] 07 or 08 of he ] 976 Unied Ses Copyrigh ct y]ihout he permission of the copyright owner is unlful.

__._ 262
h, = (23'22)1ooo(43,56OXo.o223
fr,,, = 9,415,ooO lbr/hr

o.o1 3)

19 gpm/acre

13-6. Use analogy of Eq.


q = qr + Q., W,
coLe2l

13_1g

Ql= h(W- - Wr)irgi Q. = h(t- - t*)


= 0.00765;
|

ho= h
Q/ q/
=

W-

= O.O'1 10;

Chart

144\- 9(1.15)=,- =49'23lba/(ft2-h 3 \ l' 'il 024(82 =


5)(75-50) = 25g Btu/(hr-ft2)
ft2)

49.23(0.o 11-0.00765)1o65 = 176 Btu/(hr _ ft')


.1

Q./A = 9(1
=

435 Btui(hr _

= 1'37 kWlm2

13-7.

Qr= rh,(i*-i,,)

h, = hd(WV, - W-)
h6 = h/(cr"Lezu); cp, = h =
'1

0.24 Btul(lba _ F);

'510'24 = 6'25lbal(hr

W,
h,

0'0223lb,/lba

Le2t3 =

ft')

W* = o.0096 lb,/ba
1

i- = 28.4 Btu/lba; Chart


=

6.25(300 x 15O)(O. 0223

h, = 3,572lbWhr
Q1

0.0096)

= 3,572(1,05o) = 3,75O,600 Btu/hr o

x 1,o99 kW

ny water on the deck and occupants neglected.

13-8'

lt is assumed that the blanket is folded in half over the clothes line with one side exposed to air.
ho

cp

Le-2t3

18.g7tbai(hr -ft ) #(0.g3)-2l3 =

Excerpts frm this work may be reproduced by instructors for distributiol on a nt-for-profit basis for testing or instructiona puoses only to students enrolled in ourses for which the iextbok t-'u, ""r, adopted. -sl oher rj)a""rnn or rnslion of rhis ork beynd th permitted by Secions ] 07 or ] 08 f the 976 |Jniecl Ses copyrgh't c nut n" po7'irin f the copyrigh oner is unlful.

h*

hd(Wb

W,); Wn = 0.0312;W^= 0'0152

263

hr, =

}
I 8.

'=m*/[hd(Wv_W")]
(16

- 4)

87(56)(0. 03 1 2

0.01 52)

= 0.71 hr

= 42'6

min

Say 45 min.

13-9. The procedure is the same as example 13-1 except that the
energy balance line A-B will have a positive slope
and
tl

=75"F, tlz
17

90"F

Ans: 68162"F;

.4 ft2:4.8 ft

13-'10. The solutions to this problem closely follows example 13-2.

Ans: 77169"F; 17.4

ft2;

4.8 ft

ns.

31126

C;

'1.6 m2; 3 m

13-11. The procedure is the Same aS example 13-2 exept that the energy

balance line A-B will have a negative slope and the inlet and outlet
water temps. are reversed.

ns: 71t69"F;
13
J

17

'4 ft2;5.5

ft

50

45
_

ham =5510.24=229.2 h1/h6 = -3.05

40
35 30 'l -Jt t2t
I I

=#,

4000 x

12.

A. =

rh

r/G,
X

0.071

6O/1OOO = 17 ft2

xerpts from students enrl]

o_

lJ

25
20 60

permited by S

Y
70 80 90 100

or instrutional puoses only to |ion f his wrk beyond tht gh wner is unlwful.

264

2'7, Then
11 .8 ft

L = Gry/hdm = 100 x2'71229'2 =

13-13. The solution to this problem closely follows example 13-3


13-14.

Ans: 1.4 to

1.5

13-15. Solution of this problem follows example '13-4 closely.


'13-'16.

ns:

5OO ft2; 12'2 ft

13-17. Extrapolate the 72 F wb curve in Fig. 13-9. The largest cooling tower modeI ''M'', iS not arge enough to handle 200 gpm.

Therefore use two towers of 1000 gpm each. Select the


model "L" which ls rated at about 1100 gpm.

13-'18 See example 13-3; the cooing tower must be larger.


13-19. See example '13-3; the cooling tower must be larger.

13-20. (a) Model B or C using Fig. (b) Cooling Range


=

'13-9

-t. 2= 100-85 = 15 F
'yihou

Exerpts rom this work may be reprodued by instructors for distribution on a not-for-profit basis fr testing or instrutional purposes only to students enrolled in courses for which the textbook has been adopted' ny ther reprduction or trnstion of his rk beynd th pemitted by Secins ]07 or l 08 of he ] 976 United Ses Cpyright c the permission ofhe copyrigh owner is unlful'

pproach = t. z-twol = 85 _ 76 = 9 F
Tower capacity =
Q

265

= (200 x 60 x 8.33)(1)(15) = 1,499,400 Btu/hr

13-21 q

50 5OO qpm x t; qpm = '=??o,o^o = 500x1 0 -^^. =3.0 5,000)

qpm/ton= 50 (250,000
/1

Note:

!n this

case,

'1

ton = 15,000 Btu/hr


= 70

Cold water temperature; t" From Fig. 13-7;


t*o =

10 = 60 F

42 F

13-22. lbuquerque, NM; t6 = 64 F (able B-1a) (a) From Fig. 13-7; cold water temperature
gpm/ton
=

73 F;

2'5i

\/arm
t6 =

water temperature (73 + 10) 83 F

(b) Charleston, SC;


gpm =

79 F (Table B-1a)

From Fig. 13-7; cold water temperature = 84 F,

15,000

x2'5= 83 gpm (a &

b)

13-23' (a) tons = ''?9?99o 15,000 (b) gpm/ton


=

80, gpm/ton = 24O8O= 3.O, maximum


=

two =

72F

80

= 4'o',max. t,5

65 F

13-24. Model G, nominal rating

600 gpm & 250 tons (Table 13-2).

Using Figure 13-9; assume gpm is constant.


Exerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructinal puoses only to students enrolled in courss for which the textbook has been adopted. ny other reprduction or rnsltion of this work beyond th permitted by Sections ] 07 r 0B f the ]976 Unied Sttes Copyrigh c'|)ithout he permission of the cpyright owner is unlrrwful.

266

With cooting range of (97 Max. Max.


two =

85) = 12

76 F (Figure 13-9)
tu,

With cooling range = 15,


two =

= 100 F

74 F (Figure 13-9)

Exets from this work may be reproduced by instrutors for distribution on a not-for_profit basis for testing or instructional puoses only to students enolled in courses for whih the textbook has been adopted. ny ther reproducion or trnslion of his ork beyond tht permitted by Sections ]07 or ] 0B f he 976 United Stes Cop1'ight c without the pemission of the copyrigh owner is unful.

-------_-=\

---

basis for Excerpts from this work may be reprduced by instructors for distribution on a not-for_profit textbok has been testing or instrutional pubses orty to students enrlled in courses for whih the of this work beyond tht permitted by Sections 107 or adoptd. ny other repriuction oi trnsltion the copyright owner is unlwful' Oti f the lbo ne Smtes Copyright ct withut the permission of be ddressed to the Permission Deprtment, Requests for permission or furter ffirmtion should Join Wiley & Sons, nc, ] ] Rier Street' Hoboken' J 07030'

CHAPTER 14

120-60 14-1. (a) P - 200 60


-

= 0.43
= 0.33

*=

200-180
120

F = 0.985 {Fig. 14-191


(1so - 6_q)_:(299_ 120) LMTD _ (180 - 60) ln

- 60

(200 -120)

LMTD

= 98.7oF

(b) C"

=
=

(fr

"r)",,

= 50oo

*uo -

(29'92x0'491x144)
53.35(520)

'24)

5490 Btu/hr-F

cn = cc(1,2

= '16,500 Btu/hr-F

tu1)/(t*z

t*r) = 5490(1 20

-60y(200

180)

(c)

Cn

(rh cp)* = (Q pcp)* = 16,500 Btu/hr-F

Q=

16'500

(6Ol1)

=25ft3/hr; Q

275(7.48) = 34 gpm 60

(d) q

UAF(LMTD)
C-.,

UA =

F(LMTD)

(t*z--t*l) _ 16,500(20
U UA
Cair

_ 180)

0.985(e8.7)

3390 Btu/hr-F

(e) NTU
NTU

UA
Cmin

Cc

3390 = 0.62 5490

267

^-

(f) \/

120-60 "= 200-60

0.43

268

14-2' (a)

UF(LMTD) = (rh cp),i,(1 10-50) h, = 4000 x 14'7 x 144l(53.35 x 510) = 311'2 lbmin or 18,672|b/hr Q = 18,672(0.24)(110-50) = 268,874 Btu/hr q = (rh cr,,)('l80 - tr.,o) = Q5 x 8.33)(1)(180 - tho)60
=
1

t.o =

80

p= 110-50 =0.46: *='180-159 =0.35


180 F = 0.98; Fig. 14-1

25x8.33x60

=?9y+

= 158.5 F or 159 F

-50
't[

10

- 50

LMrD=S#

=88

A = 9/(UF x LMD)' ='!u!!!^o== = 312 10x0.98x88

^J

ft2

(b)

Cair = 18,672(0'24) = 4481 = Cmin Cwat = 25 x (60.817 .48) x 60 = 12,193 =

110 180 -

5o

50

0.401'

4481 - 12,193 crr,


Cmin
,10

Cr*
= o.3T

NTU

= 0.7,

Fig. 1 4-18

UA/C,1. = O'7i

,=
x

0'7\!481

= 314

ft2

14-3. (a)

h air

= 32o x 60

53.35x555

::'::'!!-

= 13,726lb/hr
125

Cair=Cmin=3294 1ox3oo NTU = 0.91 3294 = 0.615, Fig. 14-18


at C.inlCrr, = 0

l
atr.

refri.

