REGULATOR SIZING

REGULATOR
SIZING

The capacities contained in this bulletin are based on a specific


level of performance by the regulator. The measure of performance is accuracy of regulation, also known as offset or deviation.
Each table is appended with a footnote indicating the accuracy
of regulation obtainable at the rated capacities listed.
Pertinent terms involved in the determination of accuracy of
regulation and rated capacity are defined as follows:
* REGULATED VARIABLE is the controlled condition of the
fluid either (1) flowing through a regulator or (2) in a process
served by a regulator. Reduced pressure, back pressure and
differential pressure are the typical regulated variables to be
dealt with in this instance. Other cases, such as vapor pressure
produced by a steam-heated vapor generator, will be found.
* MINIMUM CONTROLLED FLOW is the lowest flow at which
a steady condition of fluid pressure can be maintained. Any
further reduction of flow produces a noticeable deviation of the
regulated pressure toward dead-end shut off. For convenience,

minimum controlled flow is often considered as being at 5% of


rated capacity.
* SET POINT is the value of the regulated pressure at minimum
controlled flow.
* RATED CAPACITY of a pressure regulator pertains to specified
inlet and outlet conditions and is the rate of flow through the
regulator, guaranteed by the manufacturer, when the regulated
pressure deviates no more than a specified number of psi from
the set pressure at minimum controlled flow.
* ACCURACY OF REGULATION is the amount by which the
regulated pressure deviates from set point at minimum
controlled flow as the flow through the regulator is gradually
increased from minimum to rated capacity.
* LOCK-UP is the increase from set value due to dead end shut-off.
* Adapted from Definitions of Regulator Capacities, Standard
No. FCI 58-1, published by Fluid Controls Institute, Inc.

50

REDUCED PRESSURE - psi

SIZING MAIN VALVES

DEFINITIONS RELATING TO REGULATOR CAPACITY

TYPICAL REGULATION CURVE


SPENCE TYPE ED
INLET PRESSURE 100 psi

40

30

20

10

0
0

10

20

30

40

70

60

50

80

90

100

110

FLOW - PERCENT

TYPICAL REGULATION CURVE

NOTES

The performance characteristic of a Spence Pressure Regulator


is shown above. Using this curve to illustrate several terms of
reference, the following facts are evident:
REGULATED VARIABLE

REDUCED PRESSURE

Minimum Controlled Flow4%


Set Point 25.0
Reduced Pressure at Rated (100%) Flow 22.5 psi
Accuracy of Regulation, psi 2.5 psi
Accuracy of Regulation, % of set pressure 10%

The slight slope of the curve establishes a definite relationship


between flow and regulated pressure. Note that 1 psi accuracy
of regulation is obtainable at 95% of rated flow.
For back pressure regulation, or differential where the regulator
opens on increasing differential, the characteristic curve would lie
opposite to that shown. It would slope upward with flow increase
because a positive deviation is required to cancel valve opening.

ON

USE

OF

TABLES

The lowest reduced pressures are approximate critical pressures.


No appreciable increase in flow can be obtained at lower pressures.
Downstream pipe size should be enlarged at regulator outlet to
approximately equalize pipe velocities before and after the
reduction. The Steam Capacity Tables are useful for determining
steam pipe sizes and regulator size at any desired lower velocity
level.
Reduced SeatsSpence Regulators are available with a choice
of seat sizes called Full and Normal Ports. There is a capacity
table for each port with standard plugs. The Cv Valve Coefficients
shown on the back page, indicate where 75% and 50%
parabolic plugs are available. For a given pressure drop, rated
flows with various ports and plugs in the same size body may be
compared. Thus, valve and port size may be selected to limit
velocities entering and leaving the regulator. Lower velocities
mean a greater proportion of the pressure drop occurs at the
valve seat, where it belongs, rather than in the body outlet and
connected piping.
Capacity ratings apply to Spence Regulators with Type D, N and
Q Pilots which are spring loaded and have 31/2 inch diaphragms.
Other pilots having greater or lesser sensitivity will provide
proportionally greater or less accuracy of regulation.

- 108 -

A. PLANNING THE INSTALLATION


1. Locate the valve in a straight run of horizontal pipe. See Fig. 1.
2. Allow headroom above the valve for access through the blind
flange. Provide clearance for stem withdrawal underneath.
3. Prevent water hammer and erratic operation by installing
traps to provide proper drainage before and after the valve,
and before secondary PRV or control valve.
4. Avoid damaging affects of scale and dirt in pipe lines by
using a strainer as shown in Fig. 1 .
5. Provide a 3-valve by-pass to facilitate inspection without
interrupting service.
6. To eliminate excessive noise and erratic regulation with
steam and other compressible fluids enlarge the delivery
pipe size to effect a reasonable flow velocity at the reduced
pressure. A tapered transition is recommended. If possible,
avoid a sharp turn close to the regulator outlet and a bullheaded tee connection to the low pressure main.
7. Install initial and delivery pressure gauges to indicate
performance. If the pressure rating of the delivery system or
connected equipment is less than the initial steam pressure,
provide a safety valve.
B. CONTROL PIPE
1. Use 1/4 pipe for this line which connects the pilot diaphragm
chamber to the desired point of pressure control. See Fig. 1.
2. Take the control at a point of minimum turbulence. Avoid
control immediately at the valve outlet or after a turn. When
the delivery pipe expands in size select a spot at least 4 pipe
diameters beyond the point of enlargement.
3. Pitch away from pilot to avoid erratic operation and fouling.
Eliminate water pockets.
4. Locate delivery pressure gauge in control pipe to show
pressure actually reaching pilot diaphragm.

1.
2.
3.
4.
5.
6.

Inlet Pipe
Isolation Valve
Strainer
PRV Type
Bypass Pipe
Bypass Valve

C. DESIGN GUIDELINES TO MINIMIZE NOISE


1. Size the regulator to provide a maximum inlet velocity of
about 10,000 FPM.
2. Determine the regulator outlet velocity. if it would exceed
30,000 FPM, use a Spence muffling orifice or a second stage
regulator.
3 Expand regulator outlet piping to limit discharge line velocity
to about 10,000 FPM.
4. Avoid abrupt changes in pipe size. Limit pipe diameter
changes to two pipe sizes per stage of expansion. Do not
use eccentric reducers.
5. Directional changes in downstream piping should be made
only after the line size has been increased. Use long radius
fittings; avoid bull-head tee connection.
6. Provide as much straight run of pipe on both sides of
regulator as possible:
a - 10 pipe diameters minimum to the inlet.
b - 20 pipe diameters minimum of expanded line size from
the outlet.
7. Size all piping components, including strainer and stop valves
for a maximum flow velocity of about 10,000 FPM (Exception:
An outlet stop valve mounted at the regulator outlet should
be equal in size to the regulator). In areas where low sound
levels are specified, reduce this limit by 25% to 50%.
8. To limit noise transmission through the buildings structure.
keep the regulator and piping at least 3 feet away from solid
surfaces. Use sound-isolating piping supports.
9. Apply high density insulation to the regulator body, piping and
system components. Insulation reduces heat loss significantly
and can provide moderate (3-6 dB) local noise attenuation.
10. Use a Spence noise suppressor to reduce the propagation
of noise via the downstream piping.

7. Delivery Pipe
8. SRV Type
9. Drip Pan Elbow
10. Vent Stack
11. Low Pressure Trap
12. High Pressure Trap
10

Provide as much straight run of pipe on both sides of regulator as possible:


10 pipe diameters minimum to the inlet.
20 pipe diameters minimum of expanded line size from the outlet.

9
1
6

10 d1

2
7

20 d2

d1

d2

Min. 4 d2

11
12

- 109 -

PLANNING MAIN
VALVE INSTALLATION

PLANNING MAIN VALVE INSTALLATION

RULES FOR MAIN


VALVE SELECTION

RULES FOR MAIN VALVE SELECTION


When you select a Main Valve, your sizing can be based on
one of three methods. They are:

ECONOMICAL MAIN VALVE


Economical Main Valve Selection is choosing a regulator that
has the line size and rough capacity to handle the load. No
consideration is given to velocities or noise. If you are
interested in an economical selection, select a regulator type
for your application, then go to the Capacity Tables and select
the size that will provide you with the capacity needed.

ENGINEERED MAIN VALVE


Engineered Main Valve Selection takes into consideration the
inlet and outlet velocities of the regulator, It will limit these
velocities to acceptable standards. See Pressure Reducing
Station Design Guidelines on the following pages for details. If
you are interested in an engineered selection, select a regulator

RULES

FOR

type for your application, and then to the Capacity Tables and
select the size that will provide you with the capacity needed.
Verify that the velocities fall within the guidelines by consulting
the Velocity Charts in this Section.

ENGINEERED MAIN VALVE WITH NOISE SUPPRESSION


Engineered Main Valve Selection with Noise Suppression
considers both velocity and noise suppression in the selection
of the regulator. For this selection, it is recommended that you
contact your local Spence Technical Sales Representative who
can provide you with a computer generated solution.

SELECTING A REGULATOR TYPE


The following rules should be used to help you to determine
the type of regulator that you should use. You should consult
the Product Pages, Velocity Tables and Capacity Tables for
additional information on your selection.

MAIN VALVE SELECTIONSTEAM SERVICE

Together with the following rules, reference should be made to the Main Valve Specification Table or individual Product Pages for
maximum initial pressures and temperatures and minimum differentialsfor the several types of Main Valve. For pressure reduction
where fast response time is important, but capacity and accuracy are not critical, select D50 DIRECT OPERATED REGULATOR.

EITHER DEAD-END OR CONTINUOUS FLOW SERVICE


RULE 1. For Initial Pressures exceeding 15 psi:
(a) TYPE E Select when the Delivery Pressure is less than
75% of Initial Pressure. For Differential Pressures of 15-50
psi, specify optional LP Spring (10 psi minimum Differential Pressure is attainable by adding optional fittings).

RULES

FOR

(b) TYPE E5 Select when the Delivery Pressure is 75%


to 96%of Initial Pressure.
RULE 2. For Initial Pressures less than 15 psi:
(a) TYPE E2 Select when Initial Pressure is less than 15 psi.

MAIN VALVE SELECTIONAIR SERVICE

Together with the following rules, reference should be made to the Main Valve Specification Table or individual Product Pages for
maximum initial pressures and temperatures and minimum differentialsfor the several types of Main Valve.For pressure reduction
where fast response time is important, but capacity and accuracy are not critical, select D50 DIRECT OPERATED REGULATOR.

EITHER DEAD-END OR CONTINUOUS FLOW SERVICE


RULE 1. For Initial Pressures exceeding 15 psi:
(a) TYPE E Select when the Delivery Pressure is less than
75% of Initial Pressure. For Differential Pressures of 15-50
psi, specify optional LP Spring (10 psi minimum Differential Pressure is attainable by adding optional fittings).

RULES

FOR

(b) TYPE E6 Select when the Delivery Pressure is 75%


to 93%of Initial Pressure.
(c) TYPE E5 Select when the Delivery Pressure is 93%
to 96%of Initial Pressure.
RULE 2. For Initial Pressures less than 15 psi:
(a) TYPE E2 Select when Initial Pressure is less than 15 psi.

MAIN VALVE SELECTIONWATER SERVICE

Pilot Operated Regulators are not uniformly successful in liquid pressure reducing service unless the delivery system has unusual
cushioning such as afforded by an elevated tank or large air chamber.

WATER PRESSURE REDUCING VALVES


The TYPE D34 DIRECT OPERATED VALVE was developed
for application on rapidly changing and intermittent flow to an
inflexible system.
RULE 1. Select TYPE D34 DIRECT OPERATED VALVE for
pressure reducing service.

FOR PILOT OPERATED WATER REGULATORS


When a pilot operated regulator is required the following rules
for the selection of a main valve govern:
RULE 2. When pressure drop across valve exceeds 10 psi:
(a) TYPE C34 -Select for all normal requirements.

(b) TYPE E6 with Dashpot-Select where high lift is desired


or special flow requirements encountered.
RULE 3. When pressure drop across valve is between 5 and
10 psi:
(a) TYPE E5 - Select for pressure drops not less than 5 psi.
(b) TYPE E6 with Dashpot-Select if auxiliary operation is
possible.
Together with the above rules, reference should be made to
the Main Valve Specification Table for maximum initial pressures and temperatures and minimum differentials for the
several types of Main Valves.

