Anda di halaman 1dari 54

Cable Glands and Cable Accessories Hazardous and Non-hazardous

4F

Description
Application Cable Glands - International Standards Quick Selection Guide Flameproof and Increased Safety
ADE 1F ADE 4F ADE 6F ADE 6FC TWAB TWAX TWAE Ex - e Ex - i Trumpet Enlargement and Multiple

Page No. see page 66

Description
Cable Glands - Accessories
A Series B Series C Series D Series E Series Breathers and Drains

Page No.

4F

see pages 6770

see see see see see see see see see see see

page page page page page page page page page page page

71 72 73 74 75 76 77 78 79 80 81

see page 98 see page 102 see page 103 see page 104 see page 105 see page 106

Cable Tray Clamps Conduit


LCC, LCCF Series

see page 107 see page 108

Grounding Conductor
TGC Series

Cable/Conduit Sealing Devices Thru-Wall Barrier


TW Series

see pages 109110 see pages 115116 see pages 117118

Link Seal For Conduit


Environmental Seal Fire Seal

Industrial
ADE 4I TWA TUA

see page 82 see page 83 see page 84

Cable Glands - North American Standards Quick Selection Guide Explosionproof


TMCX ADE 6FC ADE 1FC CGBS EBY

see pages 6770 see see see see see page page page page page 85 86 87 88 88

General Pupose
TMC TECK CGB CGD CGE CGB1013 CGFP NCG NCGB

see page 89 see page 90 see pages 9192 see page 93 see page 94 see page 95 see page 96 see page 97 see page 97

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

65

4F

Cable Glands and Cable Accessories


Application and Selection

4F

Applications:
Cable glands and cord fittings: Provide means for passing a cord, cable (armored or unarmored) or flexible conduit into an enclosure, through a bulkhead or into a rigid conduit Form a mechanical grip and water and/or oil resistant seal for cord and unarmored or jacketed armored, round cables Form a non-slip connection or termination for flexible cord, cable (armored or unarmored), or flexible conduit Provide grounding continuity for cable armor and flexible conduit Cable glands with sealing fitting or epoxy are installed to: Provide means for passing armored, metal clad, jacketed or unjacketed and unarmored cables through a bulkhead or enclosure in hazardous areas. These fittings are suitable for use in Class I, Groups C, D, locations only when Chico A sealing compound or TSC epoxy (TMCX) is used to make the seal in the fitting.* Form a mechanical grip and water and/or oil-resistant termination Provide ground continuity of cable armor and flexible conduit TMC (non-hazardous) and TMCX (hazardous) fittings are designed for use with Type MC jacketed steel or aluminum metal clad cables with interlocked or corrugated armor and Type TC tray cable (TMCX). LCC cable tray conduit clamps are used for installation on cable tray side rails with inside flanges (requiring inside tray mounting) and outside flanges; LCCF clamps are for use exclusively on inside flanges. LCC/LCCF series cable tray conduit clamps are installed to: Provide a means of clamping metal conduit (rigid steel or aluminum, IMC and EMT) to cable tray for the exit of power and/or control cables from tray Provide a means to firmly bond exiting conduit to cable tray for best grounding continuity TW series THRU-WALL BARRIER cable/conduit sealing devices are installed to: Seal cables or conduits penetrating firerated walls, ceilings or floors Restrict entrance of water and dust and contain treated air Provide a seal for cable/conduit penetrations through steel, masonry or concrete; to restrict the entrance of contaminants through cable/conduit penetrations into clean areas TGC cable tray grounding conductor clamp provides a means for securely attaching a grounding conductor to cable tray to provide grounding continuity for the entire tray system. TGC cable tray grounding conductor clamps provide a reliable method for carrying ground fault current for equipment protection. TGC clamp may be installed on most types of cable trays with inside or outside flanges.

Considerations for Selection:


Selection of the proper cable gland involves consideration of the type of cable to be installed and the environment that will surround the cable after installation. A proper matching of the cable and its gland is necessary to prevent physical damage to the cable when installed. Some types of cable glands depend on gripping methods (set screws etc.) which may lead to damage of the cable outer covering. Cooper Crouse-Hinds cable glands and cord fittings utilize compression of split lead or tapered neoprene bushings to provide high gripping strength for adequate cable support and strain relief without damage to the cable sheath. Compression of bushing provides a strong electrical bond that assures grounding continuity. Compression of a tapered neoprene bushing, assures the watertight integrity of Cooper Crouse-Hinds cable glands. Additional watertightness, to prevent water seepage into the fitting body, can be obtained by use of a potting head filled with a hot pouring compound. To meet National Electrical Code requirements for electrical installations in hazardous atmospheres, a sealing fitting may be required in conjunction with the cable or cord fitting.
*With specific cords and cables when installed in accordance with NEC/CEC requirements.

66

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Global Cable Glands


Quick Selection Guide - International Standards

4F

4F

CABLE GLAND

ILLUSTRATION

CABLE TYPE

GLAND TYPE

STANDARD MATERIAL

CERTIFICATION

PROTECTION TYPE

ADE 1F (page 71)

Non-armoured, armoured and tray Non-armoured Nickel-plated brass cable (does not terminate the armour)

Flameproof & Increased Safety

ADE 1FC (page 87)

Non-armoured, armoured and tray Non-armoured Nickel-plated brass cable (does not barrier terminate the armour)

Flameproof & Increased Safety

ADE 4F (page 72)

SWA, SWB, STA, braided marine shipboard and lead sheathed (with addition of earthing washer)

Armoured

Nickel-plated brass

Flameproof & Increased Safety

ADE 6F (page 73)

SWA, SWB, STA and braided marine shipboard

Armoured

Nickel-plated brass

Flameproof & Increased Safety

ADE 6FC (page 74)

SWA, SWB, STA, braided marine shipboard and lead sheathed (with addition of earthing washer)

Armoured barrier

Nickel-plated brass

Flameproof & Increased Safety

TWAB (page 75)

SWA

Armoured barrier

Nickel-plated brass

Flameproof

TWAX (page 76)

SWA

Armoured

Nickel-plated brass

Flameproof

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

67

4F

Global Cable Glands


Quick Selection Guide - International Standards

CABLE GLAND

ILLUSTRATION

CABLE TYPE

GLAND TYPE

STANDARD MATERIAL

CERTIFICATION

PROTECTION TYPE

4F

TWAE (page 77)

SWA

Armoured

Nickel-plated brass

Increased Safety

EX-e (page 78)

Nonarmoured

Non-armoured

Polyamide

Increased Safety

EX-i (page 79)

Nonarmoured

Non-armoured

Polyamide

Increased Safety

Trumpet (page 80)

Nonarmoured

Non-armoured

Polyamide

Increased Safety

Enlargement and Multiple (page 81)

Nonarmoured

Non-armoured

Polyamide

Increased Safety

ADE 4I (page 82)

SWA, SWB, STA, braided marine shipboard and lead Armoured sheathed (with addition of earthing washer)

Nickel-plated brass

Industrial

TWA (page 83)

SWA

Armoured

Nickel-plated brass

Industrial

TUA (page 84)

Nonarmoured

Non-armoured

Nickel-plated brass

Industrial

68

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Global Cable Glands


Quick Selection Guide - North American Standards
CABLE GLAND CABLE TYPE Metal-clad with interlocked or continuously-welded corrugated, TECK armoured, non-armoured and tray cable Non-armoured, armoured and tray cable (does not terminate the armour) SWA, SWB, STA, braided marine shipboard and lead sheathed (with addition of earthing washer) GLAND TYPE STANDARD MATERIAL

4F

ILLUSTRATION

CERTIFICATION

PROTECTION TYPE

4F

TMCX (page 85)

Armoured barrier and non-armoured barrier

Aluminum

Explosionproof

ADE 1FC (page 87)

Non-armoured barrier

Nickel-plated brass

Flameproof & Increased Safety

ADE 6FC (page 86)

Armoured barrier

Nickel-plated brass

Flameproof & Increased Safety

CGBS (page 88)

Non-armoured and tray cable

Portable cord connector

Body: steel Gland nut: aluminum

Explosionproof

EBY (page 88)

Non-armoured

Portable cord connector

Aluminum

Explosionproof

TMC (page 89)

Metal-clad with interlocked or continuously-welded corrugated, TECK armoured, non-armoured and tray cable

Armoured or non-armoured

Aluminum

General Purpose

TECK (page 90)

TECK armoured

Armoured

Aluminum

General Purpose

CGB (page 91)

Non-armoured and tray cable

Non-armoured

Body steel Form A-D steel Form E-F iron

General Purpose

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

69

4F

Global Cable Glands


Quick Selection Guide - North American Standards

CABLE GLAND

ILLUSTRATION

CABLE TYPE

GLAND TYPE

STANDARD MATERIAL

CERTIFICATION

PROTECTION TYPE

4F

CGD (page 93)

Non-armoured and tray cable

Non-armoured

Body: iron Gland nut: steel

General Purpose

CGE (page 94)

Non-armoured and tray cable

Non-armoured

Body: iron Gland nut: steel

General Purpose

CGB1013 (page 95)