125

+
Exerpts from this work may be reproduced by instructors for distributin on a nt-for-profit basis for testing or instrutional puoses only to students enrolled in courses for whih the textbook has been adopted. ny oher reprduction or trnsltin of this ork beyond h permitted b Secons ] 07 or 08 f he 97 6 Lnied Ses Cp1'igh ct ihou the permissin of he copyrigh oner is unlcwfu.

r_.14-3.
269
(continued)

0.61s = ,':"=-'^?
125
t,o =

113'5'F

- 95

, tco = t"o = 0.6'1

s(125- gs)

+ g5

(b)

Q = Cui,(tao - tai) - rh,.irg = 3294(11 3.5 3294(1 13.5 - 95) lrl,. = ------------.6s.s = 928 tb/hr

95)

14-4' (a) ,= l y
L

lm =

(1.0

-]

R/r = 1l0.5 = 2.0i = .8, Fig' 14-4

12

- 0.5) 18.26= 0.76

90(0.00 8 l 12) J

(b)

,.,

tah(mrl)

mr

,_ '

tanh(0.9454) =0.7g 0.9454

(18.26)(0 '5112)1.243 = 0.9454

\mr) \r )\
, =

[E -,][.'+ O.35rnBj

r/

1.243

(c) Within readability of Fig.

14-4 the answers are the same

14-5.

s =

1+ A

(1 - ); = O.78 from proplem 14-4


=

s = 1-0.9(1-0.78)

0.80

'1

Uo ho?ro
J-

k(, /o
= 0.17;

1
hi(i /o
=

) 10x0.8
o and
k.opp",.

(0.01 5112) (100x1)


= 100

200x(1/9)

Assumes ;

Exerpts 1iom this work may be reproduced by instrutors for dstribution on a not-for-profit basis for testing or instructional puoses only to students enrolled in courses for which the textbook has been adopted. ny ther reprducion or rnslin f his wrk beyond th permied by Secions ]07 or 08 of he 1976 United Ses Cpyright c withou he permissin f he cpyright oner is unllful.

270

The second term may be neglected Uo = 5.9 Btu/(hr-ft2-F)

14-7.

=! Uo 10x0.8

'1

100(1/9)

=0.133

Uo = 7.5 Btu/(hr-ft2-F)

14-8. ,' -

tanh(m/)
v =| z"s _1''' =64.18 y ] l za1o.'t l]
[

m!.

e-l'''
L

6x1 o_3

m-1

mI = 64.18(6

x 1O-')

= 0.385;

0.953

14-g' ns=1 -)_1-o.s5(1 *(1


. = 0.96

_O.95)

Ar =

2LWP,
=

mm2;

= LW mm2;

Ar + (LW _ tLWPS)
1

Where P"

fin pitch in fins/in. and L = W =

= 2HLWP' + LW _ tP, _2x6x0'47 +1_0'16x'47 - '1 lo+ l' '1A' o ,L\/P' 2x6x'47

+=\:--J^ u 1400 57(0.96)

= O.O19;

U = 52.3 W(m' _ c)

Excerpts from this rork may be reprodued by instructors for distribution on a not-for-profit basis for testing or instructional puoses only to students enrolled in ourses for whih the textbook has been adopted. ny ther reprducion or trnsin f his work beyond th permitted by Secions ] 07 or l 0B of he ] 976 United Sttes Cpyrigh c lihout he permission of the cpyright owner is unlwful.

271
14-11
.

'= [}_,][,+O35.(})] R" = 1.2s ( - 0'2)'''; m = r


mr

tan h(m r/

znl1l2

L]

*=},=;;L>M
(a) Diml

=;'=

0.56 in

b = 1.35 in

Dim, =
=

' rrg)' *or1''' 2L2l


l

jo.uu)'* (1'35)'1'''=

O.73

0'56 =(0.64 t2)=1'75:3=0'73 0.56


R"
r = (2.22-- 1)t1 + O.35ln(

Then L = Dimz = 0.73in.; M = Dimr = 0.56 in. =1.3

t2=2.22 = 1.27(1.Ts)(L3-0.3)1 2.22)!= 1'56;

2x10

mr

L e0(0.01/ 12)

16.33(0.32112)1.56 = 0.631

f'''

= 16.33

ft-1

n_ '

tanh(0.762) =0.869 0.762

(b) Dim.-a-12.5mm '2


Dim2 =

L = Dimz = 12.65 mm M = Dimr = 12.5 mm

' ! lZZt + 12.5'ltt2 = 12.65 mm 2'


b=22mm

t=12'5 =2.s:g=
R"
r

12'65
12.5

=1.012

= 1.27(2.s)(1.01 2

0.g)1t2 = 2.69

Excerpts fiom this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional puoses on1y to students enolled in ourses for whih the textbook has been adopted' ny ther reproducon or rnstion ofhis lrk beyond th permitted by Sections ] 07 r ] 08 f he 97 6 United Ses Copyrigh c y,ithu the permission of he copyright owner is unlful.

272
=

0.753 = 0'85

11 =

1170(0.00018)_j mrQ = 66.67(0.005)2.26 = 0.753 _ tanh(O.753)

m=l

zxo ll=66.67m-1

2.69

1)t1 + 0.35 ln(2.69)] = 2.26 E'\vv _^ -_

'

14-12. + = hoo v-_ Uo -1-, h; (, 7no ; neslecting tube wall resistance


(a) 1o=1

(b) ro

*(1 1

) -)-1_o.9(1 _O.s4)=0.86
oo(l o)
=

_----{

1o106

:^

= 0.120; Uo =

8.60 Btu/(hr-ft2-F)

1=

=1

-0.9(1 -0.81)

0.83

0,.068ro s3

^4^
0 64(

1a.+rl o1

= 17.8; Uo

= 0.056 kW(m2

- c)

14-13. (a)

Rct = 2.222

10-6

0.010

1t12

1)'
)

.010

Rct = 4.15

]""'
10-a 1hr-ft2-r1/tu

(b)

'12

fins/in = 0.472 fin/mm

rc(1t0
Rct=3.913x10-7

0.18
0.18

72_

uott=

1)'
)
1o
1

.oe3 x 1o-41m2

- cyw

l
14-14' Re= D;=60.6

lbm/ft3

Excerpts frm this work may be reprodued by instrutors fbr distribution on a not-for-profit basis for testing or instructional purposes only to students enolled in ourses for which the textbook has been adopted. ny ther reproductin r rnsion ofthisorkbeyond tht pemitted by Secions ] 07 r 0B of the ] 976 Unied Ses Copy'igh c ihu the Permissin of he copyrigh oner is unlfut.

273
Dr = 0.545112 = 0.0454 ft;

e 'lA= 2'5

7 '48^ 60( t4)(o'o454)2

x+

Table C-2

=3.44fVsec

= o.93 lbm/(ft

Re =

60.6(3.44)0'0454 2.58x10-a

hr) = 2'58 x 1O-a lbm/(ft-sec) able A-1a


=

36,6g3i Re = 36,700

(L/D),in = 410'0454 = 88 ft Pr = 2'43 (Pr = cr/k)

lo '',u
k

= O.23

"Bu Pro';

k = 0.383 Btu/(hr-ft-F)
Btu/(hr-ft2-F1

= O.O23

(0.0454)

,f''='J. (36,7oo)o'12.431o' = 1,136


1

14-15'

= 1'o1(62.4) = 63.02 LBM/FT2 [Fig.

0-2a]
1O-2b]

= 0.7l1490

4'7 x

'1o-4

lbm/ft-sec [Fig.

Cp = 0.93 Btu/lbm-F [Fig. 14-];

K = 0.93 Btu/lbm-F [Fig. 14-9]

'045 Re=ffi=20,940
63.02(3.4 4)0
(L/D),1n = 88
lr---''ia-

fVsec [Probem M-1aJ; D = 0.0454 ft [Problem 14-14]


= 3.44

ft

[Problem 14-14]
.285

o _Cp _4'7x1o41soo)o.93 _.)

= O.O23 ,!o:',u=u], (2,94O)ou15'521o'=

(0.0454)

690 Btu/(hr-ft2-F)

14-16'

= 1.O45

x 62.4 = 65'21

lbm/ft2

= 1 '3l1490 = 8'725 x
co = 0.81

1O-a

lbm/(ft-sec)

Re=#=11,670
Exerpts from this work may be reprodued by instructors for distribution on a not-for-proit basis for testing or instrutional puosos ony to students enolled in courses for which the textbook has been adpted. Any her reproduction or trnstion of this ork beyond tht permitted by Secions ] 07 r 1 08 f he 1 976 United SeS Copyrigh c withu the permissin of he copyrigh oner is unlwful.

;k= 0.22; V

= 3.44 ft/seC,

D = 0.454 ft

274
,,"

_ 0.81x8.725x1 0-43600
0.22

= ..16
=

.1

0.023 !:?3=). (i 1 ,670)0.(.1 ..t6)0. 0.0454 '

209 Btu/(hr-ft2-F1

14-17. Use hydraulic dia.