- 110 -

FORMULA KEY
A
Cv
EDR
F
ft
G
P
P1
P2
Pc

=
=
=
=
=
=
=
=
=
=

PS =

Area of Pipe in (inches)2


Valve Coefficient
Equivalent Direct Radiation (Sq. Ft.)
Pipe Area Factor (see Pipe Factors Table)
Feet
Specific Gravity
Pressure Drop,P1 P2 psi
Inlet Pressure, psia (psi + 14.7)
Reduced Pressure, psia (psi + 14.7)
Pressure at Thermodynamic Critical Point,
psia (water = 3206 psia)

P1 Pv when P2 > Pv

P ) P when P < P

P
q = Liquid Flow Rate, U.S. gpm

PS = P1 (.96 .28

Q = Flow Rate, SCFH


T = Absolute T (T + 460)R
TSH = Steam Superheat (F) =
Total Steam Temp. Saturated Steam Temp.
v
V
W
Ws

Pv = Vapor Pressure, psia

=
=
=
=

Specific Volume FT3/#


Velocity, FPM
Steam Flow, #/Hr.
Flow, #/Hr. Superheated Steam

To avoid interpolation or solve problems beyond the scope of the table, valve sizes may be determined by calculation as follows:

Cv

LOADS

SUBCRITICAL
SATURATED
STEAM:

CRITICAL

P2 > .58 P1
W
Cv=
2.1 P (P1 + P2)

P2 < .58 P1
W
1.71 P1

Cv=

P2 > .55 P1
SUPERHEATED
STEAM:
Cv= W (1 + .0007TSH)
P2 > .5 P1
Q
Cv= 963

P (PGT P )
1+

Cv=

ABSORPTION W = 16-20 #/Hr./Ton-Hr.


STM. ATOM

Cv=

.93q

W = 0.1 #/Hr./#Oil

VELOCITY

P2 < P1 .85 PS

PG

RADIATION

Q GT
834 P1

Cv=

P2 > P1 .85 PS

LIQUID:

AIR

P2 < .5 P1

GPM X Temp. Rise (F)


2
GPM
W=
X Temp. Rise (F)
4
W = CFM X Temp. Rise (F)
900
2
f
EDR
W=
4
W=

FUEL OIL

P2 < .55 P1
W
(1
+ .0007TSH)
Cv=
1.75 P1

2.1 P (P1 + P2)

GAS:

WATER

PG

STEAM

V = 2.4

Wv
A

PIPE FACTORS
FOR STANDARD
(SCHEDULE 40) PIPE
SIZE

FLOW
STEAM

/8
/
3/8
1
/2
3/4
1
11/4
11/2
2
21/2
3
14

W = .0433 x V x F

AIR & GASES Q = .0259 x V x F x P1


T
LIQUIDS

q = .0054 x V x F

- 111 -

FACTOR

SIZE

FACTOR

.55
1.0
1.8
2.9
5.1
8.3
14
20
32
46
71

95
122
192
278
481
758
1076
1301
1699
2151
2673

3 /2
4
5
6
8
10
12
14
16
18
20

VALVE SIZING BY
COMPUTATION

VALVE SIZING BY COMPUTATION

PRESSURE STATION
DESIGN GUIDELINES

PRESSURE REDUCING STATION DESIGN GUIDELINES


I. SINGLE STAGE PRESSURE REGULATOR

A. When intermediate steam pressure is required.

1. When to use single stage regulator:

B. When concerned with PRV generated noise, use two


stage station when specific volume ratio, outlet to inlet, is
greater than 3 to 1, unless manufacturer offers
assurance or other means of meeting noise specification.

A. When load turndown requirement is generally no greater


than 10:1.
B. When ratio of specific volume of steam, outlet to inlet, is
no greater than 3 to 1.

C. When complying with Power Piping Code ANSI B31.11986, which reads, in part, in district heating and steam
distribution systems where the steam pressure does not
exceed 400 psi (2758 kPa) and where the use of relief
valves and vent piping are not feasible, two or more
pressure reducing valves may be installed in series, each
set at or below the safe working pressure of equipment
served and no relief valve is required.

C. When only one reduced steam pressure level is


required.

II. PARALLEL PRESSURE REGULATORS


1. When to use parallel pressure regulator stations:
A. When maximum specified capacity requires selection of
a pressure regulator greater than 12 inch pipe size. (It
may be more economical to install two smaller valves
than one very large one.)

IV. TWO STAGE


PARALLEL PRESSURE REGULATORS
1. Whenever any condition from II and any condition from III
applies.

B. When normal conditions require operation at 10% or


less of specified maximum capacity for sustained
periods.

SPACE CONSIDERATIONS FOR REDUCING STATIONS

C. When there are two distinct load requirements; i.e.,


summer/winter operation.

1. Following are rules of thumb for approximating space


requirements for installing reducing stations:

2. When to use a pneumatically operated parallel pressure


regulator station:

A. Single stage (with or without noise suppressors)


Inlet side: ten (10) diameters of PRV pipe size

A. When the combined accuracy of regulation of


mechanically operated controls is unacceptable.

Outlet side: twenty (20) diameters of final pipe size, where


final pipe size is determined on the basis of 10,000 fpm
line velocity.

For Spence mechanically operated regulators normal


sizing/selection results in accuracy of regulation of
approximately 5% of set pressure. Combined accuracy
of regulation of mechanically operated parallel installed
regulators is approximately 10% of set pressure.

B. Two stage
Inlet side of primary: ten (10) diameters of PRV pipe size.
Intermediate: twenty (20) diameters of secondary PRV pipe
size.

Pneumatically operated regulators equipped with reset


maintain set point within 1% for all sustained flows.

III. TWO STAGE PRESSURE REGULATORS

Outlet side: twenty (20) diameters of final pipe size, where


final pipe size is determined on the basis of 10,000 fpm
line velocity.

1. When to use two stage pressure regulator stations:

C. Two stage with muffling orifice; same as A above.

Primary PRV requires optional base bypass and 1/8" bleedport.

PRESSURE REDUCING STATION GENERAL SPECIFICATION


D.Unions shall be used on either side of screwed end bypass valve and pressure regulator to facilitate removal.

A.Pressure Reducing Station shall consist of:


-

pressure regulator
inlet strainer
inlet and outlet stop valves (gate type)
by-pass valve (globe type)
trap at inlet to pressure regulator
pressure gauges on inlet and outlet of station
pressure relief valve downstream of regulator

E. Pressure regulators 2-1/2 and larger shall have flanged


ends and be suitable for pressure and temperature
specified.
F. Limit pressure regulator inlet velocity to:
Up to and including 2
2 1/2 thru 8
Above 8

B.Stop valves and strainer shall be at least pressure regulator size


C.Expand pressure regulator outlet pipe size to obtain
discharge line velocity which will not exceed:
Up to and including 2
2 1/2 up to 8
Above 8

15,000 FPM
10,000 FPM
8,000 FPM

Regulator outlet velocity shall be limited to:


Up to and including 2
2 1/ 2 up to 8
Above 8

45,000 FPM
30,000 FPM
24,000 FPM

15,000 FPM
10,000 FPM
8,000 FPM

G.Regulator sound pressure level while operating at specified


maximum capacity shall not exceed 90 dbA as measured
at a point three feet downstream and three feet from
uninsulated pipe surface.
H.Pressure regulator capacity shall not be greater than 120 of
specified maximum capacity.
I. For details of safety valve sizing and installation, please
refer to the latest National Board Inspection Code and
ANSI B31.1 Code.

- 112 -

- 113 -

12

22

39

58

76

125

189

316

38

12

/4

11/4

11/2

21/2

10

12

474

283

187

114

87

59

33

18

631

377

249

151

115

78

43

24

17.6

14.6

10.4

7.5

4.8

1.5

.65

557

353

222

124

85

55

37

22

15.5

9.9

7.0

4.4

2.7

1.4

835

530

333

186

127

82

56

33

23.3

14.8

10.6

6.6

4.0

2.1

1113

706

444

248

169

109

74

44

31

19.8

14.1

8.8

5.4

2.8

1.5

Full

1118

748

465

255

202

143

96

68

44

27.4

18.9

11.7

7.6

E2

952

525

366

228

176

120

59

35

25

19.8

13.4

10.0

5.7

1611

1018

665

350

258

159

95

67

43

27.4

18.9

11.7

7.6

Normal Full

E5,E6

196

139

86

53

36

24

17.3

12.5

5.5

C34

.32

.32

.25

The Parabolic Discs given in the above table are designed to:
a) Improve performance at minimum flows by improving stability over wide flow ranges.
b) Provide easy field conversion to obtain a substantial increase or decrease in regulator Cv to meet system load requirements.
c) Facilitate selection of smaller size safety relief valves.
d) Size more precisely to the required Cv, thereby eliminating one of the most frequent causes of poor performance.

75% AND 50% REDUCED TRIM (Parabolic)

/4

E
Valve
Size Normal Normal Normal Full Full
50% 75%
50% 75%

REGULATOR Cv DATA

118

84

52

32

21.6

14.4

10.4

7.5

3.3

60%

D34

60

37.5

20.8

14.3

9.2

5.3

50%

N6

17.2

15.1

14.3

9.15

6.85

.4-5.22

Series
2000

REGULATOR
Cv DATA

10.8

10.1

5.0

4.9

3.3

2.2

D50

SATURATED STEAM
FLOW TABLE

SATURATED STEAM FLOW TABLE (LB/HR)


Based on Schedule 40 Pipe

SIZES 1/4" THROUGH 2"


VEL., FPM
PRESS.
(PSIG)
-10
-5
0
5
10
15
20
25
30
40
50
60
70
80
90
100
125
150
175
200
250
300

45000

45000

45000

45000

45000

45000

45000

45000

REGULATOR or PIPE SIZE (inches)


1
/4
23
51
73
97
120
142
164
186
208
251
293
336
377
420
461
503
607
710
813
916
1121
1336

3/8
43
93
134
178
220
260
301
341
381
460
538
616
692
770
846
922
1113
1302
1491
1680
2057
2452

1/2
68
148
213
284
350
415
479
543
607
732
857
981
1102
1225
1347
1468
1771
2072
2374
2675
3274
3902

3/4
120
260
373
498
613
728
841
953
1065
1285
1504
1721
1934
2150
2364
2577
3108
3636
4166
4694
5746
6848

1
195
422
605
807
994
1179
1363
1545
1726
2083
2437
2789
3134
3485
3831
4176
5037
5893
6752
7608
9313
11099

11/4
337
730
1046
1396
1720
2041
2359
2673
2987
3605
4217
4827
5424
6031
6630
7228
8718
10198
11685
13166
16118
19209

11/2
458
994
1424
1900
2342
2778
3210
3639
4065
4906
5740
6570
7383
8209
9024
9838
11866
13881
15905
17921
21938
26145

2
755
1638
2348
3132
3860
4579
5292
5998
6700
8087
9461
10829
12170
13531
14874
16216
19558
22879
26216
29539
36160
43094

30000

30000

30000

30000

24000

24000

10
9466
20524
29424
39256
48374
57390
66320
75171
83977
101355
118578
135722
152523
169579
186417
203233
245117
286743
328560
370208
453186
540098

12
13437
29134
41767
55723
68666
81464
94139
106703
119203
143871
168318
192653
216502
240713
264614
288484
347938
407024
466382
525501
643286
766655

SIZES 21/2" THROUGH 12"


VEL., FPM
PRESS.
(PSIG)
-10
-5
0
5
10
15
20
25
30
40
50
60
70
80
90
100
125
150
175
200
250
300

30000

30000

REGULATOR or PIPE SIZE (inches)

21/2
718
1558
2233
2979
3671
4356
5033
5705
6373
7692
9000
10301
11576
12870
14148
15424
18603
21763
24936
28097
34395
40991

3
1109
2405
3448
4600
5669
6725
7772
8809
9841
11878
13896
15905
17874
19873
21846
23817
28725
33603
38503
43384
53108
63293

4
1910
4142
5938
7922
9762
11581
13383
15170
16947
20454
23929
27389
30779
34221
37619
41012
49465
57865
66303
74708
91453
108992

5
3002
6509
9331
12449
15341
18200
21032
23839
26632
32143
37605
43042
48370
53779
59119
64452
77735
90936
104197
117405
143720
171283

- 114 -

6
4335
9399
13475
17978
22154
26283
30372
34426
38459
46418
54305
62156
69851
77662
85373
93074
112256
131319
150470
169544
207545
247348

8
7507
16276
23334
31131
38362
45512
52594
59613
66596
80378
94036
107631
120955
134481
147834
161169
194385
227395
260557
293586
359389
428313

Based on Schedule 40 Pipe

SIZES 3/8" THROUGH 4"


VEL., FPM
PRESS.
(PSIG)
-10
-5
0
5
10
15
20
25
30
40
50
60
70
80
90
100
125
150
175
200
250
300
400
500
600

15000

15000

15000

15000

15000

15000

15000

10000

10000

10000

REGULATOR or PIPE SIZE (inches)