Non-armoured and tray cable

Portable cord connector

Body: steel Gland nut: aluminum

General Purpose

CGFP (page 96)

Non-armoured and tray cable

Non-armoured

Form B-C: steel Form D-G: iron

General Purpose

NCG (page 97)

Non-armoured and tray cable

Non-armoured

Polyamide

General Purpose

NCGB (page 97)

Non-armoured and tray cable

Non-armoured

Thermoplastic polyester

General Purpose

70

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

ADE 1F
International Standards Flameproof and Increased Safety
Gland Type
Non-armoured

ATEX IECEx cULus Listed for Class I Zone 2 cULus Marine Listed for Class I Zone 2

CEPEL GOST-R NEPSI NEMA 4X and IP68

4F

4F

Cable Type
Non-armoured, armoured and tray cable (does not terminate the armour)

Certifications and Compliances:


ATEX LCIE 97 ATEX 6008X Exd IIC/Exe II/Ex tD /Ex II 2 GD IECEx LCI 05.0004X cULus Listed for Class I Zone 2 AEx e II/Ex e II E310130 cULus Marine Listed for Class I Zone 2 AEx e II/Ex e II E314047 NEMA 4X and IP68 CEPEL cepel-EX-558/05X GOST-R POCC FR.B02011 NEPSI N GYJ071336U & GYJ071337U

Features:
Standard material is nickel-plated brass for superior corrosion resistance Provides a flameproof and weatherproof seal on the outer sheath of the cable Standard neoprene seal suitable for use in operating temperatures ATEX (-60C to 100C), IECEx and cULus (-40C to 100C) Available with optional silicone seal for extreme temperatures Available with metric or NPT threads See pages 98101 for related accessories

SELECTION TABLE
Entry Thread Size A Gland Size 4 4 5 4 5 6 5 6 7 7 8 8 9 9 10 11 12 12 13 14 15 16 Metric Size M12 M16 M16 M20 M20 M20 M25 M25 M25 M32 M32 M40 M40 M50 M50 M63 M63 M75 M75 M90 M90 M110 Metric Catalog # CAP816404 CAP816594 CAP816504 CAP816674 CAP816694 CAP816604 CAP816774 CAP816794 CAP816704 CAP816894 CAP816804 CAP816994 CAP816904 CAP817094 CAP817004 CAP817294 CAP817204 CAP817394 CAP817304 CAP817594 CAP817504 CAP817794 NPT Size 1 /4" 3 /8" 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" 3" 31/2"
NPT Catalog #

CAP818404 CAP818594 CAP818694 CAP818674 CAP818694 CAP818604 CAP818774 CAP818794 CAP818704 CAP818894 CAP818804 CAP818994 CAP818904 CAP819094 CAP819004 CAP819294 CAP819204 CAP819494 CAP819404 CAP819594 CAP819504 CAP819604

Thread Length B Metric (NPT) 15 (12.0) 15 (12.0) 15 (12.0) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (25.3) 15 (25.3) 15 (26.0) 15 (26.0) 15 (26.5) 15 (26.5) 17 (27.2) 17 (27.2) 18 (40.5) 18 (40.5) 22 (42.0) 22 (42.0) 22 (43.2)

Cable Acceptance Outer SheathE Min 4.0 4.0 6.0 4.0 6.0 8.5 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 33.0 40.0 40.0 47.0 54.0 63.0 72.0 Max 8.0 8.5 12.0 8.5 12.0 16.0 12.0 16.0 21.0 21.0 27.5 27.5 34.0 34.0 41.0 48.0 56.0 56.0 65.0 74.0 78.0 92.0

Gland Length F (less entry) 20 20 22 20 22 25 22 25 27 27 34 34 36 36 39 41 43 43 49 56 61 62

Hexagon Dimensions Across Flats Across Corners G 16.5 20.9 20.9 26.4 26.4 26.4 33 33 33 39.6 45.1 48.4 52.8 60.5 60.5 73.7 79.2 88 93.5 104.5 121 132

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

71

4F

ADE 4F
International Standards Flameproof and Increased Safety

CEPEL ATEX GOST-R IECEx NEPSI cULus listed for Class I Zone 2 cULus Marine listed for Class I, Zone 1 NEMA 4X and IP68

4F

Gland Type:
Armoured

Cable Type:
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard and lead sheathed (with addition of earthing washer)

Certifications and Compliances:


ATEX LCIE 97 ATEX 6008X Exd IIC/Exe II/Ex tD/Ex II 2 GD IECEx LCI 05.0004X cULus listed for Class I, Zone 2 AEx e II/Ex e II E310130 cULus Marine listed for Class I, Zone 1 AEx e II/Ex e II E314047 NEMA 4X and IP68 CEPEL cepel-EX-559/05X GOST-R POCC FR.B02011 NEPSI N GYJ071336U & GYJ071337U

Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping and bonding with no reversible components for easy installation, minimizing error Provides flameproof seal on inner jacket and weatherproof seal on outer sheath of cable Optional earthing washer for use with lead sheathed cable (see page 99) Standard neoprene seal suitable for use in operating temperatures ATEX (-60C to 100C), IECEx and cULus (-40C to 100C) Available with optional silicone seal for extreme temperatures Available with metric or NPT threads See pages 98101 for related accessories

SELECTION TABLE
Entry Thread Size A Thread Length B Metric NPT (NPT) Size NPT Catalog # 1 /4" CAP848404 15 (12.0) 3 /8" CAP848594 15 (12.0) 3 /8" CAP848504 15 (12.0) 1 /2" CAP848674 15 (20.2) 1 /2" CAP848694 15 (20.2) 1 /2" CAP848604 15 (20.2) 3 /4" CAP848774 15 (20.2) 3 /4" CAP848794 15 (20.2) 3 /4" CAP848704 15 (20.2) 1" CAP848894 15 (25.3) 1" CAP848804 15 (25.3) 15 (26.0) 11/4" CAP848994 11/4" CAP848904 15 (26.0) 11/2" CAP849094 15 (26.5) 15 (26.5) 11/2" CAP849004 2" CAP849294 17 (27.2) 2" CAP849204 17 (27.2) 21/2" CAP849494 18 (40.5) 21/2" CAP849404 18 (40.5) 3" CAP849594 22 (42.0) 3" CAP849504 22 (42.0) N/A (43.2) 31/2" CAP849604 4" CAP849704 22 (44.5) Cable Acceptance Inner Sheath Outer Sheath D E Min 4.0 4.0 6.0 4.0 6.0 8.5 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 40.0 47.0 54.0 63.0 63.0 72.0 Max 8.0 8.5 12.0 8.5 12.0 16.0 12.0 16.0 20.5 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 56.0 65.0 74.0 82.0 82.0 92.0 Min 6.0 6.0 8.5 6.0 8.5 12.0 8.5 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 33.0 47.0 47.0 54.0 63.0 72.0 72.0* 85.0 Max 12.0 12.0 16.0 12.0 16.0 21.0 16.0 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 48.0 56.0 65.0 74.0 83.0 93.0 93.0* 107.0 Hexagon Dimensions Gland Length Across Armour F (less Across Corners entry) Flats G (max) 0.9 36 20.9 0.9 36 20.9 1.25 42 26.4 0.9 36 26.4 1.25 42 26.4 1.25 46 33.0 1.25 42 33.0 1.25 46 33.0 1.6 56 45.1 1.6 56 45.1 1.6 63 52.8 1.6 63 52.8 2.0 68 60.5 2.0 68 60.5 2.5 74 70.4 2.5 77 79.2 2.5 85 93.5 2.5 85 93.5 2.5 92 104.5 3.15 104 121.0 3.15 108 132.0 3.15 108 132.0 3.15 115 148.5

Gland Metric Size Size 5 M12 5 M16 6 M16 5 M20 6 M20 7 M20 6 M25 7 M25 8 M25 8 M32 9 M32 9 M40 10 M40 10 M50 11 M50 12 M63 13 M63 13 M75 14 M75 15 M90 16 M90 16 M90 17 M110

Metric Catalog # CAP846404 CAP846594 CAP846504 CAP846674 CAP846694 CAP846604 CAP846774 CAP846794 CAP846704 CAP846894 CAP846804 CAP846994 CAP846904 CAP847094 CAP847004 CAP847294 CAP847204 CAP847394 CAP847304 CAP847794 CAP847504 CAP847574 CAP847794

All dimensions in millimeters unless otherwise noted * CAP849604 outer sheath min: 85 max: 107.