D = 4rn =

for rectangular channel


=

a(AJP)

4(3/8) = 1.5 in. = 0.125 tt

= 62.4lbm/ft3 [Table A-1a]; = 3.45 lbm/(ft-hr) [Table A-1a] u':o!!_), Re = -'-?? = 32,556

(3.45l3600) cp = 1.003 Btu/lbm-F [Table a-1a] k = 0.338 Btu/(ft-hr-F); Pr = 3.45 x 1 .003/0.338 =

'10

(a) For cooin9,


h
= O.O23

h = O.O23

! D

R"o'Pro'

9 0.125 9 0.125

(32,556)0r11o.21o. = 5O9 Btu/(hr-ft2-F)

(b) For
h

heating;
(32,556)0s11O.21o. = 642Btu/(hr-ft2-F)

= O.O23

14-18.

Dr, =

0.125

ft [From problem
1o_3

14-171
1

= 62.4(1.o45) = 65'2lbm/ft3 [Fig. = 3.5/149O = 2.35 x

O-2a]

lbm/ft-sec [Fig

'

10-2b]

Re=
c,
Pr
=

0.89 btu/(lbm-F) [Fig. 14-8]


2.35 x 1 o-3136o)(o.s9) l0 '28 = 26.9

k = 0.28 Btu/(ft-hr-F) [Fig. 1a-g];


=

Excerpts rom this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instrutional puoses nly to students enrolled in courses for whih the textbook has been adopted. ny other reproducion or rnsion of his work beyond h permited by Sections ] 07 or 08 of he 1 976 United Ses Cpyrigh c y,ithou he permission of the cpyright owner is unlful.

275

(a) Cooling
h
=

0.023

#
=

('13,900)0t126.910t = 28s Btu/(hr-ft2-F)

(b) Heating: h

285 '""

(26'9):1
(26'910'e

396 Btu/(hr-ft2-F)

14-1g' (a) Re = D _
Assume L/D Then

99'2(1 '5)(0'012) _ ^''' =29'905


>

60

o'uffi

o.o23 Reo.8Pro4, Pr =

[o'sgxlo3x+'lzl

6373

e.gl

= 9 9?: 0.o12

(O.637X31 ,157)o s(3.91)o

h = 8287 W(m2

C)

8.29 kw(m',- C)

Data from Figures 10-2a, 10-2b, 14-8 and 14-9.

(b) Re =

(1

.2x10-3x3.7x10-3 ,r=ffi=8.9
1

'28)999(1 '5)(0'012) 15,4OO = 1.2x10-3

:-= o.o23 (.5o)(15,4oO)08(8.9)oo = 5140 W(m2 _ c) h ']


0.012
= 5.1

4 k\l(m2

- c)

14-20. (a) Re =

62'4(0'5)(0'3!112) = 922< 2soo (3.45l3600)


=,

hD .1.86tReP. D .,lls [ra)o 'o : ssume ( n)o'o = l.vvl.-,, L, r',,l,,1oLl,,J

xerpts from this work may be reprodued by instructors for distribution on a nt-for-prfit basis for testing or instrutional purposes only to students enolled in courses or whih the textbook has been adopted. ny oher reproductin or trnslion of this work beyond h permitted by Secins ] 07 or 08 of the ] 976 Unied Ses Copyrigh ct |ihout he permission of he cpyright lner is unlcrlfu.

276

,,=1#

=1O'4
=

sff#

p22(1o.ol(ffi),"'

66 Btu/(hr-ft2-F)
ethylene

(b) Same procedure as part a using data for

30o/o

glycol from Figures 10-2a, 10-2b,14-8 and 14-9.

14_21. Re

992.2(0.1.0)x103 = 1519 653 There is a question about the flow regime. lt is probably

in the transition region. Assume it is laminar and use

Eq. 1 4-24 and assu me | -UPr

10.14

['J

= 1.

- 1 893) '--_\n=-O.O1 1519(4'34)r']]1/3 ' 3 )'


14-22. Use average values for
Gu and

o.653X'1_3(4.182) = 4'34 0.63

328

W(m'- c)

G.

and Eq. 14-26.

G. =:o;(rh."9'v )"us= '

.''
-

0.912;(Gr)",s

= ln't,,u z(o.s9)'

=237.81bm/(ft2-hr)

4\12)

(rh,),us

(1 + 0.1)12 = 0.55 lbm/hr

(Gu),us = 0.55/4" =

290'6 lbm/(ft2-hr)
= 12 3

lt 12 , 0.95 / DGu _r0 589)r9) = 15 12 , 0.95 /

DG, _ r0.589)r?)

H=

138(pr.,,.

[#j"'L?

E)"102

xcerpts from this work may be reprduced by instrutors for distribution on a not-fr-prfit basis for testing or instrutional purposes ny to students enrotled in ourses for whih the textbook has been adopted. ny other reprduction or trnson f his work beyond th permied by Sections ] 07 or 08 f the ] 97 6 Unied Stes Copyrigh ct ilhout he permission f the copy'igh oner is unfu.

277

=2.48 0.384 i,, = 1001 Btu/lbm t 80 = 1'160 _ s0); twall

l") Pr _ 0.95(1.001) '


6
h

p'(

e")"'

.,u.o1, 61

0.0135/

o )"'

= 1oo8

=
=

13.8 g - - .58

0.384 t12

Q8)

80'F (Using water outside 2 '4n' 1]-l"u '' Ul'


L,1

the tubes)

,(u]
Gu and

,,,oo8]o

888 Btu/(hr-ft2-F)

"

14-23. Use average values of G. and


A"= (O.o15)'= 1'767 x "4
(G.
)"us =
1O-a

Eq. 14-26

mt
=

(.s8)o. 126x1o_3 z 1.767x10-a 0.126x10-3


(1 + O.
1

0.314 kg/(m2

s)

(Gu)"ug =

2) t 2

1.767x10-a

= 0.399 kg/(m2

s)

DGr _ 015(0.311) = 12'1

0.390x10_"

DGu

( r)"'
|"

O.o15(0.39_9

Pr. '
t =

O'39Ox1
= (73

L0'219J 9j1' 19x1 03 = 2'46;


O.39Ox1o_3

gz

2
l1

= 1024

0.665

ig = 2326kJ/kg

45C

_ 28); liquid water assumed outside tubes

h=13gj95)(2'46)1t3lffi].,u..o24)o2=5022W(m2-c)
h
= 5.02 kw(m2

- c)

14-24' Use q. 14-28


Excerpts students enrolled in ourses'for which tbe textbook has been adopted. ny oher reproduction or trnson of this permtted by Sections ]07 or 08 ofhe 1976 United Ses Cpyrightc\ithout he permission ofhe copyright ner is unlful.

At inlet x : 0.20; at outlet 10oF superheat p,J*FsnR 1"Q,psi?i k,':. if,'$-"t.n puoses only to from this wrk may ,l"rj],' ,,Jhm/fu wrk beynd h

R_22

278

Since X" 1.O; Cl = 8'2 x 1O-3; n = O.4 ssume tube wall thickness of 0.016 in. hen D; = 0.375 - 2(0.0161 = 0.343 in.
Ai=

'4

-g|

= 6'417

1o-4 ft2

rJ = -:-

80 rh= A j 6.417x10-a

= 124,700 lbm/(ft2

hr)

= 0'52lbm/(ft-hr) at 30'F (sat. temp. at 70 psia) GD 124,700(0.343 I 12) = 6855 =

k = 0.056 Btu/(hr-ft-F) at i1g = 88'5 Btu/lbm

0.52

30'F (sat. temp.); Table -3a


o

h h

=
=

8.2x 1O-3

(0.o56)

(O.343,

779 btu/(hr-ft2-F)

rssl, (a'qaa'sz'))lo 5(32l 7) r)L'oocc J.]

14-25. Use Equation '1 4-28


R-22;G
= 2OO kg/(m2

s); Dr = 8.5 mm; L = 2 m; P,= 210 kPa

= 30%, Xe = 100%

Tsat =

-24C a|210 kPa abs. Pres. [Table A-3b]

. = O.27O x 1O-3 N-s/m2 [Table -3b]; extrapolate k. = 0.107 W(m - c) [Table A-3b]
i= 223 kJ/kg [Table A-3b]
GD=200(0.0085_)

'270x10_3

=6296

= 8.2

'1O-3;

n = O.4

6 = 8'2x

1O-3

(o'1O7) 0.0085 L'


=

296\2

7(223)1 000

. r0.

Ie 2x9.80 7

J]

h = 4106 W(m2 _ C)

4.11 klm',_

Excerpts from this work may be reproduced by instructors for distribution on a not-for-proft basis for testing or instrutional puoses only to students enrolled in ourss for which the textbook has been adopted. ny other reprducion or rnsion f his work beyond th permitlecl by Sectins ] 07 or 08 f he ] 976 tJnited Sttes Cyright ct \ihout he permissin f the copyrigh oner is unwfu.

14-26.

lr, =

" f !!1 D2g

279
,

Assume isothermat

Re = 36,700; Probem 14-14; smooth tubes


f =0.022, Fig.
Dr = lr,

10-1;L=(6x6)+(5xl)=41

ft

0.0454 ft;

= 3.44 fUsec,

Problem 14-14

=o.o2z*

-!10.0454 2x32.17

*lt!!l,t

=3.65ft

14-27'

l . =

" f !, D2g

ssume isothermal

=O.5ft/sec; f =64/Re =641922=O.OOg

L = (10 x 10) + (9 x 1.5) = 113.5 ft; Di = 0.34 in.


l. = 0.06 n*11?^'?x12, -

0.34

2x32.17

',

1'07 ft

14-28.

