Pathfinder 48V-3kW Modular Switched Mode Rectifier System

010-537-B2

This page intentionally left blank.

Argus Technologies Ltd. Burnaby, British Columbia. Telephone: 604 436 5900 Fax: 604 436 1233 Argus Technologies reserves the right to make changes to the products and information contained in this document without notice. Copyright 2008 Argus Technologies Ltd. Argus is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Printed in Canada.

Visit www.argus.ca

Pathfinder 48V-3kW Modular Switched Mode Rectifier System


010-537-B2

The following documents and drawings are included in this manual to provide the necessary information required for installation, operation and fault diagnosis of the unit: Specifications, Pathfinder 48V-3kW: CSA/NRTL Equivalence: Warranty Policy: 010-537-B1 Rev C 048-554-10 048-507-10

Safety, Installation and Operation Instructions: 010-537-C0 Rev C Notice, Pathfinder 3kW: Outline Drawings, 19 Cabinet: Outline Drawings, 23 Cabinet: Outline Drawing, Power Module: Customer Connections, Cabinet Backplane: Spare Parts List, Pathfinder 48V-3kW: Factory Service Information: 954-330-10 030-594-06 030-577-06 010-537-06 030-577-08 010-537-G0 048-527-10

Argus Technologies Ltd. Printed in Canada. 2004 Argus Technologies Ltd. ARGUS is registered trademark of Argus Technologies Ltd. All Rights Reserved.

010-537-B2 Rev D WC

MANUAL ADDENDUM Unit Description: Pathfinder 3kW Rectifier System Manual P/N: 010-537-C0 Applies to Manual Revision: C
# 1 Date 04-06-15 Page# 11 Line# 1 Correction to be implemented Replace Section 2.2.11 with the following: 2.2.11 Forced Cooling Each module is equipped with a rear-mounted fan. The fan operates typically at temperatures above 0C. Cooling of the unit is front to rear with the hot exhaust on the back. Correct text from 3/4" cable knockouts to 1 cable knockouts. Correct Current Limit (range and default setting) from 140A to 125A.

2 3

13 24

23 14

MANUAL ADDENDUM
Authorized by: FORM 954-010-10 WD 010537c0c_1_Addendum1.doc

SPECIFICATIONS FOR ARGUS TECHNOLOGIES SWITCHED MODE RECTIFIER PATHFINDER 48V-3KW Pow er M odule Output Voltage: Current: Maximum Power: Regulation: Transient Response: Time Stability: Temperature Stability: Electrical Noise: 48 to 58VDC (standard) 42 to 58VDC (extended) 55ADC nominal (70ADC maximum) 3000W continuous/module 0.2% 25mV line and load (0.2% minimum slope) [static] 2ms to 0.1% of output for 50 to 100% load step 1% deviation for 50 to 100% load step 0.1% per year <100ppm/C over the operating range <22dBrnC (voice band) <10mVRMS to 10MHz (wide band) <150mVp-p to 100MHz <60dBa @ 3ft. (1m) The unit meets requirements of: ICES-003 Class B FCC Part 15, Subpart B, Class B Semiconductor fuse 80A, 140VDC; 200kA interrupting capacity

Acoustic Noise: EMI:

Fuse-Type/Rating:

In Accordance with FCC requirements, we provide the following statement as specified in the FCC guidelines for conformance to part 15, Class B: NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help.

ARGUS TECHNOLOGIES LTD.

010-537-B1 Rev C Page #1 of 2

SPECIFICATIONS FOR ARGUS TECHNOLOGIES SWITCHED MODE RECTIFIER PATHFINDER 48V-3KW Po w er M odule Input Voltage: Current: Power Factor: T.I.F. (Current): Efficiency: Source Impedance: Fuse Type/Rating: Recommended Feeder Breaker: Input Transient Suppression: M iscellaneous Cabinet Size: Cabinet Mounting: Module Weight: Alarm Connection Ratings: Env ironm en t al Temperature: Humidity: Elevation: Saf et y -40 to 149F (-40 to 65C) [standard] -40 to 158F (-40 to 70C) [storage] 0 to 95% non-condensing -1640 feet to 9180 feet (-500 m to 2800 m) 10.5" H x 17/21" W x 15" D (267mm H x 432/533mm W x 381mm D) 19/23" flush/offset mounting 21lb. (9.6kg) 60VDC, 0.5A maximum 176 to 275VAC (45 to 70Hz) 16.2A (208VAC nominal) @ 3000W/module >0.99 true (50 to 100% load) <100 at 100% load 90% @ 100% load (208VAC nominal) <5% inductive or resistive Fast acting 25A, 10kA interrupting capacity at 250VAC 25A (240VAC) Meets ANSI/IEEE C62.41 Category B3

!
Number of Power Modules 14

"

and

#$!

standards met.

Recommended Connect ion Wire Sizes (as per NRT L/C) NOTE: Check with local and/or national electrical codes for specific input wiring requirements, including temperature de-rating factors, etc. For operation e/w 25A feeder breaker @ 30C: Minimum Module Input Wire Size 2 10 AWG (6 mm ) for each module

NOTE: Each feeder breaker serves as a disconnect device for its associated module.

The above information is valid at the time of publication. Consult factory for up-to-date ordering information. Specifications are subject to change without notice.

ARGUS TECHNOLOGIES LTD.

010-537-B1 Rev C Page #2 of 2

CSA/NRTL MARKS BACKGROUND


What are the CSA and NRTL?
CSA (Canadian Standards Association also known as CSA International) was established in 1919 as an independent testing laboratory in Canada. CSA received its recognition as an NRTL (Nationally Recognized Testing Laboratory) in 1992 from OSHA (Occupational Safety and Health Administration) in the United States of America (Docket No. NRTL-2-92). This was expanded and renewed in 1997, 1999, and 2001. The specific notifications were posted on OSHAs official website as follows: Federal Register #: 59:40602 - 40609 [08/09/1994] Federal Register #: 64:60240 - 60241 [11/04/1999] Federal Register #: 66:35271 - 35278 [07/03/2001] When these marks appear with the indicator C and US or NRTL/C it means that the product is certified for both the US and Canadian markets, to the applicable US and Canadian standards. (1) Argus rectifier and power system products, bearing the aforementioned CSA marks, are certified to CSA C22.2 No. 950 and UL 1950, or CSA/UL 60950. As part of the reciprocal, US/Canada agreement regarding testing laboratories, the Standards Council of Canada (Canadas national accreditation body) granted Underwriters Laboratories (UL) authority to certify products for sale in Canada. (2) Only Underwriters Laboratories may grant a licence for the use of this mark, which indicates compliance with both Canadian and US requirements. (3)
The product on which either of these marks appear has been certified by CSA as meeting applicable Canada/US standards.

The product on which this mark appears has been certified by UL as meeting applicable Canada/US standards.

What are NRTLs and what do they do?

NRTLs are third party organizations recognized by OSHA, US Department of Labor, under the NRTL program. The testing and certifications are based on product safety standards developed by US based standards developing organizations and are often issued by the American National Standards Institute (ANSI). (4) The NRTL determines that a product meets the requirements of an appropriate consensus-based product safety standard either by successfully testing the product itself, or by verifying that a contract laboratory has done so, and the NRTL certifies that the product meets the requirements of the product safety standard. (4)

When was the NRTL started and who governs it?

In 1983, in a suit brought on by an independent testing laboratory, OSHA was court ordered to remove specific references to UL (Underwriters Laboratories) and FMRC (Factory Mutual Research Corporation) from its regulations. In 1988, OSHA revised its regulations to remove those references and the NRTL program was established. The NRTL Program is both national and international in scope with foreign labs permitted.

References: Information in this document has been developed from the official websites of the respective organizations. (1) www.csa-international.org (2) www.scc.ca (3) www.ulc.ca (4) www.osha.gov

048-554-10-I1 Rev C (2004/02)

argusdcpower.com

WARRANTY AND REPAIR INFORMATION


Warranty Policy
Argus Technologies Ltd. warrants all equipment manufactured by it to be free from defects in parts and labor, excluding third party OEM materials (example: air conditioners, batteries), for a period of two years from the date of shipment from the factory. For third party products the OEMs warranty shall apply. The liability of Argus applies solely to repairing, replacing or issuing credit (at Argus sole discretion) for any equipment manufactured by it and returned by the customer during the warranty period. The terms of the warranty are Ex Works (EXW) from Argus factory service location. Argus reserves the right to void the warranty if: (1) identification marks or serial numbers are removed or altered in any way, (2) invoice is unpaid, or (3) defect is the result of misuse, neglect, improper installation, environmental conditions, non-authorized repair, alteration or accident. Argus shall not be liable to the customer or other parties for any loss of profits, loss of use, costs for removal or installation of defective equipment, damages or consequential damages based upon equipment failure during or after the warranty period. There shall be no other obligations either expressed or implied. Argus will not honor warranties for batteries and other third party products without prior written Argus authorization.
Factory Service Centers Canada and International Argus Technologies Ltd. ATTN: RMA Returns 7033 Antrim Avenue Burnaby, BC, V5J 4M5 Canada Tel: +1 604 436 5900 +1 604 436 1233 Fax: Email: returns@argusdcpower.com USA Argus Technologies Inc. ATTN: RMA Returns 3116 Mercer Avenue Bellingham, WA, 98225 USA Tel: +1-360 756 4904 +1-360 647 0498 Fax: Email: returns-usa@argusdcpower.com Asia-Pacific PCM Electronics (Dong Guan) Co., Ltd. Hongli Industrial Area, Miaobian, Liaobu Town, Dongguan City, Guangdong Province, 523400 China Tel: +86 755 8895 3310 +86 755 8895 3307 Fax: Authorized Service Center Argentina Argus Technologies de Argentina Belen 315, Capital Federal, Buenos Aires, 1407l Argentina Tel: +54 (11) 4672 4821 +54 (11) 4504 4698 Fax: Cell: +54 9 (11) 4993 9996 Email: lkleiman@argus.ca Asia Argus Technologies Asia Pte Ltd Blk 6 Tagore Lane #160 Singapore 787570 Tel: +65 6458 8900 +65 6458 2122 Fax: Australia CPS National 8/376 Newbridge Rd Moorebank, NSW, 2170 Australia Tel: +61 02 9822 8977 +61 02 9822 8077 Fax: Australia/New Zealand Alpha Power Systems Pty Ltd Unit 3, 30 Heathcote Road Moorebank, NSW, 2170 Australia Tel: +61 02 9602 8331 +61 02 9602 9180 Fax: Century Yuasa 37 - 65 Colbalt Street Carole Park QLD 4300 Australian Sales & Service Tel: +61 07 3361 6587 +61 07 3361 6705 Fax: New Zealand Sales & Service Tel: +64 9 978 6689 +64 9 978 6677 Fax: Canada Compower Systems Inc. 118 Tiffield Road Toronto, ON, M1V 5N2 Canada Tel: +1 416 293 3088 +1 416 293 0671 Fax: Europe Alpha Technologies Europe Ltd. Cartel Business Estate Edinburgh Way Harlow, Essex, CM20 2DU UK Tel: +44 1279 422110 +44 1279 423355 Fax: Mexico & Central America Technologies Argus First De Mexico SA de CV Anatole France No. 17 Col. Polanco Mexico City, 11560 Mexico Tel: +52 55 5280 6990 +52 55 5280 6585 Fax: South America Argus Technologies Argentina Santo Tome 2573, Capital Federal Buenos Aires, 1416 Argentina Tel: +54 11 4504 4698 +54 9 11 4993 9996 Cell: E-pager: 541149939996@nextel.net.ar Turkey IPC Enerji Elk San ve TIC AS Inonu cad. Kanarya sok. No:20 Yenisahra - Kadikoy Istanbul, Turkey Tel: +90 216 317 41 42 +90 216 472 90 66 Fax:

Freight Policy

Customer is responsible for all shipping and handling charges (COD and freight collect will not be accepted without prior approval from Argus Technologies).