72

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

ADE 6F
International Standards Flameproof and Increased Safety
Gland Type
Armoured

ATEX IECEx cULus Listed for Class I Zone 2 cULus Marine Listed for Class I, Zone 2

CEPEL GOST-R NEPSI NEMA 4X and IP68

4F

4F

Cable Type
Steel wire armoured, steel wire braided, steel tape armoured and braided marine shipboard

Certifications and Compliances:


ATEX LCIE 97 6008X - Exd IIC / Exe II / Ex tD / Ex II 2GD IECEx LCI 05.0004X cULus Listed for Class I, Zone 2 AEx e II / Ex e II E310130 cULus Marine Listed for Class I, Zone 2 AEx e II / Ex e II E314047 NEMA 4X and IP68 CEPEL GOST-R NEPSI

Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping and bonding with no reversible components for easy installation, minimizing error Provides fully inspectable inner seal after installation Flameproof diaphragm seal on inner jacket does not damage cables exhibiting cold-flow; weatherproof seal on outer sheath of cable Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures ATEX (-60C to 100C), IECEx and cULus (-40C to 100C) Available with metric or NPT threads See pages 98101 for related accessories

SELECTION TABLE
Entry Thread Size A Gland Size 5 5 6 7 7 8 8 9 9 10 10 11 Metric Size M16 M20 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 Metric Catalog # CAP965594 CAP965674 CAP965694 CAP965604 CAP965794 CAP965704 CAP965894 CAP965804 CAP965994 CAP965904 CAP966094 CAP966004 NPT Size 3 /8" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 2" NPT Catalog # CAP967594 CAP967674 CAP967694 CAP967604 CAP967794 CAP967704 CAP967894 CAP967804 CAP967994 CAP967904 CAP968094 CAP968294 Thread Length B Metric (NPT) 15 (12.0) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (25.3) 15 (25.3) 15 (26.0) 15 (26.0) 16 (26.5) 16 (27.2) Cable Acceptance Inner Outer Sheath D Sheath E Min 3.0 3.0 6.5 9.0 9.0 12.0 12.0 17.5 17.5 23.0 23.0 28.5 Max 7.5 7.5 11.0 14.5 14.5 19.5 19.5 26.0 26.0 33.0 33.0 41.0 Min 6.0 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 Max 12.0 12.0 16.0 21.0 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 Armour (max) 0.9 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 Gland Length F (less entry) 46.0 46.0 53.0 59.0 59.0 74.5 74.5 83.5 83.5 92.0 92.0 104.0 Hexagon Dimensions Across Across Corners Flats G 20.9 26.4 26.4 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4

Larger sizes available in ADE 4F design, please refer back to page see page 72. All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

73

4F

ADE 6FC
International Standards Flameproof and Increased Safety

ATEX IECEx cULus listed for Class I, Zone 2 cULus Marine listed for Class I, Div. 1

CEPEL GOST-R NEMA 4X and IP68

4F

Gland Type
Armoured barrier

Cable Type
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard and lead sheathed (with addition of earthing washer)

Certifications and Compliances:


ATEX LCIE 97 ATEX 6008X - Exd IIC/Exe II/Ex tD/Ex II GD IECEx LCI 05.0004X cULus listed for Class I, Zone 2 AEx e II/Ex e II cULus Marine listed for Class I, Div. 2 AEx e II/Ex e II NEMA 4X and IP68 CEPEL GOST-R

Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping with no reversible components for easy installation, minimizing error Provides exposionproof compound seal (denoted by red back nut) on conductors and weatherproof seal on outer sheath of cable Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures -60C to 80C Available with metric or NPT threads See pages 98-101 for related accessories

SELECTION TABLE
Entry Thread Size A Cable Acceptance Hexagon Dimensions Inner Sheath Outer and Cores Sheath E Thread Max Max Length Gland Across Over Inner Max B Length Metric Cores Sheath No. of Armour F (less Across Corners G 'C' 'D' Cores Min Max (max) Flats (NPT) entry) 15 (12.0) 0.9 46.0 20.9 6.5 7.5 6.0 6.0 12.0 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.5) 15 (20.5) 15 (25.3) 15 (25.3) 15 (26.0) 15 (26.0) 16 (26.5) 16 (27.2) 6.5 9.5 12.0 12.0 17.0 17.0 23.0 23.0 29.0 29.0 36.5 7.5 11.0 14.5 14.5 19.5 19.5 28.0 28.0 33.0 33.0 41.0 6.0 6.0 10.0 10.0 21.0 21.0 42.0 42.0 60.0 60.0 80.0 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 12.0 16.0 21.0 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 46.0 53.0 59.0 59.0 74.5 74.5 83.5 83.5 92.0 92.0 104.0 26.4 26.4 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4

Gland Metric Size Size 5 M16 5 6 7 7 8 8 9 9 10 10 11 M20 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50

Metric Catalog # CAP969594 CAP969674 CAP969694 CAP969604 CAP969794 CAP969704 CAP969894 CAP969804 CAP969994 CAP969904 CAP970094 CAP970004

NPT Size 3 /8"


1 1 1 3 3

NPT Catalog # CAP974594 CAP971674 CAP971674 CAP971604 CAP971794 CAP971704 CAP971894 CAP971804 CAP971994 CAP971904 CAP972094 CAP972004

/2" /2" /2" /4" /4"

1" 1" 11/4" 11/4" 1 /2"


1

2"

Larger sizes available soon. All dimensions in millimeters unless otherwise noted.

74

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

TWAB
International Standards Flameproof and Increased Safety
Gland Type
Armoured barrier

IECEx

IP66 and 67

4F

4F

Cable Type
Steel wire armoured

Certifications and Compliances:


IECEx TSA 08.0004 - Exd IIC IP66 and 67

Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armoured cable Provides flameproof compound seal on conductors and weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories

SELECTION TABLE
Entry Thread Size A Thread Length B Metric 14 14 16 20 20 20 22 22 Cable Acceptance Inner Sheath D Min 6.0 7.0 11.0 17.0 24.0 30.0 40.0 53.0 Max 8.0 12.0 18.0 25.0 31.0 41.0 54.0 65.0 Outer Sheath E Min 10.2 14.0 18.0 25.0 30.0 36.0 51.0 63.0 Max 15.8 20.8 27.2 33.5 35.9 52.6 65.3 78.0 Armour Range 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.5 - 3.5 Gland Length F (less entry) 58.0 58.0 60.0 72.0 74.0 82.0 90.0 98.0 Hexagon Dimensions Across Across Corners Flats G 27.0 31.0 30.4 34.0 38.1 43.0 47.6 53.0 55.0 63.5 70.0 78.0 80.0 88.0 101.0 112.0

Gland Size 20 20 25 32 40 50 63 75

Metric Size M20 M20 M25 M32 M40 M50 M63 M75

Metric Catalog # TWAB1M16 TWAB1M20 TWAB2M27 TWAB3M34 TWAB4M40 TWAB5M53 TWAB6M66 TWAB7M78

NPT Size 1 /2" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2"

NPT Catalog # TWAB1N16 TWAB1N20 TWAB2N27 TWAB3N34 TWAB4N40 TWAB5N53 TWAB6N66 TWAB7N78

All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

75

4F

TWAX
International Standards Flameproof and Increased Safety

IECEx

IP66 and 67

4F

Gland Type:
Armoured

Cable Type:
Steel wire armoured

Certifications and Compliances:


IECEx TSA 08.0004 - Exd IIC IP66 and 67

Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armour cable Flameproof seal on inner jacket and weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories

SELECTION TABLE
Entry Thread Size A Thread Length B Metric 14.0 14.0 14.0 16.0 16.0 20.0 20.0 20.0 20.0 20.0 22.0 22.0 22.0 22.0 22.0 Cable Acceptance Inner Outer Sheath D Sheath E Min 6.3 8.4 11.0 13.5 16.5 19.5 23.5 25.8 30.8 35.5 39.5 43.5 48.5 55.5 61.0 Max 8.6 11.6 13.9 16.9 19.9 23.9 26.2 31.2 36.2 40.0 44.0 49.0 55.9 61.9 67.9 Min 10.2 13.0 15.5 19.5 23.5 27.0 30.0 33.0 38.0 43.0 48.0 52.0 58.0 64.3 70.6 Max 13.2 15.8 19.8 23.8 27.2 30.5 33.5 38.5 43.5 48.5 52.6 58.9 65.3 71.6 78.0 Armour Range 0.9 - 1.25 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.0 - 2.5 2.0 - 2.5 2.0 - 2.5 2.5 - 3.15 2.5 - 3.15 Gland Length F (less entry) 58.0 58.0 58.0 60.0 60.0 72.0 72.0 74.0 82.0 82.0 82.0 90.0 90.0 98.0 98.0 Hexagon Dimensions Across Flats 23.3 27.0 30.5 33.3 38.1 42.2 47.0 55.0 57.0 63.5 70.0 76.0 80.0 89.0 101.0 Across Corners G 26.0 31.0 34.0 37.0 43.0 47.0 53.0 64.0 62.0 71.0 78.0 85.0 88.0 102.0 112.0

Gland Size 20 20 20 25 25 32 32 40 50 50 50 63 63 75 75

Metric Size M20 M20 M20 M25 M25 M32 M32 M40 M50 M50 M50 M63 M63 M75 M75

Metric Catalog # TWAX1M13 TWAX1M16 TWAX1M20 TWAX2M24 TWAX2M27 TWAX3M30 TWAX3M33 TWAX4M38 TWAX5M43 TWAX5M48 TWAX5M52 TWAX6M60 TWAX6M65 TWAX7M71 TWAX7M78

NPT Size 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/ 2" 11/2" 2" 2" 21/2" 21/2" 3"

NPT Catalog # TWAX1N13 TWAX1N16 TWAX1N20 TWAX2N24 TWAX2N27 TWAX3N30 TWAX3N33 TWAX4N38 TWAX5N43 TWAX5N48 TWAX6N52 TWAX6N60 TWAX7N65 TWAX7N71 TWAX8N78

All dimensions in millimeters unless otherwise noted.

