Introduction 10.1
Convention of direction 10.2
Conditions for direction comparison 10.3
Circulating current system 10.4
Balanced voltage system 10.5
Summation arrangements 10.6
Examples of electromechanical
and static unit protection systems 10.7
Digital/Numerical current differential
protection systems 10.8
Carrier unit protection schemes 10.9
Current differential scheme
– analogue techniques 10.10
Phase comparison protection
scheme considerations 10.11
Examples 10.12
References 10.13
Chap10-152-169 21/06/02 8:43 Page 153
10 . 3 C O N D I T I O N S
F O R D I R E C T I O N C O M PA R I S O N
The circulating current and balanced voltage systems of
Figures 10.1 and 10.2 perform full vectorial comparison
Id> Id> of the zone boundary currents. Such systems can be
Relay G Relay H treated as analogues of the protected zone of the power
system, in which CT secondary quantities represent
Figure 10.2: Balanced voltage system
primary currents and the relay operating current
corresponds to an in-zone fault current.
• 10 • These systems are simple in concept; they are
Most systems of unit protection function through the nevertheless applicable to zones having any number of
determination of the relative direction of the fault boundary connections and for any pattern of terminal
current. This direction can only be expressed on a currents.
comparative basis, and such a comparative measurement To define a current requires that both magnitude and
is the common factor of many systems, including phase be stated. Comparison in terms of both of these
directional comparison protection and distance quantities is performed in the Merz-Price systems, but it
teleprotection schemes with directional impedance is not always easy to transmit all this information
measurement. over some pilot channels. Chapter 8 provides a detailed
A major factor in consideration of unit protection is the description of modern methods that may be used.
method of communication between the relays. This is
covered in detail in Chapter 8 in respect of the latest
fibre-optic based digital techniques. For older ‘pilot wire’ 10 . 4 C I R C U L AT I N G C U R R E N T S Y S T E M
systems, only brief mention is made. For more detailed The principle of this system is shown in outline in
descriptions of ‘pilot wire’ techniques, see reference Figure 10.1. If the current transformers are ideal, the
[10.2] in Section 10.13. functioning of the system is straightforward. The
transformers will, however, have errors arising from both unacceptable. One solution is to include a stabilising
Wattmetric and magnetising current losses that cause resistance in series with the relay. Details of how to
deviation from the ideal, and the interconnections calculate the value of the stabilising resistor are usually
between them may have unequal impedances. This can included in the instruction manuals of all relays that
give rise to a ‘spill’ current through the relay even require one.
without a fault being present, thus limiting the
When a stabilising resistor is used, the relay current
sensitivity that can be obtained. Figure 10.4 illustrates
setting can be reduced to any practical value, the relay
the equivalent circuit of the circulating current scheme.
now being a voltage-measuring device. There is
If a high impedance relay is used, then unless the relay is
obviously a lower limit, below which the relay element
located at point J in the circuit, a current will flow
does not have the sensitivity to pick up. Relay
through the relay even with currents IPg and IPh being
calibration can in fact be in terms of voltage. For more
identical. If a low impedance relay is used, voltage FF ’
details, see reference [10.2].
will be very small, but the CT exciting currents will be
unequal due to the unequal burdens and relay current IR
will still be non-zero. 10.4.2 Bias
The 'spill' current in the relay arising from these various
IPg
End G End H
IPh
sources of error is dependent on the magnitude of the
through current, being negligible at low values of
through-fault current but sometimes reaching a
RSh RLg RLh RSh disproportionately large value for more severe faults.
iSg Sh ieh Setting the operating threshold of the protection above
ieg
Id Relay the maximum level of spill current produces poor
Zeg R Zeh sensitivity. By making the differential setting
approximately proportional to the fault current, the low-
U n i t P ro te c t i o n Fe e d e r s
RR
level fault sensitivity is greatly improved. Figure 10.5
illustrates a typical bias characteristic for a modern relay
(a)
Subscripts:
p that overcomes the problem. At low currents, the bias is
G' S - CT Secondary small, thus enabling the relay to be made sensitive. At
F' L higher currents, such as would be obtained from inrush or
G''
G
h - end H through fault conditions, the bias used is higher, and thus
J H
G F the spill current required to cause operation is higher. The
relay is therefore more tolerant of spill current at higher
H' fault currents and therefore less likely to maloperate,
H
H'' while still being sensitive at lower current levels.
