Single Package

(New 50Hz, Above 5Ton)

LK5C 2004-B1

General Description
Thank you very much for your special patronage of LG air conditioners.
LGs "Roof Top or Single Package" is an ideal choice when we talk about high load applications.
As the name Roof Top signifies, this unit is generally installed on the top of the roof. Also the Single Package
signifies that both condenser and evaporator are enclosed in a single body(same as window type). The unit is
used along with ducts and has flexible air flow as per installation conditions. The air flow can be horizontal or
vertically downward which offers wider flexibility in the field applications.
Apart from common features, this unit offers some unique features like High & Low static driver kit, Oversize
motor option, Manual Hood for fresh air intake, Compact design etc.
This unit is ideal for Single story and Double story houses as they offer high static.
With its easy installation and simple controlling system, this products is suitable for Factories, Shopping malls,
Multiplex, Hotels etc.
A lot of information regarding the design & installation of this system is provided in this publication. This new
products series contains data on the same pattern.
Please utilize all the information for conducting your business efficiently.
Make sure the specification, dimension or others technical data are same as provided in enginering data book
before you start the project.
We look forward to your continuing support.

LG Electronics Inc.
Air Conditioning Division

2004 Product Data

Single Package (50Hz, Above 5 Ton)

LG Airconditioners Product Data

TABLE OF CONTENTS
Table of contents

Page

1. Models List ......................................................................................................................4


2. Model Number Nomenclature ..........................................................................................5
3. Feature & Benefits ...........................................................................................................6
4. List of Functions ...............................................................................................................9
5. Specifications ..........................................................................................................10
6. Dimensional Drawings ............................................................................................11
7. Wiring Diagrams .....................................................................................................13
8 Selection Procedure.................................................................................................14
9. Performance Data ...................................................................................................18
10. Electrical Data.......................................................................................................23
11. Refrigerant Cycle Diagrams..................................................................................24
12. Operation Range...................................................................................................25
13. Operating Space Limitations.................................................................................26
14. Function of Remote Controller ..............................................................................27
15. Mechanical Specifications.....................................................................................29
16. Appendix ...............................................................................................................30

2004 Product Data

1. Models List
1.1 Cooling Only
Nominal Capacity
Ton
30

Power Supply

Model
Refrigerant
R22

Single Package (50Hz, Above 5 Ton)

Model Name
LK-C3608H00

, V, Hz
3, 380-415V, 50Hz

2. Model Number Nomenclature

LK-C3608H00
Development Sequence
SEER Grade
Type

SEER

10

11

MICOM Control

Mechanical Control

Type of Flow
H: Horizontal
Electric Standard (Volts / Freq. / Phase)
8 : 380-415V / 50Hz / 3
Cooling / Heating Capacity
360 : 360,000 Btu/h
Model Type
C: Cooling Only
Type of Air Conditioner
LK: LG Single Package Air Conditioner

2004 Product Data

3. Features & Benefits


Cooling, Heating & Fan Operation :
- LG air conditioners can provide cooling, heating & fan operation. In the cooling mode, it cools the air with an
operation range of 18~30C. In the heating mode, it heats the air with an operation range of 16~30C. In the
fan operation mode, only indoor fan at the selected speed will run, outdoor fan and compressor will be off.

Auto Restart Operation :


- Whenever there is electricity failure the system shuts off and resumption of the power, unit will start in the
same mode as prior to the power failure. Memorized condition are on / off condition, operating mode (cooling/heating), set temperature and fan speed.

LCD Wired Remote Control :


- It can control all the functions of the unit. You can
check/set temperature, change operation mode,
set timer & also diagnose the error of the unit. It
also has the weekly program.

Two Thermistor Control(Return Air Control):(Accessory)


-There may be a significant difference between the return air temperature in the duct and the room temperature.
Return air sensing tempeaturee is designed to control temperature more accurately by applying additional thermistor which senses the return air temperature inside the duct specially.
After selecting the duct thermistor, which is connected to the main PCB, the room temperature measurement
by LCD wired remote control thermistor is neglected. It helps to control the room temperature more accurately.(Thermistor is a field-installed accessory)

Group Control :

........

- It enables to control max of 16 units with the help of


one wired remote controller. All the units will follow
same setting of temperature & other sub functions.
........

Single Package (50Hz, Above 5 Ton)

16

3. Features & Benefits


Child Lock Function :
- It prevents the children or others from tampering
with the control buttons. Unit can be controlled by
the wireless remote controller.This can be easily set
by
pressing
timer
key
&
Min
key
simultaneously.After child lock is set, by pressing
any key CL will be displayed on the LCD for 3 seconds and all the keys are ineffective.
CHILD LOCK
-Display

Time Delay Safety Function :


- It delays restarting of the compressor by three minutes thereby preventing damage to the compressor .

Self Diagnosis Function :


- This function provides diagnosis of the unit. An error code will be displayed on the LCD wired remote controller & diagnosis can be done as per the code indication.The same is also printed on key cover of the LCD
wired remote controller.

Central Control :(Accessory)


- It enables to control 16 x 8 = 128 units with the help
of 8 controllers. All units can be put on and off from
one Central Room.For Setting Temperature, Fan
Speed and other sub functions, access the LCD
wired remote controller of each unit.

Main
PCB

M
1

M
2

M
16

M
17

M
18

M
128

Sub
1

Sub
2

Sub
16

Sub
17

Sub
18

Sub
128

Controller
#1

Controller
#2

Controller
#8

Zone Control :(Accessory)


- It controls the temperature of each zone. Opening or
closing of the damper is controlled by sensing the temperature of each zone.In the cooling mode, if the temperature of a particular zone is lower than set temperature then the damper is closed. On the other hand, if
the temperature of a particular zone is higher than the
set temperature damper is open to provide cooling to
the zone and vice versa in the heating mode.

Zone A

Zone C

Zone B

Zone D

2004 Product Data

3. Features & Benefits


Electronic Thermostat:(Accessory)
Room Temp

- It provides on/off timer up to 24 hours. Also self-diagnose the


problem.

Set Temp
Cool
Heat

System

System

Fan

Heater

Timer

Auto
On

Weekly Program :

Auto
On

Fan
Heater

On/Off

Timer

- It provides on / off schedule of operation for a period of one


week.

Wireless Remote Control:(Accessory)


- It provides ease of control.

Electric Heater:(Accessory)
- Electric Heater can be used to provide heat in addition to cycle
heat. It also provides quick heating. It can also work as a stand
alone heater with only fan operation.

Fire Alarm Function:


- By purchasing a fire alarm locally, installation of the fire alarm is
possible.In case of any fire, alarm will sound and the unit will be
completely stopped.

Energy Saving Gold Fin:(Optional)


- Outdoor Heat Exchanger fins are coated with anticorrosive &
hydrophilic layers. It prevents the corrosion of heat exchanger.
Fins remains as new even after long time and maintains efficiency of heat exchanger. Saves power & maintenance Cost.

Soft Start Function:


- All single package air conditioners has soft start function i.e.
Indoor fan, outdoor fan & compressor start in sequence to prevent overcurrent during starting.

