The POINT I/O ControlNet Adapter is a communications adapter for POINT I/O modules. The adapter provides an interface for controlling and communicating with POINT I/O modules from a ControlNet network.

Publication 1734-IN582B-EN-P - February 2005

Important User Information


Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Rockwell Automation office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:

Publication 1734-IN582B-EN-P - February 2005

3 Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures. Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.

WARNING

ATTENTION

IMPORTANT

BURN HAZARD

SHOCK HAZARD

Publication 1734-IN582B-EN-P - February 2005

4 Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.

ATTENTION

Publication 1734-IN582B-EN-P - February 2005

ATTENTION

Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. If available, use a static-safe workstation. When not in use, store the equipment in appropriate static-safe packaging.

ATTENTION

POINT I/O is grounded through the DIN rail to chassis ground. Use zinc-plated, yellow-chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g., aluminum, plastic, etc.) which can corrode, oxidize or are poor conductors, can result in improper or intermittent platform grounding. When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING

Publication 1734-IN582B-EN-P - February 2005

Before You Begin


To effectively use your adapter, note the following considerations.

Understand Messaging
Class 3 (Explicit Message) requests through the 1734-ACNR adapter to a specific POINT I/O module may not always receive a response from the I/O module. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a time-out.

Establish I/O Connections


When you power up a POINT I/O system and establish I/O connections, the outputs transition to the Idle state, applying Idle state data before going to RUN mode. This occurs even when the controller making the connection is already in RUN mode.

Configure Autobaud
The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the 1734-ACNR adapter.

For More Information


The following related publications are available online at URL http://literature.rockwellautomation.com.
Publication POINT I/O ControlNet Adapter User Manual POINT I/O ControlNet Adapter Release Notes Publication Number 1734-UM008 1734-RN004

Publication 1734-IN582B-EN-P - February 2005

Install the ControlNet Adapter


ATTENTION

You must use Series C Point I/O modules with the 1734-ACNR. Series A and B Point I/O modules will not work with the 1734-ACNR.

To install the adapter on the DIN rail prior to installing other base units, proceed as follows. 1. Position the adapter vertically above the DIN rail. 2. Press down firmly to install the adapter on the DIN rail. The locking mechanism will lock the adapter to the DIN rail. 3. Set the node address on the node address thumbwheel.
WARNING

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

4. Remove the safety end cap by sliding it up. This exposes the backplane and power interconnections.
ATTENTION

Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.

Publication 1734-IN582B-EN-P - February 2005

Set the Node Address


Set the node address using the 2-position thumbwheel switch. Valid settings range from 01 to 99. Press the + or - buttons to change the number.

Module Status

Network Node Address thumbwheel Press either the + or - buttons to change the number.

0 2

PointBus Status ControlNet A Status ControlNet B Status

1734-ACNR

A
System Power

Field Power

43248

Install a Replacement ControlNet Adapter to an Existing System


ATTENTION

You must use Series C Point I/O modules with the 1734-ACNR. Series A and B Point I/O modules will not work with the 1734-ACNR.

WARNING

When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

Publication 1734-IN582B-EN-P - February 2005

9 1. Remove the existing adapter from the DIN rail as follows: a. Disconnect the ControlNet connector from the adapter. b. Pull up on the RTB removal handle to remove the terminal block. c. Remove the adjacent module from its base. d. Use a small bladed screwdriver to rotate the DIN rail locking screw to a vertical position. This releases the locking mechanism. e. Lift straight up to remove 2. Remove the safety end cap on the replacement adapter by sliding it up. This exposes the backplane and power connections. 3. Position the replacement adapter vertically above the DIN rail. (Make certain the DIN rail lock is in the horizontal position.) Slide the adapter down, allowing the interlocking side pieces to engage the adjacent module. 4. Press firmly to seat the adapter on the DIN rail. The adapter locking mechanism will snap into place. 5. Set the node address on the node address thumbwheel. 6. Insert the end opposite the handle into the base unit. This end has a curved section that engages with the wiring base. 7. Rotate the terminal block into the wiring base until it locks itself into place. 8. Replace the adjacent module in its base. 9. Connect the ControlNet cable to the adapter. Use a tap to connect the adapter to the ControlNet cable. Do not directly connect the adapter to the coax cable. Publication 1734-IN582B-EN-P - February 2005

10

Wire the ControlNet Adapter


WARNING

If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.