Refer to Fig. 14-10


Load/circuit = 10 x 1 2,000110 = 1 2,000 Btu/hr Length/ircuit = (6 X 5) + (5 x 0.75) = 33.75 ft

(a) P. /L = 0.10

psi/ft;

CF

1.25 Fig. 14-10


=

P.
CF

= 0.10 x 33.75

x 1'25

4.22 psi

(b) P. /L = 0.04
= 1.25

psi/ft

P.

= 0.04 x 33.75

x 1'25

= 1.7 psi

14-29.

Gt,^

= 18OO lbm/(hr-ft'); t, =

7O"F,tz= 120"F

(a) Figure 14-12


Excerpts frm this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instructional puoses only to students enrled in courses fr which the textbook has been adopted' ny other reprduction or tr'nsioi of his ork beyni th permitted by Sectons ] 07 or 08 of the 1 976 Unied Stes Copyrigh c ihout he pemission f the copyrigh owner is unlwfu'

280

Re, =
=

G'Xo

, Gc =

G"

''_'-''\ - = 3214 lbm/(ft2-hr) 0.56

4.6 x 10-2 lbm/(ft-hr) at t = 95oF (Table A-4a)


3214(1 .083 t12)

Re,

4.6x10-2 jG" c,

6306

j = 0.0091;f = 0.021 Fig. 14-12

Pr-2l3 = O.OO91 (3214)0.24(O.T)-2t3

8.91 Btu/(hr-ft2-F)
=

(b) Re6

6306 x 0.52511.083 = 3057; assumes expanded tubes

plus fin collars.

At D6D
JP
j=
9.

A 4xoxr _ 4 1.25x1.083x0.56
= (3057)-04(1O.OS)-015 =

0'0152x0 '525x12

= 1O.O8

0.0285 (Eq.

14-39)

1x1-3 Fig. 14-14; h = O.OO91(3214)(0.24)(0.7zl! 0.525x10 08 = 0.904 (1.25 - 0.525)


116.7

= 8.9 Btu/(hr-ft2-F)

D*=

1+

Using Eq. 14-44.

" FP= (3o57)-0 2'[oo+.1


(

0.525,0

I 1.25 - 0.525

t 0.173
f
=

4(

\67

L-

o o06) ) ]"

10.e04

'zs _,,l_o

4.2 x 1O-2 or

0.042 (Note that f may be in error up to

!35o/o (Figure 14-15)

Exerpts lrom this work may be reprodued by instructors for distributlon on a not-for-proflt basis for testing r instructinal puoses only to students enrolled in courses for whih the txtbook has been adopted. ny her reprducon or rnson of his work beyond th permitted by Sectons ] 07 r 08 f the 1 976 Unied Sttes Copyrigh c wihout he permission of the copyrigh owner is unlwful.

14-30. (a) G"

4.5 kg/(m'-.);

tp =

2OC; Re =

Gc(0'0275)

281
'

= 1 8'2 x 10-6 -s/m2 1Table A-4b]

Re =

4'5(0'027)
18.2x10-o

6800;

Cp = 1.OO5

kJ/kg-C

j = 0.009; f = 0.020 [Fig. 14-121

jG" copr-2t3 = o.oog0(4.5)1.005(0.7)-2t3

0.051 kJ/(m2-s-c)

= 0.051

kw(m2-c)

(b) See problem 14-29b for prcedure

14-31. Use Eq. 14-42 or 14-45

l,n ,'i= '

o2{ 2g-1L\,*" )lo''_' )_,

el-r,r *

e_,l*'+4l

-,

#!S#L 53.35(530)

= 0.O75 lbm/ft3; 2 = O.068 lbm/ft3

P,, = (l + 2)l2= 0'072lbmlft3

A Af,
Where V
lh

A _

_147(1.083112)5 = 118'45
(1)0.56
A1,"

= t.

xL;

_(, * o.u6), )r9 _ l)* ''= /\0.068 ) 2(32'17)(0'072)(0.075)(3600) L\ o 042(1 1s 5)(0 075)l

214)2

= 1 ft2;L = 5 x'1.083/1 2 = 0'451

072 -l
=

h = 12.2ft of air

Po =

(1i::?);'z

0 18 in. wg

xerpts from this work may be reproduced by instrutors for distribution n a not_for-profit basis for testing or instrutional puoses only to students enrolled in courses or whih the textbok has been adopted. ny other reproducion or rnsion f his wrk beyond th permtted by Sections ] 07 or 08 of the ]976 United Sttes Copyright c ihout he permissin f the cpyrigh owner is unful.

282

14-32. Use Equation 1 4-42 or 14_45 ti = 10C; t2 = 30C, ff" = 1 18.5 from problem
o =
pm =

14-31

ffi1

1O1x103

= 1.244 kg/m3; Pz= 1.161 kg/m3;

1.203 kg/m3
(0 56)2

t'

ffi[(,'.
o.O19(1 18.5)/

)(#-

1).

1!1

1.203 )

r,

= 1.67 m of air

Po = 1

6,

(#l',rool

= 2'O8mm of wg.
=

or Po = 1'67(1'244)9'807

20.4 Pa

14-g3. Re = G.Dr,

, D' = O.O101 ft
1O-2

t 65.F, = 4.39 x

e=lffi
h
=

bm/(ft-hr) [Table A-4a]

2700(0.0101)

=621
0.013, f = 0.053
1

From Fig. 14-16;j


G" co j
Pr-2t3

= 2700(0.24)O.013(0.72)-2t3 =
= O.72 From

O.

S Btu/(h r-ft2-F)

Where co= 0'24 Btu/(lbm-F); Pr

able A-4a

14-34' Use Eq.

14-33; t = 65 F
=
=

'o -ff 53.35(535)


Pm =

14.6x144

0'074lbmlft3; 2= 0.077 lbmlft3

(l + ")l2

0.076 lbmift3

xerpts from this work may be reproduced by instructors for distribution on a not-for_profit basis for testing or instructional puoses only to students enroled in urses fr which the texook has been adpted. ,lny otlrr', ir:o'-"in o, ronrtoton of his ork beyoncl ht permied by SeCionS ] 07 or 08 of he 97 6 Unied Ses Copyrgh c nout inte p,esion of the cpyrigh o,ner is untcwful.

28s

Assume a contraction ratio of 0'5 Then i -- 0 '32', " = 0 '27 Fig ' 1 4-17

A 4L -I2 == oll
Po

= 132

_ _

e7oq2
053(1

22.17

)1

4'6(1 44)(0.07

4)(3600)'

_ t(o.32 * l- os2)
_ (o 5)2

(#-

1)

-o

3r)ffi#] _ r

_'''1#'\

Po/Pg1

0'17 in' wg' Po = 4'126x 1o-4114.6)(1 44)(12)t62'4 =

=4'126x10-a

14-35. (a) Coil DescriPtion'


Type of coil = Refrigerant condenser coil Tube pattern = Staggered plate-fin-tube Material
=

luminum fins with copper tubes

Refrigerant type = Refrigerant 134

Finned side fluid = air of Hg Finned side air pressure = 29'92 inches

Face area

-- 4'44 square feet

Height of heat exchanger = 20'0 inches Width of heat exchanger = 32'0 inches

Numberofrowsoftubesintheairflowdirection=4 Numberoftubesperro\/=16circuitsontubeside=4
inches Fin pitch = 8 fins/inch Fin thickness = '006 Vertical tube spacing = 1'250 inches
* ,oi'iii)jili'bnii

puoses only to basis for testing or instructional by instructors for distribution on a not-fbr-profit of his ork beyond h xcerDts from this work may be reproduced ny- o,rnr, ,rrour'ioir-ron,oi ,-'. exibook r, ..nrjopi.*' oner is unlful' sudens enolled in courses ", *-L1. ih" prr^r,rio' oj'n" copyrigh i,o*, ] 07 ''hout permied by Sections

ciiilii, iri

284

Horizontal tube spacing = 1'083 inches Tube outside diameter = .500 inches Tube wall thickness = .016 inches lnside tube fouling factor = 'OOOO BTU-HR-SQFT-F

'/6C

14-95. (continued)

Btu/hr Total heat transfer rate = -48783'2 -48783'2 Btu/hr Sensible heat transfer rate =

Entering air conditions: Dry bulb temPerature

95'0 F

Face velocitY

650'00 FPM

CFM Air volume flow rate = 2888'9


F Dry bulb temPerature = 111'4

Leaving air conditions: Tube side conditions: 125'0 F Refrigerant saturation temperature = of water Air pressure loss = '393 inches PSI Tube side Pressure loss = 1'07 Fin efficiency =

'3gg

Surface effectiveness = '824

Tubesideheattransfercoefficient=388.88tu/hr-SQFT-F Finnedsideheattransfercoefficient=12'5Btu/hr-SQFT-F
Mean temperature difference
=

-20'7 F

(b) Yes

14-36. Coil DescriPtion'


Type of coil
=

water or brine solution

coil Tube pattern = staggered plate-fin-tube tubes Material = aluminum fins with copper

Tube side fluid

water
:;i:i'b:;,ff:;;i!:'ii:i1r,*"ir;?j':ii,:!;;iiii:i!j:'i#ii!*'' perm
c
w

:i:.J:fJ:f;':T:J$E::',i:;i1:i1i:'*iJ$'{ij:{..Ti Copyrigh i ii6 t'Jnied Ses 07 ermied by Secins "''ii')i 'i

ilhou he

286

Finned side fluid

air

Finned side air pressure = 29.92 iches of Hg

Face area

5.56 square feet

Height of heat exchanger = 20.0 inches Width of heat exchanger = 40.0 inches Number or
ro\/S

of tubes in the air flow direction = 2


ro\ =

Number of tubes per Fin pitch


=7

16 Circuits on tube side

fins/inch Fin thickness .008 inches

Vertical tube spacing = 1.250 inches orizontal tube spacing = 1.083 inches Tube outside diameter = .500 inches ube wall thickness = .016 inches lnside tube fouling factor = .0000 Btu-hr-SQFT-F
Diameter of inlet pipe/header = 1.0 inch(s)