GG' '
GG'' '' Electro-motive forces with low impedance relay
(b)
I1 I2
Figure 10.4: Equivalent circuit
of circulating current scheme
• 10 •
I3
be regarded as a voltage source. The shunt reactance of not a major constraint. For older relays, use of this
the transformer is relatively low, so the device acts as a technique over pilot wires may be possible for relatively
transformer loaded with a reactive shunt; hence the short distances, such as would be found with industrial
American name of transactor. The equivalent circuit of and urban power distribution systems. Clearly, each
the system is as shown in Figure 10.6. phase would require a separate set of pilot wires if the
protection was applied on a per phase basis. The cost of
The series connected relays are of relatively high
providing separate pilot-pairs and also separate relay
impedance; because of this the CT secondary winding
elements per phase is generally prohibitive. Summation
resistances are not of great significance and the pilot
techniques can be used to combine the separate phase
resistance can be moderately large without significantly
currents into a single relaying quantity for comparison
affecting the operation of the system. This is why the
over a single pair of pilot wires. For details of such
scheme was developed for feeder protection.
techniques, see reference [10.2].
End G End H
10 . 7 E X A M P L E S O F E L E C T R O M E C H A N I C A L
• 10 • RSg RLg RLh RSh A N D S TAT I C U N I T P R OT E C T I O N S Y S T E M S
As mentioned above, the basic balanced voltage principle
of protection evolved to biased protection systems.
Zeg Zeh
Pilot Several of these have been designed, some of which
Parameters
appear to be quite different from others. These
dissimilarities are, however, superficial. A number of
Id> Id> these systems that are still in common use are described
Relay G Relay H below.
Figure 10.6: Equivalent circuit
for balanced voltage system
10.7.1 ‘Translay’ Balanced Voltage
Electromechanical System
A typical biased, electromechanical balanced voltage
10.5.1 Stability Limit of the Voltage Balance System
system, trade name ‘Translay’, still giving useful service
Unlike normal current transformers, transactors are not on distribution systems is shown in Figure 10.7.
subject to errors caused by the progressive build-up of
U n i t P ro te c t i o n Fe e d e r s
Through current in the power circuit produces a state of This is made possible by a special adjustment (Kt) by
balance in the pilot circuit and zero current in the lower which the operating time of the differential protection
electromagnet coils. In this condition, no operating can be selectively increased if necessary, thereby
torque is produced. enabling the use of current transformers having a
correspondingly decreased knee-point voltage, whilst
An in-zone fault causing an inflow of current from each
ensuring that through-fault stability is maintained to
end of the line produces circulating current in the pilot
greater than 50 times the rated current.
circuit and the energisation of the lower electromagnets.
These co-operate with the flux of the upper Internal faults give simultaneous tripping of relays at
electromagnets to produce an operating torque in the both ends of the line, providing rapid fault clearance
discs of both relays. An infeed from one end only will irrespective of whether the fault current is fed from both
result in relay operation at the feeding end, but no line ends or from only one line end.
operation at the other, because of the absence of upper
magnet flux.
• 10 •
A
T1 - Summation transformer
B
T2 - Auxiliary transformer
C
RVO - Non linear resistor
Figure 10.8: Typical static circulating current feeder unit protection circuit diagram
ends of the line may not need to implement intertripping transmission delay between the relays. Four techniques
facilities. However, it is usual to provide intertripping in are possible for this:
any case to ensure the protection operates in the event
a. assume a value
of any of the relays detecting a fault.
b. measurement during commissioning only
A facility for vector/ratio compensation of the measured c. continuous online measurement
currents, so that transformer feeders can be included in d. GPS time signal
the unit protection scheme without the use of
Method (a) is not used, as the error between the assumed
interposing CT’s or defining the transformer as a separate
and actual value will be too great.
