= (1b)
where
H
o
=Approximate height of tsunami in flat deep ocean floor (can be determined
from the fig. 8. For rugged deep ocean floor adopt fig. 9)
H
1
= height of tsunami near the shore (m)
d
o
= water depth in the deep sea (m)
d = water depth near the shore (m)
g = acceleration due to gravity (9.81 m/s
2
)
13
Figure 8 Height of tsunami in flat deep ocean floor (depth more than 4000 m )
Figure 9 Height of tsunami in rugged ocean floor
7.5.2 Estimation of Impact Forces for Structures Located Near the Sea Front
7.5.2.1 For Structures Located Within 50 m from the Sea Front
The following procedure for estimating the design force for structures within 50 m from
the sea front shall be adopted. For structures located beyond 50 m upland, procedure
given in7.5.2.2 shall be adopted
14
a) Determination of dynamic wave pressure
The following equation gives the dynamic wave pressure:
h H g
c
K
gh
P
1
2
4
w
dm
= (2a)
or
1
4
w
dm
gH
C
K P =
(2b)
where
P
dm
= maximum dynamic wave pressure (N/m
2
)
c = wave celerity (m/s)
h = initial water depth (m)
H
1
= Height of tsunami near shore (m)
= density of seawater (kg/m
3
)
g = acceleration due to gravity (m/s
2
)
K = kinetic wave coefficient (0.3 to 0.51)
b) Determination of Sustained Wave Pressure
( )
1
2
1
dm
s m
gH
c
cos 2 0. 14
P
P
+ = (3)
where
1
: structure slope (Fig. 10)
P
sm
: maximum sustained wave pressure (N/m
2
)
P
dm
: maximum dynamic wave pressure (N/m
2
)
c : wave celerity (m/s)
g : acceleration due to gravity (m/s
2
)
H
1
: Height of tsunami near shore (m)
Figure 10 Definition sketch for
1
15
c) Determination of Impact Standing Wave pressure
The relation between the sum of maximum dynamic wave pressure P
dm
, maximum
sustained wave pressure P
sm
and maximum impact wave pressure P
im
is given by the
following equations.
<
+
=
+
1. 1
c
cot ) H (h g
for 0. 5
P P
P
2
1 1
s m dm
i m
(4)
+
=
+
1. 1
c
cot ) H (h g
for 6. 6 cos 10
P P
P
2
1 1
1
s m dm
i m
(5)
where
P
im
: maximum impact standing wave pressure. (N/m
2
)
1
: structure slope (Fig. 10)
P
sm
: maximum sustained wave pressure (N/m
2
)
P
dm
: maximum dynamic wave pressure (N/m
2
)
c : wave celerity (m/s)
g : acceleration due to gravity(m/s
2
)
H
1
:height of tsunami near shore (m)
d) Estimation of wave force
Figure 11 Pressure distribution over the vertical face
Assuming a triangular pressure distribution (Fig. 11), wave force per unit length of the
structure can be calculated based on equation
1
H Pi m 0. 5 F = (6)
where
F : Wave force / meter length of the structure (N/m)
Pim : maximum impact standing wave pressure. (N/m
2
)
H
1
: Height of tsunami near shore (m)
16
7.5.2.2 For Structures Located Upland (More than 50 M from Sea Front)
For structures located upland maximum of the wave force obtained from the following two
methods:
Method 1
a) Determination of inundation distance and inundation depth (see fig. 12)
Figure 12 Definition sketch for inundation distance and inundation depth
X
1
= Location of the structure upland from the edge of the beach.
X
2
= total inundation distance from the edge of the beach.
H
1
= Tsunami height at 6m water depth or the chosen depth.
tan = slope of the terrain ( above the beach berm )
h* = inundation depth at the structure = H
1
[ 1-(x
1
/ x
2
)]
Evaluate distance X
2
from equation (7), where suitable value of the factor has to
utilized.
=
tan
H * fact or
X
1
2
(7)
where the factors* are given in Table 2.