76

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

TWAE
International Standards Flameproof and Increased Safety

IECEx

IP66 and 67

4F

Gland Type:
Armoured

4F

Cable Type:
Steel wire armoured

Certifications and Compliances:


IECEx TSA 08.0004 - Ex e II IP66 and 67 rated

Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armour cable Forms weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads A captive sealing gasket on entry threads See page 103 for related accessories

SELECTION TABLE
Entry Thread Size A Gland Size 20 20 25 32 40 50 63 75 Metric Size M20 M20 M25 M32 M40 M50 M63 M75 Metric Catalog # TWAE1M16 TWAE1M20 TWAE2M27 TWAE3M34 TWAE4M40 TWAE5M53 TWAE6M66 TWAE7M78 NPT Size (in.) 1 /2" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" NPT Catalog # TWAE1N16 TWAE1N20 TWAE2N27 TWAE3N34 TWAE4N40 TWAE5N53 TWAE6N66 TWAE7N78 Thread Length B Metric 14.0 14.0 16.0 20.0 20.0 20.0 22.0 22.0 Cable Acceptance Outer Inner Sheath E Sheath D Min 6.0 7.0 11.0 17.0 24.0 30.0 40.0 53.0 Max 11.0 13.0 19.0 25.0 31.0 41.0 54.0 65.0 Min 10.2 14.0 18.0 25.0 30.0 36.0 51.0 63.0 Max 15.8 20.8 27.2 33.5 39.5 52.6 65.3 78.0 Armour Range 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.5 - 3.5 Gland Length F (less entry) 58.0 58.0 60.0 72.0 74.0 82.0 90.0 98.0 Hexagon Dimensions Across Across Corners Flats G 27.0 31.0 30.4 34.0 38.5 43.0 47.2 53.0 55.0 62.0 70.0 78.0 80.0 88.0 101.0 112.0

All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

77

4F

Ex-e
International Standards Flameproof and Increased Safety

Sizes M12-M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X IECEx

IP66

4F

Gland Type:
Non-armoured

Cable Type:
Non-armoured

Certifications and Compliances:


Sizes M12-M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X Ex II 2 G Ex e II/Ex II 2 D Ex tD A21 IECEx PTB 05.0004X IP66

Features:
Standard material is high-impact resistant polyamide Forms weatherproof seal on outer sheath of cable Standard silicone seal suitable for use in operating temperatures -55 to 70C (M12 and M16 for use in operating temperatures -20 to 70C) Available with optional silicone seal for extreme temperatures Available with metric threads See page 104 for related accessories

SELECTION TABLE - SHORT THREAD


Entry Thread Size A Gland Size Metric Size 12 M12 16 M16 20 M20 25 M25 32 M32 Metric Catalog # GHG 960 1955 R 0001 GHG 960 1955 R 0002 GHG 960 1955 R 0003 GHG 960 1955 R 0004 GHG 960 1955 R 0005 Thread Length B Metric 8.0 8.0 8.0 8.0 10.0 Cable Acceptance Outer Sheath E Min Max 4.0 7.0 5.5 10.0 5.5 13.0 8.0 17.0 12.0 21.0 Hexagon Dimensions Gland Length F (less entry) Across Flats Across Corners G 19.3 15.0 16.5 23.0 20.0 22.0 25.0 24.0 26.4 29.5 29.0 31.9 35.5 36.0 39.6

SELECTION TABLE - LONG THREAD


Entry Thread Size A Gland Size Metric Size 12 M12 16 M16 20 M20 25 M25 32 M32 40 M40 50 M50 63 M63 Metric Catalog # GHG 960 1955 R 0021 GHG 960 1955 R 0022 GHG 960 1955 R 0023 GHG 960 1955 R 0024 GHG 960 1955 R 0025 GHG 960 1955 R 0026 GHG 960 1955 R 0027 GHG 960 1955 R 0028 Cable Acceptance Thread Length B Metric 8.0 8.0 8.0 8.0 10.0 15.0 16.0 16.0 Outer Sheath E Min 4.0 5.5 5.5 8.0 12.0 17.0 22.0 27.0 Max 7.0 10.0 13.0 27.0 21.0 28.0 35.0 48.0 Gland Length F (less entry) 19.3 23.0 25.0 29.5 35.5 39.5 44.0 47.0 Hexagon Dimensions Across Flats Across Corners G 15.0 16.5 20.0 22.0 24.0 26.4 29.0 31.9 36.0 39.6 46.0 50.6 55.0 60.5 68.0 74.8

All dimensions in millimeters unless otherwise noted.

78

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Ex-i
International Standards Flameproof and Increased Safety

Sizes M12-M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X IECEx

IP66

4F

Gland Type:
Non-armoured

4F

Cable Type:
Non-armoured

Certifications and Compliances:


Sizes M12-M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X Ex II 2 G Ex e II/Ex II 2 D Ex tD A21 IECEx PTB 05.0004X IP66

Features:
Standard material is high-impact resistant polyamide (gland nut is blue for intrinsically safe circuits) Forms weatherproof seal on outer sheath of cable Standard silicone seal suitable for use in operating temperatures -55 to 70C (M12 and M16 for use in operating temperatures -20 to 70C) Available with metric threads See page 104 for related accessories

SELECTION TABLE SHORT THREAD


Entry Thread Size A Gland Size Metric Size 12 M12 16 M16 20 M20 25 M25 32 M32 Metric Catalog # GHG 960 1955 R 0101 GHG 960 1955 R 0102 GHG 960 1955 R 0103 GHG 960 1955 R 0104 GHG 960 1955 R 0105 Thread Length B Metric 8.0 8.0 8.0 8.0 10.0 Cable Acceptance Outer Sheath E Min Max 4.0 7.0 5.5 10.0 5.5 13.0 8.0 17.0 12.0 21.0 Gland Length F (less entry) 19.3 23.0 25.0 29.5 35.5 Hexagon Dimensions Across Flats 15.0 20.0 24.0 29.0 36.0 Across Corners G 16.5 22.0 26.4 31.9 39.6

SELECTION TABLE LONG THREAD


Entry Thread Size A Gland Size Metric Size 12 M12 16 M16 20 M20 25 M25 32 M32 40 M40 50 M50 63 M63 Metric Catalog # GHG 960 1955 R 0121 GHG 960 1955 R 0122 GHG 960 1955 R 0123 GHG 960 1955 R 0124 GHG 960 1955 R 0125 GHG 960 1955 R 0126 GHG 960 1955 R 0127 GHG 960 1955 R 0128 Cable Acceptance Thread Length B Outer Sheath E Metric Min Max 12.0 4.0 7.0 12.0 5.5 10.0 13.0 5.5 13.0 13.0 8.0 17.0 15.0 12.0 21.0 15.0 17.0 28.0 16.0 22.0 35.0 16.0 27.0 48.0 Gland Length F (less entry) 19.3 23.0 25.0 29.5 35.5 39.5 44.0 47.0 Hexagon Dimensions Across Flats 15.0 20.0 24.0 29.0 36.0 46.0 55.0 68.0 Across Corners G 16.5 22.0 26.4 31.9 39.6 50.6 60.5 74.8

All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

79

4F

Trumpet
International Standards Flameproof and Increased Safety

ATEX

IP66

4F

Gland Type:
Non-armoured

Cable Type:
Non-armoured

Certifications and Compliances:


ATEX PTB 00ATEX3121X Ex II 2 G Ex e II/Ex II 2 D Ex tD A21 IP66

Features:
Standard material is high-impact resistant polyamide Forms weatherproof seal on outer sheath of cable Flared rear seal provides protection for cable Standard neoprene seal suitable for use in operating temperatures -40 to 85C Available with metric threads See page 104 for related accessories

SELECTION TABLE
Gland Size 20 25 32 40 50 60 Entry Metric Size M20 M25 M32 M40 M50 M60 Thread Size A Metric Catalog # GHG 960 1949 GHG 960 1949 GHG 960 1949 GHG 960 1949 GHG 960 1949 GHG 960 1949 Thread Length B Metric 15.0 15.0 15.0 15.0 16.0 16.0 Cable Acceptance Outer Sheath E Min Max 8.0 13.0 11.0 16.0 15.0 20.0 19.0 27.0 26.0 34.0 35.0 46.0 Gland Length F (less entry) 49.0 50.0 65.0 71.0 79.0 89.0 Hexagon Dimensions Across Across Flats Corners G 26.0 28.6 32.0 35.2 41.0 45.1 50.0 55.0 60.0 66.0 75.0 82.5

R0111 R0112 R0113 R0114 R0115 R0116

All dimensions in millimeters unless otherwise noted.