zone increases versatility. Any interposing CT’s required
are implemented in software. Maloperation on Method (b) provides reliable data if direct
transformer inrush is prevented by second harmonic communication between relays is used. As signal
detection. Care must be taken if the transformer has a propagation delays may change over a period of years,
wide-ratio on-load tap changer, as this results in the repeat measurements may be required at intervals and
current ratio departing from nominal and may cause relays re-programmed accordingly. There is some risk of
• 10 • maloperation, depending on the sensitivity of the relays. maloperation due to changes in signal propagation time
The initial bias slope should be set taking this into causing incorrect time synchronisation between
consideration. measurement intervals. The technique is less suitable if
rented fibre-optic pilots are used, since the owner may
Tuned measurement of power frequency currents
perform circuit re-routing for operational reasons
provides a high level of stability with capacitance inrush
without warning, resulting in the propagation delay
currents during line energisation. The normal steady-
being outside of limits and leading to scheme
state capacitive charging current can be allowed for if a
maloperation. Where re-routing is limited to a few
voltage signal can be made available and the
routes, it may be possible to measure the delay on all
susceptance of the protected zone is known.
routes and pre-program the relays accordingly, with the
Where an earthed transformer winding or earthing relay digital inputs and ladder logic being used to detect
transformer is included within the zone of protection, changes in route and select the appropriate delay
some form of zero sequence current filtering is required. accordingly.
This is because there will be an in-zone source of zero
Method (c), continuous sensing of the signal propagation
sequence current for an external earth fault. The
delay, is a robust technique. One method of achieving
differential protection will see zero sequence differential
this is shown in Figure 10.9.
current for an external fault and it could incorrectly
Measured sampling time Propagation delay time TA1'TA2' - sampling instants of relay A
TB3*=(TA*-Tp2) Tp1=Tp2=1/2(TA*-TA1-Td) TB1'TB2' - sampling instants of relay B
Tp1 - propagation delay time
Current from relay A to B
TA1 vectors
TB1 Tp2 - propagation delay time
Tp1 TA1 from relay B to A
TA2
TB2 Td - time between the arrival
TB* of message TA1 at relay B
TA3 Td and despatch of message TB3
TB3* TB3 TA1* - arrival time of message TB3
TA4 and relay A
Tp2 TB4
vectors TB* - arrival time of message TA1
Current
TA5 Td and relay B
TA*
TB3 TA1 TB5 TB3* - the measured sampling
time of TB3 by relay A
Relays A and B sample signals at time TA1,TA2 …and communication channels under well-defined conditions.
U n i t P ro te c t i o n Fe e d e r s
TB1,TB2 …respectively. The times will not be coincident,
The technique can also be used with all types of pilots,
even if they start coincidentally, due to slight differences
subject to provision of appropriate interfacing devices.
in sampling frequencies. At time TA1 relay A transmits
its data to relay B, containing a time tag and other data. Method (d) is also a robust technique. It involves both
Relay B receives it at time TA1 + Tp1 where Tp1 is the relays being capable of receiving a time signal from
propagation time from relay A to relay B. Relay B a GPS satellite. The propagation delay on each
records this time as time TB*. Relay B also sends communication channel is no longer required to be
messages of identical format to relay A. It transmits such known or calculated as both relays are synchronised to a
a message at time TB3, received by relay A at time common time signal. For the protection scheme to meet
TB3 +Tp2 (say time TA*), where Tp2 is the propagation the required performance in respect of availability and
time from relay B to relay A. The message from relay B maloperation, the GPS signal must be capable of reliable
to relay A includes the time TB3, the last received time receipt under all atmospheric conditions. There is extra
tag from relay A (TA1) and the delay time between the satellite signal receiving equipment required at both
arrival time of the message from A (TB*) and TB3 – call ends of the line, which implies extra cost.
this the delay time Td. The total elapsed time is The minimum setting that can be achieved with such
therefore: • 10 •
techniques while ensuring good stability is 20% of CT
(TA* - TA1) = (Td + Tp1 + Tp2) primary current.
If it is assumed that Tp1 = Tp2, then the value of Tp1 and
Tp2 can be calculated, and hence also TB3. The relay B 10.8.2 Application to Mesh Corner
measured data as received at relay A can then be and 1 1/2 Breaker Switched Substations
adjusted to enable data comparison to be performed.
