PEA Modular Substation PROJECT

PEA Contract No.

-------------- Modular Substation

Group A Substation :Chiang Mai 5, Phitsanulok 6 , Nakhon Sawan 4 Customer Equipment : : LOXLEY PUBLIC COMPANY LIMITED MOBILE OFFICE Module D

Subject

Air Flow Calculation Rev.1

For Approval

3354/8-9 Manorom Bldg., 3rd Fl., Rama 4 Rd., Klongton, Klongtoey, Bangkok Thailand Tel : 02 685 8600 Fax 02 685 8699

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8

SUMMARY OF COOLING LOAD CALCULATION CUSTOMER INFO : ALSTOM BUILDING


Item Exterior wall 1 (north) Exterior wall 2 (East) Exterior wall 3 (South) Exterior wall 4 (West) From Partition From Ceiling From Floor From People From Lights From Motor 12022.4 Heat Gain (BTU/h) --400.12 400.12 240.6 526.29 1000 140

Air Flow Calculation

PROJECT INFO : MODULE C -22KV SWITCHGEAR

175.8

344.11 807.84

From Appliance (22 kv Switchgear and LB) From Misc Sources at 100% load factor

BTU/H

Room Heat Gain Total

---

16,057.28

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


From Ventilation From Infiltration BTU/H Appalatus Load Total GRAND TOTAL HEAT GAIN 836.2

974.58

1,810.78 = 17,868.06 BTU/H

TON OF REFRIGELATION = 17,868.06/12000 Ton Refrigeration SELECT AIR CONDITION SPLIT TYPE

18000

= 1.489 TON

BTU/H or 1.5

SUMMARY OF INDUCED DRAUGHT VENTILATION FOR TRANSFORMER ROOM


once). Select Fan Diameter 8 inch (Dia 20.32 cm) 3 sets ( Operate 2 sets per First Step: First Fan (Left) or Third fan (Right) will be alternately operated in every 12 hrs. will be operated Second Step: if the temperature room reach to 40C, Second Fan (Center) Select Incoming air cross section under floor = 30 x 30 sq.cm. = 900 sq.cm with filter and screen guard under floor Select Incoming air cross section pass transformer 50 kVA = 2820 sq.cm with screen and guard block out under transformer 1. HEAT GAIN Calculation Use Timer switch to control two steps,

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


1.1 DATA FOR CALCULATION 22 KV SWITCHGEAR CONTAINER See Drawing no.

PEA-MDL-AG-L-001 SHEET 1 AND 2, SHEET 1 3200 mm. Or

PEA- MDL-AG- L-002 SHEET 1 ,C&t-1149-01-001 Dimension of container W X L x H = 3400 x 9000 x

1 m = 3.2809 ft

3400 x 7000 x 3200 mm. Or 22.966 X 10.498 ft

Dimension of only switchgear container 1m = 3.2809 ft

W x L x H = 11.155 X 29.528 X 10.498 feet

WXLxH=

Section for cooling load calculation

W x L x H = 11.155 X

volume =2689.437 cu.ft 2000 x 3200 mm. = 768.444 cu.ft Or

is for cool 22 kv six switchgear

and one load break switch W X L x H = 3400 x volume

- Section for Induced Draght Ventilation 1m = 3.2809 ft

W X L X H = 11.155 X 6.562 X 10.498 ft 50 KVA transformer

Temperature data from typical design from LA CROSSE WISCONSIN Page 49 as attachment - SUM OUTSID INSIDE F - DIFFE

Is for air ventilation one

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


MER - DRY E F - 95 - 76 Over all Heat Transfer Coefficient sq.ft F
-

RENC E - 78 - 65 U - 17 - 11 = 1/R Btu per hr

BULB POINT

- WET

Resistance to heat flow R = 1/U = x3/k3+ 1/f2) 1/ Btu per hr sq.ft F

1/f1 +x1/k1+ x2/k2+

f1 1.46

= Coefficient of Surface Conductance Btu per hr sq ft F = Coefficient of Surface Conductance

inside air film

f2

outside air film

= 6

Btu per hr sq ft F air still =1.46-1.63 air move 7.5 mile/h = 4 air = 1/8

move at 15 mile/h =6
-

x1 = thickness of metal Material for uniform material inch


GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


-

x2 = thickness of polyurethane Material for uniform material 2 inch

x3 = thickness of metal Material for uniform material inch

= 1/8

K1 =thermal conductivity of metal sq ft per degree F

= infinity

Btu in. per hr

K2 =thermal conductivity of polyurethane = 0.17 per hr sq ft per degree F

Btu in.