80

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Enlargement and Multiple


International Standards Flameproof and Increased Safety

Sizes M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X IECEx

IP66

4F

Gland Type:
Non-armoured

4F

Cable Type:
Non-armoured

Certifications and Compliances:


Sizes M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X Ex II 2 G Ex e II/Ex II 2 D Ex tD A21 IECEx PTB 05.0004X IP66

Features:
Standard material is high-impact resistant polyamide Forms weatherproof seal on outer sheath of cable Provides reduced entry threads for larger gland size Standard silicone seal suitable for use in operating temperatures -55 to 70C (M16 for use in operating temperatures -20 to 70C) Available with metric threads See page 104 for related accessories

SELECTION TABLE ENLARGEMENT


Gland Size 16/20 20/25 25/32 32/40 40/50 50/63 Entry Metric Size M16 M20 M25 M32 M40 M50 Thread Size A Metric Catalog # GHG 960 1956 R0002 GHG 960 1956 R0003 GHG 960 1956 R0004 GHG 960 1956 R0005 GHG 960 1956 R0006 GHG 960 1956 R0007 Thread Length B Metric 12.0 13.0 13.0 15.0 15.0 16.0 Cable Acceptance Outer Sheath E Min Max 5.5 13.0 8.0 17.0 12.0 21.0 16.0 28.0 21.0 35.0 27.0 48.0 Gland Length F (less entry) 25.0 29.5 35.5 39.5 44.0 47.0 Hexagon Dimensions Across Across Flats Corners G 24.0 26.4 29.0 31.9 36.0 39.6 46.0 50.6 55.0 60.5 68.0 74.8

SELECTION TABLE MULTIPLE


Gland Size 25 32 Entry Thread Size A Metric Size Metric Catalog # M25 GHG 960 1955 R0054 M32 GHG 960 1955 R0055 Thread Length B Metric 8.0 10.0 Cable Acceptance Outer Sheath E Min Max 4.5 7.0 4.5 7.0 Maximum Number of Conductors 2 4 Gland Length F (less entry) 29.5 39.5 Hexagon Dimensions Across Across Flats Corners G 36.0 39.6 46.0 50.6

All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

81

4F

ADE 4I
International Standards Industrial

NEMA 4X and IP68

4F

Gland Type
Armoured

Cable Type
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard lead sheathed (with addition of earthing washer) and tray cable

Certifications and Compliances:


NEMA 4X and IP68

Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping and bonding with no reversible components for easy installation, minimizing error Provides seal on inner jacket and weatherproof seal on outer sheath of the cable An optional earthing washer for use with lead sheathed cable (see page 99) Standard neoprene seal suitable for use in operating temperatures of -60C to 100C Available with optional silicone seal for extreme temperatures Available with metric or NPT threads See pages 98101 for related accessories

SELECTION TABLE
Entry Thread Size A Cable Acceptance Thread Length Inner Sheath Outer Sheath E D B Metric Min Max Min Max (NPT) 15 (12.0) 4.0 8.0 6.0 12.0 15 (12.0) 4.0 8.5 6.0 12.0 15 (12.0) 6.0 12.0 8.5 16.0 15 (20.2) 4.0 8.5 6.0 12.0 15 (20.2) 6.0 12.0 8.5 16.0 15 (20.2) 8.5 16.0 12.0 21.0 15 (20.2) 6.0 12.0 8.5 16.0 15 (20.2) 8.5 16.0 12.0 21.0 15 (20.2) 12.0 20.5 16.0 27.5 15 (25.3) 12.0 21.0 16.0 27.5 15 (25.3) 16.0 27.5 21.0 34.0 15 (26.0) 16.0 27.5 21.0 34.0 15 (26.0) 21.0 34.0 27.0 41.0 16 (26.5) 21.0 34.0 27.0 41.0 16 (26.5) 27.0 41.0 33.0 48.0 17 (27.2) 27.0 41.0 33.0 48.0 17 (27.2) 33.0 48.0 40.0 56.0 18 (40.5) 40.0 56.0 47.0 65.0 18 (40.5) 47.0 65.0 54.0 74.0 22 (42.0) 54.0 74.0 63.0 83.0 22 (42.0) 63.0 82.0 72.0 93.0 (43.2) 63.0 82.0 72.0 93.0 22 (44.5) 72.0 92.0 85.0 107.0 Gland Length F (less entry) 36.0 36.0 42.0 36.0 42.0 46.0 42.0 46.0 56.0 56.0 63.0 63.0 68.0 68.0 74.0 77.0 85.0 85.0 92.0 104.0 108.0 108.0 115.0 Hexagon Dimensions Across Flats Across Corners G 20.9 20.9 26.4 26.4 26.4 33.0 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4 79.2 93.5 93.5 104.5 121.0 132.0 132.0 148.5

Gland Size 5 5 6 5 6 7 6 7 8 8 9 9 10 10 11 12 13 13 14 15 16 16 17

Metric Size M12 M16 M16 M20 M20 M20 M25 M25 M25 M32 M32 M40 M40 M50 M50 M63 M63 M75 M75 M90 M90 M110

Metric Catalog # CAP946404 CAP946594 CAP946504 CAP946674 CAP946694 CAP946604 CAP946774 CAP946794 CAP946704 CAP946894 CAP946804 CAP946994 CAP946904 CAP947094 CAP947004 CAP947294 CAP947204 CAP947394 CAP947304 CAP947594 CAP947504 CAP947794

NPT Size 1 /4" 3 /8" 3 /8" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" 3" 31/2" 4"

NPT Catalog # CAP948404 CAP948594 CAP948504 CAP948674 CAP948694 CAP948604 CAP948774 CAP948795 CAP948704 CAP948894 CAP948804 CAP948994 CAP948904 CAP949904 CAP949004 CAP949294 CAP949204 CAP949949 CAP949404 CAP949564 CAP949504 CAP949604 CAP949704

Armour (max) 0.9 0.9 1.25 0.9 1.25 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.15 3.15 3.15 3.15

All dimensions in millimeters unless otherwise noted.

82

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

TWA
International Standards Industrial
Gland Type
Armoured

IP66 and 67

4F

4F

Cable Type
Steel wire armoured

Certifications and Compliances:


IP66 and 67

Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armoured cable Forms weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories

SELECTION TABLE
Entry Thread Size A Gland Size 20 20 20 25 32 40 50 63 75 Metric Size M20 M20 M20 M25 M32 M40 M50 M63 M75 Metric Catalog # TWA1M13 TWA1M16 TWA1M20 TWA2M27 TWA3M34 TWA4M40 TWA5M53 TWA6M66 TWA7M78 NPT Size 1 /2" 1 /2" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" NPT Catalog # TWA1N13 TWA1N16 TWA1N20 TWA2N27 TWA3N34 TWA4N40 TWA5N53 TWA6N66 TWA7N78 Thread Length B Metric 14.0 14.0 14.0 16.0 20.0 20.0 20.0 22.0 22.0 Cable Acceptance Inner Sheath D Min Max 3.0 8.0 6.0 11.0 7.0 13.0 11.0 19.0 17.0 25.0 24.0 31.0 30.0 41.0 40.0 54.0 53.0 65.0 Outer Sheath E Min Max 8.0 13.0 10.2 15.8 14.0 20.8 18.0 27.2 25.0 33.5 30.0 39.5 36.0 52.6 51.0 65.3 63.0 78.0 Armour Range 0.5 - 0.9 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.5 - 3.5 Gland Length F (less entry) 56.0 58.0 58.0 60.0 72.0 74.0 82.0 90.0 98.0 Hexagon Dimensions Across Across Corners G Flats 27.0 31.0 27.0 31.0 30.4 34.0 38.5 43.0 47.2 53.0 57.0 64.0 70.0 78.0 80.0 88.0 101.0 112.0

All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

83

4F

TUA
International Standards Industrial

IP66 and 67

4F

Gland Type
Non-armoured

Cable Type
Non-armoured

Certifications and Compliances:


IP66 and 67

Features:
Standard material is nickel-plated brass Forms weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories

SELECTION TABLE
Entry Thread Size A Gland Size 16 20 20 20 25 32 32 40 50 50 50 63 63 75 75 Metric Size M16 M20 M20 M20 M25 M32 M32 M40 M50 M50 M50 M63 M63 M75 M75 Metric Catalog # TUA16M7 TUA1M10 TUA1M12 TUA1M15 TUA2M18 TUA3M23 TUA3M25 TUA4M29 TUA5M34 TUA5M38 TUA5M42 TUA6M48 TUA6M54 TUA7M60 TUA7M66 NPT Size N/A 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" NPT Catalog # N/A TUA1N10 TUA1N12 TUA1N15 TUA2N18 TUA3N23 TUA3N25 TUA4N29 TUA5N34 TUA5N38 TUA5N42 TUA6N48 TUA7N54 TUA7N60 TUA8N66 Thread Length B Metric 14.0 14.0 14.0 16.0 16.0 20.0 20.0 20.0 20.0 20.0 22.0 22.0 22.0 22.0 22.0 Cable Acceptance Outer Sheath E Min 10.2 13.0 15.5 19.5 23.5 27.0 30.0 33.0 38.0 43.0 48.0 52.0 58.0 64.3 70.6 Max 13.2 15.8 19.8 23.8 27.2 30.5 33.5 38.5 43.5 48.5 52.6 58.9 65.3 71.6 78.0 Gland Length F (less entry) 58.0 58.0 58.0 60.0 60.0 72.0 72.0 74.0 82.0 82.0 82.0 90.0 90.0 98.0 98.0 Hexagon Dimensions Across Flats 23.3 27.0 30.5 33.3 38.1 42.2 47.0 55.0 57.0 63.5 70.0 76.0 80.0 89.0 101.0 Across Corners G 26.0 31.0 34.0 37.0 43.0 47.0 53.0 64.0 62.0 71.0 78.0 85.0 88.0 102.0 112.0

All dimensions in millimeters unless otherwise noted.