Single Package (50Hz, Above 5 Ton)

Uncoated Aluminum

Gold fin

Pitting Corrosion
10mm

10mm

Salt Spray Test Result : After 360 hours


[ Test Standard: ASTM B-117, KS D 9502 ]

4. List of Functions
Model No.
Features
Cooling & Fan Operation
Cooling, Heating & Fan Operation
Auto Restart Operation
LCD Wired Remote Control
Two Thermistor Control
Group Control
Child Lock Function
Defrost/Deicing
Hot Start Function
Time Delay Relay
Self Diagnosis Function
Central Control
Zone Control
Electronic Thermostat
Wireless Remote Control
Weekly Program
Electric Heater
Fire Alarm Function
Energy Saving Gold Fin
Anti Fungus Filter
Notes:
O: Basic
Optional: Factory-installed

LK-C3608H00
O
O
O
Accessory
O
O
O
O
Accessory
Accessory
Accessory
Accessory
O
Accessory
O
Optional
O
Accessory: Field-installed
-: Not available on this system

2004 Product Data

5. Specifications
Table-1
Nominal ton
Models

(Ton)
Gross Caapctiy

Cooling Capacity

Heating Capacity

Electrical Data

Net Capacity
Net Capacity
Power Supply
M.C.A
(with standard motor)
Power Input

Performance

Cooling
Heating
Cooling
Heating

Air Circulation
EER
COP
Sound Rating
Type
Tube size(O.D)

Indoor Coil

Face area

Compressor

Type
No. Used
Diameter/Width
Drive Type/Motor Step
No.motors
Motor output(standard/oversized)
Motor rpm(Standard/oversized)
Type
Quantity
Model
Maker
Capacity
Motor Type
Motor Input
Oil Type
Oil Charge
Type
Tube size(O.D)

Outdoor Coil

inch
mm
sq.ft
m2

inch

Hp
rpm

kcal/h(Btu/h)
W
cc
inch
mm

Row/FPI
Length
Face area

Type
No. Used/Diameter(inch)
Drive Type
Outdoor Fan
CFM
No. Motor/Motor output(Hp)
Motor RPM
Dehumidification Rate
Drain Connection Size(in.)
Refrigerant

inch
mm

Row/FPI
Length

Indoor Fan

Btu/h
kcal/h(W)
Btu/h
kcal/h(W)
Btu/h
kcal/h(W)
V,PH,Hz
Amps
Amps
W
W
CFM
Btu/h W
Btu/h W
bell

Refrigerant Charge

inch
mm
sq.ft
m2

l/h
kg
lbs
Type

Refrigerant Control
Dimensions

Indoor unit (W*H*D)

Net Weight
Filter
Stuffing Quantity

Size / No Used
Filter Rack Thickness
Without S/Parts

inch
mm
kg
lbs

(20ft/40ft/40ft HI)

Notes: 1. Capacities are based on the following conditions:Cooling: - Indoor Temperature 26.7C(80F) DB / 19.4C(67F) WB
- Outdoor Temperature 35C(95F) DB
2. Nominal CFM : Fan operation mode with clean filter, dry coil.
3. Due to our policy of innovation some specifications may be changed without notification.

10

Single Package (50Hz, Above 5 Ton)

30
LK-C3608H00
360,000
90,726(105,505)
340,000
85,685(99,644)
380-415, 3, 50
84.0
33,000
12,000
10.3
10.0
High efficiency
3/8
9.52
3R/16FPI
70.28
1,785
23.43
2.18
Centrifugal Blower Fan
2EA
15"/15"
Belt/1
1EA
10Hp/N.A
2,910/N.A
Scroll
2
SM185S4BA
DANFOSS
46,720(185,400)
3 Induction
16,240
Mineral oil 160P
6,200
High efficiency
3/8
9.52
3R/16FPI
74.8
1,900
49.87
4.63
Propeller
4EA/23.6"
Direct
12,500
4/0.35
1,050
34.8
1"
9.2/Circuit
20.28/Circuit
R-22
Capillary Tube
105 5/6 * 67 5/7 * 86 3/5
2688*1720*2200
1070
2359
1075*910 / 2EA
1,2 inch
2/4/4
Heating: - Indoor Temperature 21.1C(70F) DB / 15.6C(60F) WB
- Outdoor Temperature 8.3C(47F) DB / 6.1C(43F) WB

6. Dimensional Drawings
Model No.: LK-C3608H00
UNIT Dimensions (Figure 1A)
Unit: inch(mm)
CLEARANCE 34"

UNITS

30RT

67 11/16 (1720)

86 10/16 (2200)

105 13/16 (2688)

42 13/16 (1087)

26 12/16 (680)

31 8/16 (800)

36 4/16 (920)

CLEARANCE 16"

CLEARANCE 34"
G
F
E

CLEARANCE 46"

Figure 1A

HORIZONTAL FLOW APPLICATION (Figure 1B)


Unit: inch(mm)
UNITS

30RT

49 17/16 (1255)

7 9/16 (192)

22 1/16 (561)

4 6/16 (111)

34 13/16 (885)

12/16 (19)

3 2/16 (80)

4 8/16 (115)

77 7/16 (1967)

GF

Figure 1B

2004 Product Data

11

6. Dimensional Drawings
Weights
Maximum Unit and Corner Weights (Lbs) and Center of Gravity Dimensions (In.)
Tons

Unit
Model No.

30

LK-C360*H**

Maximum Weights (lbs)

Corner Weights (lbs)

Center of Gravity (In.)

Shipping

Net

2370

2359

700

569

513

577

106

87

Note: 1.Corner weights are given for information only.


2. Weights are approximate.

E
A

CENTER OF GRAVITY

12

Single Package (50Hz, Above 5 Ton)

7. Wiring Diagrams
Model No.: LK-C3608H00
USING ELECTRIC
HEATER(OPTION)
TS

EH
R

3
3WIRE
380-415V
POWER
SUPPLY

TS

EH

V1
W1

BK
BK

BK
BK

BK

BK
WH
RD

U1

WH
RD

T.P
IN
MOTOR

BK

MAGNETIC CONTACTOR
MOTOR,INDOOR

EOCR(A)

COMP
(A)
T.P

T1(U)

BK

T2(V)

WH

T3(W)

RD

BK
WH
RD
WH
BK

L1 L2
MAGNETIC CONTACTOR(A)

Ry

YL

Ry

WH

TERMINAL BLOCK

Ry

BK

WH

WH

250V 5A

BK

T2(V)

WH

T3(W)

RD
YL

HIGH PRESSURE
SWICH(B-Cycle)

L1 L2

YL
BR
OR
BK

MOTOR
OUT
(B-2)

YL
BR
OR
BK

YL
BR
OR
BK

4 8
2 6

WH
BK
BK

BR
YL
RD

CAPACITOR

TERMINAL
BLOCK
BR
RD
YL

FIRE
ALARM

CAPACITOR

N
T
S

HUMIDIFIER

3854A20290K

TERMINAL
BLOCK

CAPACITOR

REMOTE
CONTROLLER

WH

MOTOR
OUT
(A-2)

YL
BR
OR
BK

BK

YL
BR
OR
BK

LOW PRESSURE
SWICH(A-Cycle)

POWER RELAY
MOTOR, OUTDOOR

MOTOR
OUT
(B-1)

YL
BR
OR
BK

CAPACITOR

BK

YL
BR
OR
BK

BL
WH

CN_REMO

YL
BR
OR
BK

LOW PRESSURE
SWICH(B-Cycle)

BL

CN_ZON

MOTOR
OUT
(A-1)