Terms of Payment (North America)

Payment terms are net 30 days subject to prior credit approval. All other orders require payment before shipping.

Terms of Payment (International)


Payment terms are subject to prior approval and are typically through Tele-Transfer.

Return Material Policy

Our RMA policy is designed to ensure prompt, efficient and high quality factory service. A Return Material Authorization (RMA) number must be obtained before products can be accepted for servicing by the Argus factory. For returns to an authorized service center (refer to Authorized Service Centers for locations), please consult the individual service center for specific return policies and instructions. To obtain a RMA number for a factory return, customers must call the appropriate location with the product serial and model number, as well as a brief description of the problem, shipment instructions and billing details. The original packing container should be used whenever possible. Both the shipping documents and the outside of the box must have the RMA # clearly marked and the product shipped prepaid to the Argus factory service center. Argus will endeavor to repair products within five working days of receipt. Repairs to the returned product are warranted for a period of six months. A service charge may be applied if no fault is found in the returned product. Argus will not accept products without an RMA number.

Business Hours

Argus North American office hours are 7:30 am to 5:00 pm (Pacific Standard Time) Monday to Friday.

048-507-10-I1 Rev S (09/2007)

Canada and USA toll free 24 hour emergency technical support: +1 888 GO ARGUS (462 7487)

Outside North America: +1 604 436 5547

IMPORTANT SAFETY INSTRUCTIONS


SAVE THESE INSTRUCTIONS: This manual contains important safety and operating instructions for Pathfinder 48V-3kW (24V-3kW) rectifier series.

1.

Please read this manual thoroughly prior to use to become familiar with the rectifier's numerous features and operating procedures. To obtain a maximum degree of safety, follow the sequences as outlined. This manual provides warnings and special notes to the user. Points that are vital to the proper operation or safety of the user display the heading: WARNING. Before using the rectifier, read all instructions and cautionary markings on: (1) rectifier, (2) the battery, and (3) the equipment connected to the rectifier. Do not expose rectifier to rain or snow. CAUTION - Unless otherwise noted, use of an attachment not recommended or sold by the rectifier manufacturer may result in a risk of fire, electric shock, or injury to persons. CAUTION - Do not operate the rectifier if it has received a sharp blow, been dropped, or otherwise damaged in any way return it to a qualified service center for repair. CAUTION - Do not disassemble the rectifier take it to a qualified service center for servicing. Incorrect reassembling may result in a risk of electrical shock or fire and may void the warranty.

2.

3.

4. 5.

6.

7.

Table of Contents
1.0
1.1 1.2 1.3 1.4 1.5

INTRODUCTION ..................................................................................................................1
Scope of the Manual .....................................................................................................................1 Argus Numbering System .............................................................................................................1 Notes to the User ..........................................................................................................................1 Product Overview ..........................................................................................................................2 Part Numbers and List Options.....................................................................................................3

2.0

2.1 2.1.1 2.1.2 2.1.3 2.1.4 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.6.1 2.2.6.2 2.2.6.3 2.2.6.4 2.2.6.5 2.2.6.6 2.2.6.7 2.2.6.8 2.2.6.9 2.2.6.10 2.2.7 2.2.7.1 2.2.7.2 2.2.7.3 2.2.7.4 2.2.7.5 2.2.7.6 2.2.7.7 2.2.7.8 2.2.7.9 2.2.7.10 2.2.7.11 2.2.7.12 2.2.7.13 2.2.8 2.2.9 2.2.10 2.2.11 2.2.12 2.2.13 2.2.14 2.2.15

DESCRIPTION OF FEATURES, ALARMS AND CONTROLS...........................................4

3.0

3.1 3.2 3.3 3.4 3.4.1

INSTALLATION INSTRUCTIONS .......................................................................................12


Tools Required ..............................................................................................................................12 Inspection ......................................................................................................................................12 Preparation/Mounting ....................................................................................................................12 Cabinet Grounding, Wiring and Connections ...............................................................................13 Chassis Ground .....................................................................................................................13

Cabinet Features...........................................................................................................................4 Cabinet Descriptions ..............................................................................................................4 Cabinet Alarms.......................................................................................................................5 Remote Equalize Control .......................................................................................................5 Remote Monitoring and Control.............................................................................................5 Power Module Features ................................................................................................................5 LED Indicators........................................................................................................................5 OFF/ON (O/I) Button..............................................................................................................6 Liquid Crystal Display (Optional) ...........................................................................................6 Control Buttons (Included with LCD Option) .........................................................................7 True Module Fail Alarm .........................................................................................................7 Major/Module Fail Alarms ......................................................................................................7 Remote Shutdown............................................................................................................7 Output Fuse Open............................................................................................................7 Input Fuse Open ..............................................................................................................7 AC Mains Fail...................................................................................................................7 High Voltage Shutdown....................................................................................................7 Thermal Shutdown ...........................................................................................................8 UPF Fail / Primary Power Circuit Shutdown....................................................................8 No Output Power..............................................................................................................8 Local Shutdown................................................................................................................8 Start Delay........................................................................................................................8 Minor Alarms ..........................................................................................................................8 VAC Meter Fail.................................................................................................................8 AC Mains Low ..................................................................................................................8 AC Mains High .................................................................................................................8 Fan Fail ............................................................................................................................9 Over Temperature ............................................................................................................9 Low Output Voltage..........................................................................................................9 Current Limiting/Short Circuit Protection..........................................................................9 Power Limiting..................................................................................................................9 Temperature Sense Fail...................................................................................................10 Fan Speed Error...............................................................................................................10 High Output Voltage.........................................................................................................10 Local Access Alarm (only with optional LCD)..................................................................10 Soft Start ..........................................................................................................................10 Over Voltage Protection (OVP) and High Voltage Shutdown (HVSD)..................................10 AC Inrush/Transient Suppression ..........................................................................................10 Input/Output Fuses.................................................................................................................10 Demand Based Forced Cooling.............................................................................................11 Battery Eliminator Operation..................................................................................................11 Start Delay .............................................................................................................................11 Float/Equalize/Test Modes.....................................................................................................11 Security Access Codes ..........................................................................................................11

3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 3.5

4.0

4.1 4.2 4.2.1 4.2.2 4.3 4.4 4.5 4.5.1 4.5.1.1 4.5.1.2 4.5.1.3 4.5.1.4 4.5.1.5 4.5.1.6 4.5.1.7 4.5.1.8 4.5.1.9 4.5.1.10 4.5.1.11 4.5.1.12 4.5.2 4.5.2.1 4.5.2.2 4.5.2.3 4.5.2.4 4.5.2.5 4.5.2.6 4.5.2.7 4.5.2.8 4.5.2.9 4.5.2.10 4.5.2.11 4.5.2.12 4.5.2.13 4.5.2.14 4.5.2.15 4.5.2.16 4.5.3 4.5.3.1 4.5.3.2 4.5.3.3 4.5.3.3 4.5.4 4.5.4.1 4.6 4.7 4.7.1

OPERATION AND ADJUSTMENTS ...................................................................................16


Startup and Reset Procedure (after initial system installation) ....................................................16 Module Installation and Removal..................................................................................................16 Installing Power Modules .......................................................................................................16 Removing Power Modules .....................................................................................................16 Menu Structure..............................................................................................................................16 Normal Mode Operation................................................................................................................16 Menu Descriptions.........................................................................................................................17 Status Menu ...........................................................................................................................17 Module ID #......................................................................................................................17 Module Settings (Float, Equalize, Slope, Current Limit, etc.)..........................................17 I/P V (Input Voltage).........................................................................................................17 Fan Speed........................................................................................................................17 Fan Set.............................................................................................................................17 Int. Amb Temp (Internal Ambient Temperature) ..............................................................19 Heatsink Temp .................................................................................................................19 P/I Lim Alarm (Power/Current Limit Alarm) .....................................................................19 Remote Access ................................................................................................................19 Remote Adjust..................................................................................................................19 LCL Access Alm (Local Access Alarm) ...........................................................................19 Software Version ..............................................................................................................19 Adjustments Menu .................................................................................................................19 Float Voltage ....................................................................................................................19 Equalize Voltage ..............................................................................................................20 Slope % ............................................................................................................................20 Current Limit.....................................................................................................................20 Start Delay........................................................................................................................21 HV SD Level ADJ (High Voltage Shutdown Level Adjust) ..............................................21 Low O/P Alarm .................................................................................................................21 High O/P Alarm ................................................................................................................21 Backlite Tmout..................................................................................................................21 Temp Disp C/F .................................................................................................................21 Protected Adjustments .....................................................................................................22 P/I Limit Alarm (Power/Current Limit Alarm)....................................................................22 Equalize Timeout..............................................................................................................22 Display Calibrate ..............................................................................................................22 Local Access Alarm..........................................................................................................22 Set Security Code ............................................................................................................22 Remote Communications.......................................................................................................22 Remote Access ................................................................................................................22 Remote Adjust..................................................................................................................23 Module ID# .......................................................................................................................23 Baud Rate ........................................................................................................................23 Test Mode ..............................................................................................................................23 Manual Test......................................................................................................................23 Pathfinder Module Factory Defaults and Ranges.........................................................................24 Miscellaneous Defaults/Adjustments/Controls ..............................................................................25 Adjusting the LCD Viewing Angle..........................................................................................25 Multiple Cabinet Connections (RS-485)........................................................................................26 Connecting the SM0X Panel (RS-485) .........................................................................................26 Communications using a PC/Terminal (through SM0X RS232)...................................................27 Remote Terminal Status Screen...................................................................................................28

AC Feeder Protection/Sizing..................................................................................................13 AC Input Connections ............................................................................................................13 DC Output Connections .........................................................................................................13 Alarm and Control Connections.............................................................................................14 Remote Communications Connections..................................................................................15 Initial Startup and Checkout..........................................................................................................15

5.0
5.1 5.2 5.3 5.4 6.1

REMOTE COMMUNICATIONS............................................................................................26

6.0

MAINTENANCE & SERVICE...............................................................................................29


Maintenance ..................................................................................................................................29

6.2 6.2.1 6.2.2 6.2.3 6.2.3.1 6.2.3.2 6.2.4

Service...........................................................................................................................................30 Tools Required.......................................................................................................................30 Fan Replacement...................................................................................................................30 Fuse Replacement .................................................................................................................31 AC Fuse Replacement .....................................................................................................31 DC Fuse Replacement.....................................................................................................32 MOV Replacement.................................................................................................................32

List of Figures
Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure 1 - Front View of Pathfinder 48V-3kW Cabinet (with modules) ............................................2 2 - Front View of Pathfinder 48V-3kW Modules .....................................................................2 3 - Front View of Pathfinder 48V-3kW Cabinet (modules removed) ....................................4 4 - Module Performance with Power Limiting ........................................................................9 5 - Rear Bus Bar Configuration................................................................................................14 6 - Side Access Termination ....................................................................................................14 7 - Pathfinder LCD in Normal Mode.........................................................................................17 8 - Pathfinder Menu Tree ..........................................................................................................18 9 - Pathfinder Communications Connections ........................................................................26 10 - Remote Terminal Screen ...................................................................................................28 11 - Fan Removal .......................................................................................................................30 12 - Pathfinder Cabinet (rear view, cover removed) ..............................................................31 13 - Detail of Fuse Placement ..................................................................................................31

List of Tables
Table Table Table Table Table 1 2 3 4 5 Alarm and Control Wiring Connections ..............................................................................15 Adjustments Menu Defaults .................................................................................................24 Remote Communications Menu Defaults............................................................................24 Test Menu Defaults................................................................................................................24 Navigation and Status Commands ......................................................................................27

1.0 1.1

INTRODUCTION Scope of the Manual This instruction manual explains the installation, interconnection and operation of Argus Technologies' Pathfinder 48V-3kW (24V-3kW) modular, switched mode rectifier systems. The topics covered include: product specifications, features, installation and configuration, operation and maintenance. To aid the user with installation and operation, frequent reference is made to fold-out drawings located in the rear of the manual. NOTE: All references to the Pathfinder 48V-3kW (i.e. 48 VDC output) rectifier system within this manual also include the Pathfinder 24V-3kW (i.e. 24 VDC output) rectifier system, unless specified otherwise.