84

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

TMCX
North American Standards Explosionproof
Gland Type

UL Listed CSA Certified Class I, Div. 1 Groups, A, B, C, D Class II; Class III

NEMA 4 and IP56 Wet locations

4F

4F

Armoured barrier, TECK armoured and non-armoured barrier

Cable Type
Metal-clad (interlocked or continuously welded corrugated armoured), non-armoured and tray cable

Certifications and Compliances:


UL Listed, CSA Certified Class I, Div. 1, Groups, A, B, C, D; Class II; Class III UL File E122485, CSA File LR13046 NEMA 4 and IP56 rated Wet locations

Features:
Standard material is aluminum Stainless steel copper-plated spring provides grounding continuity of cable armour (MC cable only) Provides explosionproof compound seal on conductors and watertight seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 60C Cold Shrink Kit is available for extra protection in aggressive environments (see page 105) Available with NPT threads See page 105 for related accessories

SELECTION TABLE
Entry Thread Size A NPT Size 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4" NPT Catalog # TMCX165 TMCX285 TMCX3112 TMCX4140 TMCX5161 TMCX6206 TMCX7247 TMCX8302 TMCX9352 TMCX10402 Thread Length B NPT 0.750 0.781 0.938 0.969 0.969 1.000 1.438 1.438 1.625 1.625 Min 0.440 0.600 0.800 1.100 1.330 1.570 1.930 2.450 2.950 3.500 Cable Acceptance Armour Range H Max 0.650 0.850 1.120 1.400 1.610 2.060 2.470 3.020 3.520 4.020 Outer Sheath E Min 0.490 0.650 0.850 1.150 1.380 1.630 1.990 2.525 3.025 3.585 Max 0.781 1.000 1.313 1.625 1.781 2.313 2.719 3.281 3.781 4.281 Gland Length F (less entry) 2.625 2.875 3.125 3.125 3.375 5.313 6.063 6.063 7.750 8.313 Hexagon Dimensions Across Flats 1.250 1.500 1.875 2.250 2.500 3.250 3.750 4.500 5.000 5.500 Across Corners G 1.375 1.625 2.000 2.438 2.750 3.500 4.000 4.875 5.375 5.875

All dimensions in inches unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

85

4F

ADE 6FC
North American Standards Explosionproof

CEPEL ATEX GOST-R IECEx NEMA 4X and IP68 cULus listed for Class I, Zone 2 cULus Marine listed for Class I, Div. 1

4F

Gland Type
Armoured barrier

Cable Type
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard and lead sheathed (with addition of earthing washer)

Certifications and Compliances:


ATEX LCIE 97 ATEX 6008X - Exd IIC/Exe II/Ex tD/Ex II GD IECEx LCI 05.0004X cULus listed for Class I, Zone 2 AEx e II/Ex e II cULus Marine listed for Class I, Div. 2 AEx e II/Ex e II NEMA 4X and IP68 CEPEL GOST-R

Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping with no reversible components for easy installation, minimizing error Provides exposionproof compound seal (denoted by red back nut) on conductors and weatherproof seal on outer sheath of cable Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures -60C to 80C Available with metric or NPT threads See pages 98101 for related accessories

SELECTION TABLE
Entry Thread Size A Cable Acceptance Inner Sheath and Cores Thread Max Max Length Over Inner Max B Metric Cores Sheath No. of 'C' 'D' Cores (NPT) 15 (12.0) 6.5 7.5 6 15 (20.2) 6.5 7.5 6 15 (20.2) 9.5 11.0 6 15 (20.2) 12.0 14.5 10 15 (20.5) 12.0 14.5 10 15 (20.5) 17.0 19.5 21 15 (25.3) 17.0 19.5 21.0 15 (25.3) 23.0 28.0 42.0 15 (26.0) 23.0 28.0 42.0 15 (26.0) 29.0 33.0 60.0 16 (26.5) 29.0 33.0 60.0 16 (27.2) 36.5 41.0 80.0 Outer Sheath E Hexagon Dimensions

Gland Metric Metric NPT NPT Size Size Catalog # Size Catalog # 5 M16 CAP969594 3/8" CAP974594 5 M20 CAP969674 1/2" CAP971674 6 M20 CAP969694 1/2" CAP971674 7 M20 CAP969604 1/2" CAP971604 7 M25 CAP969794 3/4" CAP971794 8 M25 CAP969704 3/4" CAP971704 8 M32 CAP969894 1" CAP971894 9 M32 CAP969804 1" CAP971804 9 M40 CAP969994 11/4" CAP971994 10 M40 CAP969904 11/4" CAP971904 10 M50 CAP970094 11/2" CAP972094 11 M50 CAP970004 2" CAP972004

Gland Length F Armour (less Across Min Max (max) entry) Flats 6.0 12.0 0.9 46 6.0 12.0 0.9 46 8.5 16.0 1.25 53 12.0 21.0 1.25 59 12.0 21.0 1.25 59 16.0 27.5 1.6 74.5 16.0 27.5 1.6 74.5 21.0 34.0 1.6 83.5 21.0 34.0 1.6 83.5 27.0 41.0 2.0 92 27.0 41.0 2.0 92 33.0 48.0 2.5 104

Across Corners G 20.9 26.4 26.4 33 33 45.1 45.1 52.8 52.8 60.5 60.5 70.4

Larger sizes available soon. All dimensions in millimeters unless otherwise noted.

86

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

ADE 1FC
North American Standards Explosionproof
Gland Type
Non-armoured barrier

ATEX IECEx cULus listed for Class I, Zone 2 cULus Marine listed for Class I, Div. 1

CEPEL GOST-R NEMA 4X and IP68

4F

4F

Cable Type
Non-armoured, armoured and tray cable (does not terminate the armour)

Certifications and Compliances:


ATEX LCIE 97 ATEX 6008X - Exd IIC/Exe II/Ex tD/Ex II GD IECEx LCI 05.0004X cULus listed for Class I, Zone 2 AEx e II/Ex e II cULus Marine listed for Class I, Div. 2 AEx e II/Ex e II NEMA 4X and IP68 CEPEL GOST-R

Features:
Standard material is nickel-plated brass for superior corrosion resistance Provides a flameproof and weatherproof seal on outer sheath of cable Provides explosionproof compound seal (denoted by red back nut) on conductors Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures -60C to 80C Available with metric or NPT threads See pages 98101 for related accessories

SELECTION TABLE
Entry Thread Size A Gland Size 4 4 5 6 6 7 7 8 8 9 9 10 10 Metric Size M16 M20 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 M63 Metric Catalog # CAP019594 CAP019674 CAP019694 CAP019604 CAP019794 CAP019704 CAP019894 CAP019804 CAP019994 CAP019904 CAP019094 CAP019004 CAP019204 NPT Size 3 /8" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/2" 2" --NPT Catalog # CAP011594 CAP971674 CAP011674 CAP011604 CAP011794 CAP011704 CAP011894 CAP011804 CAP011994 CAP011904 CAP011094 CAP011004 --Thread Cable Acceptance Length B Outer Sheath E Metric (NPT) Max Min 15 (12.0) 4.0 7.5 15 (22.2) 4.0 7.5 15 (22.2) 6.5 11.0 15 (22.2) 9.0 14.5 15 (22.5) 9.0 14.5 15 (22.5) 12.0 19.5 15 (27.3) 12.0 19.5 15 (27.3) 17.5 26.0 15 (28.0) 17.5 26.0 15 (28.0) 23.0 33.0 16 (28.5) 23.0 33.0 16 (29.2) 28.5 41.0 16 28.5 41.0 Max No. Cores 6.0 6.0 6.0 10.0 10.0 21.0 21.0 42.0 42.0 60.0 60.0 80.0 80.0 Gland Length F (less entry) 46.0 46.0 53.0 59.0 59.0 74.5 74.5 83.5 83.5 92.0 92.0 104.0 Hexagon Dimensions Across Across Flats Corners G 20.9 26.4 26.4 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4 73.7

Larger sizes available soon. All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

87

4F

CGBS and EBY


North American Standards Explosionproof

CGBS: CSA Certified Class I, Div 1. Groups C, D Class II, Div. 1 & 2, Groups E, F, G Class III

EBY: UL, cUL Listed Class I, Div. 1 Groups, B, C, D Class II, Div. 1 Groups, F, G

4F

Gland Type
Portable cord connector

Cable Type
Non-armoured and tray cable

Certifications and Compliances:


CSA Certified Class I, Div. 1, Groups C, D Class II, Div. 1 & 2, Groups E, F, G Class III CSA File LR13046

CGBS Features:
Body steel with zinc electroplate and chromate finish coat Gland nut aluminum Body well for Chico A sealing compound (for ordering information please contact customer service) Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads

SELECTION TABLE
Entry NPT Size 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/4" Thread Size A NPT Catalog # CGBS1013 CGBS2013 CGBS2014 CGBS3015 CGBS3016 CGBS4017 CGBS4018 CGBS4019 Form A A A B B B B B Outer Sheath E Min 0.312 0.312 0.375 0.500 0.625 0.750 0.875 1.000 Max 0.437 0.437 0.500 0.625 0.750 0.875 1.000 1.188 Gland Length F (less entry) 51/4" 51/4" 51/4" 27/8" 215/16" 213/16" 31/2" 39/16"

All dimensions in inches unless otherwise noted.