HIGH PRESSURE
SWICH(A-Cycle)

2
1
TERMINAL
BLOCK

CN_L/P

43
TERMINAL
BLOCK

THERMISTOR
OUT AIR

CN_CC

MAGNETIC CONTACTOR(D)

WH

RD

THERMISTOR
IN(B)

THERMISTOR
IN(A)

RD
CN_H/P

Tc Tb Ta

CN_THMO

COMP
(B)
T.P

BK

3
4WIRE
380-415V
50Hz
POWER
SUPPLY

REMOVE JUMP WIRE WHEN


CONNECTING FIRE ALARM
SYSTEM

POWER RELAY
(AC 24V)

T1(U)

THERMISTOR
RETUTN AIR
(OPTION)

CN_A_CYCLE CN_TEMP_OUT
(OUT IN)

EOCR(B)

CN_RETURN_AIR CN_B_CYCLE
(OUT IN)

FUSE

WH

R
(U)
(T1)

S
(V)
(T2)

BK
BK
WH
WH
RD
RD
BK

CN_PHASE

T
(W)
(T3)

Ry

Ry

BR

(B) (A)
CN_ECONO CN_HUMID CN_COMP CN_BYPASS

BR

FUSE
250V/1A
CN_POWER

(IN OUT1 OUT2)


CN_FAN

Ry

Ry

BK

3
4WIRE
380-415V
50Hz
POWER
SUPPLY

CN_HEATER

Ry

BK

MAIN PCB ASM

Tc Tb Ta

FIRE ALARM
(AC 24V)

FIELD
INSTALLATION

CANNOT BE USED WHEN


USING THERMOSTAT

Notes:
RY

RELAY

EH

ELECTRIC HEATER

BK

BLACK

OR

ORANGE

YL

YELLOW

BR

BROWN

RD

RED

BL

BLUE

WH

WHITE

FACTORY WIRING

COMP

COMPRESSOR

FIELD WIRING

2004 Product Data

13

8. Selection Procedure
Selection Procedure-Cooling only(English)
Cooling
Step 1.

Based on building's cooling load calculation from ASHRAE or any approved


standard method.
a. Cooling Capacity ...................................................................330,000 Btu/h
b. Sensible Cooling Capacity.....................................................240,000 Btu/h
c. Heating Capacity ...................................................................120,000 Btu/h
d. Outdoor Entering-air Temperature ........................................95F
e. Indoor Entering-air Temp.(D.B/W.B) .....................................80F/67F
f. Indoor air-flow.........................................................................12,000 CFM
g. Electrical Characteristics(V-Ph-Hz) .......................................380~415-3-50
h. External static pressure .........................................................0.64 in.Aq.

Step 2.

Select unit based on required cooling capacity.


Based on Total Cooling Capacity, choose suitable Model from table 1.
30RT unit can be selected.
Verify the unit performance at the given conditions in accordance with step #3.

14

Single Package (50Hz, Above 5 Ton)

8. Selection Procedure
Selection Procedure
Step 3.

From table-3 (LK-C3608H00), at 12,000 CFM and 95F DB outdoor ambient temperature, with
80F DB. 67F WB air entering temperature.
Total cooling capacity= 360,000 Btu/h, Sensible capacity = 270,000 Btu/h
To find capacity at intermediate conditions not in the table.
Interpolation should be used when design conditions are between two numbers that are in the
capacity table. Extra-polation is not recommended.

Step 4.

The capacity estimated at step #3 is the gross capacity of the selected unit. The generated heat
from indoor motor is a function of CFM & static pressure. The total unit static pressure, is as follows:
External Static(Duct system)

0.64 in.Aq.

Standard Filter

0.16 in.Aq.

Electric heater size 36kW

0.16 in.Aq.

Total static pressure

0.96 in.Aq.

Evaporator fan motor performance table has deducted the pressure drop for filter already in the unit.
Therefore, the actual total static pressure is 0.80 in.Aq.
With 12,000 CFM and 0.80 in.Aq., table-5 shows 6.12 BHP for this unit.
FAN MOTOR HEAT;
3.1 x BHP = MBH
3.1 x 6.12 = 19.0 MBH
Now subtract the fan motor heat from the gross cooling capacity of the unit;

Step 5.

Net cooling capacity

360.0 MBH - 19.0 MBH = 341.0 MBH

Net sensible cooling

270 MBH - 19.0 MBH = 251.0 MBH

MBH = 1000 Btu/h

If the selected unit performance will not meet the required load, either total or sensible cooling, the
next higher size unit should be selected.

Electric Heating
Step 1.

Calculate the building heating load using the ASHRAE calculation or from other standard accepted
method.

Step 2.

The required heating capacity is 120,000 Btu/h.


The electric heat accessory capacities are listed in table-8.
From the table-8 select, 36 kW electric heater with output
122.86 MBH = 122,860Btu/h.

2004 Product Data

15

8. Selection Procedure
Selection Procedure - Cooling Only(SI)

Cooling
Step 1.

Based on building's cooling load calculation from ASHRAE or any approved


standard method.
a. Cooling Capacity ...................................................................96.71 kW
b. Sensible Cooling Capacity.....................................................70.34 kW
c. Heating Capacity ...................................................................35.19 kW
d. Outdoor Entering-air Temperature ........................................35C
e. Indoor Entering-air Temp.(D.B/W.B) .....................................26.7C/19.4C
f. Indoor air-flow.........................................................................5,663 l/s
g. Electrical Characteristics(V-Ph-Hz) .......................................380~415-3-50
h. External static pressure .........................................................16.26mm Aq.

Step 2.

Select unit based on required cooling capacity.


Based on total cooling capacity, choose suitable Model from table 1.
30RT unit can be selected.
Verify the unit performance at the given conditions in accordance with step #3.

Step 3.

From table-2 (LK-C3608H00), at 5,663 l/s and 35C DB outdoor ambient temperature, with
26.7C DB. 19.4C WB air entering temperature.
Total cooling capacity= 105.5 kW, Sensible capacity = 79.1 kW
To find capacity at intermediate conditions not in the table.
Interpolation should be used when design conditions are between two numbers that are in the
capacity table. Extra-polation is not recommended.

16

Single Package (50Hz, Above 5 Ton)

8. Selection Procedure
Selection Procedure

Step 4.

The capacity estimated at step #3 is the gross capacity of the selected unit. The generated heat
from indoor motor is a function of l/s & static pressure. The total unit static pressure, is as follows:
External Static(Duct system)

16.26 mm Aq.

Standard Filter

4.06 mm Aq.

Electric heater size 36kW

4.06 mm Aq.

Total static pressure

24.38 mm Aq.

Evaporator fan motor performance table has deducted the pressure drop for filter already in the unit.
Therefore, the actual total static pressure is 20.32 mm Aq.
With 5,663 l/s and 20.3mm Aq., table-4 shows 4.57 BkW for this unit.
FAN MOTOR HEAT;
1.22 x BkW = kW
1.22 x 4.57 = 5.58 kW
Now subtract the fan motor heat from the gross cooling capacity of the unit;

Step 5.

Net cooling capacity

105.5 kW - 5.58 kW = 99.92 kW

Net sensible cooling

79.1 kW - 5.58 kW = 73.52 kW

If the selected unit performance will not meet the required load, either total or sensible cooling, the
next higher size unit should be selected.

Electric Heating
Step 1.