1.2

Argus Numbering System Argus Technologies uses an eight digit drawing number system which is broken into three blocks. The first three digits describe the category of the product: i.e. rectifier or converter. The next three digits indicate the sequence in which the product number was allocated in that particular category. The last two digits indicate the type of drawing; e.g.: 05 ........Schematic 06 ........Outline Drawing 08 ........Customer Connections Drawing 20 .......Main Assembly Argus Technologies uses an eight digit part numbering system for all components and sub assemblies. Each part is referenced by its own unique number.

1.3

Notes to the User This manual has special notes for the user. Points that are important to the performance or ease of use of the equipment are covered by a notation that is in Bold Italic typeface.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 1 of 32

1.4

Product Overview The Pathfinder 48V-3kW (24V-3kW) rectifier system uses a high frequency, switched mode conversion technique to provide a fully regulated and isolated DC output from the AC mains. A complete rectifier system consists of one or more power modules and a common cabinet enclosure. Rectifier power modules are hot swappable meaning they can be inserted or removed from the cabinet without cutting power to or from the system or the load (see rectifier removal procedure in installation section for more details). Additional power modules can be included with the system at time of ordering or added after the cabinet has been installed. The cabinet has connections for AC input, DC output, and various alarm/control relays. It also includes two RS-485 connectors for communications with the SM0X series of supervisory control panels as well as other rectifier cabinets. The Pathfinder 48V-3kW (24V-3kW) rectifier system is designed to operate with Argus SM series of intelligent supervisory control panels. This allows the user to setup, control and monitor the entire power system and ancillary components from one central, easy-to-use source.

FIGURE 1 - FRONT VIEW OF PATHFINDER 48V-3KW CABINET (WITH MODULES)

FIGURE 2 - FRONT VIEW OF PATHFINDER 48V-3KW MODULES

010-537-C0 Rev C Page # 2 of 32

ARGUS TECHNOLOGIES

Pathfinder power modules can be adjusted and monitored locally with the inclusion of an optional LCD and control-key interface. The Pathfinder systems use positive ground only. 1.5 Part Numbers and List Options The Pathfinder 48V-3kW (24V-3kW) is available with the following part numbers and list options: Description Part Number/List Option

Pathfinder 48V-3kW power module ...............................010-537-20 Pathfinder 24V-3kW power module ...............................010-539-20 Basic unit................................................................................*List 0 Standard temperature, 0 to +65 Deg. C ...............................List 40 Extended temperature, -40 to +65 Deg. C............................List 42 Gray finish..............................................................................List 55 No LCD ..................................................................................List 80 With LCD ...............................................................................List 81 Pathfinder 19 cabinet....................................................030-594-20 24 VDC/110A output ...............................................................List 1 48 VDC/55A output .................................................................List 2 Center mount........................................................................*List 19 Flush mount (optional for 19) ...............................................List 21 Gray finish..............................................................................List 55 DC rear output adapters........................................................List 81 DC output blank plate............................................................List 90 Power module blank plate .....................................................List 91 Pathfinder 23 cabinet....................................................030-577-20 24 VDC/110A output ...............................................................List 1 48 VDC/55A output .................................................................List 2 Center mount........................................................................*List 23 Flush mount (optional for 23) ...............................................List 25 Gray finish..............................................................................List 55 DC rear output adapters........................................................List 81 DC output blank plate............................................................List 90 Power module blank plate .....................................................List 91 DC side output adapter kit (optional).............................037-007-20 DC rear output adapter cover kit ...................................037-008-20
* Default option The above information is valid at time of publication. Consult factory for up-to-date ordering information.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 3 of 32

2.0 2.1

DESCRIPTION OF FEATURES, ALARMS AND CONTROLS Cabinet Features The Pathfinders cabinet contains connections for up to four rectifier power modules, AC input, DC output, several remote alarm/controls, and RS-485 communications. When the power modules are removed from the cabinet, all cabling connections to the cabinet are front-accessible with exception of DC outputs. DC connections are made at the rear of the cabinet to easily accomodate direct connections to vertical bus bars. An optional kit is available if side output adaptors are desired. FIGURE 3 - FRONT VIEW OF PATHFINDER 48V-3KW CABINET (MODULES REMOVED)

2.1.1

Cabinet Descriptions

A brief description of each cabinet feature is described below:

1 2 3 4 5 6 7 8

Module Negative ( - ) Bus Bar Connection Module Positive ( + ) Bus Bar Connection 48/24 VDC Polarizing Pin Module AC Input Connector Module Control/Alarm Connector Cabinet AC Wireway Cover (Removable) Side Output Adapters for DC Connections (Optional Kit) Universal Mounting Bracket
* Not all features appear as displayed on all models.

010-537-C0 Rev C Page # 4 of 32

ARGUS TECHNOLOGIES

2.1.2

Cabinet Alarms

The 23 cabinet has four rectifier fail alarms RF1, RF2, RF3, RF4. The 19 cabinet has three. Each alarm is associated with a rectifier power module (i.e. Power module 1 is for RF1, etc.). Alarms are extended from the cabinet for remote monitoring. These alarms all use the same common signal output and provide contact closure in an alarm condition. All alarms are real time and therefore do not latch. The alarm contacts are fail safe and will extend an alarm even without a DC power source. See drawings 030-577-08 and 030594-08 at the rear of the manual for alarm terminal locations. 2.1.3 Remote Equalize Control

A remote equalize control is available on the cabinet for placing the power modules in equalize mode. This feature operates when a positive or negative DC signal is applied to the REQ terminal. 2.1.4 Remote Monitoring and Control

All local controls and monitoring is accessible via the RS-485 serial communications interface. The Pathfinder cabinet provides two connections for serial communications with other rectifier cabinets as well as supervisory and control panels. This allows rectifier cabinets to be interconnected or daisy-chained together. 2.2 Power Module Features The power module converts AC line voltage ranging from 176 to 275 VAC to 48 or 24 VDC. The following section details the various features of the power modules: 2.2.1 LED Indicators

The LED indicators provide visual indication of module operational status and alarms. The indicators and associated colors are as follows:

AC AC

AC Mains OK (Upper Green LED) This indicator illuminates when AC input to the Pathfinder is within the valid range (176 275 VAC). It will flash when out of the normal range, see below. Flashing AC Mains OK (Upper Green LED) The upper green LED will flash when the input voltage is out of range, but the unit will continue to operate down to 70 VAC, (i.e. Current limit gradually reduces automatically to approx. 50% of max. load). Below this point, the module will shutdown, indicating an AC Mains Fail condition. Module ON/OK (Lower Green LED) The lower green LED illuminates when the module is running and sourcing power normally. The indicator will turn off under the following conditions: Remote or local shutdown Over voltage protection (OVP) shutdown Thermal shutdown Startup pending

ON

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 5 of 32

ON
FAIL

Flashing Module On (Lower Green LED) The lower green LED will flash once for every 20% (approx.) of the max. output current (70A for 48V unit, 140A for 24V unit). To view output current while the module is online, quickly press and release the power button. Module FAIL/Major Alarm (Red LED) This indicator illuminates if the module is unable to source power or experiences any of the following conditions: Remote or local shutdown Output or input fuse blown AC Mains Input Fail OVP shutdown Thermal shutdown UPF fail No output power Startup pending Over temperature standby Minor Alarm (Flashing Red LED) The red LED will flash during the following conditions: VAC meter fail AC mains input low AC mains input high Fan fail Over temperature Low output voltage Current limit Temperature Sense Fail Fan speed error High output voltage Menu access from local display Soft start

FAIL

2.2.2

OFF/ON (O/I) Button

The front panel off/on button shuts down the output power from the module. The button is also used to read the modules output current. To get a reading of output current, quickly press and release the power button. The lower green LED will flash for every 20% (approx.) of maximum output current. To shut the module down, press and hold the button for 3 seconds and release. Pressing and holding the button for longer than five seconds (and releasing) causes the module to shutdown and then restart immediately the Pathfinder interprets this as a remote signal to turn the unit on. 2.2.3 Liquid Crystal Display (Optional)

Pathfinder modules can be equipped with a 2 x 16 character liquid crystal display (LCD) panel for local control and monitoring. This enables all the modules operating parameters, status and alarms to be viewable from this display.

010-537-C0 Rev C Page # 6 of 32

ARGUS TECHNOLOGIES

2.2.4

Control Buttons (Included with LCD Option)

Modules with the LCD option have three control buttons located on the front panel. They are labeled with an up arrow ( ), down arrow ( ) and a curved arrow ( ). The up and down arrow buttons allow the user to scroll through the software menus and adjust values, whereas, the curved arrow button allows the user to enter functions and switch between float and equalize modes. 2.2.5 True Module Fail Alarm

The power modules have a true fail alarm. This provides a true indication of the power module's ability to source current. When the module's output current drops below 2.5% of the rated output, the Module Fail detection circuit is activated. This circuit momentarily ramps up the output voltage to determine if the module will source current. If no increase in current is detected, the Module Fail and No Output Power alarms are activated. The module will test every 60 seconds for the condition until current is detected. Output voltage ramping will cease upon detection of current. A minimum 2.5% load is required to avoid the No Output Power alarm. Activation of this alarm could indicate a failed module or a failed load. 2.2.6 Major/Module Fail Alarms

These alarms signify a complete failure or shutdown of the module. All the alarm conditions under this section are classified as major alarms. 2.2.6.1 Remote Shutdown

A module will turn off and extend an alarm when it receives a remote shutdown signal from the SM supervisory panel. 2.2.6.2 Output Fuse Open

This alarm indicates the modules output fuse has blown. 2.2.6.3 Input Fuse Open

This alarm indicates the modules input fuse has blown. 2.2.6.4 AC Mains Fail

This alarm is generated when the AC input voltage drops below 50V. 2.2.6.5 High Voltage Shutdown

This alarm is generated when the module enters HVSD mode (see OVP section).