Table 2 Factors Recommended for the Given Slope of the Terrain
Tan Factor
(rugged terrain)
Factor
(plain surface)
< 0.003 0.75 1.2
0.003 0.006 0.85 1.5
0.006 0.011 1.12 2.24
0.011 0.025 1.6 3.2
0.025 0.03 1.8 3.6
17
b) Estimation of wave force
The force can be directly evaluated as follows (see Fig. 12)
[ ]
=
2
1
x
x
1 (gd) v* (8)
2
a(v*) F = (9)
Where
a : the projected area of the building (h* x
1
) / meter length of the building .
v* : tsunami flow velocity (m/s)
F : Wave force / meter length of the structure (N/m)
Method 2
Let Hb be the height of the building
a) Estimation of wave force for * 3h Z 3h*, H
max b
=
( see fig. 13 a for pressure distribution )
Pressure distribution is obtained based on equation 10 (z varies from zero to 3h*)
Z)) (3h (z) P
*
m
= (10)
* *
3h g) (3h 0. 5 F = (11)
b) Estimation of wave force for
b max
*
h
H Z , 3h H = <
( see fig. 13 b for pressure distribution )
Pressure distribution is obtained based on equation 11 ( z varies from zero to Hb)
( ) z)) (3h z
m
P
*
= (12)
b
b
*
H g
2
H 6h
F
= (13)
Where
: density of seawater kg/m
3
g : acceleration due to gravity m/s
2
H
b
: height of the building
pm : pressure (N/m
2
)
F : wave force / meter length of the structure (N/m)
18
Figure 13 a Pressure distribution over a structure 3 * b H h
Figure 13 b Pressure distribution over a structure (Hb < 3 h*)
Maximum of the forces estimated based on equations (9) and (11 or 13 as applicable)
shall be adopted as design wave load.
7.6 Forces Due to Tsunami Impact on Category IV Structures
For structures which are classified as Category IV structures, the following forces due to
Tsunami such as hydrostatic force, hydrodynamic force, buoyancy force and fluid flow
drag, foundation scour and impact due to waterborne debris shall be considered. These
loads may cause large structural deformation, yielding, fracture and collapse and / or
dislodgment of coastal structures from their bases, hence should be properly considered
in design.
7.6.1 Hydrostatic Force (F
h
)
Hydrostatic force occurs when standing or slow moving water encounters a building or
building component. This load always acts perpendicular to the surface to which it is
applied. It is caused by an imbalance of pressure due to differential water depth on
19
opposite sides of a structure or structural members. The lateral hydrostatic force is given
by:
2 2
2
p
h
gd
1
h g
2
1
2g
u h
g
2
1
F
+ =
+
=
where,
F
h
: Hydrostatic force
: Density of water
g: Gravity
h: water depth
u
p
: Water velocity normal to the wall (as obtained from simulation )
The resultant force will act horizontally at a distance of h
R
above the base of the wall
where:
+
=
2g
u h
3
1
h
2
p
R
This formula applies to steady state situation of a bridge column supported by a
foundation underneath the sea. In the case of tsunami, the hydrodynamic loads are
transient and the effects of water velocity are accounted for by the hydrodynamic and / or
the surge force. The above formula may not be relevant to a building with finite breadth,
for which the water can flow around and quickly fill up behind the building. Hydrostatic
force is usually important for 2-D structures such as seawalls and dikes or for evaluation
of an individual wall panel where the water level outsides differ substantially from the
level inside.
7.6.2 Buoyant Force (F
b
)
The buoyant or vertical hydrostatic forces on a structure or structural member subjected
to partial or total submergence will act vertically through the center of mass of the
displaced volume. Buoyant forces are a concern for basement, empty above ground and
below ground tanks, and for swimming pools. The buoyant force is given by:
V g F
b
=
or
2
v L b
U A C
2
1
F =
where,
V = volume of water displaced by the structure considered.