Calculate the building heating load using the ASHRAE calculation or from other standard accepted
method.

Step 2.

The required heating capacity is 35.19kW (given).


12
x 35.19 = 120.08 MBH
35.19kW =
3.5167
The electric heat accessory capacities are listed in table-8. From the table select, 36kW Electric
Heater with output 122.86MBH.

2004 Product Data

17

9. Performance Data
Table-2

Gross Cooling Capacity (kW) 30 ton LK-C3608H00(SI)

Outdoor DB(C)

29.4

Indoor WB(C)
l/s
4530

5097

5663

6229

6795

DB(C)
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2
23.9
26.7
29.4
32.2

16.1
TGC
91.8
95.8
99.4
102.6
96.5
100.7
104.5
108.0
98.6
102.9
106.8
110.3
100.8
105.2
109.1
112.7
101.6
106.0
110.0
113.6

SHC
71.6
82.2
90.1
94.9
76.8
88.2
96.7
101.8
79.0
90.7
99.4
104.7
83.3
95.6
104.8
110.3
85.5
98.1
107.5
113.3

Outdoor DB(C)
Indoor WB(C)
l/s
4530

5097

5663

6229

6795

35.0

19.4
PI
22.46
22.53
22.60
22.67
22.66
22.73
22.79
22.86
22.85
22.92
22.99
23.06
23.05
23.12
23.19
23.26
23.24
23.31
23.38
23.45

TGC
101.5
103.3
104.8
105.9
106.7
108.7
110.2
111.4
109.0
111.0
112.6
113.8
111.4
113.4
115.1
116.3
112.3
114.3
116.0
117.2

SHC
54.2
67.9
81.8
90.9
58.2
72.8
87.7
97.5
59.8
74.9
90.2
100.2
63.1
79.0
95.1
105.6
64.7
81.0
97.6
108.4

22.8
PI
23.17
23.24
23.31
23.38
23.37
23.44
23.51
23.58
23.57
23.64
23.72
23.79
23.77
23.85
23.92
23.99
23.97
24.05
24.12
24.19

TGC
109.1
109.2
108.8
108.2
114.8
114.8
114.5
113.8
117.2
117.3
116.9
116.2
119.8
119.9
119.5
118.8
120.7
120.8
120.5
119.7

SHC
23.9
44.5
61.5
74.9
25.7
47.7
66.0
80.3
26.4
49.1
67.9
82.6
27.8
51.7
71.5
87.1
28.6
53.1
73.4
89.4

40.6
16.1

19.4

16.1
PI
23.60
23.67
23.75
23.82
23.81
23.88
23.95
24.02
24.01
24.08
24.16
24.23
24.22
24.29
24.36
24.43
24.42
24.49
24.57
24.64

TGC
87.2
91.0
94.5
97.6
91.8
95.7
99.3
102.6
93.7
97.8
101.5
104.8
95.8
100.0
103.7
107.1
96.6
100.7
104.5
108.0

SHC
71.9
82.6
90.5
95.3
77.1
88.6
97.1
102.2
79.3
91.1
99.8
104.8
83.6
96.0
103.7
107.1
85.8
96.7
104.5
108.0

19.4
PI
24.78
24.85
24.93
25.00
24.97
25.05
25.12
25.20
25.26
25.34
25.42
25.49
25.36
25.44
25.52
25.59
25.56
25.63
25.71
25.79

TGC
96.5
98.2
99.6
100.7
101.4
103.3
104.8
105.9
103.6
105.5
107.0
108.2
105.9
107.8
109.4
110.6
106.7
108.7
110.2
111.4

SHC
54.5
68.2
82.1
91.3
58.4
73.1
88.1
97.8
60.1
75.2
90.6
100.6
63.3
79.3
95.5
106.1
65.0
81.4
98.0
108.9

22.8
PI
25.56
25.64
25.72
25.79
25.76
25.84
25.92
25.99
26.06
26.14
26.22
26.30
26.16
26.24
26.32
26.40
26.36
26.44
26.52
26.60

46.1
22.8

16.1

19.4

TGC SHC
PI
103.7 24.0 26.04
103.7 44.7 26.11
103.5 61.8 26.19
102.8 75.2 26.27
109.1 25.8 26.24
109.1 47.9 26.32
108.8 66.2 26.40
108.1 80.7 26.48
111.4 26.5 26.54
111.5 49.3 26.62
111.1 68.1 26.70
110.5 83.0 26.78
113.9 27.9 26.65
113.9 51.9 26.73
113.6 71.8 26.81
112.9 87.5 26.89
114.8 28.7 26.85
114.8 53.3 26.93
114.5 73.7 27.01
113.8 89.8 27.09

51.7
22.8

16.1

DB(C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI
23.9
82.1 68.4 26.65 90.8 51.8 27.49 97.6 22.9 28.01 74.1 63.6 28.48 81.9 48.1 29.38 88.0 21.2 29.93 65.1 59.5 30.39
85.7 78.5 26.73 92.4 64.8 27.58 97.7 42.5 28.09 77.3 73.0 28.57 83.3 60.3 29.47 88.1 39.5 30.02 67.9 67.9 30.48
26.7
29.4
88.9 86.0 26.81 93.8 78.1 27.66 97.4 58.7 28.17 80.2 80.0 28.66 84.5 72.6 29.56 87.8 54.6 30.11 70.5 70.5 30.57
32.2
91.8 90.6 26.89 94.8 86.7 27.74 96.8 71.5 28.26 82.8 82.8 28.74 85.5 80.7 29.65 87.3 66.5 30.20 72.8 72.8 30.66
23.9
86.4 73.3 26.85 95.5 55.5 27.70 102.7 24.5 28.21 77.9 68.2 28.68 86.1 51.6 29.59 92.6 22.8 30.13 68.5 63.4 30.89
90.1 84.2 26.93 97.2 69.5 27.78 102.7 45.5 28.29 81.3 78.3 28.77 87.7 64.6 29.67 92.6 42.3 30.23 71.4 71.4 30.98
26.7
29.4
93.5 92.3 27.01 98.6 83.7 27.86 102.4 63.0 28.38 84.3 84.3 28.85 88.9 77.9 29.76 92.4 58.6 30.32 74.1 74.1 31.07
32.2
96.6 96.6 27.09 99.7 93.0 27.95 101.8 76.7 28.46 87.1 87.1 28.94 89.9 86.5 29.85 91.8 71.3 30.41 76.6 76.6 31.16
23.9
88.2 75.4 27.04 97.5 57.1 27.90 104.9 25.2 28.41 79.6 70.1 28.88 88.0 53.1 29.79 94.6 23.4 30.34 69.9 65.6 31.39
26.7
92.1 86.6 27.12 99.3 71.5 27.98 104.9 46.8 28.50 83.0 80.5 28.96 89.5 66.5 29.88 94.6 43.5 30.43 73.0 73.0 31.48
29.4
95.5 94.9 27.21 100.7 86.1 28.06 104.6 64.8 28.58 86.1 86.1 29.05 90.8 80.1 29.97 94.3 60.2 30.52 75.7 75.7 31.58
32.2
98.7 98.7 27.29 101.8 95.7 28.15 104.0 78.9 28.67 89.0 89.0 29.14 91.8 89.0 30.06 93.8 73.3 30.61 78.2 78.2 31.67
23.9
90.2 79.5 27.24 99.7 60.2 28.10 107.2 26.6 28.62 81.3 73.9 29.07 89.9 56.0 29.99 96.7 24.7 30.55 71.5 68.7 31.59
26.7
94.1 91.3 27.32 101.5 75.4 28.18 107.3 49.4 28.70 84.8 84.8 29.16 91.5 70.1 30.08 96.7 45.9 30.64 74.6 74.6 31.69
29.4
97.7 97.7 27.40 103.0 90.8 28.27 107.0 68.3 28.79 88.0 88.0 29.25 92.8 84.4 30.17 96.4 63.5 30.73 77.4 77.4 31.78
32.2 100.9 100.9 27.48 104.1 100.8 28.35 106.3 83.1 28.88 90.9 90.9 29.34 93.8 93.8 30.26 95.8 77.3 30.82 79.9 79.9 31.88
23.9
90.9 81.6 27.43 100.5 61.8 28.30 108.0 27.3 28.82 82.0 75.8 29.27 90.6 57.4 30.19 97.4 25.4 30.75 72.0 70.1 31.79
26.7
94.8 93.7 27.51 102.3 77.4 28.38 108.1 50.7 28.91 85.5 85.5 29.36 92.2 71.9 30.28 97.5 47.1 30.85 75.2 75.2 31.89
29.4
98.4 98.4 27.60 103.8 93.2 28.47 107.8 70.1 29.00 88.7 88.7 29.45 93.6 86.6 30.37 97.2 65.2 30.94 78.0 78.0 31.99
32.2 101.6 101.6 27.68 104.9 103.5 28.55 107.1 85.3 29.08 91.6 91.6 29.53 94.6 94.6 30.47 96.6 79.3 31.03 80.6 80.6 32.08