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 7 of 32

2.2.6.6

Thermal Shutdown

A module will shutdown and extend an alarm if the internal ambient temperature exceeds 75C (167F). The module will restart when the ambient temperature drops below 70C (158F). The module will also shutdown if the heatsink temperature exceeds 130C (266F). When the heatsink temperature is <100C (212F) it will restart. The fan continues to operate during these shutdown conditions. See the over temperature section for more information. 2.2.6.7 UPF Fail / Primary Power Circuit Shutdown

This alarm is generated when the UPF section fails or primary power circuit goes into thermal shutdown. Current limit is reduced to 65 percent of the nominal output. 2.2.6.8 No Output Power

This alarm is generated when the module ceases to produce output power for any reason. 2.2.6.9 Local Shutdown

This alarm is generated when the module is shutdown form the local off/on button. 2.2.6.10 Start Delay

This function is initiated briefly during the modules startup phase to stagger start the modules. 2.2.7 Minor Alarms

These are alarms that require service, but have no immediate effect on module output. A flashing red FAIL LED signifies a minor alarm. All of the alarms under this section are classified as minor alarms. Output capacity may be reduced during some minor alarm conditions. 2.2.7.1 VAC Meter Fail

This alarm indicates that AC meter has failed. AC meter voltage is less than 50 VAC and output current is greater than 2.5 percent. This condition must exist for at least 30 seconds before the alarm is activated. 2.2.7.2 AC Mains Low

This alarm is generated when the AC input voltage drops below 176 VAC. In this situation, current limit setting is reduced (according with the input VAC) initially to 90% of 70A (140A) @170 VAC and continues automatically adjusting the current limit setting at a linear rate down to 30% at 70 VAC. If the AC mains voltage falls below 70 VAC, the module will shutdown and will not restart until the AC is greater than or equal to 176 VAC. 2.2.7.3 AC Mains High

This alarm occurs when the AC input voltage is higher than 275 VAC.

010-537-C0 Rev C Page # 8 of 32

ARGUS TECHNOLOGIES

2.2.7.4

Fan Fail

This alarm is generated when the fan has failed. The condition must exist for 20 seconds before the alarm is extended. 2.2.7.5 Over Temperature

Each module is protected in the event of an extreme increase in heatsink temperature. When the heatsink temperature exceeds 100C, the module's output current is reduced by 3.5% of maximum output current per C to keep the temperature of the power semiconductors within operating limits until maximum reduction at 115C. Beyond this point the module goes to standby mode. Normal capacity will be returned automatically when the heatsink temperature is reduced below 100C. 2.2.7.6 Low Output Voltage

This alarm is generated when the DC output voltage drops below the LVA setting. The alarm will clear when the voltage is 1V above the LVA setting for the 48V-3kW (and 0.5V above the LVAs setting for the 24V-3kW). 2.2.7.7 Current Limiting/Short Circuit Protection

Each module has an adjustable current limit range between 18 to 70A (36 to 140A for Pathfinder 24V-3kW). Maximum output current is constant up to short circuit conditions. The current limit function determines the maximum output current limit of the module, regardless of output voltage or power. 2.2.7.8 Power Limiting

Each module is designed to limit power output to the 3000W rating ( 100W). This enables more current to be supplied at lower voltages, which in turn reduces the time needed to recharge a discharged battery. FIGURE 4 - MODULE PERFORMANCE WITH POWER LIMITING

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 9 of 32

2.2.7.9

Temperature Sense Fail

This alarm is generated if any of the DC/DC converters internal temperature sensors fail. 2.2.7.10 Fan Speed Error

This alarm is generated when the fan is sending an incorrect signal. The module will continue to run normally during this condition. 2.2.7.11 High Output Voltage

This alarm is generated when the DC output voltage increases above the HVA setting. The alarm will clear when the voltage drops 1V below the HVA setting for the 48V-3kW (and 0.5V below the HVA setting for the 24V-3kW). 2.2.7.12 Local Access Alarm (only with optional LCD)

This alarm is generated when the front panel is displaying access to a menu item. 2.2.7.13 Soft Start

To eliminate an instantaneous demand on the AC source, a soft start feature is employed. Soft Start, sometimes referred to as current walk-in, works by gradually ramping the current limit up from zero to the actual or defined customer setting. The output voltage is ramped up from the stand-by voltage to the float voltage. The output current then increases at a rate of 5A per second for the 48V-3kW (10A per second for the 24V-3kW) module. 2.2.8 Over Voltage Protection (OVP) and High Voltage Shutdown (HVSD)

The Over Voltage Protection (OVP) and High Voltage Shutdown (HVSD) feature provides protection to the load from over voltage conditions originating from the rectifiers. It operates by shutting down the offending module when a high output voltage condition occurs. Indication is through a red LED. Modules will restart automatically when the OVP condition clears. However, if a backup power source is connected, and more than three over voltage conditions occur in one minute, the module will latch and remain shutdown (HVSD condition) until it is reset. When in HVSD pressing and releasing the O/I switch will restart the unit. 2.2.9 AC Inrush/Transient Suppression

The modules' inrush current is limited to less than three times the nominal line current to prevent surges on the AC line. Modules are capable of withstanding input lightning and transient surges in accordance with IEEE/ANSI C62.41 Category B3. 2.2.10 Input/Output Fuses

Each module is equipped with fuses. Abnormal or fault conditions may blow the input or output fuse causing the red Module Fail LED to illuminate.

010-537-C0 Rev C Page # 10 of 32

ARGUS TECHNOLOGIES

2.2.11

Demand Based Forced Cooling

Each module is equipped with a rear-mounted fan. The fan operates at temperatures above 0C. It will adjust its speed automatically based on the temperature of the air flow through the fan module. Cooling of the unit is front to rear with the hot exhaust on the back. 2.2.12 Battery Eliminator Operation

Modules maintain all specifications (except where indicated) with or without a battery attached to the output. However, if a battery or another unit in parallel is not present, there will be no monitoring or control activity if there is an AC power failure. 2.2.13 Start Delay

The modules are equipped with a delay timer in order to stagger start a series of modules to prevent excessive loading of generators upon start up. The built-in timer delays the AC start of the module depending on the value programmed. A minimum five second delay is preset to allow charging of the input capacitors. 2.2.14 Float/Equalize/Test Modes

Modules can operate in one of three modes at any given time. The float mode is the default operating mode, where the rectifiers are supplying normal output power to the load and/or batteries. The equalize mode is used when boost charging batteries. Lastly, the test mode offers an extended voltage range for testing special functions such as the LVD. NOTE: Exercise caution when using the Manual Test function in test mode. Adjustments to this feature will directly effect the modules output voltage and could result in a disruption of service. For example, decreasing the voltage below the LVD setting will engage the LVD and potentially cut power to the load.

2.2.15

Security Access Codes

An adjustable three digit security code can be programmed into the Pathfinder modules to prevent access to critical control functions from unauthorized users.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 11 of 32

3.0

INSTALLATION INSTRUCTIONS This section is provided for qualified personnel to install and interconnect to the supervisory panel.

3.1

Tools Required Slotted screwdriver (Blade size 1/4") #2 Phillips screwdriver (Tip size 3/16") 4-1/2 digit digital voltmeter Cutters and wire strippers (#10 to #22 AWG) [6 to 2.5 mm2] Adjustable 24/48 VDC load (optional) Crimper (optional for large gauge wire) Combination wrenches (Imperial measure)

3.2

Inspection All Argus products are shipped in rugged, double-walled boxes and suspended via solid inserts to minimize shock that may occur during transportation. Package assemblies and methods are tested to National Safe Transit Association (NSTA) standards. Before uncrating the unit, look for signs of damage to the shipping container. Next, uncrate the unit and inspect the exterior. If any damage is observed, contact the carrier immediately. Continue the inspection for internal damage. In the unlikely event of internal damage, please inform the carrier and contact Argus Technologies for advice on the impact of the damage. NOTE: Save the original shipping container. If the unit needs to be returned for service, it should be packaged in its original shipping container. If the original container is unavailable, make sure the unit is packed with at least three inches of shock-absorbing material to prevent shipping damage. Argus Technologies is not responsible for damage caused by the improper packaging of returned units.

3.3

Preparation/Mounting The rectifier cabinet has been designed for mounting in a standard 19 or 23 EIA relay rack. Mounting brackets accommodate both 1 or 1-3/4 rack spacing. The cabinet should be mounted to the rack using two, #12 24 x 1/2" screws in each bracket. A Philips-type screwdriver should be used to eliminate the possibility of slippage and scratching of the unit's exterior. The Pathfinder cabinet should be mounted in a clean and dry environment. Also, make sure there is sufficient space in front and behind the unit for ease of access and unrestricted airflow.

010-537-C0 Rev C Page # 12 of 32

ARGUS TECHNOLOGIES

3.4

Cabinet Grounding, Wiring and Connections WARNING: Hazardous AC voltages are present. Ensure power at the AC service panel is off before attempting work on the AC connections. Use a voltmeter to verify the absence of voltage. Clearly mark the correct polarity of the battery leads before commencing work on DC connections.

NOTE: Connections to the rectifier system should comply with all local electrical codes and ordinances.

3.4.1

Chassis Ground

The rectifier cabinet (or chassis) must be connected to the AC service ground for safety. This is accomplished by connecting the ground green lead of the AC input cable to the terminal marked with the ground symbol (see drawing 030-577-08, sheet 2 for details). 3.4.2 AC Feeder Protection/Sizing

Each power module should have a dedicated protection breaker. The feeder breaker acts as the disconnect device for the associated module. See specifications section at the beginning of the manual for recommended feeder breaker and wire gauge sizes. 3.4.3 AC Input Connections

NOTE: AC input wires should be tightly bundled and routed as far away as possible from the DC power wires to minimize EMI disturbances. Remove all modules from the cabinet. Remove the metal cover from the cabinet backplane to expose the AC input terminals TB1, TB2, TB3 and TB4. Each terminal relates to an individual power module. The wireway is designed for 3/4 cable knockouts. Attach the cable connectors to the wireway hole and route the AC cables through the holes. Secure the wires to the AC input terminals as required. Tighten the cable connector to the AC cable (conduit similar) [see drawing 030-577-06 for more information]. 3.4.4 DC Output Connections WARNING: Leave cables disconnected at battery and verify output polarity using a voltmeter. Make battery connections only after all other wiring is completed.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 13 of 32

NOTE: DC output wire must be UL approved File # B64801, XHHW or RHH/RHW (for Canadian users; RW90 Type). Control and sense wires must be UL approved Style 1015 (for Canadian users; TEW type).

FIGURE 5 - REAR BUS BAR CONFIGURATION

FIGURE 6 - SIDE ACCESS TERMINATION

DC output cables can be connected through the rear of the cabinet, or at the side. A side output adapters kit (037-007-20) is available for connection convenience [48V List 2 only for 23 cabinet] (see drawing 030-577-08, sheet 1 for details). Terminate cables leads with appropriate crimp lugs. Secure the positive and negative cable to the cabinet output post of the same polarity (i.e. +Vcable to +Vpost). Install the washers and nuts on top of the lugs in the same order in which they were shipped from the factory. Tighten the post nuts as per customer connections drawing 030-577-08. 3.4.5 Alarm and Control Connections

See drawing 030-577-08, sheets 1 and 2 for location of alarm and control terminals. Insert each wire into the appropriate terminal on TB5 and tighten. Route the alarm and control cables through the alarm wireway on the rear of the cabinet to the monitoring/control equipment as needed.