C
L
= lift coefficient (normally=0.8)
A= projected area
U
v
= vertical velocity ( gd)
7.6.3 Hydrodynamic Drag Force (F
d
)
When the water flows around a building (or structural element or other object)
hydrodynamic loads are applied to the building. These loads are a function of flow
20
velocity and structure geometry, and include frontal impact on the upstream face, drag
along the sides and suction on the downstream side. These loads are induced by the flow
of water moving at moderate to high velocity. They are usually called drag forces, which
are combination of lateral loads caused by the impact of the moving mass of water and
the friction forces as the water flows around the obstruction. The hydrodynamic drag
force on a structure component in the direction of a steady flow can be expressed as:
2
p D d
u A C
2
1
F =
Where
A : Projected area normal to the direction of the flow
C
D
: Drag coefficient, the value of which is taken as follows
Circular piles 1.0
Square piles 2.0
Wall sections 1.5
For large obstructions this value is given in the following table :
Width to Depth Ratio Drag Coefficient C
D
from 1-12
1.25
13-.20 1.3
21-32 1.4
33-40 1.5
41-80 1.75
81-120 1.8
> 120 2
7.6.4 Surge Impingement (F
s
)
Surge forces are caused by the leading edge of a surge of water impinging on a
structure. The hydrodynamic force of the leading edge of the fluid flow acting per unit
area of a structure due to tsunami surge is given by:
F
s
= 4.5 g h
2
Where, h is the height of surging flow.
The resultant acts at a distance of approximately h above the base of the wall. This
equation is applicable for walls within heights equal to or greater than 3h. Walls whose
heights are less than 3h require surge forces to be calculated using appropriate
combination of hydrostatic and hydrodynamic force equations for the given situation
7.6.5 Impact Force (F
i
)
During the tsunami or storm surge, water-borne objects (e.g. boats, oil rigs, vehicles, drift
wood etc.) may hit a coastal structure with tremendous impact force. This scenario
involves highly non-linear coupled fluid (tsunami or storm surge flow)- structure-(debris)-
structure interaction and the physics is often very complex. This load can be estimated by
21
parametric study using complex finiteelement model and simulation. The generalized
expression for impact force F
i
is given by following equation:
=
t
u
m F
I
i
where,
u
I
= approach velocity that is assumed equal to the flow velocity
m = mass of the body,
t = impact duration that is equal to the time between the initial contact of the body
with the building and the maximum impact force. The value of t may be taken
from the table.
Value of t
Duration (t) of impact (sec)
Type of construction
Wall Pile
Wood 0.7-1.1 0.5-1.0
Steel Na 0.2-0.4
Reinforced Concrete 0.2-0.4 0.3-0.6
Concrete Masonry 0.3-0.6 0.3-0.6
7.6.6 Wave Breaking Force (Fbrkw)
Following expression for wave breaking force may be used:
2
b db brkw
H D C g
2
1
F =
Where, C
db
is a shape coefficient (value = 2.25 for square or rectangular piles and 1.75
for round piles), D is the pile diameter, and H
b
is the wave breaking height (H
b
= 0.78 ds,
where ds is the design still water depth).
7.6.7 Tsunami and Storm Surge Scour
Scour of supporting material at the foundation base of a structure or a bridge pier due to
tsunami or storm surge differs from the ordinary case of a bridge scour, which occurs
gradually caused by periodic waves and steady current loads. In a tsunami or storm
surge, the leading wave may scour away much of the supporting materials around the
base of a structure and weaken the foundation so much that the foundation of structure
or pier of bridge fails under the subsequent fluid drag load. The behavior of tsunami and
storm surge scour is very complex and dependent on the geometric properties of the
bridge columns as well and the material properties of the surrounding soil at the base.
Currently, no simple formula exists for scour prediction. Much experimental work needs
to be conducted to provide data for empirical prediction and analysis.
Note : As tsunami is a very low probability event and the forces due to tsunami are very huge, the
economic implication of designing all the members of the structure for tsunami forces shall be
deliberated. The infill walls may be allowed to collapse in the event of a tsunami. However, the
frame members shall be designed to withstand the tsunami forces. Alternatively, measures such as
wave arrestors can be provided at the coast to reduce the magnitude of forces so that the full
impacts of the waves are not experienced by the structures to be designed.
22
7.7 Load Combination
When tsunami forces are considered on a structure, these shall be combined as per 7.7.1
and 7.7.2 where the terms DL, IL and Ft stand for the response quantities due to dead
load, imposed load and tsunami load for the members facing the tsunami wave. These
load combinations are in addition to all other relevant load combinations that should be
considered while designing the structures as per relevant Indian Standards. Even though
tsunamis are generally caused due to earthquake, the earthquake and tsunami forces are
not considered simultaneously due to the difference in their arrival time.