Relay B performs similar computations in respect of the These substation arrangements are quite common, and
data received from relay A (which also contains similar the arrangement for the latter is shown in Figure 10.10.
time information). Therefore, continuous measurement Problems exist in protecting the feeders due to the
of the propagation delay is made, thus reducing the location of the line CT’s, as either Bus 1 or Bus 2 or both
possibility of maloperation due to this cause to a can supply the feeder. Two alternatives are used to
minimum. Comparison is carried out on a per-phase basis, overcome the problem, and they are illustrated in the
so signal transmission and the calculations are required Figure. The first is to common the line CT inputs (as
for each phase. A variation of this technique is available shown for Feeder A) and the alternative is to use a second
that can cope with unequal propagation delays in the two set of CT inputs to the relay (as shown for Feeder B).
Bus 1 Bus 2
power system currents since the systems are designed to
B2 IF B1 operate at much higher frequencies, but each medium
may be subjected to noise at the carrier frequencies that
may interfere with its correct operation. Variations of
F signal level, restrictions of the bandwidth available for
Id> relaying and other characteristics unique to each
Id>
Stub medium influence the choice of the most appropriate
bus type of scheme. Methods and media for communication
inputs are discussed in Chapter 8.
A B
Sensing of the state of the line isolator through auxiliary range of the scheme. As the fault current may be up to
contacts enables the current values transmitted to and 30 times the rated current, a scheme with linear
received from remote relays to be set to zero when the characteristics requires a wide dynamic range, which
isolator is open. Hence, stub-bus protection for the implies a wide signal transmission bandwidth. In
energised part of the bus is then possible, with any fault practice, bandwidth is limited, so either a non-linear
resulting in tripping of the relevant CB. modulation characteristic must be used or detection of
fault currents close to the setpoint will be difficult.
10 . 9 C A R R I E R U N I T P R OT E C T I O N S C H E M E S
10.10.1 Phase Comparison Scheme
In earlier sections, the pilot links between relays have
been treated as an auxiliary wire circuit that The carrier channel is used to convey the phase angle of the
interconnects relays at the boundaries of the protected current at one relaying point to another for comparison
zone. In many circumstances, such as the protection of with the phase angle of the current at that point.
longer line sections or where the route involves The principles of phase comparison are illustrated in
• 10 • installation difficulties, it is too expensive to provide an Figure 10.11. The carrier channel transfers a logic or
auxiliary cable circuit for this purpose, and other means 'on/off' signal that switches at the zero crossing points
are sought. of the power frequency waveform. Comparison of a local
In all cases (apart from private pilots and some short logic signal with the corresponding signal from the
rented pilots) power system frequencies cannot be remote end provides the basis for the measurement of
transmitted directly on the communication medium. phase shift between power system currents at the two
Instead a relaying quantity may be used to vary the ends and hence discrimination between internal and
higher frequency associated with each medium (or the through faults.
light intensity for fibre-optic systems), and this process Current flowing above the set threshold results in turn-
is normally referred to as modulation of a carrier wave. off of the carrier signal. The protection operates if gaps
Demodulation or detection of the variation at a remote in the carrier signal are greater than a set duration – the
receiver permits the relaying quantity to be reconstituted phase angle setting of the protection.
for use in conjunction with the relaying quantities
derived locally, and forms the basis for all carrier systems Load or through fault currents at the two ends of a
of unit protection. protected feeder are in antiphase (using the normal relay
convention for direction), whilst during an internal fault
Carrier systems are generally insensitive to induced the (conventional) currents tend towards the in-phase
condition. Hence, if the phase relationship of through binary information, the techniques associated with
fault currents is taken as a reference condition, internal sending teleprotection commands. Blocking or
faults cause a phase shift of approximately 180° with permissive trip modes of operation are possible, however
respect to the reference condition. Figure 10.11 illustrates the more usual blocking mode,
since the comparator provides an output when neither
Phase comparison schemes respond to any phase shift
squarer is at logic '1'. A permissive trip scheme can be
from the reference conditions, but tripping is usually
realised if the comparator is arranged to give an output
permitted only when the phase shift exceeds an angle of
when both squarers are at logic '1'. Performance of the
typically 30 to 90 degrees, determined by the time delay
scheme during failure or disturbance of the carrier
setting of the measurement circuit, and this angle is
channel and its ability to clear single-end-fed faults
usually referred to as the Stability Angle. Figure 10.12 is
depends on the mode of operation, the type and function
a polar diagram that illustrates the discrimination
of fault detectors or starting units, and the use of any
characteristics that result from the measurement
additional signals or codes for channel monitoring and
techniques used in phase comparison schemes.
transfer tripping.