010-537-C0 Rev C Page # 14 of 32

ARGUS TECHNOLOGIES

TABLE 1 - ALARM AND CONTROL WIRING CONNECTIONS TERMINAL LABEL RF1 RF2 RF3 RF4 RFC REQ REQC NOTES: ALARM DESCRIPTION Module Fail 1 Alarm Module Fail 2 Alarm Module Fail 3 Alarm Module Fail 4 Alarm Module Fail Common Remote Equalize Control Remote Equalize Common DEFAULT SIGNAL TYPE NC* NC* NC* NC* COM** Input Neg (-) or Pos (+) COM

* RF1-4 are open and contacts will close upon alarm condition. ** RF1-4 relay contact commons are connected together and are available as RFC.

3.4.6

Remote Communications Connections

See remote communications section for details on remote communications connections. 3.5 Initial Startup and Checkout After completing the system wiring and installation, perform the following startup and test procedure to ensure proper operation. (1) Ensure all power modules are removed from the cabinet. Verify correct out put polarity using a voltmeter, and connect battery (if required) to the output of the system. Install power modules (see section 4.2 for details) and verify that the Module Fail LED(s) illuminate (assuming a battery is connected to the system providing backup power). This indicates correct output polarity. Verify AC input voltage is correct and turn on each AC input feeder breaker(s). The AC and ON LED(s) should illuminate and system will begin charging batteries. Test functionality of various module alarms and controls (see operations/adjustments section for details). In addition, perform a load test with the system using a resistive loadbox. In the adjustments menu, set float and equalize voltage to the levels specified by the battery manufacturer (see operations/adjustments section for details on float adjustment).

(2)

(3)

(4)

(5)

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 15 of 32

4.0 4.1

OPERATION AND ADJUSTMENTS Startup and Reset Procedure (after initial system installation) When the Pathfinder module is powered-up or reset, it will display the corporate name and product serial number and various identification messages. The three front panel LEDs will illuminate, however the FAIL LED should extinguish after the system has finished its soft start procedure. Next, the LCD will display the module's parameters as shown in Figure 7 in Normal operating mode.

4.2

Module Installation and Removal WARNING: Turn unit off before removing. WARNING: Do not force a module into position if it does not seat properly. All units are keyed to ensure that the correct module type is used. 4.2.1 Installing Power Modules

To insert a power module, place it on the cabinet bottom and slide into the rear connector in the backplane. Ensure that you tighten the bottom screws to the cabinet. The module will automatically power up within seconds. 4.2.2 Removing Power Modules

Press and hold the O/I button for at least three seconds this shuts down the modules output power. Loosen the two screws on the bottom of the module faceplate, grasp handle firmly and pull out of the cabinet. Wait two minutes for all LEDs to extinguish before handling. 4.3 Menu Structure On the Pathfinder version with no LCD, the menu interface is only available remotely through the SM0X supervisory panel or a computer terminal emulation program (refer to these product manuals for more information on the user interface). In both the Pathfinder LCD and no LCD version, the menu structure consists of two basic components: Menu Categories and Sub-Menu Items. To scroll through these items, press the and buttons to display the correct item and then the button to select that item/enter a submenu (this procedure is the same for both the Pathfinder and the SM0X supervisory panel). 4.4 Normal Mode Operation The Pathfinders default operation is in Float mode. The module ON LED and AC LED is illuminated and various identification messages are displayed on the LCD. See Figure 7 for a sample screen. When a user attempts to scroll through the menu, he will be prompted to enter a password before entering some submenus. See Figure 8 for locations. Once the correct password is verified, access will be granted. If no password is entered, the user will not gain access.

010-537-C0 Rev C Page # 16 of 32

ARGUS TECHNOLOGIES

FIGURE 7 - PATHFINDER LCD IN NORMAL MODE

4.5

Menu Descriptions The following section describes each of the Pathfinders menu items, including alarms, controls and configuration items. They are arranged as they would appear in the LCD menu. For a graphical representation of the Pathfinder software, command and menu structure, refer to the menu tree (Figure 8). 4.5.1 Status Menu

This menu category is used for reviewing module setup and status information. 4.5.1.1 Module ID #

Displays the assigned module identification number. Modules with the LCD option are assigned a factory default identification number of 01. The ID number is used for remote communications only. No user intervention is required for systems using the SM0X supervisory panel. 4.5.1.2 Module Settings (Float, Equalize, Slope, Current Limit, etc.)

This function allows the user to scroll through the various power system parameters. See Figure 8 for a detailed list. 4.5.1.3 I/P V (Input Voltage)

Displays the AC input voltage to the module. 4.5.1.4 Fan Speed

Displays the off/on status of the fan speed function. 4.5.1.5 Fan Set

Displays the off/on status of the fan.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 17 of 32

MODULE ID# = MODULE SETTINGS I/P V = FAN SPEED = FAN SET = INT AMB TEMP = HEATSINK TEMP I LIM ALARM REMOTE ACCESS REMOTE ADJUST LCL ACCESS ALM SOFTWARE VX.XX RETURN EXIT

FLOAT = XX.XV EQUALIZE = XX.XV SLOPE = X.XX% CUR LIM = XXXA STRT DLAY = XXXs O/P HV = XX.XV LOW O/P = XX.XV HIGH O/P = XX.XV BKLT TO = XXmin EQ TMOUT = XXXhr RETURN EXIT

FLOAT VOLTAGE EQUALIZE VOLTAGE SLOPE % CURRENT LIMIT START DELAY HV SD LEVEL ADJ LOW O/P ALARM HIGH O/P ALARM BACKLITE TMOUT TEMP DISP DEG C/F PROTECTED ADJUST RETURN EXIT

PROMPT FOR PASSWORD

P/I LIMIT ALARM EQUALIZE TIMEOUT DISPLAY CALIBRATE LOCAL ACCESS ALRM SET SECURITY CODE RETURN EXIT

PROMPT FOR PASSWORD

REMOTE ACCESS REMOTE ADJUST MODULE ID# BAUD RATE RETURN EXIT

PROMPT FOR PASSWORD

MANUAL TEST EXIT

FIGURE 8 - PATHFINDER MENU TREE

010-537-C0 Rev C Page # 18 of 32

ARGUS TECHNOLOGIES

4.5.1.6

Int. Amb Temp (Internal Ambient Temperature)

Displays the internal air temperature of the module. 4.5.1.7 Heatsink Temp

Displays the converters heatsink temperature. 4.5.1.8 P/I Lim Alarm (Power/Current Limit Alarm)

Displays the enable/disable status of the current/power limit alarm. 4.5.1.9 Remote Access

Displays the enable/disable status of the remote access function. This function is always enabled if no LCD is installed. 4.5.1.10 Remote Adjust

Displays the enable/disable status of the remote adjust function. This function is always enabled if no LCD is installed. 4.5.1.11 LCL Access Alm (Local Access Alarm)

Displays the enable/disable status of the local access alarm. Setting has no effect if no LCD is installed. 4.5.1.12 Software Version

Displays the current software version onboard the power module. 4.5.2 Adjustments Menu

This menu category consists of functions that can be adjusted by the user. It includes float and equalize voltage, slope, current limit, alarms, etc. See Table 2 for default settings and ranges for each item below. 4.5.2.1 Float Voltage

This is the modules default mode at startup and during normal system operation. This mode is indicated by the FL on the LCDs upper left corner. The float voltage cannot be changed when a module is off or in equalize mode. Similarly, it cannot be increased while the module is in current or power limit an error message will result. Float voltage should be adjusted to the level recommended by the battery manufacturer. NOTE: Since all modules are connected in parallel local adjustment of modules will cause interaction between units.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 19 of 32

To adjust float voltage follow the steps below: 1. Measure the battery voltage with a multimeter at the battery output posts or with the power systems meter. 2. Scroll to the float voltage item in the ADJUSTMENTS menu (Make sure the module is in float mode). 3. Using the arrow keys, adjust each modules float voltage up or down until the battery voltage is set to the desired level. Avoid putting the modules in current limit during this procedure. 4. Once the battery voltage is correct, fine tune the each modules output voltages to balance the current outputs equally. 5. With the multimeter, check that the battery voltage is correct.

4.5.2.2

Equalize Voltage

The equalize mode is used to equalize or boost charge a battery string. It is indicated by the EQ on the LCDs left corner. This mode can be selected by pushing the button and holding (for more than 3 seconds) while in normal operating mode, or via a remote command through the serial port, or remote hardware signal through the REQ terminal. The equalize voltage cannot be changed if the module is off and cannot be increased while in current or power limit an error message will result. Scroll to the Equalize item in the ADJUSTMENTS menu and follow the same series of steps as described above for the float voltage. 4.5.2.3 Slope %

This function allows the user to adjust the slope percentage. Output slope is a method of load sharing which operates by altering the output voltage regulation of the Pathfinder module. Output slope is factory default at 1% and it is recommended to leave it at that value. Slope settings must be the same for all rectifiers in that system and should be 1%. NOTE: Set slope before float or equalize adjustments.

4.5.2.4

Current Limit

This function allows the user to program the setting at which the current limit function engages. If the output current reaches this level, the output voltage will decrease and subsequently limit the output current of the module. A current limit alarm will also be extended. If the module is driven far into current limit, the output voltage may decrease to the point of a LOW O/P VOLTAGE alarm. During a MODULE FAIL condition, the CURRENT LIMIT alarm may be activated. This may indicate a high current condition inside the module.

010-537-C0 Rev C Page # 20 of 32

ARGUS TECHNOLOGIES

4.5.2.5

Start Delay

The modules are equipped with a delay timer in order to stagger start a series of modules to prevent excessive loading of standby generators upon start up. The timer delays the AC start of the module depending on the value programmed. Delay times range from 5 - 250 seconds in 5 second multiples. A minimum five second delay is preset to allow for charging of the capacitors. Delay is initiated upon application of AC. At the end of the delay period Soft Start is initiated and the module goes into Float mode by default. When active, the message START DELAY and the time remaining are displayed on the LCD. The START DELAY message is extended remotely in the Operation Status section of the Status screen. There is no delay when the module is returning to operation after a remote shutdown signal removal. The count can be aborted locally by pressing the key (local entry of equalize is inhibited during delay start). The count can also be remotely activated by toggling the remote shutdown control signal. 4.5.2.6 HV SD Level ADJ (High Voltage Shutdown Level Adjust)

This feature provides protection to the load from over voltage conditions originating from the power system. OVP cannot be adjusted while the PathFinder is operating in current limit or power limit. Minimum OVP adjustment is either the Float or Equalize level plus 1.0V, which ever is higher. OVP trigger hysteresis is 1.0V. The Module Fail LED will turn on and the Module Fail Relay will de-energize. The O/P HV SHUTDOWN and MODULE FAIL alarms will be extended remotely. The over voltage shutdown feature of the PathFinder is selective and operates at 5% higher voltage in a less than 2.5% load condition. 4.5.2.7 Low O/P Alarm

This function allows the user to program the setting for the low output voltage alarm. When the output of the module drops below this level, the LOW O/P VOLTAGE alarm will be extended remotely. The alarm has a fixed hysteresis of 1.0V for 48V units and 0.5V for 24V units. When the output rises the hysteresis voltage above this level, the alarm extinguishes. 4.5.2.8 High O/P Alarm

This function allows the user to program the setting for the high output voltage alarm. When the output of the module rises above this level, the HIGH O/P VOLTAGE alarm will be extended remotely. The alarm has a fixed hysteresis of 1.0V for 48V units and 0.5V for 24V units. When the output level the hysteresis voltage below this level, the alarm extinguishes. 4.5.2.9 Backlite Tmout