19.4
TGC
72.0
73.3
74.3
75.1
75.7
77.1
78.2
79.0
77.3
78.7
79.9
80.7
79.0
80.5
81.6
82.5
79.7
81.1
82.3
83.1

SHC
45.1
56.4
67.9
75.1
48.0
60.1
72.4
79.0
49.7
62.2
74.9
80.7
52.0
65.2
78.5
82.5
53.1
66.5
80.1
83.1

22.8
PI
31.35
31.44
31.54
31.63
31.86
31.96
32.05
32.15
32.38
32.47
32.57
32.67
32.59
32.68
32.78
32.88
32.80
32.90
32.99
33.09

TGC
77.4
77.4
77.2
76.7
81.4
81.4
81.2
80.7
83.1
83.2
82.9
82.4
85.0
85.0
84.8
84.3
85.6
85.7
85.4
84.9

SHC
19.9
37.0
51.1
62.2
21.2
39.4
54.4
66.3
21.9
40.7
56.3
68.6
23.0
42.7
59.0
71.9
23.4
43.5
60.2
73.3

PI
31.93
32.02
32.12
32.22
32.45
32.55
32.65
32.74
32.98
33.08
33.18
33.27
33.19
33.29
33.39
33.49
33.41
33.51
33.61
33.71

Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB
= Dry Bulb Temperature (C), WB = Wet Bulb Temperature (C)
3. l/s
= Liters per second
4. TGC = Total Gross Cooling Capacity(Unit : kW)
5. SHC = Sensible Heat Capacity(Unit : kW)
6. PI
= Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

18

Single Package (50Hz, Above 5 Ton)

9. Performance Data
Table-3

Gross Cooling Capacity (MBH) 30 ton LK-C3608H00(English)

Outdoor DB(F)
Indoor

WB(F)

CFM

DB(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

9600

10800

12000

13200

14400

85
61
TGC
313.3
326.8
339.2
350.3
329.5
343.8
356.7
368.5
336.5
351.1
364.4
376.3
344.0
358.9
372.5
384.7
346.7
361.7
375.4
387.7

SHC
244.4
280.7
307.7
324.0
262.1
301.0
329.9
347.4
269.6
309.6
339.3
357.3
284.2
326.3
357.6
376.6
291.7
334.9
367.1
386.5

67
PI
22.46
22.53
22.60
22.67
22.66
22.73
22.79
22.86
22.85
22.92
22.99
23.06
23.05
23.12
23.19
23.26
23.24
23.31
23.38
23.45

Outdoor DB(F)
Indoor

WB(F)

CFM

DB(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

9600

10800

12000

13200

14400

95

TGC
346.4
352.6
357.7
361.5
364.3
370.8
376.2
380.2
372.1
378.8
384.2
388.4
380.3
387.2
392.8
397.0
383.3
390.2
395.8
400.1

73

SHC
185.1
231.8
279.2
310.2
198.5
248.6
299.4
332.6
204.1
255.6
307.9
342.1
215.2
269.5
324.5
360.6
220.9
276.6
333.1
370.1

PI
23.17
23.24
23.31
23.38
23.37
23.44
23.51
23.58
23.57
23.64
23.72
23.79
23.77
23.85
23.92
23.99
23.97
24.05
24.12
24.19

TGC
372.4
372.5
371.5
369.2
391.6
391.8
390.7
388.3
400.0
400.2
399.1
396.6
408.9
409.1
407.9
405.5
412.1
412.3
411.1
408.6

SHC
81.7
151.8
210.0
255.7
87.6
162.8
225.2
274.2
90.1
167.4
231.6
282.0
95.0
176.5
244.1
297.3
97.5
181.1
250.5
305.1

61
PI
23.60
23.67
23.75
23.82
23.81
23.88
23.95
24.02
24.01
24.08
24.16
24.23
24.22
24.29
24.36
24.43
24.42
24.49
24.57
24.64

105
61
TGC
280.3
292.4
303.5
313.5
294.8
307.6
319.2
329.7
301.1
314.2
326.0
336.7
307.8
321.2
333.3
344.2
310.2
323.7
335.9
346.9

SHC
233.3
267.9
293.6
309.2
250.2
287.3
314.9
329.7
257.3
295.5
323.8
336.7
271.2
311.5
333.3
344.2
278.4
319.7
335.9
346.9

TGC
309.9
315.5
320.0
323.5
326.0
331.8
336.6
340.2
332.9
338.9
343.8
347.5
340.3
346.4
351.4
355.2
343.0
349.1
354.2
358.0

SHC
176.7
221.3
266.5
296.1
189.5
237.3
285.8
317.5
194.9
244.0
293.9
326.5
205.4
257.2
309.8
344.2
210.8
264.0
317.9
353.2

67

SHC
245.4
281.8
308.9
325.3
263.2
302.2
331.2
348.8
270.7
310.8
340.6
357.7
285.3
327.6
354.0
365.6
292.8
330.2
356.8
368.5

PI
24.78
24.85
24.93
25.00
24.97
25.05
25.12
25.20
25.26
25.34
25.42
25.49
25.36
25.44
25.52
25.59
25.56
25.63
25.71
25.79

TGC
329.2
335.1
339.9
343.6
346.2
352.5
357.5
361.4
353.6
360.0
365.2
369.1
361.5
368.0
373.3
377.3
364.3
370.9
376.2
380.3

SHC
185.9
232.8
280.3
311.4
199.3
249.6
300.6
334.0
205.0
256.7
309.1
343.4
216.1
270.6
325.9
362.0
221.8
277.7
334.5
371.6

73
PI
25.56
25.64
25.72
25.79
25.76
25.84
25.92
25.99
26.06
26.14
26.22
26.30
26.16
26.24
26.32
26.40
26.36
26.44
26.52
26.60