Since the carrier channel is required to transfer only
End G End H
U n i t P ro te c t i o n Fe e d e r s
Phase
E comparator
Pulse length
discrimination
Load or through fault Internal fault
F G IG IH H G IG IH H
1 1
B. Squarer output at end G
0 0
• 10 •
C. Summation voltage at end H
1 1
D. Squarer output at end H 0 0
(Received at end G via
ideal carrier system as D'
1 1
E. Comparator output at end G
0 0
E=B+D'
1 1
F. Discriminator output at end G
0 0
Stability setting
frequency channels using frequency shift keying (FSK) or attenuation due to the fault.
PLC techniques. The noise immunity is also very good, making the scheme
Voice frequency channels involving FSK use two discrete very reliable. Signal propagation delay is easily allowed
frequencies either side of the middle of the voice band. for in the stability angle setting, making the scheme very
This arrangement is less sensitive to variations in delay or sensitive as well.
frequency response than if the full bandwidth was used.
Blocking or permissive trip modes of operation may be
implemented. In addition to the two frequencies used 10 . 11 P H A S E C O M PA R I S I O N P R OT E C T I O N
for conveying the squarer information, a third tone is S C H E M E C O N S I D E R AT I O N S
often used, either for channel monitoring or transfer One type of unit protection that uses carrier techniques
tripping dependent on the scheme. for communication between relays is phase comparison
For a sensitive phase comparison scheme, accurate protection. Communication between relays commonly
compensation for channel delay is required. However, uses PLCC or frequency modulated carrier modem
since both the local and remote signals are logic pulses, techniques. There are a number of considerations that
• 10 • simple time delay circuits can be used, in contrast to the apply only to phase comparison protection systems,
analogue delay circuitry usually required for current which are discussed in this section.
differential schemes.
The principles of the Power Line Carrier channel 10.11.1 Lines with Shunt Capacitance
technique are illustrated in Figure 10.13. The scheme
operates in the blocking mode. The 'squarer' logic is used A problem can occur with the shunt capacitance current
directly to turn a transmitter 'on' or 'off' at one end, and that flows from an energising source. Since this current is
the resultant burst (or block) of carrier is coupled to and in addition to the load current that flows out of the line,
propagates along the power line which is being protected and typically leads it by more than 90°, significant
to a receiver at the other end. Carrier signals above a differential phase shifts between the currents at the ends
threshold are detected by the receiver, and hence produce of the line can occur, particularly when load current is low.
a logic signal corresponding to the block of carrier. In The system differential phase shift may encroach into the
contrast to Figure 10.11, the signalling system is a 2-wire tripping region of the simple discriminator characteristic,
rather than 4-wire arrangement, in which the local regardless of how large the stability angle setting may
transmission is fed directly to the local receiver along be. Figure 10.14 illustrates the effect and indicates
with any received signal. The transmitter frequencies at techniques that are commonly used to ensure stability.
End G End H
Line trap
Line trapp
Coupling
Summation filter
network
A
Squarer Transmitter B
Identical
relay
C to end G
Receiver
Pulse length
discriminator
D Trip
Trip Load or through fault Internal fault
1 1
A. Squarer output at end G 0 0
U n i t P ro te c t i o n Fe e d e r s
B. Composite carrier signal at end G
1 1
D. Discriminator output 0 0
Stability setting
decreasing mark-space ratio at low currents, and with a In the absence of pre-fault load current, the voltages at
suitable threshold level the extra phase shift θc which is the two ends of a line are in phase. Internal faults are
permitted can be arranged to equal or exceed the phase fed from both ends with fault contributions whose
shift due to capacitive current. At high current levels the magnitudes and angles are determined by the position of
capacitive current compensation falls towards zero and the fault and the system source impedances. Although
the resultant stability region on the polar diagram is the magnitudes may be markedly different, the angles
usually smaller than on the keyhole characteristic, giving (line plus source) are similar and seldom differ by more
improvements in sensitivity and/or dependability of the than about 20°.
scheme. Since the stability region encompasses all
Hence |θG - θH| ≤ 20° and the requirements of Equation
through-fault currents, the resetting speed of any fault
10.3 are very easily satisfied. The addition of arc or fault
detectors or starter (which may still be required for other
resistance makes no difference to the reasoning above, so
purposes, such as the control of a normally quiescent
the scheme is inherently capable of clearing such faults.
scheme) is much less critical than with the keyhole
characteristic.