Gland Type
Portable cord connector

Cable Type
Non-armoured

Certifications and Compliances


UL, cUL Listed Class I, Div. 1, Groups, B, C, D Class II, Div. 1, Groups, F, G UL File E10279

EBY Features:
Standard material is aluminum Factory sealed conductors and seal on outer sheath of cable Three, 12-inch long, #12 type SF-2 (150C rating) stranded pigtails; two circuit wires and one identified grounding wire Three pressure connectors for 3-conductor cord, range #18 to #12 AWG Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads

SELECTION TABLE
Entry Thread Size A NPT Size 3 /4" 3 /4" 3 /4" NPT Catalog # EBY2672 EBY2682 EBY26102 Outer Sheath E Min Max 0.250 0.437 0.375 0.500 0.500 0.625

All dimensions in inches unless otherwise noted.

88

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

TMC
North American Standards General Purpose
Gland Type
Armoured, TECK armoured and non-armoured

UL, cUL Listed

NEMA 4 and IP56 Wet locations

4F

4F

Cable Type
Metal-clad (interlocked or continuously welded corrugated armoured), non-armoured and tray cable

Certifications and Compliances:


UL, cUL Listed UL File E36379 NEMA 4 and IP56 Wet locations

Features:
Standard material is aluminum Stainless steel copper-plated spring provides grounding continuity of cable armour (MC cable only) Watertight seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 60C Cold Shrink Kit is available for extra protection in aggressive environments (see page 105) Available with NPT threads See page 105 for related accessories

SELECTION TABLE
Entry Thread Size A NPT Size 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4" NPT Catalog # TMC165 TMC285 TMC3112 TMC4140 TMC5161 TMC6206 TMC7247 TMC8302 TMC9352 TMC10402 Thread Length B NPT 0.750 0.781 0.938 0.969 0.969 1.000 1.438 1.438 1.625 1.625 Cable Acceptance Armour Range H Min Max 0.440 0.650 0.600 0.850 0.800 1.120 1.100 1.400 1.330 1.610 1.570 2.060 1.930 2.470 2.450 3.020 2.950 3.520 3.500 4.020 Outer Sheath E Min Max 0.490 0.781 0.650 1.000 0.850 1.313 1.150 1.625 1.380 1.781 1.630 2.313 1.990 2.719 2.525 3.281 3.025 3.781 3.585 4.281 Gland Length F (less entry) 2.375 2.625 2.625 2.750 2.750 4.500 4.750 4.875 5.375 5.500 Hexagon Dimensions Across Flats 1.250 1.500 1.875 2.250 2.500 3.250 3.750 4.500 5.000 5.500 Across Corners G 1.375 1.625 2.000 2.438 2.75 3.500 4.000 4.875 5.375 5.875

All dimensions in inches unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

89

4F

TECK
North American Standards General Purpose

CSA Certified Class II, Div. 1, Div 2 Groups, E, F, G Type 4 and IP56 Class III - CSA Wet locations

4F

Gland Type
Armoured

Cable Type
TECK armoured

Certifications and Compliances:


CSA Certified Class II, Div. 1 & Div. 2, Groups, E, F, G; Class III CSA File LR13046 Type 4 and IP56 Wet locations

Features:
Standard material is aluminum Stainless steel copper-plated spring provides grounding continuity of cable armour (TECK cable only) Watertight seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 60C Cold Shrink Kit is available for extra protection in aggressive environments ( see page 105) An integral o-ring seal on entry threads Available with NPT threads See page 105 for related accessories

SELECTION TABLE
Stainless Steel Catalog # TECK050 1SS TECK050 2SS TECK050 3SS TECK050 4SS TECK075 5SS TECK075 6SS TECK100 7SS Hexagon Gland Entry Cable Acceptance Dimensions Length Thread F Across Size A Thread Armour Range H Outer Sheath E (less Across Corners NPT Length Min Max Min Max entry) Size B NPT G Flats 1 /2" 0.630 0.415 0.570 0.525 0.650 2.300 1.250 1.350 1 /2" 0.630 0.490 0.680 0.600 0.760 2.300 1.375 1.500 1 /2" 0.630 0.615 0.805 0.725 0.885 2.300 1.500 1.600 1 /2" 0.630 0.715 0.905 0.825 0.985 2.300 1.500 1.600 3 /4" 0.630 0.770 0.985 0.880 1.065 2.500 2.000 2.125 3 /4" 0.630 0.915 1.125 1.025 1.205 2.500 2.000 2.125 1" 0.750 1.077 1.295 1.187 1.375 2.625 2.250 2.400 0.800 1.240 1.545 1.350 1.625 3.500 3.000 3.125 11/4" 0.800 1.390 1.545 1.500 1.625 3.400 3.000 3.125 11/4" 0.800 1.490 1.795 1.600 1.875 3.500 3.000 3.125 11/4" 0.800 1.590 1.885 1.700 1.965 3.800 3.750 3.600 11/2" 0.800 1.790 2.107 1.900 2.187 3.900 3.500 3.750 11/2" 2" 0.825 1.790 2.107 1.900 2.187 4.000 3.750 4.000 2" 0.825 1.990 2.280 2.100 2.375 4.000 3.750 4.000 2" 0.875 2.190 2.485 2.300 2.565 4.000 4.125 4.400 2" 0.875 2.390 2.656 2.500 2.750 4.000 4.125 4.400 1.300 2.240 2.560 2.380 2.640 5.000 4.500 4.750 21/2" 1.300 2.440 2.750 2.580 2.840 5.000 4.500 4.750 21/2" 3" 1.400 2.640 2.970 2.790 3.060 5.000 4.600 4.900 3" 1.400 2.870 3.190 3.000 3.270 5.000 4.900 5.250 3" 1.400 3.042 3.390 3.210 3.480 5.000 5.000 5.250 1.400 3.270 3.590 3.420 3.690 5.000 5.600 5.900 31/2" 31/2" 1.400 3.440 3.770 3.610 3.870 5.000 5.500 5.900 4" 1.400 3.600 3.930 3.810 4.030 5.000 6.125 6.500 4" 1.400 3.755 4.065 3.965 4.185 5.000 6.125 6.500 4" 1.400 3.910 4.220 4.120 4.340 5.000 6.125 6.500

Aluminum Catalog # TECK050 1 TECK050 2 TECK050 3 TECK050 4 TECK075 5 TECK075 6 TECK100 7 TECK125 8 TECK125 9 TECK125 10 TECK150 11 TECK150 12 TECK200 13 TECK200 14 TECK200 15 TECK200 16 TECK250 17 TECK250 18 TECK300 19 TECK300 20 TECK300 21 TECK350 22 TECK350 23 TECK400 24 TECK400 25 TECK400 26

Steel Catalog # TECK050 1S TECK050 2S TECK050 3S TECK050 4S TECK075 5S TECK075 6S TECK100 7S TECK125 8S TECK125 9S TECK125 10S TECK150 11S TECK150 12S TECK200 13S TECK200 14S TECK200 15S TECK200 16S TECK250 17S TECK250 18S TECK300 19S TECK300 20S TECK300 21S TECK350 22S TECK350 23S TECK400 24S TECK400 25S TECK400 26S

PVC Catalog # TECK050 1PVC TECK050 2 PVC TECK0503PVC TECK050 4PVC TECK075 5PVC TECK075 6PVC TECK1007PVC TECK125 8PVC TECK125 9PVC TECK125 10PVC TECK150 11PVC TECK150 12PVC TECK200 13PVC TECK200 14PVC TECK200 15PVC TECK200 16PVC TECK250 17PVC TECK250 18PVC TECK300 19PVC TECK300 20PVC TECK300 21PVC TECK350 22PVC TECK350 23PVC

All dimensions in inches unless otherwise noted.