WARNING

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Publication 1734-IN582B-EN-P - February 2005

11

Node Address

Module Status

0 2

PointBus Status ControlNet A Status ControlNet B Status

Module Status PointBus ControlNet A ControlNet B

1734-ACNR

Network

System Power Field Power

System Power Field Power

Coaxial
B

NC CHAS GND C V
43264

Coaxial NC = No Connection

12/24V

NC NC Do not connect 2 3 120/240V ac CHAS CHAS


4

C V

C V

V dc

This dc supply will be connected to NC = No Connection C=

30880

Publication 1734-IN582B-EN-P - February 2005

12

Troubleshoot with the Indicators


Module Status

Module Status PointBus Status ControlNet A ControlNet B

0 2

PointBus Status ControlNet A Status ControlNet B Status

1734-ACNR

A
System Power

Field Power

System Power Field Power


43265

Indication Field Power Off Green System Power Off Green Module Status Off Alternating Red/Green Flashing Red

Probable Cause

Not active; field power is off Power on; 24V present

Not active; field power is off or dc-dc converter problem System power on; dc-dc converter active (5V)

No power applied to device LED powerup test (module self-test) Recoverable fault has occurred: Firmware (NVS) update MAC ID changed CPU load exceeded

Publication 1734-IN582B-EN-P - February 2005

13
Solid Red Unrecoverable fault has occurred: self test failure (checksum failure at powerup, ramtest failure at powerup) firmware fatal error Flashing Green Solid Green ControlNet A/B Status Viewed Together Both Steady Off Alternating Red/Green Alternating Red/Off Both Steady Red Viewed Individually Steady Off Flashing Red/Green Flashing Red/Off Flashing Green/Off Steady Green PointBus Status Off Alternating Red/Green Flashing Red Device not powered - check module status indicator LED powerup test Recoverable fault has occurred: at power up the number of expected modules does not equal the number of modules present a module is missing node fault (I/O connection timeout) Channel disabled or channel not supported Invalid link configuration Severe Link error - link fault or no MAC frames received Temporary channel error or listen-only Normal operation - MAC frames are being received without detected errors Reset, no power or entire network interface deactivated Self test mode Bad/invalid node configuration (such as duplicate MAC ID) Failed link interface Waiting for connection or ControlNet cable break Module is operating correctly (normal mode)

Publication 1734-IN582B-EN-P - February 2005

14
Red Unrecoverable fault has occurred: The adapter is bus off The adapter has failed its duplicate MAC ID check Flashing Green Adapter on-line with no connections established adapter chassis size has not been configured controller in program/idle mode ControlNet cable break Green ControlNet A/B Status Viewed Together Both Steady Off Alternating Red/Green Alternating Red/Off Both Steady Red Reset, no power or entire network interface deactivated Self test mode Bad/invalid node configuration (such as duplicate MAC ID) Failed link interface Adapter on-line with connections established (normal operation, in run mode)

Publication 1734-IN582B-EN-P - February 2005

15

North American Hazardous Location Approval


The following information applies when operating this equipment in hazardous locations:
Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation. EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. Substitution of components may impair suitability for Class I, Division 2. If this product contains batteries, they must only be changed in an area known to be nonhazardous.

Informations sur lutilisation de cet quipement en environnements dangereux :


Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent qu une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livr avec des marquages sur sa plaque didentification qui indiquent le code de temprature pour les environnements dangereux. Lorsque plusieurs produits sont combins dans un systme, le code de temprature le plus dfavorable (code de temprature le plus faible) peut tre utilis pour dterminer le code de temprature global du systme. Les combinaisons dquipements dans le systme sont sujettes inspection par les autorits locales qualifies au moment de linstallation. AVERTISSEMENT RISQUE DEXPLOSION Couper le courant ou sassurer que lenvironnement est class non dangereux avant de dbrancher l'quipement. Couper le courant ou s'assurer que lenvironnement est class non dangereux avant de dbrancher les connecteurs. Fixer tous les connecteurs externes relis cet quipement l'aide de vis, loquets coulissants, connecteurs filets ou autres moyens fournis avec ce produit. La substitution de composants peut rendre cet quipement inadapt une utilisation en environnement de Classe I, Division 2. Sassurer que lenvironnement est class non dangereux avant de changer les piles.

WARNING

Publication 1734-IN582B-EN-P - February 2005

16

European Hazardous Location Approval


European Zone 2 Certification (The following applies when the product bears the EEx Marking) This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC. DEMKO certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No 03NK30347. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021.

IMPORTANT

Observe the following additional Zone 2 certification requirements. This equipment is not resistant to sunlight or other sources of UV radiation. The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments. Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments. This equipment shall be used within its specified ratings defined by Allen-Bradley. Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.

Publication 1734-IN582B-EN-P - February 2005

17

Specifications
Specifications - 1734-ACNR ControlNet Adapter Expansion I/O Capacity Maximum of 63 modules Maximum of 5 Rack Optimized connections (for digital modules only) Maximum of 25 Direct connections 1734-ACNR backplane current output = 1.0A maximum. See list following for backplane current consumption for each Point I/O catalog number and current consumption for each of the Point modules connected to the 1734-ACNR. Verify it is below 1.0A. Backplane current can be extended beyond 1.0A with a 1734-EP24DC Backplane Extension Power Supply. The 1734-EP24DC can supply up to an additional 1.3A of backplane current.