3/8
14
31
45
59
73
87
100
114
127
153
179
205
231
257
282
307
371
434
497
560
686
817
1065
1326
1591

1/2
23
49
71
95
117
138
160
181
202
244
286
327
367
408
449
489
590
691
791
892
1091
1301
1696
2110
2532

3/4
40
87
124
166
204
243
280
318
355
428
501
574
645
717
788
859
1036
1212
1389
1565
1915
2283
2976
3703
4444

1
65
141
202
269
331
393
454
515
575
694
812
930
1045
1162
1277
1392
1679
1964
2251
2536
3104
3700
4823
6002
7202

11/4
112
243
349
465
573
680
786
891
996
1202
1406
1609
1808
2010
2210
2409
2906
3399
3895
4389
5373
6403
8347
10387
12464

11/2
153
331
475
633
781
926
1070
1213
1355
1635
1913
2190
2461
2736
3008
3279
3955
4627
5302
5974
7313
8715
11361
14138
16965

2
252
546
783
1044
1287
1526
1764
1999
2233
2696
3154
3610
4057
4510
4958
5405
6519
7626
8739
9846
12053
14365
18725
23303
27963

21/2
239
519
744
993
1224
1452
1678
1902
2124
2564
3000
3434
3859
4290
4716
5141
6201
7254
8312
9366
11465
13664
17812
22166
26599

3
370
802
1149
1533
1890
2242
2591
2936
3280
3959
4632
5302
5958
6624
7282
7939
9575
11201
12834
14461
17703
21098
27502
34225
41070

4
637
1381
1979
2641
3254
3860
4461
5057
5649
6818
7976
9130
10260
11407
12540
13671
16488
19288
22101
24903
30484
36331
47360
58936
70724

10000

8000

8000

8000

8000

8000

8000

8000

16
7071
15332
21980
29325
36136
42871
49542
56153
62731
75713
88579
101385
113936
126677
139255
151817
183105
214199
245437
276549
338534
404358
525936
654498
785398

18
8951
19407
27822
37119
45740
54265
62708
71078
79404
95836
112121
128331
144217
160345
176265
192166
231770
271128
310668
350048
428507
510687
665717
828448
994137

20
11122
24115
34572
46124
56836
67430
77921
88321
98667
119086
139321
159464
179204
199244
219027
238785
287997
336904
386036
434970
532463
634579
827219
1029428
1235314

24
16087
34878
50002
66710
82204
97526
112700
127741
142706
172238
201505
230638
259189
288174
316787
345363
416540
487276
558337
629112
770120
917814
1196436
1488898
1786677

SIZES 5" THROUGH 24"


VEL., FPM
PRESS.
(PSIG)
-10
-5
0
5
10
15
20
25
30
40
50
60
70
80
90
100
125
150
175
200
250
300
400
500
600

10000

10000

REGULATOR or PIPE SIZE (inches)

5
1001
2170
3110
4150
5114
6067
7011
7946
8877
10714
12535
14347
16123
17926
19706
21484
25912
30312
34732
39135
47907
57094
74426
92620
111143

6
1445
3133
4492
5993
7385
8761
10124
11475
12820
15473
18102
20719
23284
25887
28458
31025
37419
43773
50157
56151
69182
82449
107479
133751
160501

8
2502
5425
7778
10377
12787
15171
17531
19871
22199
26793
31345
35877
40318
44827
49278
53723
64795
75798
86852
97862
119796
142771
186112
231607
277928

10
3155
6841
9808
13085
16125
19130
22107
25057
27992
33785
39526
45241
50841
56526
62139
67744
81706
95581
109520
123403
151062
180033
234685
292053
350464

12
4479
9711
13922
18574
22889
27155
31380
35568
39734
47957
56106
64218
72167
80238
88205
96161
115979
135675
155461
175167
214429
255552
333130
414562
497474

- 115 -

14
5413
11737
16826
22448
27662
32818
37924
42986
48021
57959
67808
77611
87219
96972
106601
116217
140168
163972
187884
211700
259150
308850
402609
501024
601229

SATURATED STEAM
FLOW TABLE

SATURATED STEAM FLOW TABLE (LB/HR)

SELECTING
PRESSURE PILOTS

SELECTING PRESSURE PILOTS


Any of the Main Valves described in the Main Valve Section can
be combined with any of the Pilots listed below to produce the
SPENCE Pressure Regulator. This Regulator will reduce and
regulate a steady or varying initial pressure, within the range

specified, so as to maintain a constant, adjustable,


predetermined delivery pressure. The table below lists the
principal Pressure Pilots.

PRESSURE REGULATOR PILOTS


Type

Service Conditions
Cast Iron

Cast Bronze

Diaphragm

Cast Steel

250

450

600

750

Main Valve

Delivery Pressure

Maximum Maximum Maximum Maximum Maximum Maximum


Normal
Initial
TemperInitial
TemperInitial
TemperAccuracy
Pressure ature Pressure ature Pressure ature Minimum Maximum
psi
F
psi
F
psi
F
psi
psi

Loading

150

D2

250

450

600

750

100

300

D5

250

450

25

1 psi

31/2

St. Stl.

Spring

E or C Series

2 psi

3 /2

St. Stl.

Spring

E or C Series

12

/ psi

53/4

St. Stl.

Spring

E or C Series

1 psi

12

250

450

600

750

4/

St. Stl.

Spring

E or C Series

A73

250

450

600

750

31/2-71/4b

St. Stl.

Air

E or C Series

A53

250

450

600

750

12

31/2-53/4b

St. Stl.

Air

E or C Series

250

450

600

750

12

31/2

St. Stl.

Air

E or C Series

250

450

A54

250

450

600

750

A70

250

450

600

750

A86

250

450

600

750

A87

250

450

600

750

A85

250

450

600

750

150

Material

D120

A35

Diameter
inches

/2 psi
/ psi
/ psi

See response
curves on
A Pilot

/8 psi

1 b
2

5 /4-3 /

St. Stl.

Air

E or C Series

1 psi

41/2-53/4b

St. Stl.

Air

E or C Series

2 psi

7 /4

St. Stl.

Air

E or C Series

41/2

St. Stl.

Air

E or C Series

14

7/

St. Stl.

Air

E or C Series

31/2-53/4b

St. Stl.

Air

E or C Series

/2 psi

Product Page

12

/ psi

/2 psi

50

A84

250

450

600

750

12

A83

250

450

600

750

12

12

3/

St. Stl.

Air

E or C Series

31/2

St. Stl.

Air

E or C Series

/8 psi

5 /4

St. Stl.

Air

E or C Series

/ psi
/ psi

A82

250

450

Safety
Pilot

300

500

600

750

175

31/2

St. Stl.

Spring

E or C Series

P125

250

450

600

750

175

1 psi

41/2

St. Stl.

Spring

E or C Series

These Pilots have dual diaphragms, the first size being the control diaphragm and the second, the air loading diaphragm.

NOTES

ON

SELECTION

OF

PILOTS

D SERIES PILOTS meet the requirements of the majority of all


pressure regulator problems. They are spring-loaded. Other
Pilots are modifications of the D Series for specific purposes.
A SERIES PILOTS are air-loaded. These Pilots are recommended where frequent changes in setting must be made and
the Regulator is not easily accessible.

Water Service Pilot operated Regulators are not uniformly


satisfactory as water reducing valves unless the delivery
system has the ample cushioning afforded by an elevated tank
or air chamber. When the flow is intermittent to an inflexible
system, the SPENCE Type D34 Direct Operated Pressure
Reducing Valve is recommended.

In any one Series of Pilots a larger Diaphragm will produce closer


accuracy of control but with less range in delivery pressure.

- 116 -

DATA REQUIRED

FOR

EXAMPLE

ORDERING

(a) Maximum/Minimum.

Select size and type Regulator to pass 14,600 lb. steam per
hour reducing from 175/150 psi saturated to 40/20 psi. Ends
to be flanged, pilot spring loaded and pressure controlled
within 2 psi.

(b) Superheat, Gravity, etc.

1. Steam

1. SERVICE Fluid flowing though Regulator.


2. INITIAL (INLET) PRESSURE

(1) Steam ServiceTotal Temperature or Degrees


Superheat, if any.
(2) Air, Gases, Water and LiquidsTemperature and
Specific Gravity.
3. DELIVERY (OUTLET) PRESSURE Maximum/Minimum.
4. CAPACITY Maximum required flow through Regulator.

2.
(a) 175/150 psi
(b) None (saturated, 378F total temperature)
3. 40/20 psi
4. 14,600 lb. per hour
5. Flanged, if 21/2" size or larger

5. END CONNECTIONS Screwed or Flanged. (If flanged,


state drilling.)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE
A. TYPE See Selection Criteria
for Steam, Air, Gases or Water
and Liquids in beginning of this
Section.

OF

REGULATOR

See Selection Criteria


and Selection Charts
opposite.

OF

TYPE

AND

MAIN VALVE

PILOT

B. SIZESee applicable Valve


Capacity Tables in this Section.

C. MATERIAL See Main Valve


Selection Chart in Technical
Reference Section or individual
Product Pages.

SELECTION

A. Since maximum Delivery


Pressure is less than 75%
of minimum Initial Pressure
and the least pressure drop
exceeds required minimal
differential.
SELECT TYPE E

SIZE

OF

REGULATOR

PILOT
Since maximum Initial
Pressure 175 psi, Total
Temperature 378F maximum Delivery Pressure 40
psi, Pilot spring loaded and
required accuracy 2 psi:
SELECT TYPE D

B. For 14,600 lb. per hour


and 150 psi minimum
Initial Pressure Economical:
SELECT 3" FULL PORT
Engineered: SELECT 4"
NORMAL PORT
See Pilot Selection
Chart opposite or individual Product Pages.

D. ACCESSORIESSee Accessories in Other Products


Section.

C. For 175 psi, 378F:


SELECT CAST IRON,
FLANGED 250 LB.

For 175 psi, 378F:


SELECT CAST IRON

D. None required in this case.

None required in this case.

ECONOMICAL SOLUTION: 3" FULL PORT SPENCE TYPE ED, CAST IRON BODY, 250 LB. FLANGED ENDS
ENGINEERED SOLUTION: 4" NORMAL PORT SPENCE TYPE ED, CAST IRON BODY, 250 LB. FLANGED ENDS.
NOTE:Pressure Regulators should always be protected by properly designed Strainers.

- 117 -

SIZING PRESSURE
REGULATORS

SIZING PRESSURE REGULATORS

SELECTING TEMP.
PILOTS

SELECTING TEMPERATURE PILOTS


Any of the Main Valves described in the Main Valve Section can
be combined with any of the Pilots listed below, to produce the
SPENCE Temperature Regulator. This Regulator is designed to
control the flow of fluid to a heating or cooling element so as to
maintain a constant, adjustable, precise predetermined temperature. Pilots fully stroke valve within 5F. The table below lists
the principal Temperature Pilots.
The Thermostats of these SPENCE Pilots are of the Vapor
Tension Type. They are ruggedly constructed and will not be
injured by overheating.

These SPENCE Temperature Pilots can be furnished with 150F


range of temperature adjustment on special order. It should be
noted that since heavier Adjusting Springs are required for this
greater range the regulation will not be quite so accurate.
TEMPERATURE RANGES
20F to 120F
150F to 300F
50F to 150F
170F to 270F
70F to 170F
250F to 350F
120F to 220F

Thermostats can be furnished for temperatures


higher than 350F on
special order.

TEMPERATURE REGULATOR PILOTS


Type

Service Conditions
Cast Iron
Cast Bronzea
Cast Steel
Delivery
Maximum Maximum Maximum Maximum Maximum Maximum Pressure
Initial
TemperInitial
TemperInitial
TemperPressure ature Pressure ature Pressure ature
Maximum
psi
F
psi
F
psi
F
psi

Operating Characteristics

Main Valve

Cascade ControlCloses on rise in temperaturecontrols delivery pressuredecreases


delivery pressure as temperature increases
& vice versaspring loaded pressure control.

E or C Series

Closes on rise in temperature.

E or C Series

Closes on rise in temperaturecontrols


delivery pressure at predetermined setting
spring loaded pressure control

E or C Series

T134

250

450

600

750

20

T124

250

450

125

T14

250

450

600

750

T14D

250

450

600

750

150

T14D2

250

450

600

750

300

T52

250

450

Opens on rise in temperature.

E or C Series

Safety
Pilot

300

500

Prevents excessive temperature rise.

E or C Series

Bronze Body Pilots are recommended for water service.