7.7.1 Load Factors for Plastic Design of Steel Structures
In the plastic design of steel structures following additional load combinations involving
tsunami forces shall be accounted for:
i) 1.7 (DL + F
t
)
ii) 1.3 (DL + IL + F
t
)
7.7.2 Partial Safety Factors for Limit State Design of Reinforced and Prestressed
Concrete Structures
In the limit state design of reinforced and pre-stressed concrete structure, following
additional load combinations involving tsunami forces shall be accounted for:
i) 1.2 (DL+IL+F
t
)
ii) 1.5 (DL + F
t
)
iii) 0.9 DL + 1.5 F
t
8 Construction Aspects of Category I Buildings
For earthquake resistant design and construction of buildings of Category I, IS 4326 & IS
13828 shall be followed as appropriate for the material of construction and the Seismic
Zone of the area where such buildings are to be constructed. Besides special
considerations will be required if the buildings are situated in high cyclone prone and
storm surge prone or tsunami prone coastal areas. Such special considerations are
provided in the following clauses:
8.1 Siting of Buildings
Coastal areas of low elevations within 500 m to 1.5 Km from the shore may suffer due to
impact of tsunami flow and inundations. Also such areas may also suffer on account of
high wind speeds in the tropical cyclones and storm surge of the sea water under the
action of cyclones. Therefore it is recommended that:
i) The selection of site should preferably avoid areas likely to be submerged under
tsunami or storm surge inundation.
ii) Building should be founded on soil strata reliably stable against scour and erosion
and should not be susceptible to liquefaction due to earthquake.
iii) The site should preferably be selected at higher elevation as possible
23
8.2 Foundation
The following safety considerations may be applied for determining the depth and type of
foundation:
i) Shallow foundations have the risk of being scoured by the receding tsunami wave
hence a minimum depth of foundation of 1.5 m below natural ground level is
recommended.
ii) Use of under ream piles or concrete pedestal piles or reinforced brick pedestal
piers going to more than 2 m depth will be preferable. Such foundation shall have a
ground level reinforced concrete beam at the top of piles/pedestals for supporting the
super structure walls.
iii) Where the storm surge or tsunami wave height is estimated to be more than 5 to
6m, the building may be constructed on stilts, the columns being founded on piles with
a ground level interconnecting beam and knee braces provided near the top of the stilt
columns (full diagonal brasses are to be avoided so as not to obstruct the passage of
the floating debris during storm surge & tsunami)
Note: The ground floor in stilt buildings can be used for various temporary purposes like storage,
running of classes for small children, play area of children or any community function.
8.3 Planning of the Building
i) An integrated enclosure of a room by the four walls creates a stable structure
against the onslaught of lateral water pressure. But if the rooms have very long walls,
those may be destroyed under the hydrostatic and hydrodynamic pressures since
such walls act like vertical cantilevers. A crate like plan will be much more stable.
Hence wall lengths in the rooms may be restrained to 4 m.
ii) Every building may be planned to work for vertical evacuation of the residents by
providing a flat roof accessible through a stair case. The roof may also have a strong
parapet to assure the safety of the people on the roof.
iii) The staircase may be made without vertical risers having only treads so as to
permit free flow of water without breaking the staircase.
iv) The external wall corners may be made chamfered or curved in plan to permit
smoother flow of water.