115

67
PI
26.65
26.73
26.81
26.89
26.85
26.93
27.01
27.09
27.04
27.12
27.21
27.29
27.24
27.32
27.40
27.48
27.43
27.51
27.60
27.68

TGC
297.8
310.6
322.4
333.0
313.2
326.7
339.1
350.2
319.9
333.7
346.3
357.7
327.0
341.1
354.0
365.6
329.5
343.8
356.8
368.5

73
PI
27.49
27.58
27.66
27.74
27.70
27.78
27.86
27.95
27.90
27.98
28.06
28.15
28.10
28.18
28.27
28.35
28.30
28.38
28.47
28.55

TGC
333.2
333.3
332.4
330.4
350.4
350.6
349.6
347.5
357.9
358.1
357.1
354.9
365.9
366.0
365.0
362.8
368.7
368.9
367.9
365.6

SHC
78.0
144.9
200.4
244.1
83.6
155.4
214.9
261.7
86.0
159.8
221.0
269.2
90.7
168.5
233.0
283.7
93.1
172.9
239.1
291.2

61
PI
28.01
28.09
28.17
28.26
28.21
28.29
28.38
28.46
28.41
28.50
28.58
28.67
28.62
28.70
28.79
28.88
28.82
28.91
29.00
29.08

TGC
252.7
263.7
273.6
282.6
265.8
277.3
287.8
297.3
271.5
283.3
294.0
303.6
277.6
289.6
300.5
310.4
279.7
291.8
302.8
312.8

SHC
217.0
249.1
273.1
282.6
232.6
267.2
287.8
297.3
239.3
274.7
294.0
303.6
252.2
289.6
300.5
310.4
258.9
291.8
302.8
312.8

TGC
279.4
284.5
288.6
291.7
293.9
299.2
303.5
306.8
300.2
305.6
310.0
313.3
306.9
312.4
316.9
320.3
309.2
314.8
319.4
322.8

SHC
164.3
205.7
247.8
275.3
176.2
220.6
265.7
295.2
181.2
226.9
273.3
303.6
191.0
239.2
288.0
320.0
196.0
245.5
295.6
322.8

SHC
82.0
152.4
210.8
256.8
88.0
163.5
226.1
275.3
90.5
168.1
232.5
283.1
95.4
177.2
245.1
298.5
97.9
181.9
251.6
306.3

PI
26.04
26.11
26.19
26.27
26.24
26.32
26.40
26.48
26.54
26.62
26.70
26.78
26.65
26.73
26.81
26.89
26.85
26.93
27.01
27.09

125

67
PI
28.48
28.57
28.66
28.74
28.68
28.77
28.85
28.94
28.88
28.96
29.05
29.14
29.07
29.16
29.25
29.34
29.27
29.36
29.45
29.53

TGC
353.9
354.1
353.1
350.9
372.2
372.4
371.4
369.1
380.2
380.4
379.3
377.0
388.6
388.8
387.7
385.4
391.7
391.9
390.8
388.4

73
PI
29.38
29.47
29.56
29.65
29.59
29.67
29.76
29.85
29.79
29.88
29.97
30.06
29.99
30.08
30.17
30.26
30.19
30.28
30.37
30.47

TGC
300.4
300.6
299.7
297.9
316.0
316.1
315.2
313.3
322.7
322.9
322.0
320.0
329.9
330.1
329.1
327.1
332.5
332.6
331.7
329.7

SHC
72.5
134.8
186.4
227.0
77.8
144.5
199.9
243.4
80.0
148.6
205.5
250.3
84.3
156.6
216.7
263.8
86.5
160.8
222.4
270.8

61
PI
29.93
30.02
30.11
30.20
30.13
30.23
30.32
30.41
30.34
30.43
30.52
30.61
30.55
30.64
30.73
30.82
30.75
30.85
30.94
31.03

TGC
222.2
231.8
240.6
248.5
233.7
243.8
253.0
261.3
238.7
249.0
258.4
266.9
244.0
254.6
264.2
272.9
245.9
256.5
266.2
275.0

SHC PI
203.0 30.39
231.8 30.48
240.6 30.57
248.5 30.66
216.3 30.89
243.8 30.98
253.0 31.07
261.3 31.16
223.8 31.39
249.0 31.48
258.4 31.58
266.9 31.67
234.6 31.59
254.6 31.69
264.2 31.78
272.9 31.88
239.3 31.79
256.5 31.89
266.2 31.99
275.0 32.08

67
TGC
245.7
250.1
253.7
256.4
258.4
263.0
266.8
269.7
263.9
268.6
272.5
275.4
269.8
274.6
278.6
281.6
271.9
276.7
280.7
283.8

SHC
153.8
192.6
231.9
256.4
163.8
205.2
247.1
269.7
169.5
212.2
255.6
275.4
177.6
222.4
267.9
281.6
181.2
226.9
273.3
283.8

73
PI
31.35
31.44
31.54
31.63
31.86
31.96
32.05
32.15
32.38
32.47
32.57
32.67
32.59
32.68
32.78
32.88
32.80
32.90
32.99
33.09

TGC
264.1
264.2
263.5
261.9
277.8
277.9
277.1
275.4
283.7
283.9
283.1
281.3
290.0
290.2
289.3
287.6
292.3
292.4
291.6
289.8

SHC PI
67.9 31.93
126.1 32.02
174.4 32.12
212.4 32.22
72.3 32.45
134.4 32.55
185.8 32.65
226.3 32.74
74.8 32.98
139.0 33.08
192.2 33.18
234.1 33.27
78.4 33.19
145.7 33.29
201.5 33.39
245.4 33.49
80.0 33.41
148.6 33.51
205.6 33.61
250.3 33.71

Notes:
1. All capacities are gross, evaporator fan motor heat is not deducted. To obtain net cooling capacity, subtract evaporator fan motor heat.
2. DB
= Dry Bulb Temperature (F), WB = Wet Bulb Temperature (F)
3. CFM
= Cubic Feet per minute
4. TGC = Total Gross Cooling Capacity(Unit : MBH = 1000Btu/h)
5. SHC = Sensible Heat Capacity(Unit : MBH = 1000Btu/h)
6. PI
= Power Input(kW), Sum of Compressor & Outdoor Fan Power Input

2004 Product Data

19

9. Performance Data
Table-4
l/s

Evaporator Fan Performance Data LK-C3608H00 (SI)

External Static Pressure(mm Aq.)


2.5
5.1
7.6
10.2
12.7
15.2
17.8
20.3
22.9
25.4
27.9
30.5
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW

4247

556 1.03 572 1.24 588 1.44 603 1.65 619 1.86 635 2.07 650

2.28 666 2.48 682 2.69 697 2.90 713 3.11 729 3.32

4719

576 1.72 591 1.93 607 2.14 623 2.35 639 2.55 654 2.76 670

2.97 686 3.18 701 3.39 717 3.59 733 3.80 748 4.01

5191

595 2.42 611 2.62 627 2.83 642 3.04 658 3.25 674 3.46 690

3.66 705 3.87 721 4.08 737 4.29 752 4.50 768 4.70

5663

615 3.11 631 3.32 646 3.52 662 3.73 678 3.94 693 4.15 709

4.36 725 4.57 741 4.77 756 4.98 772 5.19 788 5.40

6135

635 3.80 650 4.01 666 4.22 682 4.43 697 4.63 713 4.84 729

5.05 744 5.26 760 5.47 776 5.67 792 5.88 807 6.09

6607

654 4.50 670 4.70 686 4.91 701 5.12 717 5.33 733 5.54 748

5.74 764 5.95 780 6.16 795 6.37 811 6.58 827 6.78

l/s

External Static Pressure(mm Aq.)