10.11.3 Effect of Load Current
10.11.2 System Tripping Angles When a line is heavily loaded prior to a fault the e.m.f.'s
For the protection scheme to trip correctly on internal of the sources which cause the fault current to flow may
faults the change in differential phase shift, θ0, from the be displaced by up to about 50°, that is, the power system
through-fault condition taken as reference, must exceed stability limit. To this the differential line and source
the effective stability angle of the scheme. Hence: angles of up to 20° mentioned above need to be added.
θ0 = ϕs + θc …Equation 10.1 So |θG - θH| ≤ 70° and the requirements of Equation 10.3
are still easily satisfied.
where
For three phase faults, or solid earth faults on phase-by-
ϕs = stability angle setting
U n i t P ro te c t i o n Fe e d e r s
Most phase comparison schemes use summation The fault current in Equation 10.6 is the effective earth
techniques to produce a single modulating quantity, fault sensitivity IE of the scheme. For the typical values of
responsive to faults on any of the three phases. Phase
M = 6 and N = -1
sequence components are often used and a typical
modulating quantity is: M
= −6
IM = MI2 + NI1 …Equation 10.5 N
where 3
∴ IE =− IL
I1 = Positive phase sequence component 5
I2 = Negative phase sequence component Comparing this with Equation 10.4, a scheme using
M,N = constants summation is potentially 1.667 times more sensitive
With the exception of three phase faults all internal than one using phase current for modulation.
faults give rise to negative phase sequence (NPS) Even though the use of a negative value of M gives a
currents, I2, which are approximately in phase at the lower value of IE than if it were positive, it is usually
ends of the line and therefore could form an ideal preferred since the limiting condition of Im = 0 then
modulating quantity. In order to provide a modulating applies at the load infeed end. Load and fault
signal during three phase faults, which give rise to components are additive at the outfeed end so that a
positive phase sequence (PPS) currents, I1, only, a correct modulating quantity occurs there, even with the
practical modulating quantity must include some lowest fault levels. For operation of the scheme it is
response to I1 in addition to I2. sufficient therefore that the fault current contribution
Typical values of the ratio M: N exceed 5:1, so that the from the load infeed end exceeds the effective setting.
modulating quantity is weighted heavily in favour of For faults on B or C phases, the NPS components are
NPS, and any PPS associated with load current tends to displaced by 120° or 240° with respect to the PPS
be swamped out on all but the highest resistance faults.
U n i t P ro te c t i o n Fe e d e r s
components. No simple cancellation can occur, but
For a high resistance phase-earth fault, the system instead a phase displacement is introduced. For tripping
remains well balanced so that load current IL is entirely to occur, Equation 10.2 must be satisfied, and to achieve
positive sequence. The fault contribution IF provides high dependability under these marginal conditions, a
equal parts of positive, negative and zero sequence small effective stability angle is essential. Figure 10.15
components IF /3. Assuming the fault is on 'A' phase and illustrates operation near to the limits of earth fault
the load is resistive, all sequence components are in sensitivity.
phase at the infeed end G: Very sensitive schemes may be implemented by using
MI FG NI FG high values of M _ but the scheme then becomes more
∴ I mG = NI L + + N
3 3 sensitive to differential errors in NPS currents such as
the unbalanced components of capacitive current or spill
and from partially saturated CT's.
θG ≈ 0 Techniques such as capacitive current compensation and
reduction of M _ at high fault levels may be required to
At the outfeed end load current is negative, N • 10 •
ensure stability of the scheme.