8.4 Building Super Structure
i) The construction of walls, masonry piers etc. should follow the Guidelines given in
IS 4326 or IS 13828 as the case may be. Notwithstanding the earthquake safety
requirements provided in these codes for moderate seismic zones, in the storm surge
or tsunami prone area the following safety measures should be adopted for the load
bearing masonry buildings:
ii) The safety measures provided in IS 4326 for the most sever Seismic Zone V should
be adopted for strengthening the walls by the following measures:
24
a) Use of rich mortar as specified for zone V
b) Control on the size and placing of door and window openings
c) Provision of seismic bands at plinth and lintel levels in buildings with
reinforced concrete slab floor and roofs
d) Additional provision of seismic bands at eave level, around the gable
masonry in the case of pitched roofs
e) Provision of vertical reinforcement on all corners and junctions of walls from
the foundation masonry through the floor and anchored into the roof
f) Provision of vertical bars at the jambs of door and window openings,
anchored into the plinth and the lintel bands
Note: All these provisions will incorporate such strengthening measures that the total
disintegration may not occur under the tsunami impact as it may not be able to destroy the
building totally but create damages in opposite walls to create openings for the water to follow
through.
25
ANNEX A
( Clause 2.1)
LIST OF REFERRED INDIAN STANDARDS
IS No. Title
IS 456: 2000 Code of practice for plain and reinforced concrete (fourth
revision)
IS 800: 2007 Code of practice for general construction in steel (second
revision)
875(Parts 1 to 5):1987 Code of practice for design loads (other than earthquake) for
building structures:
Part 1 Dead loads - Unit weights of building material and
stored materials (second revision)
Part 2 Imposed loads (second revision)
Part 3 Wind loads (second revision)
Part 4 Snow loads (second revision)
Part 5 Special loads and load combinations (second revision)
IS 1786 : 2008 High strength deformed steel bars and wires for concrete
reinforcement Specification
1893 (Part 1): 2002 Criteria for earthquake design of structures:
Part 1 General Provisions and buildings
IS 1904 : 1986 Code of practice for design and construction of foundations
in soils : General requirements
IS 1905 : 1987 Code of practice for structural use of unreinforced masonry
IS 2062 : 2006 Hot rolled low, medium and high tensile structural steel
IS 2911 : Part 1 : Sec 1
: 1979
Code of practice for design and construction of pile
foundations: Part 1 Concrete piles, Section 1 Driven cast in-
situ concrete piles ( Revision under print )
IS 2911 : Part 1 : Sec 2
: 1979
Code of practice for design and construction of pile
foundations: Part 1 Concrete piles, Section 2 Bored cast-in-situ
piles ( Revision under print )
IS 2911 : Part 1 : Sec 3
: 1979
Code of practice for design and construction of pile
foundations: Part 1 Concrete piles, Section 3 Driven precast
concrete piles ( Revision under print )
26
IS 2911 : Part 1 : Sec 4
: 1984
Code of practice for design and construction of pile
foundations: Part 1 concrete piles, Section 4 Bored precast
concrete piles ( Revision under print )
IS 2911 : Part 2 : 1980 Code of practice for desing and construction of pile
foundations: Part 2 Timber piles
IS 2911 : Part 3 : 1980 Code of practice for design and construction of pile
foundations: Part 3 Under reamed piles
IS 2911 : Part 4 : 1985 Code of practice for design and construction of pile
foundations: Part 4 Load test on piles
IS 4326: 1993 Code of practice for earthquake resistant design and
construction of buildings (third revision)
IS 13828 : 1993 Improving earthquake resistance of low strength masonry
buildings - Guidelines
IS 13920: 1993 Ductile detailing of reinforced concrete structures subjected to
seismic forces
27
ANNEX B
SOME LESSONS FROM THE GREAT INDIAN OCEAN TSUNAMI OF DEC. 26, 2004
B-1 Dynamic Forces
The force of some tsunamis is enormous. Large rocks weighing several tones along with
boats and other debris can be moved inland hundreds of meters by tsunami wave
activity. Trees are uprooted, and homes and other buildings are destroyed. All this
material and water move with great force and can kill or injure people.
B-2 Effect on Off-Shore/On-Shore Structures
It was observed that a number of jetties and other harbor walls were severely damaged
by the tsunami through its hydro-dynamic force as well as scouring of foundations acting
simultaneously. This damage very adversely affected the relief work to be carried to the
Andaman & Nicobar Islands through ships from the Indian mainland.
B-3 Lessons for Protection and Structural Safety
The important lesson learnt from the Tsunami impact on off-shore structures and
buildings near the coast and is that the brute force of tsunami waters if allowed to flow
freely, may not cause any damage. But if it is resisted structurally, the resistance required
will have to be very high against the breaking of the bore and the hydro-dynamic force of
the flowing water. These forces will be further enhanced due to the debris created by the
tsunami and flowing with the water creating impact on any obstructing element, wall or
column.