33.0
35.6
38.1
40.6
43.2
45.7
48.3
50.8
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW

4247

745 3.52 760 3.73 776 3.94 792 4.15 807 4.36 823 4.57 839 4.77 854 4.98

4719

764 4.22 780 4.43 796 4.63 811 4.84 827 5.05 843 5.26 858 5.47 874 5.67

5191

784 4.91 799 5.12 815 5.33 831 5.54 847 5.74 862 5.95 878 6.16 894 6.37

5663

803 5.61 819 5.81 835 6.02 850 6.23 866 6.44 882 6.65 898 6.85 913 7.06

6135

823 6.30 839 6.51 854 6.72 870 6.92 886 7.13 901 7.34

6607

843 6.99 858 7.20 874 7.41

10Hp STANDARD MOTOR & DRIVE


10Hp STANDARD MOTOR & HIGH STATIC DRIVE

Fan motor heat(kW)= 1.22 x Fan BkW


Test Condition: Voltage : 415V
Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater
Do not operate the unit at a cooling airflow that is less then 165 l/s or 0.35kW
Motor S.F:1.15

20

Single Package (50Hz, Above 5 Ton)

9. Performance Data
Table-5

Evaporator Fan Performance Data LK-C3608H00 (English)

CFM

External Static Pressure(in. Aq.)


0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

9000

556 1.38 572 1.66 588 1.94 603 2.22 619 2.50 635 2.77 650 3.05 666 3.33 682 3.61 697 3.89 713 4.17 729 4.45

10000

576 2.31 591 2.59 607 2.87 623 3.15 639 3.43 654 3.70 670 3.98 686 4.26 701 4.54 717 4.82 733 5.10 748 5.38

11000

595 3.24 611 3.52 627 3.80 642 4.08 658 4.36 674 4.63 690 4.91 705 5.19 721 5.47 737 5.75 752 6.03 768 6.31

12000

615 4.17 631 4.45 646 4.73 662 5.01 678 5.29 693 5.56 709 5.84 725 6.12 741 6.40 756 6.68 772 6.96 788 7.24

13000

635 5.10 650 5.38 666 5.66 682 5.94 697 6.22 713 6.49 729 6.77 744 7.05 760 7.33 776 7.61 792 7.89 807 8.17

14000

654 6.03 670 6.31 686 6.59 701 6.87 717 7.15 733 7.42 748 7.70 764 7.98 780 8.26 795 8.54 811 8.82 827 9.10

CFM

External Static Pressure(in. Aq.)


1.3
1.4
1.5
1.6
1.7
1.8
1.9
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

9000

745 4.73 760 5.01 776 5.29 792 5.56 807 5.84 823 6.12 839 6.40 854 6.68

10000

764 5.66 780 5.94 796 6.22 811 6.49 827 6.77 843 7.05 858 7.33 874 7.61

11000

784 6.59 799 6.87 815 7.15 831 7.42 847 7.70 862 7.98 878 8.26 894 8.54

12000

803 7.52 819 7.80 835 8.08 850 8.35 866 8.63 882 8.91 898 9.19 913 9.47

13000

823 8.45 839 8.73 854 9.01 870 9.28 886 9.56 901 9.84

14000

843 9.38 858 9.66 874 9.94

10Hp STANDARD MOTOR & DRIVE


10Hp STANDARD MOTOR &
HIGH STATIC DRIVE

Fan motor heat(MBH)= 3.1 x Fan Bhp


Test Condition: Voltage : 415V
Operating Mode: Fan operation mode with clean filter,dry coil without electric heater
Do not operate the unit at a cooling airflow that is less then 350CFM/1.2MBH
Motor S.F:1.15

Table-6

Fan speed Data LK-C3608H00

6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open

Closed

Standard Motor & Drive


Fan Speed

563

602

641

680

719

758

797

Standard Motor & High Static


Drive Accessary Fan Speed

720

771

822

873

924

NA

NA

Factory set at 3 turns open.

2004 Product Data

21

9. Performance Data
Table-7

Accessory Static Pressure Drops

Unit Model No. CFM

l/s

7440 3511
LK-C3608H00 12000 5663
14400 6795

Table-8
MODEL

in Aq
0.10
0.16
0.21

9kW
in. Aq.
mm Aq.
-

mm Aq
2.54
4.06
5.33

18kW
in. Aq.
mm Aq.
-

36

122.86

No. of Stages
2

Input(kW)
18

Stage 1
Output(MBH)
61.43

Note: 1. The output ratings shown above is at 415V.


For other voltage, Output = Capacity Multiplier x Rated Output
2. E/heater Voltage range is 380~415V.

Table-9

Stage 2
Input(kW)
Output(MBH)
18

61.43

< Correction Coefficient>


Voltage

Capacity Multiplier

380

0.84

400

0.92

415

1.0

Air Temperature Rise Across Electric Heater(F)

Capacity

Stage

9kW

LK-C3608H00
(12,000 CFM)
-

18kW

36kW

9.5

22

36kW
in. Aq.
mm Aq.
1.0
2.54
0.16
4.06
0.20
5.08

Electric Heating Capacity

Total
Input(kW) Output(MBH)

LK-C3608H00

Electric Heater

Standard Filter

(kW x 3413)
(1.08 x CFM)
If you want to take temp rise at different airflow use above equation.

Temp. Rise across Electric Heater =

Single Package (50Hz, Above 5 Ton)

9. Performance Data
Electrical Data Unit wiring

Table-10
Tons

MODEL

Unit Operating
Voltage Range

30

LK-C3608H00

342~456

Oversized indoor fan motor


*M.C.A.
*M.F.S.
*M.C.B.

Standard indoor fan motor


*M.C.A.
*M.F.S.
*M.C.B.
84

110

110

Note: *M.C.A.: Minimum Circuit Ampacity


*M.F.S. : Maximum Fuse Size
*M.C.B.: Maximum Circuit Breaker

Electrical Data Unit wiring with electric heater.

Table-11
MODEL

Electric
Heater (kW)

LK-C3608H00

36

Standard indoor fan motor


*M.C.A.
*M.F.S.
*M.C.B.

Unit Operating
Voltage Range
3,380/415V,
50Hz

82

120

Oversized indoor fan motor


*M.C.A.
*M.F.S.
*M.C.B.

120

Note: Heater kW ratings are at 380/415 V unit.

Table-12
MODEL
LK-C3608H00

Standard evaporator fan motor


No
1

Table-13
MODEL
LK-C3608H00

Electrical Characteristics --- Evaporator Fan Motor --- 50 Hz

Volts Phase
380/415

HP
10

FLA

LRA

15.2/14 94.5/103

No
-

LRA

Electrical Characteristics --- Compressor and Outdoor Fan Motor --- 50 Hz


Compressor

No

Oversized evaporator fan motor


Volts Phase HP
FLA

Volts Phase
380~415

HP

FLA

LRA

No

13.5

24.2

175

Outdoor Fan Motor


Volts Phase HP
FLA
220~240

0.44

LRA

1.8

4.5

Note: FLA-Full Load Amps.