AIR CONTROLLED TEMPERATURE PILOTS


SPENCE Air Control Pilots, listed below, have been developed
to meet special conditions when used in conjunction with A
Series Pressure Pilots. The fast bi-metal thermostats have a
200F adjustable range and protection against damage from
Bulb
Style

Bulb
Material

No.736

Bronze

No. 737

St. Stl.1

T64

No. 738

St. Stl.1

T60

No.745

St. Stl.2

Type
T61

Bulb
Mounting

over-heating. By cascading an air signal onto a pressure regulator, the EAT Series temperature control reduces steam pressure
to an adjustable limit as well as regulating output temperature.
Range
F

Maximum Bulb
Temperature F

Control
Mode

Action

50-250

350

Proportional

Reverse*

50-250

350

Proportional

Reverse*

50-250

350

Proportional

Reverse*

180
350

Proportional
Proportional

Reverse*
Reverse*

/2 NPT

/2 NPT
Sanitary
Thermometer
Bushing
1
/2 NPT
Union
Mounted

30-150
100-300***

* Rising output pressure on falling temperature. This action applied to an EA Series Regulator increases steam flow with decreasing
temperature. Direct action available for cooling control.
1
2
**Rate or reset available on application
***Other ranges on application
Type 304
Type 347 or optional Type 316

NOTES

ON

SELECTION

OF

PILOTS

HEATING CONTROL Single Pilot Types T134 and Combination Pilot Type T14D2 reduce the steam pressure as well as
regulate the output temperature. A choice should be made
according to the maximum required delivery pressure, i.e., the
pressure needed in the heater to carry the peak load. Pilot
Types T14D and T14D2 in cast steel are designed for initial
steam pressures in excess of 500F.
Of the Air Control Pilots, the Type T61 is the general choice.
The Type T60 is used for temperature indication or for remote
adjustment. The required heater pressure will determine the
choice of the A Series Pilot. See Product Pages.

COOLING CONTROL Pilot Type T52 is employed With Type


E or C Series Main Valves to control temperature by regulating
the flow of a cooling medium. This Pilot opens the Main Valve on
rising temperature and exercises no control over the delivery
pressure. The Air Control Pilots can be furnished with increasing
air signal on temperature rise for use in cooling control.
TEMPERATURE RANGES Selection of the following ranges of
temperature adjustment is recommended for the services noted:
50F to 150F Room or air duct control
120F to 220F Domestic or laundry hot water service.
70F to 170F Fuel oil preheating.
170F to 270F Fuel oil heating.

- 118 -

DATA REQUIRED

FOR

EXAMPLE

ORDERING

Select size and type Regulator for heating 120 gpm water from
50F entering temperature to 170F final temperature in an
instantaneous heater. Steam supply at 125 psi pressure to be
reduced to 30 psi maximum in heater.

1. SERVICE
(a) Fluid flowing though Regulator.
(b) Type heater to be controlled.

1. (a) Steam

2. INITIAL (INLET) PRESSURE

(b) Instantaneous

(a) Maximum/Minimum.

2. (a) 125 psi

(b) Superheat, Gravity, etc.

(b) None (saturated, 353F total temperature)

(1) Steam ServiceTotal Temperature or Degrees


Superheat, if any.

3. 30 psi

(2) Air, Gases, Water and LiquidsTemperature and


Specific Gravity.

4. See Capacity Tables in this Section.

3. DELIVERY (OUTLET) PRESSURE Maximum required on


heater.
4. CAPACITY Maximum required flow through Regulator or
the following data leading to same:
(a) Quantity and type of fluid to be heated or cooled.

(a) 120 gpm water.


(b) 170-50 = 120F Rise
120 x 120 = 7200#/Hr.
2
5. (a) 170FSelect standard Temperature Range from facing
page to include this final temperature.

(b) Temperature rise or drop, F.

(b) Close on temperature rise.

5. THERMOSTAT CHARACTERISTICS:

(c) Style No. 700 bronze. (See Options Section)

(a) Controlled Temperature, FMaximum/Minimum.


(b) OperationOpen or Close on temperature rise.

(d) Ten (10) feet, brassfurnished unless otherwise specified.


6. Flanged, if 21/2" size or larger.

(c) Thermostat BulbStyle Number and Material.


(d) Flexible TubingLength and Material.
6. END CONNECTIONS Screwed or Flanged. (If flanged,
state drilling)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE
A. TYPE See Selection Criteria
for Steam, Air, Gases or Water
and Liquids in beginning of this
Section.

OF

REGULATOR

OF

TYPE

AND

MAIN VALVE

PILOT
See Selection Criteria
and Selection Charts
opposite.

A. Since maximum Delivery


Pressure is less than 75%
of minimum Initial Pressure
and the least pressure drop
exceeds required minimal
differential.
SELECT TYPE E

SIZE

OF

REGULATOR

PILOT
Since maximum Initial
Pressure 125 psi, Total
Temperature 353F
maximum Delivery
Pressure 30 psi
SELECT TYPE T124

B. Using Capacity Tables in


this Section, for 7200#/Hr
and 125 psi initial pressure
SELECT 2" FULL PORT

B. SIZESee applicable Valve


Capacity Tables in this Section.

C. MATERIAL See Main Valve


Selection Chart in Technical
Reference Section or individual
Product Pages.

SELECTION

See Pilot Selection


Chart opposite or individual Product Pages.

D. ACCESSORIESSee Accessories in Other Products


Section.

C. For 125 psi, 353F:


SELECT CAST IRON,
NPT 250

For 125 psi, 353F:


SELECT CAST IRON

D. None required in this case.

None required in this case.

ECONOMICAL SOLUTION: 3" SPENCE TYPE ET124, CAST IRON BODY, NPT 250 ENDS
TEMPERATURE RANGE 120-220F EQUIPPED WITH 10 FEET OF BRASS FLEXIBLE TUBING
AND STYLE NO. 700 BRONZE THERMOSTAT BULB.
Temperature Regulators should always be protected by properly designed Strainers.

- 119 -

SIZING TEMPERATURE
REGULATORS

SIZING TEMPERATURE REGULATORS

SELECTING
DIFFERENTIAL PILOTS

SELECTING DIFFERENTIAL PRESSURE PILOTS


SPENCE Differential Pressure Regulators may usually be classified in one or the other of the following groups:

sure on a steam atomizing oil burner at a constant differential


above the oil pressure at the nozzle.

1. Control of the delivery pressure at a constant, adjustable, predetermined differential above another source of fluid pressure.
This case is illustrated by the use of the SPENCE Type EN
Differential Pressure Regulator on a boiler feedwater make-up
line to control the delivery pressure of the feedwater at a constant differential above the boiler steam pressure. Another
example is the use of the Type EN to control the steam pres-

2. Control of the differential pressure or pressure drop across


the Pressure Regulator itself. This case is illustrated by the use
of the SPENCE Type EN24 Differential Pressure Regulator
installed in parallel with a heat exchanger to maintain a constant differential across it, thereby limiting the flow rate of
fluid through the heater.
The table below lists the principal Differential Pilots.

DIFFERENTIAL PRESSURE REGULATOR PILOTS


Type

Service Conditions
Cast Iron

Cast Bronzea

Diaphragm
Differential
Pressure
Max.

Operating
Characteristics

Cast Steel

Max.
Max. Max.
Max.
Max.
Max.
Max.
Max.
Initial Temper- Diaph. Initial Temper- Diaph. Initial Temper- Diaph.
Pressure ature Pressure Pressure ature Pressure Pressure ature Pressure
psi
F
psi
psi
F
psi
psi
F
psi

Normal
Accuracy

Min.
psi

Max.
psi

Main
Valve

Loading
Diameter Material
inches

250

450

240

300

500

290

600

750

300

150

1 psi

31/2 St. Stl. Spring

N33

250

450

240

300

500

290

600

750

300

150

1 psi

31/2 St. Stl. Spring

N20

250

366

250

300

366

300

300

366

300

150

1 psi

31/2 St. Stl. Spring

Closes on increase in differential


Delivery pressure controlled at set
differential above loading pressure
Loading Pressure may be any fluid
Opens on increase in differential
Initial pressure controlled at set
differential above loading pressure
Loading pressure may be any fluid

E or C
Series
E or C
Series
E or C
Series

Bronze Body Pilots are recommended for water service.

NOTES

ON

SELECTION

OF

PILOTS

TYPE N AND N33 PILOTS require that the delivery pressure


(pressure of fluid discharged from the Regulator) be controlled
at a given differential above some separate source of loading
pressure.
TYPE N meets the requirements of most boiler feedwater
make-up and steam atomizing oil burner differential control
problems as described in the first group in the above table.

TYPE N33 is a version of the Type N in which two separated


diaphragms are employed to preclude the possibility of contact
between the two fluids applied to the pilot.
TYPE N20 is a differential relief pilot which causes the Main
Valve to open when its initial pressure exceeds the loading
pressure by a set differential.

- 120 -

DATA REQUIRED

EXAMPLE

ORDERING

FOR

Select size and type Regulator to control the flow of water from
a Motor-Driven Centrifugal Boiler Feed Pump maintaining an
Excess or Differential pressure of 50 psi between the boiler
feedwater and the boiler steam pressure. The feedwater
temperature is 240F. The boiler steam pressure is 150 psi.
Flow 90 gpm at 220 psi pump discharge pressure.

1. SERVICE Fluid flowing though Regulator.


2. INITIAL (INLET) PRESSURE
(a) Maximum/Minimum.
(b) Superheat, Gravity, etc.
(1) Steam ServiceTotal Temperature or Degrees
Superheat, if any.

1. Water
2. (a) 220 psi

(2) Air, Gases, Water and LiquidsTemperature and


Specific Gravity.

(b) 240F
3. (a) 150 psi Boiler Pressure

3. LOADING PRESSURE

(b) Steam

(a) Maximum/Minimum.

4. (a) 200 psi (Loading plus Excess Pressure)

(b) Fluid

(b) Water

4. CONTROLLED PRESSURE
(a) Maximum/Minimum.

5. Identical with Controlled Pressure, Item 4

(b) Fluid

6. 90 gpm
7. Flanged, if 21/2" size or larger

5. DELIVERY PRESSURE Maximum/Minimum.


6. CAPACITY Maximum required flow through Regulator.
7. END CONNECTIONS Screwed or Flanged. (If flanged,
state drilling.)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE

OF

REGULATOR

SELECTION

PILOT

TYPE

AND

SIZE

MAIN VALVE

See Selection Criteria


and Selection Charts
opposite.

A. TYPE See Selection Criteria


for Steam, Air, Gases or Water
and Liquids in beginning of this
Section.

OF

REGULATOR

PILOT

A. Since pressure drop across


valve (Initial Pressure minus
Delivery Pressure) is greater
than 10 psi:
SELECT TYPE E

B. SIZESee applicable Valve


Capacity Tables in this Section.

OF

Since Initial Pressure 220 psi,


240F, Differential (Excess)
Pressure 50 psi and the
Delivery and Controlled
Pressures are the same:
SELECT TYPE N

B. For 90 gpm: SELECT 3"


See Pilot Selection
Chart opposite or individual Product Pages.

C. MATERIAL See Main Valve


Selection Chart in Technical
Reference Section or individual
Product Pages.

D. ACCESSORIESSee Accessories in Other Products


Section.

C. For 220 psi, 240F:


SELECT CAST IRON,
FLANGED 250 LB.

For 220 psi, 240F:


SELECT BRONZE

D. For Water Service:


Dashpot required.

None required in this case.

ANSWER: 3" SPENCE TYPE EN, CAST IRON BODY, 250 LB FLANGED ENDS,
EQUIPPED WITH BRONZE DASHPOT AND BRONZE PILOT BODY.
NOTE: Differential Regulators should always be protected by properly designed Strainers.

WATER CAPACITY TABLEFLOW

IN

GALLONS

PER

MINUTE

These flow rates provide a simple method for sizing regulators or water pipes with inlet velocities in the
range of 240 to 600 fpm. Spence Regulators have variable seat sizes. The factory will select the proper
seat for particular flow and pressure drop. Additional capacity data is available on request.
VALVE OR PIPE SIZE
2
21/2
3
Velocity, fpm
fpm
Velocity,

14

38

12

34

11/4

11/2

247

251

255

262

270

277

285

300

315

1.3

2.5

4.0

7.3

12

22

30

52

78

- 121 -

10

12

330

360

390

420

480

540

600

127

238

405

630

1250

2210

3490

SIZING DIFFERENTIAL
REGULATORS

SIZING DIFFERENTIAL PRESSURE REGULATORS

SELECTING BACK
PRESSURE PILOTS

SELECTING BACK PRESSURE PILOTS


Any of the Main Valves described in the Main Valve Section can
be combined with any of the Pilots listed below to produce the
SPENCE Back Pressure Regulator. Provided the delivery (discharge) pressure is sufficiently below the desired back pressure
to operate the Regulator, it will maintain a steady back pressure
regardless of fluctuations in the load. The Pilot is guaranteed to
shut tight when the back pressure falls below a predetermined

setting. The table below lists the principal Back Pressure Pilots.
THE SPENCE BACK PRESSURE REGULATOR IS NOT A
SAFETY VALVE AND SHOULD NEVER BE USED AS SUCH.
The discharge pressure must always be low enough in relation
to the back pressure to provide the required minimum differential listed in the Main Valve Selection Chart in the Technical
Reference Section.