Multiple 1734-EP24DC modules can be used to reach the maximum of 63 modules.

Publication 1734-IN582B-EN-P - February 2005

18

Specifications - 1734-ACNR ControlNet Adapter (continued) Expansion I/O Capacity Cat. No. 1734-IB2 1734-IB4 1734-IB8 1734-IV2 1734-IV4 1734-OB2 1734-OB4 1734-OB8 1734-OB2E 1734-OB2EP 1734-OB4E 1734-OB8E 1734-OV2E 1734-OV4E 1734-OW2 1734-OX2 1734-IE2C 1734-OE2C 1734-IE2V 1734-OE2V 1734-IA2 1734-IM2 1734-OA2 1734-IJ2 1734-IK2 1734-IR2 1734-IT2I 1734-SSI 1734-232ASC 1734-VHSC5 1734-VHSC24 PointBus Current Requirements 75mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 80mA 100mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 160mA 160mA 220mA 175mA 110mA 75mA 180mA 180mA

ControlNet Communication Rate 5Mbits/s (fixed value) Module Location Starter module - left side of the 1734 system

Publication 1734-IN582B-EN-P - February 2005

19

Power Supply Specifications Input Voltage Rating Field Side Power Requirements Inrush Current Interruption 24V dc nominal 10-28.8V dc range 24V dc (+20% = 28.8V dc maximum) @ 425mA maximum 6A maximum for 10ms Output voltage will stay within specifications when input drops out for 10ms at 10V with maximum load.

General Specifications Indicators 4 red/green status indicators Adapter status PointBus status ControlNet A status ControlNet B status 2 green power supply status indicators: System Power (PointBus 5V power Field Power (24V from field supply) Power Consumption Power Dissipation PointBus Output Current Input Overvoltage Protection Thermal Dissipation Isolation Voltage Field Power Bus Nominal Voltage Supply Voltage Range Supply Current Dimensions Inches (Millimeters) 10.2W maximum @ 28.8V dc 5.0W maximum @ 28.8V 1A maximum @ 5V dc 5% (4.75 - 5.25) Reverse polarity protected 16.9 BTU/hr maximum @ 28.8V dc Tested to withstand 750Vac for 60s 24V dc 10-28.8V dc range, 10A maximum 3.0H x 2.16W x 5.25L (76.2H x 54.9W x 133.4L)

Publication 1734-IN582B-EN-P - February 2005

20

ESD Immunity Radiated RF Immunity

IEC 61000-4-2: 6kV contact discharges 8kV air discharges IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% pulse 100%AM from 900MHz IEC 61000-4-4: +4kV at 5.0kHz on power ports +2kV at 5.0kHz on communications ports IEC 61000-4-5: +1kV line-line(DM) and +2kV line-earth(CM) on power ports +2kV line-earth(CM) on communications ports IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz CISPR 11 Group 1, Class A None (open-style) 14 AWG (2.5mm2) - 22 AWG (0.25mm2) solid or stranded copper wire rated at 75oC or higher 3/64 inch (1.2mm) insulation maximum

EFT/B Immunity

Surge Transient Immunity

Conducted RF Immunity

Emissions Enclosure Type Rating Power Conductors Wire Size

ControlNet Conductors Wiring Category1,2 Terminal Base Screw Torque Mass Publications - User Manual

See Publication CNET-IN002A 1 - on power ports 2 - on communications ports 7 pound-inches (0.6Nm) 9.0 oz/255 grams 1734-UM008

Publication 1734-IN582B-EN-P - February 2005

21

Environmental Conditions Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20 to 55 C (-4 to 131 F) IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40 to 85 C (-40 to 185 F) IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5 to 95% noncondensing IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30g 50g IEC 60068-2-6 (Test Fc, Operating) 5g @ 10-500Hz

Storage Temperature

Relative Humidity Shock Operating Nonoperating Vibration

Publication 1734-IN582B-EN-P - February 2005

22
Certifications3 (when product is marked) c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada EEX European Union 94/9/EC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection n (Zone 2) CE European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR11; Industrial Emissions ControlNet Intl conformance tested to ControlNet specifications

CI
1 2 3

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Use this Conductor Category information for planning conductor routing as described int he appropriate System Level Installatin manual. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

POINT I/O is a trademark of Rockwell Automation. ControlNet is a trademark of ControlNet International.

Publication 1734-IN582B-EN-P - February 2005

23

Notes:

Publication 1734-IN582B-EN-P - February 2005

Rockwell Automation Support


Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:
United States Outside United States 1.440.646.3223 Monday Friday, 8am 5pm EST Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return


Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process. Please contact your local Rockwell Automation representative for return procedure.