LRA-Locked Rotor Amps.

2004 Product Data

23

11. Refrigerant Cycle Diagrams


Model No.: LK-C3608H00
INDOOR
COIL

OUTDOOR
COIL
LOW-PRESSURE
SWITCH
(OPTIONAL )

HI-PRESSURE
SWITCH
(OPTIONAL )
PRESSURE
PORT

PRESSURE
PORT

DISCHARGE LINE

SUCTION LINE

COMPRESSOR
LOW-PRESSURE
SWITCH
(OPTIONAL )

HI-PRESSURE
SWITCH
(OPTIONAL )
PRESSURE
PORT

PRESSURE
PORT

DISCHARGE LINE

SUCTION LINE

COMPRESSOR
CAPILLARY TUBE
CAPILLARY TUBE

NOTE : : Cooling

24

Single Package (50Hz, Above 5 Ton)

12. Operation Range

Inlet air temperature


(Cooling)

Range
Outdoor air temperature C D.B.(F)

Item

54(129.2)

Standard operation

21(69.8)

15(59)

24(75.2)

Indoor air temperature C W.B.(F)

Outdoor air temperature C W.B.(F)

Inlet air temperature


(Heating)

18(64.4)

Standard operation

-10(14)
10(50)

24(75.2)

Indoor air temperature C D.B.(F)

Power source voltage

Rating 10%

Voltage at starting

Min. 85% of rating

2004 Product Data

25

13. Operating Space Limitations


Model No.: LK-C3608H00

CLEARANCE 34"

CLEARANCE 46"

26

Single Package (50Hz, Above 5 Ton)

CLEARANCE 16"

CLEARANCE 34"

14. Function of Remote Control


LCD Wired Remote Control

Heat Pump Model


AUTO SWING

OPERATION

SET TEMP
Room Temp

AUTO Heater Preheat


JET Defrost Humidify
Filter Out door
ZONE
1 2 3 4

HI
MED
LO

Time
Timer

Operation unit

On Off
Set no. Time 01

03

SUB FUNCTION

Program set
05

07

09

11

13

15

17

19

21

23

Cooling Model

Signal receptor

88
9
11

10
12

Timer

Cancel

Program

Week

4
5

13

Holiday

6
7
16

SET/CLR

14
Hour

Min

RESET

15

Heater Button

Timer Cancel Button


Used to cancel the timer.

10

Timer Set Button


Used to set the on/off timer.

Set Temperature Button


Used to set the required temperature.

11

Week Button
Used to set the day of the week.

FAN Operation Button


Used to circulate room air without cooling or
heating.

12

Program Button
Used to set the weekly timer.

13

Holiday Button
Used to set the holiday of the week.

14

Time Set Button


Used to set the time of the day and change
the time in the weekly timer Function.

15

Set and Clear Button


Used to set and clear the weekly timer.

16

Reset Button
Used to set the current time and clear the setting time.

Operation display
Displays the operation conditions.
On/Off Button
Operation starts when this button is pressed,
and stops when the button is pressed again.

Operation Mode Selection Button


Used to select the operation mode.
Cooling Operation Mode
Soft Dry Operation Mode
Heating Operation Mode(except cooling
model)

Humidify Button

Room Temperature Checking Button


Used to check the room temperature.

2004 Product Data

27

14. Function of Remote Control


Wireless Remote Control(Optional)
1
1

Signal Transmitter
Transmits the signals to the air conditioner

Operation Display of the Remote Control


LED displays operation status(on or off) of
air conditioner.

Humidify Button

Cooling ON Button

Temperature Setting Buttons

Power ON/OFF Button


Operation will start when this button is
pressed, and stop when the button is
pressed again.

Timer Set Button


Subsequent pressing of the button,
changes the set time in the incremental
order from 1 hr to 7 hr. If you select "0:000"
the off timer function will be considered.

Indoor Fan Operation Button

Heating Button (Heat Pump Model Only)

10

Electric Heater ON/OFF Button(Optional)

11

Soft Dry Operation Button

2
10
3
11
7

6
5

(Cooling Model)
1
2

10

3
11

6
5

(Heat pump Model)

28

Single Package (50Hz, Above 5 Ton)

15. Mechanical Specifications


Mechanical Specifications
General
Factory assembled fully self contained, single piece design to operate up to 129F and down to 14F in cooling
with optional electric heater.
Unit shall be rated in accordance with ARI standard testing procedure, fully charged with R-22. Units shall fully
factory test before shipment.

Casing
Unit casing shall be constructed of having gauge zinc coated, galvanized steel. The cabinet shall be exterior
painted and weather resistance. The cabinet shall be design to allow maintenance from one side only.
Unit shall have a water and air tight service panels with minimum number of screws per panel for easy servicing.

Filters
Washable filters shall be standard on all units (Except 6.25 Ton unit). Filter rack can be converted to one inch(bellow
71/2 ton).
Two inch filters shall be installed on all units above 7.5ton.

Compressors
LG single packaged units shall be direct drive hermetic compressor, scroll type with internal built in lubricating
mechanism for all moving parts. Motor shall be suction gas cooled with internal temperature and over current
sensitive motor over load, for maximum protection. Factory rubber shock mounted and internally spring isolation for sound and vibration control.

Refrigerant Circuits
Each refrigerant circuit shall have independent fixed capillary tube devices and service pressure ports, low
pressure switches and refrigerant line filter factory-installed as standard.

Evaporator and Condenser Coils


Shall be aluminum plate fins, mechanically bonded to copper tubes.
Coil shall be factory test for leakage and pressure.

Outdoor Fans
Statically and dynamically, direct drive outdoor fan in vertical discharge position. Permanently lubricated fan
motors with built in thermal overload protection.

Indoor Fan
Direct drive indoor motor for 6.25 tons with forward curve centrifugal fans. Belt drive with adjustable motor pulley for all unit above 6.25 ton. All motors shall be thermally overload protected. For higher static pressure
requirement over size motor is available.

Controls
All units shall be supplied with centralized micom-processor. Heating and cooling shall be control by micom
through input signals from indoor and outdoor temperature sensors. Micom shall provide anti-short cycle timer
and time delay between compressor.

2004 Product Data

29

16. Appendix
Unit Conversion
Cooling Capacity
RT

Btu/h

kcal/h

12,000

3024.2

3516.7

Volume
CMM

CFM

l/s

35.3

16.67

Length
m

cm

mm

inch

100

1000

39.37

Power
HP

kW

746

0.746

Temperature
C = 5 (F - 32)
9
Where,
C is Temperature in C
F is Temperature in F

30

Single Package (50Hz, Above 5 Ton)

Approvals:

ST

IR

EN ISO 9001

F
S
O E R E D 97
9
001 A8

BS EN ISO 9001
ANSI/ASQC Q9001

TYPE
APPROVED

ctronics
Ele
In

I
REG I

P/No.: 3828A20428M

TV
Rheinland
Product Safety

c.

BAUART
GEPRFT

20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355


Seoul 150-721, Korea
Phone :3777-7969 Fax:3777-5137/8
http://www.lge.com
http://biz.lgservice.com

KS A 9001

For continual product development, LG reserves the right to change specifications without notice.
LG Electronics INC. Printed in Korea. May/2004