BACK PRESSURE REGULATOR PILOTS


Type

Service Conditions
Cast Iron

Cast Steel

Diaphragm

Main Valve

Delivery Pressure

Maximum Maximum Maximum Maximum


Normal
Initial
TemperInitial
TemperAccuracy
Pressure ature Pressure ature Minimum Maximum
Diameter
psi
F
psi
F
psi
psi

inches

Material

150

366

150

366

150

1 psi

31/2

St. Stl.

E or C Series

Q2

250

450

600

750

100

400

2 psi

31/2

St. Stl.

E or C Series

Q73

150

366

150

366

150

/2 psi

3 /2-7 /

St. Stl.

E or C Series

F14

250

450

600

750

150

1 psi

412

St. Stl.

E or C Series

F13

250

450

600

750

100

300

2 psi

3 2

St. Stl.

E or C Series

F15

250

450

600

750

25

1/2 psi

534

St. Stl.

E or C Series

F32

250

450

600

750

200

2000

10 psi

8 piston

St. Stl.

E or C Series

1 c
4

Type Q73 is air adjusted, all others are spring loaded.


These Pilots have dual diaphragms, the first size being the control diaphragm and the second, the air loading
diaphragm.

b
c

NOTES

ON

SELECTION

OF

PILOTS

TYPE Q SERIES meet the requirements of the majority of all


back pressure problems. They are packless and spring or air loaded.
The Type Q Pilot can be furnished for service on refrigerants on
special order.
TYPE F SERIES have bellows stem seals and separate diaphragm chambers. They are designed for applications where a
regulator is required to open on rise in pressure of a fluid other

than that flowing through the regulator. Type F Series Pilots are
also recommended for usual back pressure service in the event
that long control pipes are unavoidable.
In either series of back pressure pilots, a larger Diaphragm will
produce closer accuracy of control but with less range in back
pressure.

- 122 -

DATA REQUIRED

FOR

EXAMPLE

ORDERING

(a) Maximum/Minimum.

Select size and type Regulator to pass 9000 lb steam per hour
retaining a back pressure of 5 psi and exhausting into a
condenser at 6" Hg vacuum. Pilot to be packless, spring
loaded and to control the pressure within 1/2 psi.

(b) Superheat, Gravity, etc.

1. Steam

1. SERVICE Fluid flowing though Regulator.


2. INITIAL (INLET) PRESSURE

(1) Steam ServiceTotal Temperature or Degrees


Superheat, if any.

2. (a) 5 psi

(2) Air, Gases, Water and LiquidsTemperature and


Specific Gravity.

3. 6" Hg vacuum

3. DISCHARGE (OUTLET) PRESSURE Maximum/Minimum.


4. CAPACITY Maximum required flow through Regulator.

(b) None (saturated, 228F total temperature)


4. 9000lb. per hour
5. Flanged, if 21/2" size or larger

5. END CONNECTIONS Screwed or Flanged. (If flanged,


state drilling.)

SELECTION

OF

TYPE

AND

SIZE

MAIN VALVE
A. TYPE See Selection Criteria
for Steam, Air, Gases or Water
and Liquids in beginning of this
Section.

OF

REGULATOR

PILOT
See Selection Criteria
and Selection Charts
opposite.

OF

TYPE

AND

MAIN VALVE
A. Since Initial Pressure is less
than 15 psi and the least
pressure drop exceeds
minimum differential:
SELECT TYPE E2

SIZE

OF

REGULATOR

PILOT
Since maximum Initial Pressure 5 psi, Total Temperature
228F, accuracy of control 12
psi and Pilot spring loaded:
SELECT TYPE F15

B. For 9000 lb. per hour and


5 psi Initial Pressure:
SELECT 8" SIZE.

B. SIZESee applicable Valve


Capacity Tables in this Section.
C. MATERIAL See Main Valve
Selection Chart in Technical
Reference Section or individual
Product Pages.

SELECTION

See Pilot Selection


Chart opposite or individual Product Pages.

D. ACCESSORIESSee Accessories in Other Products


Section.

C. For 5 psi, 228F:


SELECT CAST IRON,
FLANGED 125 LB.

For 5 psi, 228F:


SELECT CAST IRON

D. For discharge into vacuum:


Condensation Chamber
required.

None required in this case.

ANSWER: 8" SPENCE TYPE E2F15, CAST IRON BODY, 125 LB. FLANGED ENDS,
EQUIPPED WITH CONDENSATION CHAMBER.
NOTE: Back Pressure Regulators should always be protected by properly designed Strainers.

- 123 -

SIZING BACK PRESS.


REGULATORS

SIZING BACK PRESSURE REGULATORS

SELECTING PUMP
GOVERNOR PILOTS

SELECTING PUMP GOVERNOR PILOTS


SPENCE Pump Governors are classified in four groups as follows:
1. Constant Pressure Pump Governor which is illustrated by
the SPENCE Type EP14 Pump Governor. This Regulator
governs the steam supply to a pump, either reciprocating or
turbine-driven, and maintains a constant, adjustable pump
discharge pressure.
2. Excess Pressure Pump Governor which is illustrated by the
SPENCE Type EN Differential Pressure Regulator. Although
this Regulator is not a Pump Governor, it is recommended to
govern the steam supply to boiler feed pump where it is
desired to maintain the pump discharge pressure at a constant, adjustable differential pressure in excess of the boiler
steam pressure.

3. Vacuum Pump Governor which is illustrated by the SPENCE


Type EF46 Pump Governor. This Regulator governs the
steam supply to a vacuum pump and maintains a constant,
adjustable vacuum on the pump suction.
4.Differential Control for electric motor-driven centrifugal pumps
which is illustrated by the SPENCE Type EN Differential
Pressure Regulator. Although this Regulator is not a Pump
Governor, it is recommended to maintain a constant, adjustable differential between the feedwater pressure and the boiler
steam pressure; i.e., a constant pressure drop across the
feedwater regulator.
The table below lists the principal Pump Governor Pilots.

PUMP GOVERNOR PILOTS


Type

Service Conditions
Cast Iron

Cast Steel

Maximum Maximum Maximum Maximum


Initial
TemperInitial
TemperPressure
ature
Pressure
ature
psi
F
psi
F

Diaphragm

Main Valve

Type of Control

Pump Discharge
Pressure
Minimum
psi

Maximum
psi

Diameter
inches

Material

P13

250

450

600

750

100

300

31/2

St. Stl.

E or C Series Constant Pressure

P14

250

450

600

750

150

41/2

St. Stl.

E or C Series Constant Pressure

P15

250

450

600

750

25

53/4

St. Stl.

E or C Series Constant Pressure

P32

250

450

600

750

200

2000

7
/8
Piston

St. Stl.

E or C Series Constant Pressure

F46

250

450

600

750

30
Hg vac

41/2

St. Stl.

E or C Series

Vacuum

250

450

600

500

3b

300b

31/2

St. Stl.

E or C Series

Differentialc

Regulator discharge pressure


For electric motor driven centrifugal pump applications only, differential pressure range 3 to 150 psi

b
c

NOTES

ON

SELECTION

OF

PILOTS

P SERIES PILOTS are used for constant pressure control. In


this Series a larger Diaphragm will produce closer accuracy of
control but with less range in pump discharge pressure.
TYPE F46 is a vacuum pump governor Pilot.
TYPE N is a differential pressure Pilot which is applied to the
discharge of a constant speed centrifugal pump to effect

excess pressure control. The design of the Pilot requires that


the delivery pressure (pressure of fluid discharged from Regulator) be controlled at a given differential above some separate
source of loading pressure. In typical service, boiler feedwater
flows through the Regulator and is delivered at constant excess
pressure above the boiler steam pressure.

- 124 -

TYPE E MAIN VALVEFULL PORT


VALVE INFO
PAGE 28

Pounds of Saturated Steam per Hour


PRESSURE-psig
INLET REDUCED

VALVE SIZE (inches)


38

12

34

14

1/

1/

12

21/2

10

12

20

5-0

90

165

370

520

835

1175

1840

2610

4390

6470

10030

14715

26345

41890

66040

25

10
5-0

100
100

185
190

350
365

575
595

920
955

1290
1345

2025
2105

2870
2985

4830
5025

7115
7400

11030
11475

16185
16835

28980
30140

46080
47930

72645
75560

30

15
10-0

105
115

195
215

380
415

615
675

990
1080

1390
1515

2175
2370

3085
3365

5190
5655

7645
8330

11855
12920

17400
18955

31150
33940

49530
53965

78080
85075

40

25
20
15-0

120
135
140

220
250
260

425
480
505

695
780
825

1115
1250
1320

1565
1760
1850

2450
2755
2900

3475
3905
4115

5850
6570
6920

8615
9680
10195

13355
15005
15805

19600
22020
23195

35085
39425
41530

55790 87950
62690 98830
66035 104105

50

35
30
25
20-0

130
150
160
165

245
275
300
310

470
530
580
600

765
865
945
975

1225
1385
1515
1560

1720
1945
2125
2190

2695
3045
3325
3430

3830
4320
4720
4870

6435
7270
7940
8185

9480
10705
11695
12060

14700
16600
18130
18700

21575
24360
26605
27440

38625
43615
47635
49125

61415 96820
69350 109330
75745 119410
78110 123140

60

45
40
35
30-0

140
160
175
190

265
300
330
350

510
575
630
680

830
940
1030
1105

1330
1505
1650
1770

1865
2115
2320
2490

2925
3310
3630
3895

4150
4700
5155
5530

6975
7905
8665
9300

10280
11645
12765
13700

15935
18055
19790
21240

23385
26495
29045
31170

41865
47435
51995
55805

66570
75425
82680
88735

104945
118905
130345
139885

75

55
50
45
40-0

180
195
210
225

330
365
395
420

640
705
760
805

1045
1150
1235
1315

1670
1840
1980
2105

2350
2585
2785
2955

3675
4045
4360
4630

5215
5740
6185
6570

8775
9655
10405
11050

12925
14220
15325
16275

20040
22050
23760
25230

29405
32355
34865
37025

52645 83710
57930 92110
62420 99255
66285 105400

131970
145215
156475
166160

100

75
60
50-0

225
275
295

420
510
550

810
985
1060

1320
1610
1725

2115
2575
2765

2970
3620
3885

4655
5665
6080

6605
8045
8630

11110
13525
14515

16365
19925
21380

25370
30890
33145

37230
45330
48640

66650 105985 167080


81155 129045 203440
87085 138475 218300

125

100
75
65-0

250
335
360

470
630
670

905
1215
1290

1475
1980
2100

2360
3170
3370

3315
4455
4730

5190
6970
7405

7370
9895
10510

12395
16645
17680

18255
24515
26040

28305
38010
40370

41535 74360 118235 186400


55775 99860 158785 250320
59245 106065 168655 265880

150

125
100
80-0

275
370
425

515
695
790

990
1340
1520

1610
2185
2480

2585
3500
3970

3625
4915
5575

5680
7695
8730

8060
10920
12390

13555
18370
20840

19970
27055
30700

30960
41945
47595

45430 81340 129335 203895


61555 110205 175235 276255
69845 125045 198835 313460

175

150
125
100
95-0

295
405
475
485

555
755
890
910

1065
1455
1715
1750

1740
2370
2790
2855

2785
3800
4475
4575

3915
5335
6285
6425

6130
8355
9835
10055

8695
11860
13960
14275

14625
19945
23480
24005

21545
29375
34585
35360

33405
45545
53625
54820

49020 87765 139555 220005


66835 119660 190270 299960
78690 140880 224015 353155
80450 144030 229015 361045

200

150
125
110-0

435
515
550

810
960
1030

1560
1850
1980

2545
3015
3230

4080
4825
5175

5725
6780
7265

8965
10615
11380

12725
15065
16150

21405
25335
27160

31525
37320
40005

48880
57860
62025

71730 128420 204200 321920


84910 152015 241715 381060
91020 162960 259120 408500

225

175
150
125-0

460
550
615

860
1025
1145

1660
1975
2210

2710
3220
3600

4340
5155
5765

6095
7240
8100

9540
11335
12680

13540
16090
18000

22770
27065
30270

33540
39865
44585

52000 76310 136620 217240 342475


61810 90700 162380 258200 407055
69130 101440 181615 288785 455265

250

200
175
150
140-0

490
580
655
675

910
1085
1220
1265

1755
2095
2350
2435

2860
3410
3830
3970

4585
5465
6135
6360

6440
7675
8615
8930

10080 14305
12020 170601
13490 19145
13985 19845

24060
28690
32200
33380

35440
42255
47435
49165

54945 80630 144355


65515 96145 172130
73540 107920 193210
76230 111860 200270

Based on 10% (2 psi minimum) accuracy of regulation.