The lessons from behavior of various structures impacted by the Indian Ocean Tsunami
are summarized in Tables 1 & 2, which would be helpful in planning the various new
structures in coastal areas considered prone to impact of future tsunamis.
28
Table 1 Phenomenon of Inundation
Effect Design Solution
Flooded basement Choose sites at higher elevations
Flooding of lower floors Raise the buildings plinth above flood elevation
Flooding of mechanical
electrical & communication
system & equipment
Do not stack or install vital material or equipments on floors or basement
lying below tsunami inundation level
Damage to building materials
& contents
Protect hazardous material storage facility located in tsunami prone area.
Contamination of affected
areas with water borne
pollutants
Locate mechanical systems & equipments at higher location in the
building
Use corrosion resistant concrete & steel for the portions of the
building which are liable to inundation.
Hydrostatic forces (Pressure
on walls by variation in water
depth on opposite sides
Provide adequate openings such as louvers to allow water to reach
equal heights inside & outside of buildings.
Design for static water pressure on walls.
Consider suction tensions on walls under receding waters.
Buoyancy floatation or uplift
forces caused by buoyancy
Elevate building to avoid floatation due to flooding.
Anchor building to foundation to prevent floatation
Saturation of soil causing
slope instability and/or loss of
bearing capacity
Evaluate bearing capacity & shear strength of soil that support
building foundation & embankment slopes under condition of
saturation.
Avoid slopes or setbacks from slope that may be destabilized when
inundated.
Table 2 Phenomenon of Currents, (wave break & bore)
Effect Design Solution
Hydrodynamic forces
(pushing forces on
the front face of the
building and drag
caused by flow
around the building
Elevate building on stilts to avoid hydrodynamic pressures
Design infill wall panels on ground floor, in R.C. frame buildings, to fail under
flowing water pressure without causing failure of columns. Anchor columns
to foundations deep enough to escape soil erosion under receding waters.
Design for dynamic water forces on walls: off-shore and on-shore jetties,
protection walls, break waters etc.
Debris Impact Elevate building to permit free flow of water and avoid debris impact.
Design for Impact loads.
Scour Use deeper foundation (piles or piers).
Protect against scour and erosion around foundation.
29
ANNEX C
Maximum Probable Storm Surge Height and Seismic Zone in
Coastal Districts of India
Sl.
No.
Coastal
States and
UTs
Coastal Districts Strom
Surge
height
above
Concurrent
Sea Level,
m
Indian
Ocean
Tsunami
run-up and
Inundation,
m (m)
Seismic
Zone (IS
1893:2002)
Height of
Tsunami
Run-up, m
Recom-
mended
Height
of bund
above
High
Tide
Line, m
1 Andhra
Pradesh
Srikakulam 4 II 4.5 4.5
Vizianagaram
4
II
4.5 4.5
Vishakha Pattanam
4
II
4.5
4.5
East Godawari
4.5 III 5 5.0
West Godawari