Total heat transfer rate Entering air conditions:

-95759.1 Btu/hr
=

Sensible heat transfer rate

-95759.1 Btu/hr

Dry bulb temperature 7. F

Face velocity

650.00 FPM
=

Air volume flow rate Leaving air conditions:

3611.1 CFM

Dry bulb temperature = 94.6 F

Tube side conditions:


Entering fluid temperature = 150.0 F

Leaving fluid temperature = 128.2 F


Excerpts from this work may be reproduced by instructors for distribution on a not-for_prfit basis for testing or instructional purposes only to 'work beyond th students enrolled in courses for whih the textbook has been adopted . ny oher reprduction r trnstion of his permitted by Sections l 07 r 08 of he ] 976 t]nied Stes Copyrigh ct wthou he permissin f he copyrigh oner is unwful'

ube side fuid velocity

4.00 FPS
=

287 9.0 GPM

Cooling or heating liquid flow rate Tube side head loss


Fin effiiency
= 8.20

Air pressure loss = .187 inches of water


feet or water

- .831

Surface effectiveness = .846

Tube side heat transfer coefficient = '1368.8 Btu/hr,SQFT-F Finned side heat transfer coefficient = 14.4 Btu/hr-SQFT-F Mean temperature difference
=

-56.8 F

14-37. From problem

14-29, Re = 6306 (based on xp)

and h5 = 8.9'1 btu/(hr-ft2-F) jn : _.1r -1280 Nr(Re)-1 2 (Eq. 14-42) =


j

then _ 1_ 1280 x 5 (Re)-1'2

1_ 6400 Re_1 '2

i 1_(8x12so)(6306)_1 1 and J_ , ^

js

_ (5x1 2s0)(63o 6l_ 'z


= j/js

o 872 g J.r,

now h/hs
ha =

= 0'872

h = 0'872(8.91)

7.77 Btu/(hr-ft2-F)
=

14-38. From problem 14-30, Re

jsjs

jn

1- 128oNr(Re)l 1- 64OORe-1
2

6800 and h5 = 51W(m'- C)

[From sotution

to

14-371

j _ 1_(6x128)(680)] 1- 64OO(6801-r z

= 0.96

Excerpts from this work may be reprodued by instructors for distribution on a nt_for_profit basis for testing or instructional puoses only to students enrolled in curses for which the textbook has been adopted. ny ther reprducion or rnslion of his ork beyond tht permed by Sections ]07 r 08 ofthe ]976 United Sttes Cpyrighcwithu the permSsion ofhe copyright o'ner is unlwful.

288

l ur rr s = jo/js = 0.96

h = 0'96 x 51 = 49W(m2

- C)

or o.o49 kW(m2

- c)

14-39' Re, = %xo

j = 0.0095 (Fig. 14-12)

(1.os3/12) x 60 = 8225 = =o':1:= 0.0445 0.54

l - jcco

Pr-2l3 = O.OO85 x

.o73,

ffi
)

x60x

o-24(o'-2t3

h = 10.5 Btu/(hr-ft2-F) 0.0092 .1 Using Chart c.. _ 0.0123 = .033 x 1O-a,) v _

or

0.0123-0.0063 .^^ z- -- 85_q5


Cavg

85

55

= 1.5 x

1O-a

PSYC

1'27 x1O-a;

Use Eq. 1 4-7o &14-73',k = 1z*s};

From Table 5-1a.


M2 =

##l, -]
1'27

= u, 3;

M = 22'7 = 1'265

ft-1

r
*=

(- o.3)"' =
+

(1

o.3)1t2

'r [E'_ l)[l /


= (1 '265 Mr = 22.7

O.35n&l

_ 1)[1

r)
=

+ 0.35 ln(1.265)] = 0'287

xO'287

0'285

m-_--'-

'

tanh(mrl)
mr

g7.4o/o = 0.g74 or

,s

1 *

(1 -

,)

f _O.94(1 _ o'g74)=

O.98 or 98%

14-40' For

80/67oF;

tp =

60oF

surface temperature must be equal to or less than 60"F'


puoses only to for distribution on a not-for-profit basis for testing or instrutiona Exerpts from this work may be reproduced by instructors th uJopt.. ny her reproucion r trnsin of this wrk beyond bee, students enrolled in ourses for whih the texook has ihe permission of the cpyright owner is unl'wful' hout permited by Secions 07 * l '"iinr''i ii'6-Unirrd Sror cipyr,gh 'aci

289
Moisture would condense at the base of the fin on the tube outer surface if it condenses at all' Let t* be this temPerature.

where --"-'_

1 =-1' *,1*,r=Ai UAi hiA k, ,n 1 =!*41= :_""- U, hi ' k 1000 12x190 '9o]:^
t* = tr

UiAi(t,-

tr) = h69A(i,

ir)

= O.OO1

Ui = l OOO Btu/(hr-ft2-F); where k"opp", = 190 Btu/(ft-hr-F)

ffi(i,-

i*) = 50 +

ffi

(31.7

i*)

ssume a value for tr, read

i* from

chart 1 and compute t* to

check assumption' Assume t* = 55'8'F then i' = 23'7 Btu/lba and the calculated t* checks O.K. Therefore moisture will condense at the base of the fin and on some portion of the fin. There will probably be no condensation near the outer edge of the
fin.

14-41. For 2719 g,

t =

15 C

Solution is similar to problem 14-40


UiAi(t, _ tr) = h66(i3 _ i*)

ui 53
t*=ti

+0'0005
58

= O.O1888;

U= 52.98

ffi

(i"_i*)

=14'3-,g4,,* 4.2_i,)

*H

For t* = 16, i* = 45. Checks O.K.


puoses only to on a not-for-profit basis for testing or instrutinal xcerpts for this work may be reprodued by instrutors for distribution or rnsion f his rk beyond thl in ourses 1br which the textiook has been adopted. ny oher reprduction students enrled he copyright ner is unlwful' ihe permissin prr^t'rca y srctins ] 07 or l ij rni l oz Lnied Stes cip)rgnt 'ci lthu

290

is There will be no condensation because the tube outside wall

greaterthanthedewpointtemperatureoftheair. 14-42" This problem is intended for computer solution because


considerable iteration is required'

Coil DescriPtion:
Type of coil
=

water or brine solution

Tube pattern = staggered plate-fin-tube coil Material = aluminum fins with copper tubes Tube side fluid
=

water
=

Finned side fluid

air

Finned side air pressure = 29'92 inches of Hg

Face area = 12.50 square feet Height of heat exchanger = 30'0 inches
Width of heat exchanger = 60'0 inches; W = 2H Number of rows of tubes in the air flow direction = 5

Number of tubes per

ro\/ =

24

Circuits on tube side = '12

Finpitch=12fins/inchFinthickness=.008inches
Vertical tube spacing = 1'250 inches Horizontal tube spacing = 1'083 inches Tube outside diameter = '500 inches Tube wall thickness = '016 inches

lnsidetubefoulingfactor=,OOO0Btu-hr-SQFT-F Diameter of inlet pipeihead er = 2'5 inch(s)


or instructional purposes only to for distribution on a not-for_profit basis for tsting xerpts from this work may be reproduced by instructors trnsion of his work beyond th or iy o" has *,' students enrolled in courses fbwhich the texibook "p'oucon "J"pi". 'q ihe permission f the copyrigh owner is unlful' coiir|gn, 'a"i permited by Sectins ] 07 * '"iir''i ii'6-in,"d S,o'r, 'thout

14.42. (continued)
Total heat transfer rate = 232885.0 Btu/hr

291

Sensible heat transfer rate = 164919.4 Btu/hr


Entering air conditions: Dry bulb temperature = 80.0 F Wet bulb temperature 68.0 F

Enthalpy = 32'3 Btu/LBM


Humidity ratio = 83.3 grains/LBMA

Face velocity

550.00 FPM
=

Air volume flow rate Leaving air conditions:

6875.0 CFM

Comment: coil is 34.3 percent dry


Dry bulb temperature = 57.4 F

Wet bulb temPerature = 57.1 F


EnthalPY = 24'4 Btu/LBMA umidity ratio = 68.7 Grains/LBMA

Tube side conditions:


Entering fluid temperature = 45.0 F

Leaving fluid temperature = 62.4 F ube side fluid velocity


=

4.00 FPS

Cooling or heating liquid flow rate = 26.9 GPM

Air pressure loss = .774 inches of water


ube side head loss = 14.09 feet of water
Fin efficiency = .gg9

Surface effectiveness = .819

Tube side heat transfer coefficient = 822.3 Btu/hr-SQFT-F Finned side heat transfer coefficient = 10.0 Btuihr-SQFT-F
Exepts from this work may be reproduced by instructors 1br drstribution on a not-for-pro1lt basis for testing or instructional purposes only to students enrolled in courses fr whih the textbook has ben adopted. ny oher reproducion or rnstion of his wrk beyond th permitled by Sections ] 07 r 08 of he ] 976 tJnied Stes Copyright ct without he permissin f the cpyrigh ner is unfu.