K3 =thermal conductivity of metal sq ft per degree F

= infinity

Btu in. per hr

R = 1/U =

1/f1 +x1/k1+ x2/k2+ x3/k3+ 1/f2)

1/ Btu per hr sq.ft F


-

= 1/1.46 +1/8 /infinity +2/0.17 +1/8 /infinity + 1/6 = 0.6849 + 0 + 11.76 + 0 + 0.166 = 12.62

Resistance to heat flow (R)

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


Over all Heat Transfer Coefficient (U) = 1/R = 1/12.62 = 0.079 BTU/hr sq.ft. F correction factor for solar radiation Type of surfaces Dark-colored surfaces such as Slate Roofing Tar Roofing Black Plaints Medium-colored surfaces such as Unpainted wood Brick Red tile 6 4 6 15

see Ref Refrigeration and air condition table 10.5

Allowance for Solar Radiation (F) East wall 8 South Wall 5 West wall 8 Flat roof 20

Dark cement

Red gray or green paint Light-colored surfaces such as White stone White paint Light-Colored cement 4 2 4 9

1.2
.

STEP FOR HEAT GAIN CALCULATION


GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


Assume Transformer room temperature = 104F Outdoor temperature

Switchgear room temperature = 78C

1.2.1

A x U x TD

Heat Gain through Exterior Walls of Transformer Room A = Exterior wall Area (North) = N/A

= 95C

Q=

Btu per hr Sq.ft F

U = Over all heat transfer coefficient =

N/A

sides of the wall or roof N/A

TD = Difference in temperature between the air on the two = Transformer room 104 F -Switchgear room 78 F =

Calculated in Switch Gear Room Part ]

Q = N/A [ Heat Gain of Transformer Room is not

1.2.2 Heat Gain through Exterior Walls Correction factor of solar Radiation) ft = 241.185 sq.ft A = Exterior wall Area (East) =

Q = A x U x (TD + 7 m x 3.2 m = 22.97 x 10.5 0.079

Btu per hr. Sq.ft F

U = Over all heat transfer coefficient =

sides of the wall or roof


.

TD = Difference in temperature between the air on the two

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


= Outside 95 F -Switchgear room 78 F = 17 F

Q = 241.185 x 0.079 x ((95-78)+ 4) Q = 400.12 BTU/H

1.2.3 Heat Gain through Exterior Walls Correction factor of solar Radiation) Correction factor of solar Radiation see =

Q = A x U x (TD + table 10.5

10.5 ft = 117.128 sq.ft Btu per hr Sq.ft F

A = Exterior wall Area (South)

3.4 m x 3.2 m = 11.155 x 0.079

U = Over all heat transfer coefficient =

sides of the wall or roof

TD = Difference in temperature between the air on the two = Outside 95 F -Switchgear room 78 F = 17 F

Q = 117.128 x 0.079 x ((95-78)+ 2) 1.2.4 Heat Gain through Exterior Walls Correction factor of solar Radiation) Q = 175.8 BTU/H

Q = A x U x ( TD + table 10.5

ft = 241.185 sq.ft

A = Exterior wall Area (west)

Correction factor of solar Radiation see =

7 m x 3.2 m = 22.97 x 10.5 0.079

Btu per Hr Sq.ft F


.

U = Over all heat transfer coefficient =

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


TD = Difference in temperature between the air on the two = Outside 95 F -Switchgear room 78 F = = 400.12 BTU/H 17 F

sides of the wall or roof

1.2.5

Heat Gain through Partition Walls

Q = 241.185 x 0.079 x ((95-78)+ 4)

11.155 x 10.5 ft = 117.128 sq.ft Btu per hr. Sq.ft F

A = Partition wall Area (North)

Q = A x U x TD

3.4 m x 3.2 m = 0.079

U = Over all heat transfer coefficient =

sides of the wall or roof 26 F

TD = Difference in temperature between the air on the two = Transformer room 104 F -Switchgear room 78 F = 117.128 x 0.079 x 26 240.6 BTU/H

Correction factor of solar Radiation) 11.155 ft = 256.23 sq.ft Btu per hr Sq.ft F
.