- 125 -

229540
273700
307225
318445

361865
431485
484355
502025

TYPE E FULL PORT


CAPACITY TABLE

RATED STEAM CAPACITY TABLE

TYPE E NORMAL PORT


CAPACITY TABLE

RATED STEAM CAPACITY TABLE


TYPE E MAIN VALVENORMAL PORT
VALVE INFO
PAGE 28

Pounds of Saturated Steam per Hour


PRESSURE-psig
INLET REDUCED

VALVE SIZE (inches)


38

12

34

14

1/

12

1/

21/2

10

12

20

5-0

40

90

285

445

615

865

1045

1425

2550

4630

6825

8960

14775

22370

37440

25

10
5-0

40
45

100
100

315
325

490
510

680
705

955
990

1150
1195

1565
1630

2805
2920

5090
5295

7505
7805

9855
10250

16250
16905

24605
25595

41185
42835

30

15
10-0

45
50

105
115

335
365

525
575

730
795

1025
1115

1235
1345

1685
1835

3015
3285

5470
5960

8070
8790

10595
11540

17470
19035

26450
28815

44265
48230

40

25
20
15-0

50
60
60

120
135
140

380
425
450

595
665
700

820
925
975

1155
1295
1365

1390
1565
1645

1895
2130
2245

3400
3820
4020

6165
6925
7295

9090
10210
10755

11930
13410
14125

19675
22110
23290

29790
33475
35265

49865
56030
59020

50

35
30
25
20-0

55
65
70
70

130
145
160
165

420
470
515
530

650
735
805
830

905
1020
1115
1150

1270
1435
1565
1615

1530
1730
1890
1945

2090
2360
2575
2655

3740
4225
4615
4755

6785
7660
8370
8630

10005
11295
12340
12725

13135
14835
16200
16705

21660
24460
26715
27550

32795
37035
40445
41710

54890
61985
67695
69810

60

45
40
35
30-0

60
70
75
80

140
160
175
190

455
515
560
605

705
800
880
945

980
111
1220
1305

1375
1560
1710
1835

1660
1880
2060
2210

2265
2565
2810
3015

4055
4595
5035
5405

7355
8335
9135
9805

10845
12285
13470
14455

14240
16130
17685
18980

23480
26600
29160
31295

35545
40275
44150
47385

59495
67410
73895
79305

75

55
50
45
40-0

75
85
90
95

180
195
210
225

570
625
675
715

890
980
1055
1120

1235
1355
1460
1555

1730
1905
2055
2180

2085
2295
2475
2630

2845
3130
3375
3585

5100
5610
6045
6420

9250
10175
10965
11645

13635
15005
16170
17170

17905
19700
21230
22545

29525
32485
35005
37175

44700
49185
53005
56285

74820
82325
88710
94205

100

75
60
50-0

100
120
125

225
275
295

720
875
940

1125
1370
1470

1560
1900
2040

2190
2670
2865

2640
3215
3450

3605
4385
4705

6455
7860
8435

11710
14255
15300

17265
21020
22555

22670
27600
29615

37380
45515
48840

56595 94725
68910 115335
73945 123760

125

100
75
65-0

110
145
155

250
335
360

805
1080
1145

1255
1685
1790

1740
2340
2485

2445
3285
3490

2950
3960
4205

4020
5400
5735

7200
9670
10270

13065
17545
18635

19260
25865
27470

25290
33960
36070

41700
56000
59485

63140 105675
84790 141915
90060 150740

150

125
100
80-0

120
160
185

275
370
420

880
1190
1350

1375
1860
2110

1905
2580
2930

2675
3625
4110

3225
4370
4955

4395
5955
6760

7875
10675
12110

14290
19360
21970

21065
28545
32390

27660
37480
42525

45615 69065 115595


61805 93575 156620
70130 106175 177715

175

150
125
100
95-0

130
175
205
210

295
405
475
485

950
1295
1525
1555

1485
2020
2380
2435

2055
2805
3300
3375

2885
3935
4635
4735

3480
4745
5585
5710

4745
6470
7615
7785

8500
11590
13645
13950

15420
21020
24750
25300

22730
30995
36490
37305

29850
40695
47915
48980

49220 74520 124730


67105 101605 170055
79010 119625 200215
80770 22295 204690

200

150
125
110-0

190
225
240

435
515
550

1390
1645
1760

2170
2570
2755

3010
3560
3815

4225
5000
5360

5090
6025
6460

6940
8215
8810

12435
14720
15780

25560
26708
28630

33260
39375
42210

43675
51700
55420

72020 109040 182510


85250 129075 216035
91390 138370 231595

225

175
150
125-0

200
240
265

460
550
615

1475
1755
1965

2310
2745
3070

3200
3805
4255

4495
5340
5970

5415
6435
7200

7385
8775
9815

13230
15725
17590

24000
28525
31905

35385
42060
47040

46465 76620 116005 194160


55225 91065 137880 230775
61765 101850 154210 258105

250

200
175
150
140-0

210
250
285
295

490
580
655
675

1560
1860
2090
2165

2440
2910
3265
3385

3380
4030
4525
4690

4745
5660
6355
6585

5720
6825
7660
7940

7805
9305
10445
10825

13980
16670
18710
19395

25360
30240
33945
35180

37390
44585
50045
51870

49095 80955 122575


58540 96530 146155
65710 108355 164055
68110 112315 170050

Based on 10% (2 psi minimum) accuracy of regulation.

- 126 -

205155
244625
274585
284615

TYPE E2 MAIN VALVE


VALVE INFO
PAGE 30

Pounds of Saturated Steam per Hour


PRESSURE-psig
INLET REDUCED

VALVE SIZE (inches)


34

14

1/

1/

12

/4

1
11/4
11/2
2
21/2
3
4
5
6
8
10
12

21/2

10

12

15

12
10
8
5
2.5

150
245
295
345
375

230
375
455
530
575

375
605
735
860
930

545
880
1070
1245
1345

875
1415
1715
2000
2160

1350
2185
2650
3085
3340

1905
3085
3740
4360
4715

2840
4595
5570
6495
7025

4010
6490
7870
9170
9925

5060
8195
9935
11580
12530

9230
14945
18120
21110
22850

14850
24040
29145
33960
36755

22195
35930
43560
50760
54935

12

9
7
5
2

145
230
280
325

220
355
430
495

355
570
690
805

515
830
1005
1165

825
1330
1610
1870

1275
2060
2490
2890

1800
2910
3515
4080

2680
4330
5235
6075

3785
6115
7395
8585

4780
7720
9340
10835

8715
14080
17030
19760

14020
22650
27390
31785

20955
33855
40940
47510

10

7
5
2
1 HG VAC

135
220
280
310

210
340
435
480

340
550
705
775

490
795
1020
1125

790
1275
1635
1805

1220
1970
2525
2795

1725
2780
3565
3945

2570
4145
5315
5875

3630
5855
7505
8295

4580
7390
9475
10475

8355
13475
17280
19095

13440
21670
27795
30720

20090
32395
41545
45915

6
4
2
2 HG VAC

135
215
260
300

205
330
400
460

330
535
645
745

480
775
935
1080

775
1245
1500
1730

1195
1925
2320
2675

1685
2715
3275
3780

2510
4045
4880
5625

3550
5715
6890
7950

4480
7215
8700
10035

8170
13160
15865
18300

13140
21165
25515
29435

19645
31640
38140
43995

5
3
3.1 HG VAC

130
210

200
325

325
520

470
755

755
1215

1165
1875

1645
2650

2455
3950

3465
5575

4375
7040

7980
12835

12835
20650

19185
30865

285

440

710

1035

1660

2565

3620

5390

7615

9610

17530

28195

42145

4
2
4.3 HG VAC

125
205
275

195
315
420

315
510
680

460
735
985

735
1185
1585

1140
1830
2450

1605
2580
3460

2395
3845
5150

3380
5435
7275

4270
6860
9185

7785
12505
16750

12520
20120
26945

18715
30070
40275

3
1
5.5 HG VAC

125
200
260

190
305
405

310
495
650

445
715
945

720
1150
1515

1110
1780
2340

1565
2510
3305

2330
3740
4925

3295
5285
6955

4160
6675
8780

7585
12170
16010

12200
19575
25755

18235
29255
38495

2
0
6.7 HG VAC

120
195
250

185
295
380

300
480
615

435
695
895

700
1120
1435

1080
1730
2215

1525
2440
3130

2270
3635
4660

3205
5135
6485

4045
6480
8310

7380
11820
15155

11870
19010
24380

17740
28415
36440

Based on 1 psi accuracy of regulation.


K-Factor is included in the above tabulations.

Size

E2 Cv
Valve Coefficient

P
Nominal

K
Factor

7.6
11.7
18.9
27.4
44
68
96
143
202
255
465
748
1118

3
4
5
6
7
8
9
10
11
12
15

0.635
0.785
0.855
0.895
0.915
0.928
0.935
0.937
0.938
0.940
0.940

TYPE E2 MAIN VALVE ONLY


Used at such low pressure drops, a 1 psi deviation of reduced
pressure at rated capacity is a significant portion of the total
drop. It must be accounted for in calculations dealing with a
subcritical flow condition.
Also, because E2 valve opening, for 1 psi accuracy of
regulation, varies with the pressure drop, a regulation factor K
is inserted in the formula.
Cv=

W
2.1 K

Where

P(P1 +P2)

K = Factor from accompanying table


Cv = Valve coefficient
W = Flow, #/Hr. (saturated steam)
P = P nominal plus 1 psi
P1 = Inlet pressure, psia (psi + 14.7)
P2 = Reduced pressure, psia (psi + 14.7)
P2 = P2 nominal (set point value) minus 1 psi
P = Pressure drop, psi

NOTE: When computing W for safety valve sizing, use K = 1.0

- 127 -

TYPE E2
CAPACITY TABLE

RATED STEAM CAPACITY TABLE

TYPE E5 FULL PORT


CAPACITY TABLE

RATED STEAM CAPACITY TABLE


TYPE E5 MAIN VALVEFULL PORT
VALVE INFO
PAGE 32

Pounds of Saturated Steam per Hour


PRESSURE-psig
INLET REDUCED

VALVE SIZE (inches)


34

11/4

11/2

21/2

10

12
60708
82453
95592

20

15
10
5.4

286
389
451

441
599
694

712
967
1121

1033
1402
1626

1620
2201
2551

2525
3429
3976

3580
4862
5637

5992
8138
9435

9722
13205
15309

13189
17914
20768

25059
34036
39459

38361
52103
60405

25

20
15
10
8.3

308
420
496
516

474
647
764
794

766
1046
1234
1283

1110
1516
1788
1860

1742
2379
2807
2919

2714
3707
4373
4548

3848
5256
6201
6449

6440
8796
10378
10794

10450
14273
16839
17515

14176
19363
22844
23760

26935
36789
43404
45145

41232 65251
56318 89124
66444 105149
69109 109366

30

25
20
15
11.2

328
450
533
581

505
692
821
894

815
1118
1326
1445

1182
1621
1922
2094

1855
2544
3017
3287

2890
3965
4700
5121

4098
5622
6665
7262

6859
9409
11154
12153

11130
15267
18100
19721

15099
20711
24554
26753

28688
39351
46652
50831

43916 69498
60239 95329
71417 113018
77813 123140

40

35
30
25
17

365
503
601
711

561
775
925
1094

907
1251
1494
1768

1315
1814
2165
2563

2063
2847
3398
4022

3215
4436
5295
6267

4558
6290
7507
8886

7629
10527
12565
14872

12379
17082
20388
24133

16793
23173
27658
32738

31906
44029
52550
62202

48843 77295
67400 106662
80445 127305
95221 150688

50

45
40
35
22.8

398
551
661
841

613
849
1018
1294

990
1371
1644
2091

1435
1988
2384
3031

2252
3120
3741
4757

3509
4862
5828
7413

4976
6894
8264
10511

8327
11538
13832
17591

13512
18722
22444
28544

18331
25397
30447
38723

34829 53317 84374


48255 73870 116901
57849 88558 140144
73574 112628 178236

75

70
65
60
37.3

471
657
793
1166

726
1011
1220
1795

1172
1634
1971
2899

1699
2368
2857
4203

2667
3717
4484
6596

4155
5791
6987
10277

5891
8211
9907
14572

9860
13743
16581
24389

15999
22300
26905
39574

21704 41238 63128 99902


30251 57477 87988 139242
36499 69349 106161 168001
53685 102002 156148 247106

100

95
90
85
51.8

535
748
905
1491

823
1151
1393
2295

1329
1859
2251
3707

1927
2695
3263
5374

3025
4230
5121
8434

4713
6590
7979
13141

6683
9345
11314
18633

11184
15640
18935
31186

18148
25378
30725
50603

24620 46778 71608 113321


34428 65412 100135 158465
41682 79195 121234 191855
68648 130431 199667 315977

125

120
115
110
90
66.3

591
828
1005
1476
1816

910
1275
1547
2272
1751

1470
2060
2500
3671
191

2131
2987
3624
5322
7874

3345
4687
5687
8352
12019

5212
7303
8861
13013
19297

7390
10355
12564
18451
27890

12368
17331
21028
30882
43660

20069
28121
34120
50110
67921

27225 51727 79185


38149 72484 110960
46287 87946 134630
67979 129159 197720
96226 160923 261002

125312
175596
213055
312896
354004

150

145
140
135
110
80.8

643
902
1096
1717
2140

990
1389
1687
2644
2075

1598
2243
2726
4270
191

2317
3252
3951
6191
8545

3637
5103
6201
9716
13051

5667
7952
9662
15138
20965

8035
11275
13700
21465
30308

13448
18871
22930
35925
47454

21820 29601 56243 86098


30620 41539 78924 120819
37207 50475 95902 146809
58293 79080 150252 230010
73834 104610 174955 283770