This function allows the user to adjust the duration that the LCD backlight stays on after the last keypress. 4.5.2.10 Temp Disp C/F

This function allows the user to toggle the display of ambient and heatsink temperature values between the Celsius and Fahrenheit scales.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 21 of 32

4.5.2.11

Protected Adjustments

This function allows the user to enter a list of password protected settings. 4.5.2.12 P/I Limit Alarm (Power/Current Limit Alarm)

When enabled, power limit and current limit conditions cause the Minor Alarm to be activated. The POWER LIMIT and CURRENT LIMIT alarms are extended remotely. This control toggles between the enabled and disabled states. Setting does not affect flashing "pl" & "cl" indicators which are always enabled. 4.5.2.13 Equalize Timeout

This adjusts the maximum time that the module will remain in equalize mode when equalize mode is selected locally or from the equalize key on the SM0X front panel. Equalize time-out is overridden by the remote equalize signal. 4.5.2.14 Display Calibrate

This function allows increases/decreases to output voltage display calibration offset. 4.5.2.15 Local Access Alarm

When this function is enabled, activity of the module control keys in the ADJUSTMENTS, REMOTE COMMUNIC and TEST MODE menus causes the Minor Alarm to be activated. The control toggles between the enabled and disabled states. 4.5.2.16 Set Security Code

This function allows the user to set the security codes for access to the Protected Adjust, Remote Communication and TEST menus. The security code is set one digit at a time with the or keys until the desired number is displayed and the key is used to select the number. Anytime a menu item that requires a password is selected, the message SECURITY = - - - will show and the first dash will be replaced with a zero as the first digit. 4.5.3 Remote Communications

This menu category consists of functions and controls related to remote communications between the module and a SM0X supervisory panel, a computer terminal emulation program, etc. 4.5.3.1 Remote Access

This function allows the user to enable/disable access to the module from a remote unit. It is always enabled on modules with no LCD. When set to LOCKOUT: All remote communications are disabled by this selection. If baud rate is set correctly, the module always responds "REMOTE LOCKOUT" to any received communication.

010-537-C0 Rev C Page # 22 of 32

ARGUS TECHNOLOGIES

4.5.3.2

Remote Adjust

This control allows the user to enable/disable remote adjustment control from specific menus. It is always enabled on modules with no LCD. When set to ACCESS: Full access is granted to all Setup, Adjustment and Remote Communication menu items. When set to LOCKOUT: Access is allowed only to the Status menu; accessing the Status menu causes the Status screen to be transmitted. Access is not allowed to the Adjustments and Test Mode menus; accessing the these menus causes the PathFinder to respond with "ADJUST LOCKOUT". Access must be allowed to the Remote Communications menu. The PathFinder security code is required to make any changes. 4.5.3.3 Module ID#

This control allows the user to set the module ID#. In order for a module to be correctly identified for remote communications, every module on the same RS-485 bus must be assigned a unique identification number. If two modules have the same ID#, a line conflict will occur which will result in garbled communications. 4.5.3.3 Baud Rate

This control allows the user to set the baud rate for communications between the module and a remote unit. 4.5.4 Test Mode

This menu category consists of a manual test function. It enables operators to check the functionality of the output voltage. 4.5.4.1 Manual Test

The simulated output voltage is adjusted by pressing the and buttons on the front panel. Manual Test mode is indicated by the "MT" beside the output voltage display. The purpose of this function is to provide an extended operating voltage range for testing power system parameters. NOTE: Exercise caution when using the Manual Test function in test mode. Adjustments in this mode will directly effect the modules output voltage and could result in a disruption of service. For example, decreasing the voltage below the LVD setting will engage the LVD and potentially cut power to the load.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 23 of 32

4.6

Pathfinder Module Factory Defaults and Ranges

TABLE 2 - ADJUSTMENTS MENU DEFAULTS


Submenu Item Float Voltage Programmable Range 24.0 - 29.0V 21.0 - 28.0V (24V-3kW) 48.0 - 58.0V 42.0 - 58.0V (48V-3kW) standard extended standard extended 27.5V 1% 140A 5 28.5V 22.0V 27.8V 5 Celsius Disable 30 hours N/A Enable 123 Default Setting (24VDC Systems) 27.0V 54.0V Default Setting (48VDC Systems)

Equalize Voltage Slope % Current Limit Start Delay HVSD Level (OVP) Low O/P Alarm (LVA) High O/P Alarm (HVA) Backlight Timeout Temp Display C/F P/I Limit Alarm Equalize Timeout Display Calibrate Local Access Alarm Set Security Code

25.0 - 31.0V (24V-3kW) 50.0 - 62.0V (48V-3kW) 0.2 - 2% 36 - 140A (24V-3kW) 18 - 70A (48V-3kW) 5 - 250 seconds 27.0 - 31.5V (24V-3kW) 54.0 - 63.0V (48V-3kW) 21.0 - 26.0V (24V-3kW) 42.0 - 52.0V (48V-3kW) 26.0 - 31.5V (24V-3kW) 52.0 - 63.0V (48V-3kW) 0 - 255 minutes Celsius/Fahrenheit Enable/Disable 1 - 255 hours N/A Enable/Disable 000 - 999

55.0V 1% 70A 5 57.50V 44.0V 55.5V 5 Celsius Disable 30 hours N/A Enable 123

TABLE 3 - REMOTE COMMUNICATIONS MENU DEFAULTS


Submenu Item Remote Access Remote Adjust Module ID # Baud Rate Programmable Range Enable/Disable Enable/Disable 01 - 99 1200 - 38400 baud Default Setting (24VDC Systems) Enable Enable 01 9600 baud Default Setting (48VDC Systems) Enable Enable 01 9600 baud

TABLE 4 - TEST MENU DEFAULTS


Submenu Item Manual Test Programmable Range 21.0 - 32.5 (24V-3kW) 40.1 - 62.2 (48V-3kW) Default Setting (24VDC Systems) N/A Default Setting (48VDC Systems) N/A

010-537-C0 Rev C Page # 24 of 32

ARGUS TECHNOLOGIES

4.7

Miscellaneous Defaults/Adjustments/Controls 4.7.1 Adjusting the LCD Viewing Angle

Adjustment of the viewing angle/LCD contrast is made as follows: press and hold the Enter () button. While depressing the Enter button, press the up () button. ADJUST VIEW ANGLE message should show up on the screen. Next, adjust the angle to setting desired using the up () and down () buttons. Press the Enter () button to return to normal mode.

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 25 of 32

5.0

REMOTE COMMUNICATIONS The Pathfinder rectifier system is optimized for remote communications. It can be controlled, monitored and tested via the SM0X intelligent supervisory panel or via an ASCII display terminal (through the SM0X RS232).

5.1

Multiple Cabinet Connections (RS-485) Cabinets can be daisy-chained together via the RS-485 interface. Refer to the customer connection drawings 030-577-08 for locations and pinout details of the SCI connectors. The interconnect cable is RJ11 (standard telephone type RJ12 connectors). Connect the cable from one connector labeled RS-485 to another connector labeled RS-485 on the next shelf.

5.2

Connecting the SM0X Panel (RS-485) Local control and monitoring can be accomplished by connecting the SM0Xs RS-485 interface. Connect the straight through cable (RJ12 connectors) to the SM0Xs RS-485 port from the Pathfinder cabinets RS-485 port.

Lan Interface

Modem

SM02
RS-232

RSM/CSM RS-485

RS-485 RS-485 RS-485 RS-485 RS-485 RS-485


Local Terminal

Pathfinder Power System

FIGURE 9 - PATHFINDER COMMUNICATIONS CONNECTIONS

010-537-C0 Rev C Page # 26 of 32

ARGUS TECHNOLOGIES

5.3

Communications using a PC/Terminal (through SM0X RS232) The Pathfinder is designed to communicate directly with an ANSI terminal to eliminate the need for additional software. Communication with a PC is also possible with a terminal emulation program such as PROCOMM or TELIX. Display information and setup parameters are virtually identical to that available from the built-in front panel keyboard and LCD. Before connecting the host equipment, ensure the communications access parameters, including default baud rate of your terminal is set to match the Pathfinder module. The default parameters are set to 8 data bits, 1 stop bits, and no parity. The remote terminal must be capable of handling continuous communications at the Pathfinders specified baud rate. Set the remote terminal for Half Duplex (Local Echo) communications in order to view commands entered. Once all hardware is setup and a communications link is established, you will need to know how to talk to the Pathfinder modules. There has to be DC power present at the output for the remote communications to function. There are five commands available for navigating the Pathfinder menus and retrieving status information. The and commands are used to scroll through menu items and change module settings. The command is used to select menu items and accept changes. The status command causes a formatted screen of information to be sent from the module containing the module settings and operating status. The Display command causes the PathFinder to respond with the 2-line x 16-character display information as found on the power module. Commands are not case sensitive and can be sent as either upper or lower case characters. Command String format: [ ...........command initiator character ## ........Module ID# 01 - 99; use 00 to broadcast the command to all modules @.........remote command character ] ...........command terminator character TABLE 5 - NAVIGATION AND STATUS COMMANDS

Command U D E S ?

Definition Up Down Enter Status Display

Description Scroll up or increase setting Scroll down or decrease setting Select menu item or accept module setting Send status screen Send display information

Command Example [01U] [01D] [00E] [10S] [08?]

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 27 of 32

5.4

Remote Terminal Status Screen The following is a typical screen page layout as the Pathfinder responds to the status command after selecting a module.

----------------------------------------- PathFinder Status V1.00 -------------------------------------------Module ID #: 1 Serial No: 1234 5678 Model: PFM 48V-3kW ------------------------------------------------------------------------------------------------------------------------OPERATIONAL STATUS Float/Equalize Mode Input Volts = xxxVAC Current/Power Limit Output Current = xx.xADC Output Voltage = xx.xVDC Fan Speed/Set = spd/spd Int Amb Temp = xxxC Manual Test Mode Remote Equalize Remote Shutdown START DELAY = xxx Sec Heat Sink Temp = xxxC SOFT START MODULE STATUS Float = xx.xVDC Equalize = xx.xVDC OVP Shutdown = xx.xVDC Low O/P Alarm = xx.xVDC Slope = x.xx% O/P I Limit = xx.xA Equalize Timeout = xxxhrs Start Delay = xxx Sec Backlight Tmout = xxx Min P/I Limit Alarm En/Dsabled Local Access Alarm E/Dable High O/P Alarm = xx.xVDC MODULE ALARMS REMOTE SHUTDOWN REMOTE EQUALIZE O/P FUSE OPEN I/P FUSE OPEN VAC METER FAIL AC MAINS FAIL AC MAINS HIGH FAN FAIL MODULE FAIL OVER TEMPERATURE O/P HV SHUTDOWN LOW O/P VOLTAGE CURRENT LIMIT THERMAL SHUTDOWN TEMP SENSE FAIL FAN SPEED ERROR POWER LIMIT UPF FAIL/PRI SD AC MAINS LOW Minor Alarm HIGH O/P VOLTAGE NO OUTPUT POWER LOCAL SHUTDOWN STARTUP PENDING OVERTEMP STANDBY

FIGURE 10 - REMOTE TERMINAL SCREEN Note: PFM (PathFinder, Modular) will appear on the module remote status screen as the unit type i.e. PFM 48V-3kW or 24V-3kW.