292

14-43. Coil DescriPtion.


ype of coil = Direct expansion Tube pattern Material
=

Staggered circular-fin-tube coil

Aluminum fins with copper tubes


air

Refrigerant tYPe = refrigerant22

Finned side fluid

Finned side air pressure = 29.92 inches of Hg

Face area

= 10.31 square feet

Height of heat exchanger = 24.8 inches Width of heat exchanger = 60.0 inches Number of rows of tubes in the air flow direction = 4 Number of tubes per ro\ =

16

Circuits on tube side = 16

Fin pitch = 12

Fins/inch

Fin thickness .014 inches

Vertical tube spacing = 1.500 inches


Horizontal tube spacing = 1.300 inches

Tube outside diameter = .625 inches Tube wall thickness = .022 inches lnside tube fouling factor = .0000 Btu-HR-SQFT-F Total heat transfer rate
Entering air conditions: Dry bulb temperatue = 82.0 F
purposS only to Ecets fim this work may be rprduced by instructors for drstribution on a not-for-profit basis for testing or instutional of this ork beynd tht students enrolled in courses for which the texibook has been adopted. ny oher reproducion or trnstin oner is unlful' permitted by Secins ] 07 or 08 f he ] 976 (nited Ses Cpyrght ct \hou the permissin of he copyrigh

241221.0 Btu/hr

Sensible heat transfer rate = 162201'8 Btu/hr

293 Wet bulb temPerature


=

67.0 F

Enthalpy = 31.4 Btu/LBMA


umidity ratio = 74'9 Grains/LBM

Face velocity

500'00 FPM
=

Air volume flow rate Leaving air conditions:

5156.3 CFM

Comment: Coil is .0 Percent drY


Dry bulb temPerature = 52'2 F Wet bulb temperature 50.7 F

Enthalpy = 20.6 Btu/LBMA


Humidity ratio = 52.1 Grains/LBMA

Tube side conditions. Refrigerant saturation temperature = 35.0 F

Air pressure loss = .623 inches of water


Tube side pressure loss = 1.36 PSI Refrigerant quality entering/leaving evaporator = '29 Enthalpy change in evaporator = 62'75 Btu/LBM
Fin efficiency =

.679

Surface effectiveness = '885


=

Tube side heat transfer coefficient

375.5 Btu/hr-sQFT-F

Finned side heat transfer coefficient = 9.3 Btu/hr-SQF-F

14-44. Coil DescriPtion:


TYPe of coil = Steam

Tube pattern
Material
=

Triangular plate-fin-tube coil

Aluminum fins with copper tubes

ube side fluid = Steam Finned side fluid


=

Air

Finned side air pressure = 29'92 inches of Hg


basis for testing or instructional purposes only to Excets frm this work may be reproduced by instructors for distibution on a not-for-profit ny ther reprducion or trnslifi ofthiswrkbeynd ht Students enroled in courses for whih the texibook has been adopted. ihe permission of he copyrigh owner is unlrful' permitted by Sectins 07 r l iiin, ] 9t76 (Jnitecl Sttes Copjrght ,ci ithout

294

Face area = 12.00 square feet Height of heat exchanger = 24'0 inches
Width of heat exchanger = 72'0 inches Number of rows of tubes in the air flow direction = 2 Circuits on tube side = 16 Number of tubes per ro\M =

16

Finpitch=8Fins/inch

Fin thickness = .006 inches

Vertical tube spacing = 1.500 inches


orizontal tube spacing = 1'299 inches

ube outside diameter = '625 inches Tube wall thickness = .0'18 inches lnside tube fouling factor = .0000 Btu-hr-SQFT-F Total heat transfer rate Entering air conditions:
Dry bulb temperature 60.0 F
=

-554503'6 Btu/hr
=

Sensible heat transfer rate

-55453'6 Btu/hr

Face velocitY

750'00 FPM
=

ir volume flow rate Leaving air conditions:

9000.0 cFM

Dry bulb temperature 116'1 F

Tube side conditions: Steam temPerature


= 227

'1 F
=

Steam saturation pressure

5'000 PSIG

Air pressure loss = '269 inches of water Fin efficiency = .738 surface effectiveness = '756
purposes only to on a not-for_profit basis for tsting or instrutional Excets from this work may be reprodued by instrutors 1br distribution ny her reprucion or rnsltion f his ork beyond th students enrolled in ourses tbr w*ch the texibook has b..n uJo|t"d. ner is unful' isiz Lnitel Ses cpyrglt ,ci thout the permission of he copyright permitted by Sections ] 07 r l ^"i

'n,

295

14-44. (continued)
ube side heat transfer coefficient = 2051.7 Btu/hr-SQFT-F Finned side heat transfer coefficient = 14.6 Btu/hr-SQFT-F

14-45. Coil DescriPtion:


Type of coil
=

Water or brine solution

Tube pattern = Staggered plate-fin-tube coil Material = Aluminum fins with copper tubes

ubesidefluid=3Oo/oethyleneglycolsolution
Finned side fluid
=

ir

Finned side air pressure = 29'92 inches of Hg

Face area

= 5.56

square feet

Height of heat exchanger = 20'0 inches Width of heat exchanger = 40'0 inches Number of rows of tubes in the air flow direction = 2 Circuits on tube side = 4 Number of tubes per ro\/ =

16

Fin pitch

Fins/inch

Fin thickness = .008 inches

Vertical tube spacing = 1'250 inches Horizontal tube spacing = 1'083 inches Tube outside diameter = .500 inches Tube wall thickness = .016 inches

Insidetubefoulingfactor=.OOO0Btu-hr-SQFT-F
'1'0 inch(s) Diameter of inlet pipe/header =

Total heat transfer rate

-9610'1 Btu/hr
=

Sensible heat transfer rate


'n,

-90610'1 Btu/hr

purposes only to distribution on a not-for-profit basis for testing or instructional EXcetS fiom this work may be reprodued by instructors tbr ny other reproucion or rcnsion of his ork beyond ht aJopte. students enrolled in ourses fbr which the texibook has been copyrigh oner is unlfu' i sz (Jnied SeS cip)rgt 'ci hu ihe permission of he permited by Secions ] 07 or l ^"i

296 Entering air conditions:


Dry bulb temperature = 70.0 F

Face velocity

650.00 FPM
=

ir volume flow rate

3611.1 cFM

Leaving air conditions:


Dry bulb temperature = 93.3 F

Tube side conditions:


Entering flud temperature = 150.O F

Leaving fluid temperature = 128.4 F Tube side fluid velocity = 4.00 FPS Cooling or heating iquid flow rate
= 9.O

GPM

ir pressure loss = '186 inches of water ube side head loss ='10.13 feet of water
Fn efficiency

.83'1

Surface effectiveness = .846


= 796.O

Tube side heat transfer coefficient

Btu/hr-SQF-F

Finned side heat transfer coefficient = 14.4 Btu/hr-seFT-F Mean temperature difference = -57.6 F here is a 5 percent reduction in capacity and increased pressure loss on the tube side.

14-46. Coil Description:


Type of coil Material
Excts

Water or brine solution Staggered plate-fin-tube coil


= 30o

ube pattern
=

luminum fins with copper tubes


ethylene glycol solution
nytherreprucionrrnstioiofhislorkbeynith

Tube side fluid

studentsenroIedincoursesfrwhihthetextbookhasbeenadopted.

from this work may be reproduced by instrutors for distribution on a nt-for-profit basis or testing or instrutional purposes only to

permited by Sectins ] 07 or 08 of he 1 976 United Ses Cpyrigh ct

ithu ihe permission of he copyright olner is unlful.

Finned side fluid

Air

297

Finned side air pressure = 29.92 inches of Hg

Face area = 12.50 square feet


Height of heat exchanger = 30.0 inches Width of heat exchanger = 60.0 inches Number of rows of tubes in the air flow direction = 5 Number of tubes per
ro\/ =

24

Circuits on tube side = 12

Fin pitch = 12

Fins/inch

Fin thickness .008 inches

Vertical tube spacing = 1.250 inches Horizontal tube spacing = 1.083 inches ube outside diameter = .500 inches ube wall thickness = .016 inches lnside tube fouling factor = .0000 Btu-hr-SQFT-F
Diameter of inet pipe/header = 2'5 inch(s)

Total heat transfer rate = 211374.2 Btu/hr

Sensible heat transfer rate = 155955.9 Btu/hr


Entering air conditions: Dry bulb temperature 80. F

Wet bulb temperature 68.0 F


EnthalPY = 32'3 Btu/LBMA umidity ratio = 83.3 Grains/LBMA

Face velocity

550.00 FPM
=

ir volume flow rate

6875.0 cFM

Comment: Coil is 43.6 percent dry


Excerpts from this rrk may be reproduced by instructors for distribution on a not-for-pro1'it basis for testing or instructional purposes only to students enolled in courses for whih the textbook has been adopted. ny oher reproductin of trns.]tin ofthis ork beyond ht pemied by Secions ] 07 or 08 f he l 976 Unied Ses Copyrigh ct |ihout he permission of the copyrigh oner is unlwfu.

298

14-46. (continued)
Leaving air conditions:
Dry bulb temperature 58.6 F Wet bulb temperature 58.2 F

Enthalpy = 25'1 Btu/LBMA


Humidity ratio = 71.4 Grains/LBM

Tube side conditions:


Entering fluid temperature = 45.0 F

Leaving fluid temPerature ube side fluid velocity


=

62.0 F

4'00 FPS

Cooling or heating liquid flow rate = 26'9 GPM

ir pressure loss

= .756

inches of water

Tube side head loss = 18.13 feet of water


Fin efficiency =

.699

Surface effectiveness = '819

Tube side heat transfer coefficient = 476.4 Btu/hr-sQFT-F Finned side heat transfer coefficient = 10.0 Btu-hr-SQFT-F The capacity is reduced by about 9 percent, the pressure loss on the
tube side is increased and the leaving air temperatures have increased
by about 1 degree.