136251
191198
232328
363994
384891

175

170
165
160
125
95.3

691
970
1180
2048
2465

1063
1493
1817
3153
2400

1717
2412
2934
5094
191

2490
3497
4254
7384
9165

3907
5488
6676
11589
14007

6088
8552
10402
18057
22508

8632
12125
14750
25603
32545

14447
20294
24686
42851
50966

23442 31801 60422 92495 146375


32930 44672 84877 129932 205619
40057 54340 103247 158053 250121
69532 94327 179221 274356 434172
79306 112368 187941 304841 413476

200

195
185
150
109.8

735
1258
2198
2790

1132
1937
3384
4296

1828
3129
5467
6939

2651
4537
7925
10060

4160
7119
12437
15787

6481
11093
19379
24598

9190
15729
27477
34878

15381
26325
45989
58375

24958 33858 64330 98478 155843


42716 57949 110102 168548 266729
74623 101233 192342 294443 465960
94721 128498 244146 373745 591458

250

245
235
200
138.8

817
1402
2471
3440

1258
2158
3804
5296

2032
3486
6145
8555

2946
5054
8908
12402

4624
7932
13980
19463

7205
12359
21784
30327

10215
17524
30887
43001

17098 27743 37636 71508


29330 47592 64563 122670
51695 83883 113795 216210
71969 116780 158423 301004

Based on 10% (2 psi minimum) accuracy of regulation.

- 128 -

109467
187786
330979
460784

173233
297174
523780
729198

TYPE E5 MAIN VALVENORMAL PORT


VALVE INFO
PAGE 32

Pounds of Saturated Steam per Hour


PRESSURE-psig
INLET REDUCED

VALVE SIZE (inches)


3

/4

11/4

11/2

21/2

10

12

20

15
10
5.4

215
292
338

377
512
593

505
686
795

746
1013
1175

942
1280
1483

1319
1791
2077

2223
3020
3501

4522
6142
7120

6632
9008
10443

8592
11669
13529

12662
17197
19937

19784
26870
31152

35874
48725
56489

25

20
15
10
8.3

231
315
372
387

405
553
653
679

543
741
875
910

802
1095
1292
1344

1013
1383
1632
1697

1418
1936
2284
2376

2390
3264
3851
4005

4860
6639
7832
8146

7129
9737
11487
11948

9235
12613
14881
15478

13609
18588
21930
22810

21264
29044
34266
35641

38559
52667
62136
64628

30

25
20
15
11.2

246
337
400
436

431
592
702
764

578
793
940
1024

854
1172
1389
1513

1078
1479
1754
1911

1510
2071
2455
2675

2545
3491
4139
4510

5177
7101
8418
9172

7593
10415
12347
13453

9836
13492
15995
17428

14495
19882
23572
25683

22648
31066
36831
40129

41069
56333
66786
72768

40

35
30
25
17

273
377
450
533

480
662
790
935

643
887
1059
1253

950
1311
1565
1852

1199
1655
1976
2338

1679
2317
2766
3274

2831
3906
4662
5519

5758
7945
9483
11224

8444
11653
13908
16463

10939
15095
18017
21326

16121
22246
26552
31428

25189
34759
41487
49107

45676
63030
75229
89047

50

45
40
35
22.8

299
414
496
631

524
726
870
1106

702
972
1166
1483

1037
1437
1722
2191

1309
1814
2175
2766

1833
2540
3045
3872

3090
4281
5133
6528

6285
8708
10439
13276

9218
12771
15311
19472

11941
16545
19834
25225

17598
24382
29229
37174

27496 49860
38096 69081
45671 82816
58084 105326

75

70
65
60
37.3

353
493
594
874

620
864
1043
1534

831
1158
1397
2055

1228
1711
2065
3037

1550
2161
2607
3835

2170
3025
3650
5369

3659
5100
6153
9050

7441
10372
12514
18406

10914
15212
18354
26996

14139
19707
23777
34972

20836
29041
35039
51538

32556 59036
45377 82284
54749 99278
80528 146024

100

95
90
85
51.8

401
561
679
1118

703
984
1191
1961

943
1318
1596
2628

1393
1948
2358
3884

1759
2459
2977
4903

2462
3443
4168
6865

4150
5803
7026
11572

8441
11804
14291
23536

12380
17312
20960
34520

16038
22427
27153
44719

23635 36930 66966


33050 51641 93643
40014 62523 113374
65902 102972 186722

125

120
115
110
90
66.3

443
621
754
1107
1362

778
1090
1322
1942
1313

1042
1461
1772
2603
143

1540
2158
2619
3846
4465

1945
2725
3306
4856
7725

2722
3815
4629
6798
10303

4589
6431
7803
11459
15155

9334
13080
15870
23307
19098

13690
19184
23276
34184
26679

17735
24852
30153
44283
44875

26136 40837 74051


36623 57224 103766
44436 69431 125902
65259 101968 184902
91124 133581 173006

150

145
140
135
110
80.8

482
676
822
1288
1605

846
1187
1442
2259
1557

1133
1590
1932
3028
143

1675
2350
2855
4474
4842

2114
2967
3605
5649
8387

2960
4154
5047
7908
11190

4990
7002
8509
13331
16466

10149
14242
17306
27113
20752

14885
20888
25382
39766
28996

19283
27060
32881
51515
48780

28417 44402 80516


39877 62308 112986
48456 75712 137291
75917 118620 215098
99066 145230 188097

175

170
165
160
125
95.3

518
728
885
1536
1849

909
1276
1553
2695
1800

1218
1710
2080
3611
143

1799
2527
3074
5336
5191

2271
3191
3881
6738
8999

3180
4467
5434
9433
12010

5361
7530
9160
15901
17678

10903
15316
18631
32341
22284

15991
22464
27325
47433
31140

20716 30529 47701 86499


29101 42885 67008 121508
35399 52167 81510 147806
61447 90554 141490 256568
52394 106417 156011 202063

200

195
185
150
109.8

551
944
1649
2093

967
1656
2892
3671

1296
2219
3876
4920

1915
3278
5727
7269

2418
4139
7231
9178

3386
5795
10123
12850

5707
9768
17065
21661

11608
19868
34708
44056

17026
29140
50906
64616

22056 32504 50787 92093


37749 55631 86923 157620
65946 97183 151849 275353
83707 123358 192747 349514

250

245
235
200
138.8

613
1051
1853
2580

1075
1845
3251
4526

1441
2472
4357
6065

2129
3652
6438
8962

2688
4612
8128
11316

3764
6456
11379
15842

6344
10883
19183
26706

12904
22136
39015
54316

18926 24517 36131 56454


32466 42058 61980 96844
57222 74129 109243 170692
79664 103201 152086 237634

Based on 10% (2 psi minimum) accuracy of regulation.

- 129 -

102370
175611
309521
430910

TYPE E5 NORMAL
PORT CAPACITY TABLE

RATED STEAM CAPACITY TABLE

TYPE C20
CAPACITY TABLE

RATED STEAM CAPACITY TABLE


TYPE C20 MAIN VALVE
AVAILABLE ON SPECIAL ORDER ONLY CONSULT FACTORY

Pounds of Saturated Steam per Hour


PRESSURE-psig
INLET REDUCED

VALVE SIZE (inches)


1

11/4

11/2

21/2

10

12

25

5-0

510

950

1360

2035

3190

4685

7805

12625

16970

29600

47520

73520

30

10-0

575

1070

1530

2295

3595

5275

8790

14215

19110

33325

53505

82780

40

20
15-0

665
700

1245
1310

1775
1870

2665
2805

4175
4395

6125
6455

10210
10755

16515
17400

22200
23385

38715
40780

62160 96170
65475 101300

50

30
25
20-0

735
805
830

1375
1500
1550

1965
2145
2215

2945
3220
3320

4615
5040
5200

6780
7405
7635

11295
12340
12725

18270
19955
20580

24555
26820
27660

42830
46775
48240

68760 106385
75100 116190
77445 119820

60

40
35
30-0

800
880
945

1495
1640
1760

2135
2340
2515

3205
3515
3770

5020
5505
5905

7370
8080
8670

12285
13470
14455

19870
21785
23375

26710
29280
31420

46580
51060
54800

74780 115700
81980 126830
87980 136115

75

55
50
45
40-0

890
980
1055
1120

1660
1825
1970
2090

2370
2610
2810
2985

3555
3915
4220
4480

5575
6130
6610
7015

8180
9000
9700
10300

13635
15005
16170
17170

22055
24270
26150
27770

29645
32620
35150
37325

51695 83000
56885 91330
61295 98415
65090 104505

100

75
60
50-0

1125
1370
1470

2100
2560
2745

3000
3655
3925

4505
5485
5885

7055
8590
9220

10360
12610
13535

17265
21020
22555

27920
34000
36480

37530
45695
49035

65450 105080 162575


79695 127950 197955
85515 137295 212415

125

100
75
65-0

1255
1685
1790

2345
3150
3345

3350
4500
4780

5025
6745
7165

7870
10570
11230

1555
15520
16485

19260
25865
27470

31150
41835
44435

41870 73020 117230 181375


56225 98060 157435 243575
59720 104155 167220 258715

150

125
100
80-0

1375
1860
2110

2565
3475
3945

3665
4965
5635

5495
7445
8450

8610
11665
13235

12640
17125
19435

21065
28545
32390

34075
46165
52385

45800 79875 128235 198400


62050 108220 173745 268810
70410 122795 197145 305015

175

150
125
100
95-0

1485
2020
2380
2435

2765
3775
4440
4540

3955
5390
6345
6490

5930
8085
9520
9730

9290
12665
14915
15245

13640
18595
21895
22385

22730
30995
36490
37305

36765
50130
59020
60335

49415 86185 138310 214075


67375 117505 188655 291875
79325 138345 222110 343640
81095 141435 227070 351310

200

150
125
110-0

2170
2570
2755

4050
4795
5140

5785
6845
7340

8675
10270
11010

13595
16090
17250

19955
23625
25325

33260
39375
42210

53800
63680
68265

72310 126105 202465 313245


85595 149275 239660 370790
91755 160025 256920 397490

225

175
150
125-0

2310
2745
3070

4310
5120
5725

6155
7315
8180

9230
10970
12270

14460
17190
19225

21230
25235
28225

35385
42060
47040

57235 76925 134160 215395 333245


68025 91430 159455 256010 396080
76080 102260 178340 286330 442995

250

200
175
150
140-0

2440
2910
3265
3385

4550
5425
6090
6315

6505
7755
8705
9020

9755
11630
13055
13530

15280
18220
20455
21200

22435
26750
30025
31125

37390
44585
50045
51870

60475 81280 141755


72110 96920 169025
80940 108790 189730
83895 112765 196660

Based on 10% (2 psi minimum) accuracy of regulation.