010-537-C0 Rev C Page # 28 of 32

ARGUS TECHNOLOGIES

6.0 6.1

MAINTENANCE & SERVICE Maintenance Although very little maintenance is required with Argus rectifier systems, routine checks and adjustments are recommended to ensure optimum system performance. Repairs should be done by qualified service personnel. The following table outlines several maintenance procedures for this rectifier system. These procedures should be performed once a year. WARNING: Use extreme care when working inside the rectifier cabinet while the rectifier system is energized. Do not make contact with live components or parts. HIGH VOLTAGE AND SHOCK HAZARD. WARNING: Ensure redundant rectifiers or batteries are used to eliminate the threat of service interruptions while performing maintenance on the systems alarms and control settings. Procedure Clean ventilation openings Inspect fans (if equipped) Inspect all system connections (retorque as necessary) Inspect batteries (consult battery manufacturer's recommended procedure) Verify alarm/control settings Verify float voltage New Setting Date

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 29 of 32

6.2

Service 6.2.1 6.2.2 Tools Required Slotted screwdriver (Blade size 1/2") #2 Phillips screwdriver (Tip size 3/16") 7/16 socket, rachet, and extension or nutdriver Pair of sidecutters (for MOV replacement only) Fan Replacement 1. Shut off the unit. 2. Remove the screws that secure the module to the cabinet and remove the module from the cabinet. 3. Turn the module around to face the back of the unit and remove the fan power lead wire connector from the cabinet. 4. Remove the four screws which secure the fan to the power module and remove the fan. 5. Install the replacement fan following the preceding steps in reverse order.

FIGURE 11 - FAN REMOVAL

010-537-C0 Rev C Page # 30 of 32

ARGUS TECHNOLOGIES

6.2.3

Fuse Replacement

FIGURE 12 - PATHFINDER CABINET (rear view, cover removed)

6.2.3.1

AC Fuse Replacement 1. Shut off the unit and remove the screws that secure the module to the cabinet and remove the module from the cabinet. 2. Turn the module around to face the back of the unit and remove the six screws securing the rear cover. 3. Remove the cover and locate the AC fuses (see Figure 13) on the vertical printed circuit board to the left side of the unit, they are the round cartridge fuses in the clip-style holder. 4. Remove the fuse(s) and install the new fuse(s), then replace the cover and secure with the screws and replace the module in the cabinet and secure with retaining screws.

DC FUSE AC FUSES METAL OXIDE VARISTOR (MOV)

FIGURE 13 - DETAIL OF FUSE PLACEMENT


SPADE TERMINATIONS

ARGUS TECHNOLOGIES

010-537-C0 Rev C Page # 31 of 32

6.2.3.2

DC Fuse Replacement 1. Shut off the unit and remove the screws that secure the module to the cabinet and remove the module from the cabinet. 2. Turn the module around to face the back of the unit and remove the six screws securing the rear cover. 3. Remove the cover and locate the DC fuse (see Figures 12 & 13) on the left of the main DC output socket. 4. Remove the old fuse and replace with a new fuse, then replace the cover and secure with the screws, replace the module in the cabinet and secure with the retaining screws.

6.2.4

MOV Replacement The MOVs (Metal Oxide Varistor) are used to protect the power modules from power line surges and lightning. High capacity surges may permanently damage MOVs but they are easily replaced in the field using the following procedure. 1. Shut off the unit. 2. Remove the screws that secure the module to the cabinet and remove the module from the cabinet. 3. Turn the module around to face the back of the unit and remove the six screws securing the rear main cover. 4. Remove the main cover and locate the MOVs (see Figures 12 & 13). 5. The MOV may be removed by using a pair of sidecutters to cut the leads. 6. Decontaminate the printed circuit board with flux remover or a similar cleaning compound to remove any metallic particles which may have been deposited when the MOV failed. 7. Install the replacement MOV pack printed circuit board by plugging it into the available spade terminations. 8. Replace the cover and secure with the screws, replace the module in the cabinet and secure with retaining screws.

010-537-C0 Rev C Page # 32 of 32

ARGUS TECHNOLOGIES

NOTICE
Due to continuing product improvements to the Pathfinder 48-3kW 24-3kW UPF, a module interlock feature has been added. This requires re-configuration when new Pathfinder modules are used with earlier production cabinets.

OPERATIONAL PROBLEM?
When the module is installed into earlier issued cabinets, both GREEN LEDs will not illuminate (on the front of the module), and the RED LED may or may not illuminate. As well, the rectifier module will fail to supply power.

If this module operates in this manner, please follow steps ! to ":


! Remove the module from the cabinet. # Locate the Interlock Select jumper at the bottom of the module back-plate (see below). $ Move the P21 (Interlock) jumper from the ON to the OFF position. " Install module into desired cabinet position.

954-330-10 Rev A

Date Issued: Oct.14, 1999

Argus Technologies Customer Service: 1-888-GO-ARGUS (Canada & USA), 1-604-436-5547 (International)

ARGUS TECHNOLOGIES SPARE PARTS LIST PATHFINDER 48V-3kW

DRAWING # 010-537-G0 Rev E Type W0 Page 1 of 5 APPROVED: ______________ ISSUED: ______________

ITEM

QTY

PART NO.

REV

DESCRIPTION

CIRCUIT DESIGNATION OR REMARKS

List 0; On Site: 1 2 3 4 5-10 1 1 1 2 707-123-20 747-105-20 460-187-10 460-190-10 Assy,PCB,Trans Protn,RSM 48/50 UPF Assy,Fan,12VDC,7W,107CFM,w/ taco & Temp Snsr Fu,80A 140VDC,1.65" Ctr Fu,13/32"x1-1/2",25A 250VAC,Fast Not Used (A1) EF1 F3(A2) F1,2(A1)

List 1; On Site Optional: None

List 2; Depot Repair (Internal Use Only): 11 12 13 14 15 16 17 18 19-22 23 24 25 26 27 28 29 30 1 5 6 7 1 6 2 5 322-005-10 320-001-10 320-013-10 322-015-10 322-004-10 322-013-10 322-016-10 330-032-10 1 2 2 2 1 1 1 1 611-127-19 545-541-10 567-162-10 561-191-10 561-024-10 545-592-10 567-202-10 424-036-10 A A C Tab,Prechrg,Hard-Tooled,Pathfinder, Ph Brz,Bare Conn,To Bus Bar,250 ADC (A2) J2,3(A2)

Insulr,30GSR,TO-264,Adh Back,w/ Mtg hole (Q3,4)(A2) Insulr,Slcn Rbr,TO-220 Adh Back, No Mtg Hole Insulr,Slcn Rbr,TO-218 Conn,1 Row,3 Pins,R Ang,Ml,Spcl, Tell Cu Pin,PCB Insulr,Slcn Rbr,Dual TO-264,Berg 1009 Sw,PB,SPST-NO,PCB Mnt,Vert,Mini,Blk Not Used Xstr,PNP,40V,MPS750,TO-92 Xstr,NPN,25V,MPS6601,TO-92 Xstr,NPN,65V,BC846A,SOT-23 Xstr,PNP,25V,ZTX749,TO-92 Xstr,PNP,40V,2N4403,TO-92 Xstr,PNP,60V,MMBT2907A,SOT-23 Xstr,PNP,80V,MMBTA56,SOT-23,hFE=50 min. Xstr,MOSFET,N-Chnl,0.5A 60V,2N7002, SOT-23 Q10(A1) Q7,9(A2),Q1,4,7(A1) Q3,5,8,17-19(A3) Q5,6,8,10(A2) Q2,5,8(A1) Q11(A1) Q1,2,6,12,13,15(A3) Q11,14(A3) Q4,7,9,10,16(A3) (D7,8)(A1) (Q9)(A1) P1(A1) (Q3+6)(A1) SW1(A1)

ARGUS TECHNOLOGIES SPARE PARTS LIST PATHFINDER 48V-3kW

DRAWING # 010-537-G0 Rev E Type W0 Page 2 of 5 APPROVED: ______________ ISSUED: ______________

ITEM

QTY

PART NO.

REV

DESCRIPTION

CIRCUIT DESIGNATION OR REMARKS Q1-4(A2) Q9(A1) Q3,6 (A1)

31 32 33

4 1 2 Or

330-072-10 330-079-10 330-080-10 330-058-10

Xstr,MOSFET,N-Chnl,500V 0.10 Ohm,Av, TO-264 Xstr,MOSFET,N-Chnl,500V 0.20 Ohm 0.42C/W,TO-247 Xstr,MOSFET,N-Chnl,500V 0.16 Ohm 0.35C/W,TO-247 Xstr,MOSFET,N-Chnl,500V 0.20 Ohm 0.34C/W,TO-247 Not Used

34-37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 3 2 1 1 3 1 2 3 2 6 1 4 5 1 6 5 1 4 2 1 4 161-001-10 161-027-10 161-032-10 300-026-10 301-010-10 303-005-10 303-020-10 303-021-10 303-029-10 303-036-10 303-510-10 303-522-10 304-011-10 305-001-10 310-008-10 310-009-10 310-010-10 310-012-10 310-013-10 312-018-10 312-027-10

Dio,Transzorb,500W 5V,SA5.0A Dio,Transzorb,500W 15V,SA15A Dio,Transzorb,Bidir,1.5KW 250V, 1.5KE250CA Dio Brdg,Std Rcvy,35A 1000V,Wire Ld Dio,Std Rcvy,1A 1000V,1N4007 Dio,Ultra Fast,4A 600V MUR460

D1(A4),D8,22(A3) D13(A1),D16(A2) D21(A2) D2(A1) D1,3,4(A1) D6(A1)

Dio,Ultra Fast,15A 600V,MUR1560,TO-220AC D8,10(A1) Dio,Ultra Fast,1A 600V,MUR160 Dio,Ultra Fast,1A 150V,SOD-87 Dio,Ultra Fast,1A 100V,BYD73B,Av rated, SOD81 D12(A1),D23,24(A2) D18,21(A3) D17,18,31-34(A2)

Dual Dio,Ultra Fast,2x15A 600V,MUR3060PT D9(A1) Dual Dio,Ultra Fast,2x15A 300V 1V, TO-247,STTH Dio,Schottky,1A 40V,1N5819 Dio,Hyper Fast,15A 600V,RHRP1560 Dio,Sig,Dual,2x250mA 70V,BAW56,SOT-23, Com Ad Dio,Sig,Schottky,Dual,2x100mA 30V, SOT-23,Com Cath Dio,Sig,Schottky,Dual,2x100mA 30V, SOT-23,Sers Dio,Sig,Schottky,Dual,2x100mA 30V, SOT-23,Com An) Dio,Sig,Dual,2x215mA 70V,BAV70,SOT-23, Comm-Cth Dio,Zener,500mW 20V 5%,1N5250B Dio,Zener,500mW 18V 5%,1N5248B Not Used D11-14(A2) D2-5,9(A2) D7(A1) D12,13,15,17, 20,24(A3) D2,5,6,9,23(A3) D14(A3) D3,4,7,16(A3 D1,10(A3) D11(A3) D1,6-8(A2)

ARGUS TECHNOLOGIES SPARE PARTS LIST PATHFINDER 48V-3kW

DRAWING # 010-537-G0 Rev E Type W0 Page 3 of 5 APPROVED: ______________ ISSUED: ______________

ITEM

QTY

PART NO.