1.2.6 Heat Gain through Ceiling Walls A = Ceailing wall Area =

Q = A x U x ( TD + 7 m x 3.4 m = 22.97 x

U = Over all heat transfer coefficient = 0.079

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


TD = Difference in temperature between the air on the two = Outside 95 F -Switchgear room 78 F = 17 F

sides of the wall or roof

[Table 10.5]

Correction factor of solar radiation on ceiling walls = 9 Q = 256.23 x 0.079 x (17+9) 526.29 BTU/H

1.2.7 Heat Gain through Floor Walls 11.155 ft = 256.23 sq.ft Btu per Hr Sq.ft F A = Ceiling wall Area

7 m x 3.4 m = 22.97 x 0.079

Q = A x U x TD

U = Over all heat transfer coefficient =

sides of the wall or roof Q 1.2.8 Q

TD = Difference in temperature between the air on the two = Outside 95 F -Switchgear room 78 F = = 256.23 x 0.079 x 17 = 344.11 BTU/H 17 F

conditioning manual Table 3-14 People x Sensible Heat Value

Heat Gain From People (Occupanted) see ref Trane air Sensible Heat Gain QS = No. of

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


Latent Heat Gain QL = No. of

People x Latent Heat Value = 330 = 670 = 1000 BTU/h BTU/h BTU/h table 3-14

For Laboratory Sensible Heat value For Laboratory Latent Heat value

Total Heat Gain = Qs + QL = 330 + 670

Lights x 3.4 x allowance factor open lamp less than 6 Lamps 1.1 as

1.2.9

Heat Gain From Light

Total Watt of Fluorescent

12 Lamps open for service day ,normal Ballast Electronic allowance factor =

as 120 121

Conventional Ballast allowance factor = 1.2 Q = 6 x 36 w x 3.4 x 1.1 = 807.84

BTU/H 1.2.10

Break and bus bar )


.

Heat Gain From Appliance (22 kv Switchgear and Load

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


See Ref Data Power loss from manufacturer

Load Break Sw. + Busbar loss )x 3.414 x 553 ) + (5 x 469) = 2898 W x 150 w = 150W

Q =( Total Watt loss of switchgear + watt loss of Total watt loss of Switchgear = ( 1 Watt loss of load Break SW
2

=1

[ Average Bus bar Current ]

I = Current pass Bus bar about 1250 A

Busbar loss =3 x I x rho x L/A

Sq.mm /m [ Ref.ABB manual 10 Table1-15 Page32 ]


th

Rho = Resistivity of copper = 0.01785 ohm. L = Length of Busbar in meter = = 800 sq.mm

3.290+1.250 = 4.540 m.

A = Cross section of Busbar

0.01785 x 4.54 / 800 = 473.5 w Q Q = =

Bus bar loss = 3 x 1250 x 1250 x

( 2898 +150 + 473.5) x 3.414 12022.4 BTU/H

1.2.11

Heat Gain From Motor

Heat Gain From Electric motor


.

See Ref Trane Air conditioning Manual table 3-16

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


NAMEPLATE RATING, HP APPROXIMATE EFFICIENCY HEAT GAIN FOR

BTUH PER HP CONTINUOUS RUN

Up to to 1 1 to 5 7 to 20 OVER 20

60 70 80 85 88

4200 3600 3200 3000 2900

Q = Nameplate motor x heat gain btu/hp 1/30 hp fan motor select 4200

In switchgear building have one up to Q = 1/30 x 4200

1.2.12

Heat Gain for Ventilation air /Infiltration See Ref

= 140 BTU/H

1.2.12.1 Heat Gain for Ventilation air

recommends 20 cfm per Occupant for a

Trane air conditioning manual

table 3-22

Laboratories The outdoor air

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


must be reduced to the design temperature . This represents a

load on the air conditioning equipment

Sensible heat QS

cfm. = 95 F Room = 78 F 367.2 BTU/H HRI)

Q = Total of Occupants in To = Outside temperature Ti = Inside temperature

= 1.08 Q (To - Ti )