- 130 -

227590
271375
304615
315740

128410
141300
152260
161685

352115
419855
471280
488495

TYPE C34 WATER


CAPACITY CHART

RATED WATER CAPACITY CHART


TYPE C34 PILOT OPERATED MAIN VALVE
(Specific Gravity of 1)

VALVE INFO
PAGE 38

200

PRESSURE DROP PSI

90
80
70
60
50
40

30

20

10

20

30

40

50

60

80

100

200

300

400

600

800

1000

1500

FLOW IN GALLONS PER MINUTE

VALVE SIZE SELECTION

EXAMPLE

Prior to selecting valve size, the maximum required flow and


the pressure drop across the valve must be determined. Enter
the Capacity Chart at the maximum required flow GPM and
follow vertically to the intersection of the horizontal pressure
drop line. The valve size nearest to, but to the right of this
intersection is the smallest valve that will satisfy the flow
requirements.
The vertical portion of the curves indicate the flow at which
approximately 15 feet per second velocity is reached. By
selecting the next larger size valve, a lower velocity may be
maintained. For general service, 8 to 10 feet per second is
recommended.

Required maximum flow is 100 GPM, Inlet Pressure is 60 psi,


Delivery Pressure is 35 psi (Pressure drop is 25 psi). Enter the
Capacity Chart at the 100 GPM line and follow up to 25 psi
pressure drop. It falls to the right of the 11/2" valve size line,
therefore 2" is the minimum valve size required.

- 131 -

TYPE N6 & D34 WATER


CAPACITY TABLES

RATED WATER CAPACITY CHART


TYPE N6 DIFFERENTIAL PRESSURE VALVE
(Specific Gravity of 1)
34

/"

VALVE INFO
PAGE 98

11/4"

1"

11/2"

2"

100
90
80
21/2"

70
60

PRESSURE DROP PSI

50

40

30

20

10
15

20

30

40

50

60

70

80

90

100

150

200

250

300

FLOW IN GALLONS PER MINUTE

RATED WATER CAPACITY TABLE


TYPE D34 VALVE
Water in GPM
PRESSURE

VALVE SIZE (inches)


14

12

DROPpsig

1/

1/

21/2

5
10
15
20
30
50
75
100
125
150
175

7.4
10
13
15
18
23
29
33
37
40
44

17
24
29
33
41
53
65
75
84
92
100

23
33
40
47
51
74
90
104
116
127
138

32
45
55
64
79
102
125
144
161
176
190

48
68
84
97
118
153
187
216
241
265
285

71
101
124
143
175
226
277
320
358
392
423

116
164
201
233
285
368
450
520
581
637
688

188
266
325
376
460
594
727
840
939
1029
1111

263
373
457
528
646
834
1022
1180
1320
1445
1560

- 132 -

400

500

GENERAL CONSIDERATIONS

EXAMPLE

When sizing a water valve, the following points should be


considered:

SPECIFIED CONDITIONS
Initial Pressure
Reduced No Flow Pressure
Capacity Required
Allowable Droop

(a) The recommended velocity in the pipe (8-10 ft./sec.)


(b) The droop which is the fall-off pressure below the no flow
pressure setting.

100 PSIG
50 PSIG (lock-up pressure)
30 GPM
10-15 PSIG

1. Enter Capacities vs. Droop Chart, below, at 30 GPM. Move


up until you intersect a curve line (possibly more than one
curve). e.g. points (a), (b)etc.

FLOW VS. VELOCITY CHART


(Specific Gravity of 1)

The lowest point indicates the minimum size valve required


(3/4") at a droop of approximately 16 psi.

500
400

2"
200

11/2"

FLOW IN GALLONS PER MINUTE

=
=
=
=

11/4"
100
80

2. Enter Flow vs. Velocity Chart (left) at 30 GPM and move up


until you reach the 3/4" pipe size curve. Move downward and
note that the velocity is approximately 18.5 ft./sec., which is
unacceptably high.
At the point of intersection of 30 GPM with the next valve
curve (1"), the velocity will be approximately 11 ft./sec.,
which is closer to the recommended value.

1"

60

/4"

40

Referring back to the Capacities vs. Droop Chart, you will


find that the droop for a 1" valve is only 11 psig, which is also
more acceptable.

/2"

20

SELECT A 1" TYPE D36


10
8

NOTE: The capacities shown in the Capacities vs. Droop


Chart are based on a difference of 50 psig or more between
the initial pressure and the regulator lock-up pressure.
Where this difference is less than 50 psig, deduct 20% from
the capacity obtained.

SCHEDULE 40 PIPE SIZE

6
4

0
5

10

15

20

25

VELOCITY FT./SEC.
VALVE INFO
PAGE 104

CAPACITIES VS. DROOP CHART


0

DROOP PSIG

5
10

15

20

/"

/"

1 2

10

20

3 4

30

40

11/4"

1"

50

60

70
80
90
100
GALLONS PER MINUTE

- 133 -

11/2"

110

120

130

2"

140

150

160

170

SIZING D36 WATER


PRESSURE VALVE

SIZING D36 WATER PRESSURE REDUCING VALVE

TYPE D50
CAPACITY TABLE

RATED STEAM, AIR AND WATER CAPACITY TABLE


TYPE D50 DIRECT ACTING PRESSURE REGULATOR
VALVE SIZE
CV
PSI

1 2

IN
10
20
30
40
50
75
100
125
150
175
200
250
60
75
85
100
125
150
175
200
250
85
100
125
150
175
200
225
250
110
125
150
200
225
250
135
150
175
200
225
250
160
175
200
225
250

A
14
23
35
29
43
72
98
105
145
170
195
240
38
63
77
96
125
155
180
205
260
44
72
110
140
170
200
225
250
65
105
155
235
275
310
70
115
165
210
255
295
105
145
195
240
280

OUT S
5
41
10
68
10 100
87
130
200
255
30 315
370
425
480
595
115
190
230
280
50 340
405
465
525
650
130
215
325
75 405
465
525
585
650
190
310
460
100 675
755
830
210
340
500
125 635
755
830
315
425
140 580
710
835

/"
2.2

3/4"
3.3

W
3
4.2
5.9
4.2
5.9
8.8
11
13
15
16
17
20
4.6
7.2
8.5
10
12
14
16
18
20
4.6
7.2
10
12
14
16
18
19
6
9
13
19
21
23
5.9
9.3
13
16
19
21
8.3
11
14
17
19

S
59
97
145
125
185
290
370
450
530
615
695
855
165
275
335
410
500
590
675
765
945
190
315
470
590
675
765
855
945
310
500
745
1095
1220
1350
340
550
810
1030
1230
1350
510
690
940
1150
1350

A
20
33
50
42
63
105
140
175
210
245
280
350
55
92
110
140
185
225
265
305
380
64
105
160
205
245
290
330
370
105
170
250
385
445
505
115
185
270
345
410
475
170
230
315
385
455

W
4.2
6.0
8.5
6.0
8.5
13
16
19
21
23
25
28
6.6
10
12
15
18
21
23
26
30
6.6
10
15
18
21
23
26
28
9
15
21
30
34
37
9.5
15
21
26
30
34
13
18
23
28
31

S
80
130
195
170
250
390
495
605
715
825
930
1150
250
420
510
625
760
895
1030
1170
1440
290
480
720
895
1030
1170
1300
1440
380
620
920
1350
1510
1670
420
680
995
1270
1510
1670
630
855
1160
1420
1670

1"

11/4"

4.9

5.0

A
27
44
67
57
84
140
190
240
285
330
375
470
85
140
170
215
280
340
400
460
580
98
160
240
310
375
440
500
560
125
210
310
475
550
620
140
225
335
425
505
585
210
285
390
475
560

W
5.7
3.1
11
8.1
11
17
21
25
28
31
33
38
10
16
19
23
28
32
36
39
45
10
16
23
28
32
36
39
42
12
19
26
37
41
45
12
19
26
32
37
41
17
22
29
34
39

S Steam (#/hr.)
A Air (SCFM)
W Water (GPM)

- 134 -

S
91
150
220
190
285
440
565
690
810
935
1060
1305
260
430
525
645
785
925
1065
1205
1485
300
495
740
925
1065
1205
1345
1485
400
655
970
1430
1590
1760
440
715
1050
1340
1500
1760
665
900
1220
1500
1760

A
30
50
76
64
95
160
215
270
325
375
430
535
87
145
175
220
290
350
415
475
595
100
165
250
320
390
455
515
580
135
220
325
500
580
655
150
240
350
450
535
615
225
300
410
505
590

11/2"
10.1
W
6.5
9.2
13
9
13
19
24
28
32
35
38
43
10
17
20
23
29
33
37
40
47
10
17
23
29
33
37
40
44
12
20
28
39
44
48
12
20
28
34
39
44
17
23
30
36
41

S
105
170
250
250
375
580
740
900
1065
1230
1390
1710
355
585
715
875
1070
1260
1450
1640
2020
410
675
1010
1260
1450
1640
1830
2020
465
755
1120
1650
1840
2030

A
35
57
87
85
125
210
285
355
425
495
560
700
120
195
240
300
390
480
565
650
815
140
225
340
440
530
620
705
790
155
255
375
575
665
760

VALVE INFO
PAGE 96

2
10.8
W
7.4
10
15
12
17
25
32
37
42
46
50
56
14
23
27
32
39
45
50
55
65
14
23
32
39
45
50
55
60
14
23
32
45
50
55

S
120
230
290
265
395
610
780
950
1120
1290
1460
1800
395
655
800
1000
1190
1400
1620
1830
2260
455
750
1130
1400
1620
1830
2040
2250
515
840
1250
1830
2040
2250

A
40
77
100
89
130
220
295
375
445
520
590
735
130
220
270
335
435
535
630
720
905
155
250
380
485
590
685
785
880
170
280
415
640
740
840

W
8.5
14
17
13
18
27
33
39
44
48
52
60
16
25
30
35
43
50
56
61
71
16
25
35
43
50
56
61
66
16
25
35
50
56
61

EXAMPLE 1
FOR CONDITIONS

WITHIN

EXAMPLE 2
FOR CONDITIONS

CAPACITY TABLE

Given an initial steam pressure of 100 PSIG and a required flow


of 500 #/hr. at a reduced pressure of 30 PSIG, determine
droop, minimum controllable flow pressure and valve size.
In the Capacity Table opposite, the droop has been fixed at
25% of the maximum range of the adjusting spring. Therefore,
for a 30 PSIG delivery pressure, a 25-80 adjusting spring
would be selected. Thus, the droop is (25% x 80 = 20) 20 PSI.
Minimum controllable flow pressure = Reduced Pressure +
Droop = 30 + 20 = 50 PSIG
Entering the Capacity Table at a minimum controllable flow pressure (OUT) of 50 PSIG, an initial pressure (IN) of 100 PSIG, the
smallest valve size capable of delivering 500 #/hr. is the 1" size.

Given an initial steam pressure of 150 psig and a required flow


of 900 #/hr. at a reduced pressure of 25 PSIG, determine the
valve size, droop and minimum controllable flow pressure.
P2 = (25 + 14.7) = 39.7 = .24 thus P = .24P < .58P
2
1
1
P1 (150 + 14.7) 164.7
Therefore, use Critical Flow Cv formula:
W =
900
900
Cv =
=
= 3.2
1.71P1
1.71 (150 + 14.7)
1.71 (164.7)
Referring to the Cv line of the Capacity Table opposite, the 3/4"
valve size (Cv = 3.3) is the smallest valve with the required
capacity.
Droop is a function of valve size (3/4"), regulator capacity in
percent [(3.2 3.3) x 100 = 97%] and adjusting spring range
(10-30). Enter the 3/4" Valve Droop Chart (below) at 97% and
draw a line upward until you intersect the 10-30 curve. From
there , draw a line left to the vertical axis. Droop in this case is
11 PSIG.
Minimum Controllable Flow Pressure = Reduced Pressure +
Droop = 25 + 11 = 36 PSIG
Repeating the above procedure substituting a 1" valve size
with a maximum Cv of 4.9, droop would be 8 PSIG and
minimum controllable flow pressure would be 33 PSIG.

12

34

/ " VALVE DROOP CHART

/ " VALVE DROOP CHART

3-15

10

DROOP, PSIG

DROOP, PSIG

CAPACITY TABLE

OUTSIDE

10-30

15
25-80

25

3-15

10-30

10
15
25-80

25

75-140
35
10

20

30

40

50

60

70

80

90

100

10

20

30

40

50

60

70

80

90

REGULATOR CAPACITY IN PERCENT

REGULATOR CAPACITY IN PERCENT

1" & 11/4" VALVE DROOP CHART

11/2" & 2" VALVE DROOP CHART

100

3-15

10

DROOP, PSIG

DROOP, PSIG

75-140

35
0

10-30

15
25-80

25

10

20

30

40

50

3-15
10
10-40

15
25

75-140

35

30-100

35
60

70

80

90

100

REGULATOR CAPACITY IN PERCENT

10

20

30

40

50

60

70

80

REGULATOR CAPACITY IN PERCENT

- 135 -

90

100

SIZING D50

SIZING D50 DIRECT ACTING PRESSURE REGULATOR

REGULATORS

NOTES:

- 136 -