14-47. Check Examples 14-1 through 14-5

Coil Description:
Type of Coil Material
=

Water or Brine Solution

ube Pattern = Staggered Plate_Fin-Tube Coil


=

luminum Fins With Copper Tubes


'n,

basis for testing or instrutional purpses nly to Excerpts 1ior this wrk may be reproduced by instructors fbr distribution on a not-for-profit reproducion or rnstion f his work beyond th students enroled in ourses for whih the texibook has been adopted. ny oher ]976 Unied Ses Copyrigh ,ci ithou ihe permission of he copyright oner is unlwfu' permited by Sectins ] 07 or l o i7

Tube Side Fluid

Water
=

299

Finned Side Fluid

Air

Finned Side Air Pressure Face Area

0. FT. of levation

2.17 Square Feet

eight of Heat Exchanger = 12.5 ]nches Width of Heat Exchanger = 25.0 linches Number of Rows of Tubes in the ir Flow Direction = 5 Number of Tubes Per Row =

10

Circuits on ube Side = 5

Fin Ptch = 8

Fins/lnch

Fin Thickness = .006 lnches

Vertical Tube Spacing = 1.250lnches


Horizontal Tube Spacing = 1.083 lnches

Tube Outside Diameter = .525 lnches


Tube Wall Thickness = .015 lnches

lnside Tube Fouling Factor = .0000 R-FT2_F/Btu


Diameter of Inlet Pipe/eader = 1.3 lnch(s)

Total Heat ransfer Rate = -133026.9 Btu/HR

Sensible Heat Transfer Rate = -133026.9 BtuiHR


Entering ir Conditions: Dry Bulb emperature = 50.0 F

Face Velocity = 950.00 FPM ir Volume Flow Rate= 2061.6 cFM


Leaving Air Conditions: Dry Bulb Temperature = 107.6 F

Tube Side Conditions: Entering Fluid Temperature = 150.0 F


EXcerpts fim this work may be reproduced by instrutrs or drstribution on a not-for-profit basis for testing or instrutional purpses only to students enrolled in courses for whih the textbok has been adopted. ny ther reproducon or trnsion of this ork beyond th permited by Sections ] 07 r 08 of he 976 United Saes Cpyrigh ct withu he permission of he copyright oner is unl:ful.

300

Leaving Fluid Temperature = 128.3 F ube Side Fuid Velocity

4.00 FPS

Cooling or Heating Liquid Flow Rate = 12.5 GPM

ir Pressure Loss = 1.13'1 lnches of Water


Tube Side Head Loss Fin EfficieCy

6.77 Feet of Water

= '750

Surface Effectiveness = '771

Tube Side eat Transfer Coefficient = '1 354.2 Btu/hr-SQF-F Finned Side eat ransfer Coefficient = '19.5 Btu/hr-SQF-F Mean Temperature Difference
=

-58.5 F

he above results show that a 5 row coil would easily satisfy


the specified requirements. he manual calculation of the

examples are very conservative.

Exerpts from this work may be reproduced by instrutors for distribution on a not-for-profit basis for testing or instrutional purposes only to students enrolled in courses for which the textbook has been adopted. ny oher reproducion or trnsltion f this wrk beyond h permitted by Secions ] 07 or 08 of the ] 976 Unied SteS Copyrigh ct 1ihout he permission of he copyrigh owner is unlful'

Excets from this wrk may be reproduced by instrutors for distribution on a not-for-prort basis fr testing or instrutional purps, on1y to students enrolled in courses for whih the textbook has been ]07 or ]08 adoptd. ny ther repiodiction r trnsltion of this work beyond tht permitted by Sections is unlwful. o7 ile lz (]nited Smtes Copyright ct without the permission of the copyright owner iequests for permission or furtier-idormtion should be ddressed to the Permission Deprtment, Jhn Wiley & Sons, nc, 11 Rier Street, Hoboken, ]\J 07030.

Chapter 15
15-1

COP

qe/\rv;

UseP-idiagram

_V = i+_ig =119.5_105.5

= - 14.0 Btu

lbm

p
4

Q"=il -i=42'5-119'5
=

-77 Btu / lbm

ooF

tlooF

14

ooF

g"=-Q"+\M=77-14
=

63 Btu / lbm

(a) (b)

COP=63 114=4.5
CoP"".n.1 = 50

l (570- 5)
%

7'14

0r=
(c)

4.5 7.14

0.63 or 63

= Q"

coP

10 (12,000) _26,667 Btu 4.5


=

lhr =

1.5

HP N

7.8 kW

then

ton 10 =

HP

10'5

1.O5 and

=O.22 kW
=

(d)

Qe = hQe o h =

10 (12,000)

63

1905 lbm / hr = 0.24 kg /s

300

(e) W

10.5 HP from (c) above = 7.8 kW

(f)

PD

rhv.

1905_0'68) = 21'6 ft3 / min 60

O.O1 m3 / s

15-2

2.5 kW; rh = 0.05 kg / s _v

(a) 8c=il_i,
i+

i+_i

=ig

_W / rir

398.4 + 2'5 / 0.5 = 448'4 kJ / kg


448'4
=

Qc = i1

-i4:260'3 -i4
=

-188'1 kJ / kg
kJ / kg
/ kg

w
9e

i3

398.4

- 448'4: -50

9c -\M

- 188.1-50 : 138.1 kJ

(b) COP
(
(c) (d)

= 138.1 I 50 = 2.76
)carnot =

coP

#*:3.86
o/o

= 448'4 kJ / kg from part (a)

0r = 2.76 /

3.86 = 0 '72 or 72

15-3

R- 134a; Energy Balane


rh1i1 +

mi =m2i2+ rh5i5

rh1 =

fi2=

rh3 = rh = rhs

is =

i.l

+i _iz

= 44'94

101 '54 _ 37.98

: 108'5

Btu / Ibm

Ps

= P+

:16.6 Psia

!
-r0
F

100 F sat. liquid

w=i6-is,So=Ss

P1: 138.8 Pjsla 5

sat. vapor 80 F
Excerptsfromthiswrkmaybereproduedbyinstructorsfordistributionona.not-for-profitbasisfortestingorinstructionalpurposesonlyto ,l -_...__^ll^r;^^^llfaAqfnru,lihthetextbkhasbeenadontel. notherreroducionortrnsliono{thiswrkb?bdth^2v":1'^)
_

301 io

:'127 Btu / lbm lChart

3]

\/

127 - 108.5 = 18.5 Btu / lbm

Qe = i+

_i3 : i

_iz =

1o1 '54

37'98 = 63'6

15-3 (continued)

^t ton rhge

HP

TT8

132
P

ton
15-4

HP

(18.5) 778 (12,ooo) =1.37 (63.6) 60 (33,000)

t9

_ 0 =| 1+ C

.
L

^ c rr..1l"'
I

\PoJl

v3 vb

n = k = 1.17; 1

ln= 0.855

P./P6:180120:9
v3

r80
P
2

v6= ? -1I: 2.38


=|+

o.9o [chart 4 tab le 3a] 0.90


=

(a)

nu

uuu] O.O3 - o.03 (9)o


]11

0.75

,..

: ftua or 'v

PD

PD

v3

0u lb

/ ft3

rh PD
(b)

0.75 2.14
,

* o.15_ o.15 (91o'ss

0.90

0.15

Exemtsfrmthiqrnrl-tra\,L--__-^j,'^^lL-.:__}_'.^a^.^.--f,j_+-:!_,'+:^-_-___^}^--.nfi'+-"iaff

tt;frinctrlotinnql

nllrnnssnnlvt^

rh /

PD =

0.15 t 2-14 = O'07 lb / ft3

o'07 (e\ fr, - tro \v" rha = 1- 0.35 = o.8o or 80 %

(d) Power is directly proportional

to the mass flow rate

therefore, Power compares as in (c) above'


0 =o'7o

15-5

4
P

cyl
=

3" bore, 4" stroke, 800 rPm

49]

psia (chart 3) psia (chart 3)


=
1

= 138.8

2 qsoF
'o4 ft3 / Ibm;

fr2, / PD; 2a

Table -2a @ 55 F / 52 psia


_ Qz = rh (i2 )

a PD= Gl() 00) = 52.36


1728
i __i = 46 Btu / tbm
iz = 112 Btu / lbm

ft3 / min

1z=Pt" (iz_,.,l 2a

#f4

(.'46)

2g26 Btu / min

or
15-6

912=139,560 Btu/hr = 11'6tons

R-22, assume suPerheat = 20 F


_.

--

__^fi+

L-.].

f^f tea1in nr instnlctina nurooses onlv to

303

Subcooling = 10 F

(a)

3t
P 90

120 E
-3
\

t.

130 F, te

45 F

'15-6 (Continued)

P |1

;.} b* 4\'d

tl:130-10=120F

35

i:iz:46
(b)

Btu / lb

Q" = 144,000 Btu / hr (Fig. 15-7)

Wc

14.8

kW = 50,498

Btu / hr
=

(c)

te

32.5

(Fig. 1 5-); W

13.3 kW

15-7

Refer to Fig ' 15-7 cP = 133,000 Btu/hr te= 47 F

l1

.'jL''L:^-.^_-^^+f^r-nrnfithasisfrtestinsorinstructional purposesonyto

304

Evapl a),( c)
t-

o () o
o (d
-

(,

-
_

b)

o(a)( c)

io

orator
15-8

Design

Pointo

-o(

-c

o o o

13.7

oc
()

'

o(

Measured Operating Points


Excerpts from this work may students enrolled in courses by Secions ]07 r ]08 f he 1976 United

S*ewff#{&eff&Etrwib,gerugffi'"'^''n'''

his work

only to h permied

-305

Pe = 69

psia; te

30

(able A-4)
'1

(a) he condensing temperature is still about

'15

F, but the

evaporating temperature is low, about 30 to 31 F.