MI FH NI FH
∴ I mH = − NI L + +
3 3
10.11.5 Fault Detection and Starting
Now, for
For a scheme using a carrier system that continuously
ImH > 0,θH = 0, and |θG - θH| = 0°
transmits the modulating quantity, protecting an ideal
and for line (capacitive current=0) in an interconnected
ImH < 0,θH = 180°, and |θG - θH| = 180° transmission system, measurement of current magnitude
Hence for correct operation ImH ≥ 0 might be unnecessary. In practice, fault detector or
starting elements are invariably provided and the scheme
Let ImH = 0
then becomes a permissive tripping scheme in which
Then both the fault detector and the discriminator must
operate to provide a trip output, and the fault detector
3I L
I FH = = IE may limit the sensitivity of the scheme. Requirements
M
+1 for the fault detectors vary according to the type of
N …Equation 10.6 carrier channel used, mode of operation used in the
NILG
NILG 10.11.8 Scheme with Capacitive
120° NI
E NIE 120° Current Compensation (Blocking Mode)
3 3 ImG
ImG
MIE MIE When the magnitude of the modulating quantity is less
3 3 than the threshold of the squarer, transmission if it
(c) B phase to earth fault IF = IE (d) C phase to earth fault IF = IE
occurred, would be a continuous blocking signal. This
|θG- θH |=70°
might occur at an end with a weak source, remote from
U n i t P ro te c t i o n Fe e d e r s
U n i t P ro te c t i o n Fe e d e r s
Idmin = (k2IL -(k2-k1)Is2 + Is1)/(1-0.5k2)
10.12.1 Unit Protection of a Plain Feeder for Ibias >Is2
The circuit to be protected is shown in Figure 10.16. It where IL = load current
consists of a plain feeder circuit formed of an overhead and hence the minimum operating current at no load is
line 25km long. The relevant properties of the line are: 0.235p.u. or 94A.
Line voltage: 33kV
Z = 0.157 + j0.337Ω/km In cases where the capacitive charging current is very
Shunt charging current = 0.065A/km large and hence the minimum tripping current needs to
be set to an unacceptably high value, some relays offer
To arrive at the correct settings, the characteristics of the
the facility of subtracting the charging current from the
relays to be applied must be considered.
measured value. Use of this facility depends on having a
The recommended settings for three of the adjustable suitable VT input and knowledge of the shunt
values (taken from the relay manual) are: capacitance of the circuit.
• 10 •
8
The delta/star transformer connection requires phase
shift correction of CT secondary currents across the
transformer, and in this case software equivalents of
7 interposing CT’s are used.
Since the LV side quantities lag the HV side quantities by
6 30°, it is necessary to correct this phase shift by using
software CT settings that produce a 30° phase shift.
There are two obvious possibilities:
5
a. HV side: Yd1
Idiff
LV side: Yy0
4
b. HV side: Yy0
LV side: Yd11
3
Only the second combination is satisfactory, since only
this one provides the necessary zero-sequence current
2 trap to avoid maloperation of the protection scheme for
earth faults on the LV side of the transformer outside of
the protected zone.
1
Ratio correction must also be applied, in order to ensure
that the relays see currents from the primary and
0
0 1 2 3 4 5 6 secondary sides of the transformer feeder that are well
Ibias balanced under full load conditions. This is not always
Figure 10.17: Relay characteristic; inherently the case, due to selection of the main CT
plain feeder example ratios. For the example of Figure 10.18,
U n i t P ro te c t i o n Fe e d e r s
10.12.2 Unit Protection of a Transformer Feeder Transformer turns ratio at nominal tap
Figure 10.18 shows unit protection applied to a 11
= = 0.3333
transformer feeder. The feeder is assumed to be a 100m 33
length of cable, such as might be found in some
industrial plants or where a short distance separates the Required turns ratio according to the CT ratios used
33kV and 11kV substations. While 11kV cable 400
capacitance will exist, it can be regarded as negligible for = 1 = 0.32
1250
the purposes of this example. 1
20 MVA
33kV 33/11kV
11kV
400/1 Dyn1 Cable 1250/1
100m
350A 1050A
• 10 •
0° -30°
0.875A 0.84A
Digital communication
channel
Id> Id>
U n i t P ro te c t i o n Fe e d e r s
k2 = 150%
10 . 1 3 R E F E R E N C E S
10.1 Merz-Price Protective Gear. K. Faye-Hansen and
G. Harlow. IEE Proceedings, 1911.
10.2 Protective Relays Application Guide – 3rd
Edition. ALSTOM Transmission and Distribution
Protection and Control, 1987.