Anda di halaman 1dari 2

<<Contents>> <<Index>>

General Specications
GS 33K10D50-50E

Model LHS5420, LHM5150 Test Function

GENERAL

This GS covers the specications of the Test Function running on a Human Interface Station (HIS). LHM5150 is the package for CENTUM VP Entry class that is for small systems. There is no difference between LHM5150 and LHS5420 in functions.

FUNCTION SPECIFICATIONS

With the Test Function, the user can perform a virtual test without a Field Control Station (FCS) and a target test using an FCS. To check FCS operation, use the operation/monitoring functions. The following shows the conguration of the Test Function.
Test Function Virtual test Target test I/O disconnection (Use virtual I/O) Use real I/O
F01E.ai

Safety Control Station(SCS) can be also tested when ProSafe-RS and CENTUM VP are integrated.

Virtual test
A virtual test uses an FCS simulator instead of a real FCS. An FCS simulator simulates the functions and actions of FCS on a PC.

Target test
A target test uses a real FCS, but without eld wiring. It uses I/O singles by software. Neither I/O cards nor devices for virtual I/O are required.

Scope of test
A virtual test is conducted for the entire multiple FCSes. The following table lists the functions of the Test Functions.
Test Functions
Test Item FCS operation function Wiring function Input/output disconnection function Break point function One-shot run function Proler function Other - Station Communication Reception Test function for FOUNDATION eldbus Faceplate Block (*1) *1: X Test Method Target Virtual Test Test X X X X X X X X X X X Remarks Used to change the run status of the FCS (run, stop, pause, step-by-step run, etc.), and display the FCS run status. Used to simulate the process input/output (PI/O) signals. Used to simulate the input/output signals for each process input/output unit of the real FCS. Used to set a break condition for a data item of a function block in the FCS, and suspend the control functions of the FCS when the break condition is met. Includes block one-shot run function and message one-shot output function. The block one-shot run function runs a function block on the FCS one time. The message oneshot output function outputs messages on the FCS one time. Includes the functions to display CPU use ratio, communication load, and number of running all function blocks, and the function block proling function. Used to monitor the operating status of the FCS. Runs in conducting a test using a real FCS. Used to simulate the input signals from other FCS and to disconnect global switches. It is possible to specify to run and stop. Used to test FCS applications while eldbus devices are disconnected. The following functions can be performed for FOUNDATION eldbus Faceplate Block: Change alarm status Change block mode I/O action

Each function included in the test function for FOUNDATION eldbus faceplate block enables only the occurrence of events instead of simulating real operation of eldbus function block. Therefore, an additional test must be done for the FCS connected with actual eldbus devices.

Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33K10D50-50E Copyright Aug. 2011 (YK) 1st Edition Aug. 19, 2011 (YK)

<<Contents>> <<Index>>

2
MODEL AND SUFFIX CODES
Model Sufx Codes LHS5420 -V 1 1 Description Test Function [Media model: LHSKM50-V11] Software license Always 1 English version Description Test Function (for CENTUM VP Entry Class) [Media model: LHSKM50-V11] Software license Always 1 English version

APPLICATION CAPACITIES

In virtual test environment, the maximum number of FCS/SCS simulators can be run in a single PC is 8.

OPERATING ENVIRONMENT

The Test Function runs on a general-purpose IBM PC/AT-compatible PC which meets the following requirements:

Hardware Requirements
Refer to operating environment of LHS5100 Standard Builder Function.
Model Sufx Codes LHM5150 -V 1 1

Software Requirements
Model LHS1100 Standard Operation and Monitoring Function (If LHS5420 is used) Model LHS5100 Standard Builder Function (If LHS5420 is used) Model LHM1101 Standard Operation and Monitoring Function (If LHM5150 is used) Model LHM5100 Standard Builder Function (If LHM5150 is used)
HIS

ORDERING INFORMATION
Specify model and sufx codes.

TRADEMARKS

F02E.ai

CENTUM and ProSafe are registered trademarks of Yokogawa Electric Corporation. FOUNDATION of FOUNDATION eldbus is a registered trademark of Fieldbus Foundation. Other product and company names appearing in this document are trademarks or registered trademarks of their respective holders.

Example of System Conguration for Virtual Test


HIS

Control network FCS

Example of System Conguration for Target Test

F03E.ai

All Rights Reserved. Copyright 2011, Yokogawa Electric Corporation Subject to change without notice.