Question 1: Predict how the operation of this relay logic circuit will be affected as a result
of the following faults. Consider each fault independently (i.e. one at a time, no multiple faults):

Pushbutton switch A fails open: Relay coil CR2 fails open: Relay contact CR1-1 fails open: Relay contact CR2-1 fails shorted: Relay contact CR2-2 fails shorted:

For each of these conditions, explain why the resulting effects will occur.

Solution:
When no relay is defected
A
0 0 1 1

B
0 1 0 1 Lamp 1= A + B ;

Lamp 1
1 1 0 1 Lamp 2 = (A+B)

Lamp 2
1 0 0 0

Results: Case 1- Pushbutton switch A fails open


A
0 0 1 1

B
0 1 0 1

Lamp 1
1 1 1 1

Lamp 2
1 0 1 0

Results:
Lamp 1= 1 (Always ON) ; Lamp 2 = B

Case 2- Relay coil CR2 fails open


A
0 0 1 1

B
0 1 0 1

Lamp 1
1 1 0 0

Lamp 2
1 1 0 0

Results:
Lamp 1= Lamp 2 = A

Case 3- Relay contact CR1-1 fails open


A
0 0 1 1

B
0 1 0 1

Lamp 1
0 1 0 1

Lamp 2
1 0 0 0

Results:
Lamp 1=B ; Lamp 2 = (A+B)

Case 4- Relay contact CR2-1 fails shorted


A
0 0 1 1

B
0 1 0 1

Lamp 1
1 1 1 1

Lamp 2
1 0 0 0

Results:
Lamp 1=1(Always ON) ; Lamp 2 = (A+B)

Case 5- Relay contact CR2-2 fails shorted


A
0 0 1 1

B
0 1 0 1

Lamp 1
1 1 0 1

Lamp 2
1 1 0 0

Results:
Lamp 1=A + B ; Lamp 2 = A

Question 2:

Predict how the operation of this motor control circuit will be affected as a result of the following faults. Consider each fault independently (i.e. one at a time, no multiple faults):

"Stop" pushbutton switch fails open: Relay contact CR1-1 fails open: Relay contact CR1-2 fails open: Relay coil CR1 fails open: For each of these conditions, explain why the resulting effects will occur.

Solution:
When there is no fault, the above circuit is known as holding or latching circuit. Once the pushbutton Start is pressed, it will excite relay coil CR1 and consequently the relay contact CR1-1 will provide path for current, even after releasing the pushbutton. Relay contact CR1-2 will be ON to make the motor ON. To stop the motor, Stop pushbutton (normally closed) will be pressed.

Case 1- "Stop" pushbutton switch fails open


In this condition, the relay coil CR1 will never get excited. So both contacts will not be ON. Consequently, Motor run lamp and Motor will not be ON.

Case 2- Relay contact CR1-1 fails open


In this condition, the relay coil CR1 will get excited up till Start pushbutton is pressed. As CR1-1 will never be ON, so coil will de-excite after releasing the start pushbutton. Consequently, Motor run lamp and Motor will be ON only when Start pushbutton is pressed.

Case 3- Relay contact CR1-2 fails open


In this condition, Motor run lamp will work as it should, but the motor will never ON because of open condition of CR1-2.

Case 4- Relay coil CR1 fails open


When CR1 coil fails open, neither relay contact CR1-1 nor CR1-2 will be ON. Hence, motor will never be ON. The Motor run lamp will glow as the start pushbutton is pressed, but it will also turn OFF after releasing Start pushbutton.