REV

DESCRIPTION

CIRCUIT DESIGNATION OR REMARKS DS1(A4)

60 61 62-66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86

1 4

394-017-10 172-001-10

Dspl,LCD,2x16 Char,Yel LED,Blu Bkgd, +/-5V Sply

Temp Snsr,Lin PTC,LM335,10mV/deg.K,TO-92 U2(A1),U3,6(A2) U21(A3) Not Used

2 1 1 4 1 2 1 1 1 1 1 1 2 1 1 1 2 1 1 4 OR

340-411-10 340-413-10 341-016-10 341-017-10 341-036-10 341-207-10 343-212-10 344-020-11 345-001-10 346-076-10 346-087-10 360-019-10 360-031-10 360-217-10 364-012-10 366-094-10 366-097-10 367-207-10 369-250-10 385-023-10 385-022-10 368-012-11 385-018-10 385-005-10 A C

IC,SMD,V Ref,5.0V 0.5%,LM4040-5.0,SOT-23 U4,16(A3) IC,SMD,V Ref,5.0V 1%,REF02,SO-8 U15(A3)

IC,SMD,Op Amp,Dual,TLC277,500uV Ofs,SO-8 U10(A3) IC,SMD,Op Amp,Dual,TLC272,SO-8 U11,12,14(A3) U5(A4)

IC,SMD,Op Amp,Dual,Rail-to-Rail I/P,SO-8 U13(A3) IC,SMD,Comptr,Dual,LM2903,SO-8 IC,SMD,CMOS V Convtr,7662,SOIC IC,SMD,SMPS Ctrlr,MC33067,SO-16L, Ext Temp IC,SMD,Dio Array,SP721,SOIC IC,SMD,Lgc,74HC573,3-State Latch,SOIC IC,SMD,Lgc,74HC125AD,3-State Bfr,SO-14 IC,VR,Lin,Pos 5V 0.1A,LP2951ACM,SO-8 U2,3(A3) U1(A4) U1(A3) U4(A4) U3(A4) U2(A4) U24(A3)

IC,VR,Lin,Pos Adj 5-20V 1A,LM2941,TO-220 U4,5(A2) IC,Reg,Switchmode,PWM,SI9100,Plstc DIP IC,Dgtl Pot,64 Step,Quad,10K,Ext Temp, DIP IC,Lgc,4426,Inv,MOSFET Drvr,1.5A, Plstc DIP IC,Lgc,4424,Dual Non-Inv,MOSFET Drvr, 3A,PDIP IC,68HC11F1,w/ RSM 48/50 Fr Pnl uP Prgm IC,EPROM,27C512,Ext T,PFM Frmwr, Ext Volt Range Opto,Xstr Fairchild Opto,Xstr Fairchild Out,CTR 63-125%, CNY17F-2 Out,CTR 73-117%, MOC8102 U25(A3) U17(A3) U1(A1) U1,2(A2) U23(A3) U22(A3) U5-7,28(A3)

87 88 89 90-94

1 2 1

IC,LTC485I,RS-485/422 Drvr/Rcvr, Plstc DIP,Ext T

U30(A3)

Optoisolator,AND Out,H11L1 w/ Hysteresis U26,27(A3) Optoisolator,AC Inp,Xstr Out,H11AA4 Not Used U3(A1)

ARGUS TECHNOLOGIES SPARE PARTS LIST PATHFINDER 48V-3kW

DRAWING # 010-537-G0 Rev E Type W0 Page 4 of 5 APPROVED: ______________ ISSUED: ______________

ITEM

QTY

PART NO.

REV

DESCRIPTION

CIRCUIT DESIGNATION OR REMARKS C17(A3) C1,3,9(A4) C73-75(A3) C17(A1) C10(A1),C1(A2) C2,3,12,13(A2)

95 96 97 98 99 100

1 3 3 1 2 4 Or

221-003-10 221-002-10 201-019-10 194-023-10 196-033-10 193-025-10 193-019-11 192-001-10 191-054-10 200-017-10 200-158-10 200-128-10 200-019-10 200-111-10 200-150-10 200-156-10 200-091-10 200-505-10

Cap,SMD,Tant,2.2uF 25V 20%,3528 Cap,SMD,Tant,15uF 10V 20%,3528(B) Cap,SMD,Tant,22uF 25V 20%,7343, D or E case Cap,Polyest Film,330nF 400V 10%, 15mm Ld Sp Cap,Polyprop Film,4.7uF 400V 10%,Axl Cap,Mica,2.7nF 1000V 5%,0.234" Ld Sp, 0.21" Thk Cap,Mica,3.0nF 1000V 5%,0.234" Ld Sp, 0.21" Thk Cap,MLP,4uF 100V 10%,3 Ld/Side Cap,MLC,6.8uF 100V Y5U 20%,0.4" Ld Sp Cap,Elctlt,47uF 100V,Rdl Ld,5mm Ld Sp Cap,Elctlt,100uf 35V 20%,Rdl,3.5mm Ld, 105 deg.C Cap,Elctlt,100uf 35V 20%,Rdl,3.5mm Ld, 85 deg.C Cap,Elctlt,220uF 25V,Rdl Ld,5mm Ld Sp, 85 deg.C Cap,Elctlt,470uF 16V,105deg.C,5mm Ld Sp Cap,Elctlt,470uF 35V,Rdl,5mm Ld, 10mmx16mm Cap,Elctlt,470uF 450V,35x50 10mmLS, 85deg.C,Snap Cap,Elctlt,1200uF 75V,Rdl Ld,3-Pin Cap,Elctlt,390uF 80V,Rdl,5mm Ld Sp, 105.C,LowESR Not Used

101 102 103 104 105 106 107 108 109 110 111 112-115 116 117 118 119 120 121

2 4 1 3 1 1 1 2 5 2 6

C10,11(A2) C26,27,35,54(A2) C66(A3) C40,44,50(A2) C32(A1) C52(A2) C51(A2) C42,43(A2) C19,21-24(A1) C29,32 C81-86(A2)

1 1 2 2 9 4

121-504-10 170-013-10 160-014-10 160-030-10 264-085-10 264-104-10

Res,WW,5W,1.0 Ohm 5%,Vit Enam Thms,PTC,15 Ohm @25deg.C,265VAC MOV,420VAC 560VDC,Disc MOV,300VAC 385VDC 173J,20mm Disc Bead,Ferr,5mm OD 1.5mm ID Bead,Ferr,0.13" ODx0.05" ID,28 Matl, Coated

R24(A2) R9(A1) VR2,3(A1) VR1,4(A1) (D9)(A1) (D11-14)(A2) (C2,3,12,13)(A2)

ARGUS TECHNOLOGIES SPARE PARTS LIST PATHFINDER 48V-3kW

DRAWING # 010-537-G0 Rev E Type W0 Page 5 of 5 APPROVED: ______________ ISSUED: ______________

ITEM

QTY

PART NO.

REV

DESCRIPTION

CIRCUIT DESIGNATION OR REMARKS

Revisions: A B C D E 1998-06-04 1999-11-02 2000-02-01 2000-09-25 2005-06-07 First Release Added List 2, Items 11-121 List 2 title changed Items Affected: 23,27,111 List Option Affected: 2 Item Affected: 86

FACTORY SERVICE INFORMATION


Technical Support
Technical support staff are available for answering general questions related to installation, operation and maintenance of Argus products. In Canada and the USA, call Argus toll free 7:30 am to 5:00 pm Pacific Standard Time at:

+1-888 GO ARGUS
(+1-888-462-7487)
For emergencies, call +1-888-GO-ARGUS 24 hours a day, seven days a week. Customers outside Canada and the USA, call +1-604-436-5547 for technical support.

Factory Service Centers Canada and International Argus Technologies Ltd. ATTN: RMA Returns 7033 Antrim Avenue Burnaby, BC, V5J 4M5 Canada Tel: +1 604 436 5900 +1 604 436 1233 Fax: Email: returns@argusdcpower.com USA Argus Technologies Inc. ATTN: RMA Returns 3116 Mercer Avenue Bellingham, WA, 98225 USA Tel: +1-360 756 4904 +1-360 647 0498 Fax: Email: returns-usa@argusdcpower.com Asia-Pacific PCM Electronics (Dong Guan) Co., Ltd. Hongli Industrial Area, Miaobian, Liaobu Town, Dongguan City, Guangdong Province, 523400 China Tel: +86 755 8895 3310 +86 755 8895 3307 Fax: Authorized Service Center Argentina Argus Technologies de Argentina Belen 315, Capital Federal, Buenos Aires, 1407l Argentina Tel: +54 (11) 4672 4821 +54 (11) 4504 4698 Fax: Cell: +54 9 (11) 4993 9996 Email: lkleiman@argus.ca Asia Argus Technologies Asia Pte Ltd Blk 6 Tagore Lane #160 Singapore 787570 Tel: +65 6458 8900 +65 6458 2122 Fax: Australia CPS National 8/376 Newbridge Rd Moorebank, NSW, 2170 Australia Tel: +61 02 9822 8977 +61 02 9822 8077 Fax: Australia/New Zealand Alpha Power Systems Pty Ltd Unit 3, 30 Heathcote Road Moorebank, NSW, 2170 Australia Tel: +61 02 9602 8331 +61 02 9602 9180 Fax: Century Yuasa 37 - 65 Colbalt Street Carole Park QLD 4300 Australian Sales & Service Tel: +61 07 3361 6587 +61 07 3361 6705 Fax: New Zealand Sales & Service Tel: +64 9 978 6689 +64 9 978 6677 Fax: Canada Compower Systems Inc. 118 Tiffield Road Toronto, ON, M1V 5N2 Canada Tel: +1 416 293 3088 +1 416 293 0671 Fax: Europe Alpha Technologies Europe Ltd. Cartel Business Estate Edinburgh Way Harlow, Essex, CM20 2DU UK Tel: +44 1279 422110 +44 1279 423355 Fax: Mexico & Central America Technologies Argus First De Mexico SA de CV Anatole France No. 17 Col. Polanco Mexico City, 11560 Mexico Tel: +52 55 5280 6990 +52 55 5280 6585 Fax: South America Argus Technologies Argentina Santo Tome 2573, Capital Federal Buenos Aires, 1416 Argentina Tel: +54 11 4504 4698 +54 9 11 4993 9996 Cell: E-pager: 541149939996@nextel.net.ar Turkey IPC Enerji Elk San ve TIC AS Inonu cad. Kanarya sok. No:20 Yenisahra - Kadikoy Istanbul, Turkey Tel: +90 216 317 41 42 +90 216 472 90 66 Fax:

Training

Argus offers various levels of product and technical training. These workshops provide a mix of theory and hands on application for qualified customers. Please consult your sales representative for course schedules, locations and costs, or visit our website at www.argusdcpower.com.

Factory Repair and Servicing

All service, beyond initial adjustments, should be carried out by qualified factory service personnel. For these procedures, please contact Argus Technologies at the locations listed to the right.

Product Returns

Before returning any product for service, please obtain a Return Material Authorization (RMA) number from an Argus factory service representative. The representative will require the model and serial number, as well as a brief description of the problem prior to issuing the RMA number. All material must be pre-authorized before being returned. See document 048-507-10 Warranty and Repair Information for more details.

Moving and Storage

Units must be suitably packed in the original shipping container (or equivalent) prior to re-shipping. The box should be completely enclosed and constructed of wood or double-wall, corrugated cardboard. At least 3 of foam or shock absorbing packing material must surround the unit.

048-527-10-I1 Rev L (09/2007)

Canada and USA toll free 24 hour emergency technical support: +1 888 GO ARGUS (462 7487)

Outside North America: +1 604 436 5547