(b)

(q

_q) / a

1_*=0.36
305

or 36 % low

(c)

lt appears that the evaporator is not loading the compressor.

Check for proper air fow over evaporator. Fan speed may be
low or an obstruction exists.

15-9

Suction valve,

P:2

psia
= 4 psia

Discharge valve, P
'10

lz s

ssia
sat R-22 ao '
P=90.73psia
,-

F S.H. in intake man. and cyl.

Piston clearance=5o'

u=|

r"']"nl " 1+C_.


1
rPoJ.]
]

450F

uo

Excrpts from this work may be reprodued by instructors for distribution on a not-for-profit basis for testing or instructional purposes only to l students enroled in ctlrses fnr whinh tL +__}L^^l'- L^^ L^^- ^j^_'

V3 = Vg at 45

F;

vg = 0.604 ft3 / lbm (able -3a)

vo

0.66 ft3 / lbm (Chart 4 at 55 F / 89 psia)


Pb = 90.73

Pc=275+4= 279 psia;

-2= 88.73 psia

n:1.16, C=0.05

(a)
(b)
ri'r

o" =| 1+ O.O5 _ o.O5

L "_v'v's&rcJ

(+\1/1

16l /o o+\

.*

0'e

.,l

- ry, (PD) / v. :

(.838) 20 / 0.604

27.75|bmlmin N 0.2 kg /s I
]

(c)

=!, W=*o",[[
*
=

P.

.n-1
n

I P)

-11
I
I

1J9(ss.73)
0.16'

(144) (o .66) l (

)l ' '|(8zs)_.'

l, 2'79 ,oi6

15-9 (cont inued)


=
1

0,466 ft - lbf

/lbm

x 31 kJ/kg
1.1.0

w _27.75(10,4666) _
0.80(33,00) '15-10 (a)

HP x

8.2 kW

ou

'

=|l+ O.04

_ o.o4

Note: n average value

'u'

)'''o]
c>f

*l

k assumed and 2 psi p res. loss

Excerpts from this work may be reprodued by instrutors for distribution on a not_for-profit basis for testing or instrutional purposes only to
ctrr.lan+. ^--^iri

307

assumed in suction header and valve.


Tv = 0.90,
h =

(PD) u

lz

19

*p=zoo
ir

= 9'4 (.90) l 0'74 rh ='l

o6o

'55
tz 6.

t"
\l
I I

oor

1.44 lbm / min

60.oF
I

\ l ['] -_1!- (53)/ 44 (o'77)/L53/ (1'4_1) \


1

1'4_1

=94 91( ft _ lb / lbm

vl =

fr*
0m

9491 (11.44) / (0.9 x778)


3O,OOO

1t55

Btu / min

QH=+Q=(155x60) +

= 39,3ooBtu/hr

15-10 (Continued)

or qH

655 Btu / min

W23 =i2

-i3,

iZ

=iZt

W = 133 +

j9491

778

=125.2Btu / bm

9 = ia

_i3i

i = 9 +iu =

_#+
11.44

+125'2= 68 Btu / lbm

(b)

lteration is required
P3 will decrease with the lighter load but Pz is (P3 / P2) t'n will be about the same

also lower and

as part

(a);

2 l 6 will be about constant. Then Tv : Constant.

Excerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis
-+,,f,^-+-.-.---rl j

flr testin r l'nstnlctina nlrnses

onlv to

308
However , 2= O.85 and rh
=

: (PD) l e

(9.4) 0.87 / 0.85

9.62 lbm / min.


=

oWW
W=
(1

9491 (48)(1 03) : 53 (0.77) 778

14.78 Btu / tbm

4.78) (9.62) (601 = 8530 Btu/hr;

Qn = 8530 + 24,000 = 32,530 Btuihr

Which assumes Ps I Pz is constant and 2 psi pres. loss in the


valve.
ie = iz

t w :83.5

14'78 --94'3 Btu / lbm

i =iz_ 9z = 111_24,000 / 9'62 (60) = 69'4 Btu / lbm

,,

(50) = 188

psia

18

Ps
41.9 .83.5 9 4.3
t

15-11

Reduced air flow reduces the load on the evaporator. Without suction pressure control the evaporator pressure will decrease
until condensate will freeze and completely block the

evaporator air flow. Liquid refrigerant will return to the

purposes only to xerpts from this work may be reproduced by instructors for distribution on a not-for-profit basis for testing or instructional

309

compressor and eventually cause the compressor suction valve to fai.


15-12

lnstall an evaporator pressure regulator set to maintain a pressure such that the temperature of the evaporator surface will not decrease below the freezing point for water.

15-'13

lnstall a suction pressure regulator on the compressor inlet. he regulator shoud be set to limit the suction pressure to a
level compatible with the compressor capacity.

15-14 (a) Using chart 2 with the construction shown,


the final temperature is 9 F

(b)

'v - L=!=0.18s m ( 20
18.5
o/o

or
i

vapor (Use chart 2)

15-15

Using chart 2
X3
=

tb ammonia/lb sol.
=

0.495; ts

125 F

l8ooF

28ooF

Tz7 l6TT-sia
0.25

.495
+

Excerpts from this rork may be reproduced by instructors for distribution on a not-for_profit basis for testing or instrutiona purposes only to students enrolled in courses fbr whih the textbook has been adopted. ny other reproduction or trnslin of this work beond h nemilto) by Sectins ]07 or ]08 fhe !Q76 [nifa'] Slnlo" r'^'.'-':'-'' ''

310

15-16

(coP)ma, = :fd: \ _ - /la


Tg(To _
=

)'

T^ = '9 -

180

460

64OR;

Te=75

460

535

R;

To

=]00

460 = 560 R

(COP)ma x = 2.675

15-17

Refer to Chart 5 for saturated vapor at 10 mm hg.

Vapor must first be condensed to sat. liquid at


Q" = irs,
i'n =

'10 mm hg.

Table -1a;

164.8 Btu/lbmu for 1 lbm of vapor o 9. = 1064.8 Btu

at 50 F, P = 0.178 psia or 15-17 (continued)

P = 10 mm hg Locate point I at x Locate point s atx


= =

0; P

= 10 mm hg

0.6 ; P = 10 mm hg

ffru=1;m.=5

ms5mv mm6ms
5lv = ; tS = i ob
E

x 45'5

37.g

(depends on scale used)

(a) x = 0.50 (b)


Q, =

i, -

io =

-50

(-70) = 20 Btu / lbm of solution

Exerpts rom this work may be reproduced by instrutors for distribution on a not-fr-profit basis for testing or instrutional purposes only to students enoled in ourses for which the textbook has been adopted. ny oher reproducion or rnslion of his rk beyond th pemed by Sectins 07 or ]08 ofhe ]976 tnited Ss Canrioh ?r1!a!"^''a n'^ ' '

311

Qtot

: 1064.8
i

+ (6

x 20) = 1 ,184.8 Btu

lm

ib

70

\m -1
h9

0.5

0.6

0.8

Excerpts from this work may be reprodued by instrutors for distribution on a not_for_profit basis fo testing or instructional purposes only to students enolled in ourses for whih the textbook has been adopted. ny other reproduction or trnsltion of his ork beyond th permited b Sections ]07 or ]08 fhe ]976 [kitad Stntc nh1'';-L} ^l''':'1''' ' ''

311

ADDENDUM
to Solutions Manua fr McQuiston, VAC 6e Probem 6-10 For the floor, it is unlear what2 in. vertial edge insulation means (whether 2 in. is the thikness of insulation or the depth of the edge insulated). . The solution assumes that the insulation has R-value of 5.4 hr-ft2-oF/Btu and the depth of the edge is 2 ft. For the door, Table 5-8 in the 6th edition does not have U-value for the wood storm door and there are three types of the wood door with 1 % in. thickness. The solution assumes that the doors are panel doors with metal storm dor; hene, its U-value is 0.28 But/hr-ft'-'F.

robem 7-9
The standard time zone for ottawa, ontario is astern Standard Time instead of Central Standard Time. The solution uses Eastern Standard Time.

Prblem 7-14
For the specified loatin, the sunset ours before 9:00 p.m. CDST on June 21. The solution uses 8:0 p.m. CDST instad of 9:00 p.m.

Prblems 8-25 and 8-26


Both problems do not specifu the window orientation. . The solutions assume the west-facing window for both prblems.

Tabte 8-20
Reommended radiative and convetive frations for solar heat gains should be revised sine the 6th edition uses the SHGC values in the calulation of the (ombined) solar heat gain for the RS methd.

Example 8-16
he example actually uses 90%/10% of radiative/onvetive split of the cmbined solar
and 6301370 for the absorbed slar heat gain.

heatgain. owever,thetext (page270) says 100%/0oforthetransmittedsolarheatgain

L--**-

312

Probems 8_25 and 8-26


The solutions for both problems use 90%11,0% for the combined solar heat gain.

Exampe

9_1

The alulation for this example should be

"

('111?2oi19.']!o:9 _ 22'606 (0.ssx70- 0)(1000)

(Changing 13 to24 and 122790 to 122606).

Anda mungkin juga menyukai