Qs = Latent Heat

1.08 x 20 x (95-78) QL

= 0.7 Q ( HRO

Humidity of outside air

105 grains/lb

H RO at 95F DB and 76 F WB =

Humidity of inside air

71.5 grains/lb 71.5) = 469 BTU/H

H Ri at 78 F DB and 65 F WB = QL = 0.7 x 20 x (105-

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


Total Heat Gain = Qs +QL = 367.2 + 469 = 836.2

BTU/H

1.2.12.2 Heat Gain for Infiltration INFILTRATION THROUGH WINDOWS Type of w windo Metal Sash Description of window

See Ref Trane air conditioning manual Table 3-21 (CFH/ft) Wind MPH 7 1/2 Velocity, 15 70 74 32

Non-weather stripped Locked Non-weather stripped UnLocked Weather stripped UnLocked

33 34 13

See Drawing No. as item 1.1 +(2.4 x 2)+(2.4 x2)+(1.6 x 2) 2)+(0.8 x 2) in meter = 32.8 x 3.2809 = 107.6 lin ft

Parameter of each window = (2.4 x 2) +(2.4 x 2) +(2.4 x 2) +(2 x = 32.8 meter

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


Flow rate = Sensible heat QS 13 x 107.6 = CFH or

1398.8/60 = 23.31 CFM

CFM = 95 F Room = 78 F (95-78) = 427.97 BTU/H HRI)

Q = Total of Occupants in To = Outside temperature Ti = Inside temperature Qs = 1.08 x 23.31 x

= 1.08 Q (To - Ti )

Latent Heat

QL

= 0.7 Q ( HRO

Humidity of outside air

105 grains/lb

H RO at 95F DB and 76 F WB =

Humidity of inside air

71.5 grains/lb 71.5) = 546.6 BTU/H

H Ri at 78 F DB and 65 F WB = QL = 0.7 x 23.31 x (105-

Total Heat Gain = QH +QL =

427.97 + 546.6 = 974.58 BTU/H

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8

2.3 FAN FOR SWITCHGEAR AND TRANSFORMER ROOMS As E.I.T For the cooling air requirement of the transformer rated 50 KVA Service Transformer Power dissipation Pv = no load loss + Load Loss at 75 celcius see Ref Data power loss from manufacturer as annex 2 data = 125 + 775 watt Ventilation Fan Pv = 900 watt

Define Incoming air cross section

Transformer and more than 0.05 sq.m

> 0.001 sq.m x KVA of

0.001 x 50 > 0.05 sq.m > 500 sq.cm

Exhaust air must installed fan and ventilate air out more than 8.40 cu.m/min .kwloss at full load 6.4.12.3.2 MIN
.

As Standard of EIT 2001-51 item 6.4.12.3.1 and item CFAN > 8.40 x KW LOSS CU.M /

1 m= 3.2809 ft

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


CFAN > 35.316 x 8.40 x KW LOSS CFAN > 296.65 x KWLOSS

CFM CFM

KWLOSS Full Load Loss of 50 KVA Transformer = 0.9 KW CFM

CFAN > 296.66 x 0.9

267

CFM

REFERENCE
1.

.. 3003-40 2547

2. 3. TRANE AIR CONDITIONING MANUAL LA CROSSE WISCONSIN 1965 4. ABB MANUAL 11 EDITION
5.

PAGE 159-169 10 Edition


th

. . 2549

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


6

.. 2551

ADDITIONAL REFERENCE

1. ABB SWITCHGEAR MANUAL 9TH EDITION PAGE 154 2. ENERGY EFFICIENCY GUIDE FOR INDUSTRY IN ASIA PAGE2 3. TRANE AIR CONDITIONING MANUAL LA CROSSE WISCONSIN PAGE
49

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8

ABB SWITCHGEAR MANUAL 9TH EDITION

PAGE 154

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8

ENERGY EFFICIENCY GUIDE FOR INDUSTRY IN ASIA PAGE2

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


TRANE AIR CONDITIONING MANUAL LA CROSSE WISCONSIN

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8


FAN CONTRAINER LOGIC CONTROL DIAGRAM

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8

GRID

11 KV SWITCHGEAR (S18B1) FOR CCG HDS PROJECT PANEL A6 & B8