5 III 5.5 5.5
Krishna
5.5 III 6 6.0
Guntur
7.5 III 8 7.0
Prakasam
6 III 6.5 6.5
Nellore 4.5 III 5 5.0
2 Goa North Goa
4.5 III 5 5.0
South Goa 4.5 III 5 5.0
3 Gujarat Kachchh
3.5 V 4 4.0
Surendra Nagar
3.5 IV 4 4.0
Rajkot
3.5 IV 4 4.0
Jam Nagar
3.5 IV 4 4.0
Porbandar
3.5 III 4 4.0
Junagarh
3.5 III 4 4.0
Amreli
4 III 4.5 4.5
Bhavnagar
4.5 III 5 5.0
Ahemdabad
4.5 III 5 5.0
Anand
4.5 III 5 5.0
Bharuch
4.5 III 5 5.0
Surat
4.5 III 5 5.0
Navsari 4.5 III 5 5.0
Valsad
5 III 5.5 5.5
30
4 Karnataka Uttara Kannada
4.5 III 5 5.0
Udupi
4.5 III 5 5.0
Dakshina Kannada 4.5 III 5
5.0
5 Kerala Kesaragod
4 III 4.5 4.5
Kannur
4 III 4.5 4.5
Kozhikod
4.5 III 5 5.0
Malappuram
4.5 III 5 5.0
Thrissur
4.5 III 5 5.0
Ernakulam
4 III 4.5 4.5
Kottayam
4 III 4.5 4.5
Kollam
3.5 III 4 4.0
Thrivunanthapuram 3
III 3.5 3.5
6 Maharashtra Thane
5 III 5.5 5.5
Mumbai
5 III 5.5 5.5
Raigarh
5 IV 5.5 5.5
Ratnagiri
4 IV 4.5 4.5
Sindhudurg 4
III 4.5 4.5
7 Orissa Baleshwar
11 III, II 11.5 7.0*
Bhadrak
9.5 II 10 7.0*
Kendrapara
8.5 III 9 6.0*
Jagatsinghpur
6.5 III 7 6.0*
Puri
4 III 4.5 5.0
Ganjam 4
II 4.5 4.5
8 Tamil Nadu Thiruvallur
3.5 2.1-3.5 (500-
700)
III 4 4.0
Chennai 3.5 2.2-2.3 (500-
700)
III 4 4.0
Kanchipuram
3.5 2.7-4.7 (100-
400)
III, II 5.2** 4.0
Viluppuram 3.5 3.3-4.8(300-
500)
II 5.3** 4.0
Cuddalore 3.5 1.8-4.6(140-
1500)
II 5.1** 4.0
Thiruvarur
(East Coast)
3.5 3.5-4.8 (700-
1000)
II 5.3** 4.0
Thiruvarur
(South Coast)
5.5 3.5-4.8 (700-
1000)
II 6 6.0
Nagapattinam
4.5
3.0-5.0 (300-
1500)
II 5.5** 5.0
Thanjavur
5.5 ? II 6 6.0
Pudukkottai
7 ? II 7.5 6.0*
31
Ramnathapuram
(East Coast)
12 ? II 12.5 8.0*
Ramnathapuram
(South Coast)
7 ? II 7.5 6.0*
Toothukudi 7 3.5-5.1 (60-
600)
II 7.5 6.0*
Tirunelveli
7 3.6-4.0(40-
750)
II 7.5 6.0*
Kaniyakumari 3 2.2-3.3(90-
200
III 3.8** 3.5
9 West Bengal South 24 Parganas
12 IV 12.5 8.0*
Medinipur 13
III 13.5 8.0*
10 Andaman &
Nicobar
Islands
Chattam wharf
? 3.4 V 3.9** 3*
Jugli ghat
? 3.8 V 4.3** 3.5*
Bamboo flat jetty
? 4.0 V 4.5** 3*
Hut bay ? 6.1 V 6.6** 5*
Chidiatapu
? 3.9 V 4.4** 3*
Havelock island
? 3.0 V 3.5** 2*
Mayabandar
? 2.9 V 3.4** 2*
Diglipur
? 2.9 V 3.4** 2.5*
Nicobar Island ? 6-10 V 6-10.5** 4.6*
11 Daman &
Diu
Daman
5 III 5.5 5.5
Diu 3.5 III 4 4.0
12 Lakshdeep ?
III 3 3.0
13 Pondicherry Karaikal
3.5 III 4 4.0
Mahe
4 III 4.5 4.5
Pondicherry
5 III 5.5 5.5
Yanam ? III 3 3.0
* Overtopping to be considered in design,
** Places where measured Tsunami run-up exceeded storm surge height
NOTE -1) Indian Ocean Tsunami run-up and Inundation (m) have been provided by IIT Madras.
2) The recommended height of bund above high tide lines is, in most cases, 0.5m above the storm
surge height which is more frequent than occurrence of the worst tsunami hence not considered
even if higher than surge height. In few cases where the maximum surge height was very high,
say more than 6 m, the bund height is recommended from economy consideration with the
guiding footnote that design may take the overlapping possibility in a rare event into account.