90

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

CGB
North American Standards General Purpose
Gland Type
Non-armoured

cULus Listed

4F

4F

Cable Type
Non-armoured and tray cable

Certifications and Compliances:


cULus Listed - UL File E23223

Features:
Form A - D bodies and gland nuts steel with zinc electroplate and chromate finish coat Form E - F bodies and gland nuts Feraloy iron alloy with electrogalvanized and aluminum acrylic paint Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads Available in all aluminum construction See page 105 for related accessories

SELECTION TABLE
Entry Thread Size A NPT Size 3 /8" 3 /8" 3 /8" 3 /8" 3 /8" 3 /8" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 1" 1" 1" 1" 1" 1" 1" 1" 1" NPT Catalog # CGB3814 CGB3816 CGB3817 CGB3892 CGB3893 CGB3894 CGB114 CGB116 CGB117 CGB192* CGB193* CGB194* CGB195* CGB196* CGB197* CGB292 CGB293 CGB294 CGB295 CGB296* CGB297* CGB298* CGB393 CGB394 CGB395* CGB396* CGB397* CGB3239 CGB398* CGB399* CGB3911* Form A A A B B B A A A B B B B C C B B B B C C D B B C C C C D D D Thread Length B NPT 0.438 0.438 0.438 0.438 0.438 0.438 0.625 0.625 0.625 0.750* 0.750* 0.750* 0.750* 0.625* 0.625* 0.625 0.625 0.625 0.625 0.625* 0.625* 0.625* 0.688 0.688 0.688* 0.688* 0.688* 0.688 0.625* 0.625* 0.625* Cable Acceptance Outer Sheath E Min 0.125 0.250 0.375 0.125 0.250 0.375 0.125 0.250 0.375 0.125 0.250 0.375 0.500 0.625 0.750 0.125 0.250 0.375 0.500 0.625 0.750 0.875 0.250 0.375 0.500 0.625 0.750 0.875 0.875 1.000 1.188 Max 0.250 0.375 0.437 0.250 0.375 0.500 0.250 0.375 0.437 0.250 0.375 0.500 0.625 0.750 0.875 0.250 0.375 0.500 0.625 0.750 0.875 1.000 0.375 0.500 0.625 0.750 0.875 1.000 1.000 1.188 1.375 Gland Length F (less entry) 1.063 1.063 1.063 1.313 1.313 1.313 1.000 1.000 1.000 1.313 1.313 1.313 1.313 1.750 1.750 1.375 1.375 1.375 1.375 1.750 1.750 2.500 1.375 1.375 1.688 1.688 1.688 1.688 2.375 2.375 2.375 External Diameter G 2.250 2.375 2.375 2.375 Hexagon Dimensions Across Flats 0.750 0.750 0.750 1.000 1.000 1.000 0.875 0.875 0.875 1.000 1.000 1.000 1.000 1.500 1.500 1.060 1.060 1.060 1.060 1.630 1.630 1.375 1.375 1.500 1.500 1.500 Across Corners G 0.875 0.875 0.875 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.656 1.656 1.250 1.250 1.250 1.250 1.656 1.656 1.625 1.625 1.875 1.875 1.875 1.875

All dimensions in inches unless otherwise noted. *With optional Sealing Gasket. With optional Aluminum Construction.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

91

4F

CGB
North American Standards General Purpose

cULus Listed

4F

Entry Thread Size A NPT Size 11/4" 11/4" 11/4" 11/4" 11/4" 11/2" 11/2" 11/2" 11/2" 11/2" 2" 2" 2" 2" 21/2" 21/2" 21/2" 21/2" 3" 3" NPT Catalog # CGB498 CGB499 CGB4911 CGB4913 CGB4915 CGB598 CGB599 CGB5911 CGB5913 CGB5915 CGB6913 CGB6915 CGB6917 CGB6920 CGB7913 CGB7915 CGB7917 CGB7920 CGB8917 CGB8920 Form D D D E E D D D E E E E F F E E F F F F

Thread Length B NPT 0.688 0.688 0.688 0.688 0.688 0.813 0.813 0.813 0.813 0.813 0.813 0.813 0.813 0.813 1.000 1.000 1.000 1.000 1.000 1.000

Cable Acceptance Outer Sheath E Min 0.875 1.000 1.188 1.375 1.625 0.875 1.000 1.188 1.375 1.625 1.375 1.625 1.875 2.188 1.375 1.625 1.875 2.188 1.875 2.188 Max 1.000 1.188 1.375 1.625 1.875 1.000 1.188 1.375 1.625 1.875 1.625 1.875 2.188 2.500 1.625 1.875 2.188 2.500 2.188 2.500

Gland Length F (less entry) 2.313 2.313 2.313 2.625 2.625 2.313 2.313 2.313 2.625 2.625 2.625 2.625 2.563 2.563 2.625 2.625 2.625 2.625 2.625 2.625

External Diameter G 2.250 2.250 2.250 3.000 3.000 2.250 2.250 2.250 3.000 3.000 3.000 3.000 3.750 3.750 3.125 3.125 3.750 3.750 3.750 3.750

Hexagon Dimensions Across Flats Across Corners G

92

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

CGD
North American Standards General Purpose

cULus Listed

4F

Gland Type
Non-armoured

4F

Cable Type
Non-armoured and tray cable

Certifications and Compliances:


cULus Listed - Ul File E23223

Features:
45 angle with male thread Standard body material is Feraloy iron alloy Standard gland nut material is steel Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories

SELECTION TABLE
Entry Thread Size A NPT Size NPT Catalog # 1 /2" CGD192 /2" /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4"
1 1

Thread Length B NPT 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630

Cable Acceptance Outer Sheath E Min Max 0.125 0.250 0.250 0.375 0.500 0.625 0.750 0.125 0.250 0.375 0.500 0.625 0.750 0.375 0.500 0.625 0.750 0.875 0.250 0.375 0.500 0.625 0.750 0.875

Gland Length F (less entry) 1.688 1.688 1.688 1.688 2.063 2.063 1.938 1.938 1.938 1.938 2.000 2.000

External Diameter G 1.188 1.188 1.188 1.188 1.625 1.625 1.141 1.141 1.125 1.125 1.625 1.625

CGD193 CGD194 CGD195 CGD196 CGD197 CGD292 CGD293 CGD294 CGD295 CGD296 CGD297

All dimensions in inches unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

93

4F

CGE
North American Standards General Purpose

cULus Listed

4F

Gland Type
Non-armoured

Cable Type
Non-armoured and tray cable

Certifications and Compliances:


cULus Listed - UL File E23223

Features:
90 angle with male thread Standard body material is Feraloy iron alloy Standard gland nut material is steel Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories

SELECTION TABLE
Entry Thread Size A NPT Size /2" /2" 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 1" 1" 1" 1" 1" 1" 1"
1 1

NPT Catalog # CGE192 CGE193 CGE194 CGE195 CGE196 CGE197 CGE292 CGE293 CGE294 CGE295 CGE296 CGE297 CGE395 CGE396 CGE397 CGE3239 CGE398 CGE399 CGE3911

Thread Length B NPT 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710

Cable Acceptance Outer Sheath E Min 0.1250 0.2500 0.3750 0.5000 0.6250 0.7500 0.1250 0.2500 0.3750 0.5000 0.6250 0.7500 0.5000 0.6250 0.7500 0.8750 0.8750 1.0000 1.1880 Max 0.2500 0.3750 0.5000 0.6250 0.7500 0.8750 0.2500 0.3750 0.5000 0.6250 0.7500 0.8750 0.6250 0.7500 0.8750 1.0000 1.0000 1.1880 1.3750

Gland Length F (less entry) 1.438 1.438 1.438 1.438 2.000 2.000 1.406 1.406 1.406 1.406 1.875 1.875 2.063 2.094 2.094 2.094 2.656 2.656 2.656

External Diameter G 1.188 1.188 1.188 1.188 1.625 1.625 1.188 1.188 1.188 1.188 1.625 1.625 1.625 1.625 1.625 2.250 2.250 1.625 2.250

All dimensions in inches unless otherwise noted.

94

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

CGB1013
North American Standards General Purpose

cULus Listed

4F

Gland Type
Portable cord connector

4F

Cable Type
Non-armoured and tray cable

Certifications and Compliances:


cULus Listed - UL File E23223

Features:
Body steel with zinc electroplate and chromate finish coat Gland nut material is aluminum Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories

SELECTION TABLE
Entry Thread Size A NPT Size NPT Catalog # 1 /2" CGB1013 1 /2" CGB1014 1 /2" CGB1015 3 /4" CGB2013 3 /4" CGB2014 3 /4" CGB2015
All dimensions in inches unless otherwise noted.

Outer Sheath E Min 0.312 0.375 0.500 0.312 0.375 0.500 Max 0.437 0.500 0.625 0.437 0.500 0.625

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

95

4F

CGFP
North American Standards General Purpose

4F

Gland Type:
Non-armoured

Cable Type:
Non-armoured and tray cable

Features:
Form B - C standard body and gland nut are turned steel Form D - G standard body and gland nut are Feraloy iron alloy Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories

SELECTION TABLE
Entry Thread Size A NPT Size 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 1" 1" 1" 11/4" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" 3" 31/2" 31/2" 4" 4" NPT Catalog # CGFP192 CGFP193 CGFP194 CGFP195 CGFP296 CGFP297 CGFP2239 CGFP396 CGFP397 CGFP3239 CGFP499 CGFP4911 CGFP599 CGFP5911 CGFP6913 CGFP6915 CGFP7917 CGFP7920 CGFP8917 CGFP8920 CGFP923 CGFP927 CGFP1023 CGFP1027 Form B B B B C C C C C C D D D D E E F F F F G G G G Thread Length B NPT 0.750 0.750 0.750 0.750 0.750 0.750 0.750 0.938 0.938 0.938 0.938 0.938 0.938 0.938 1.000 1.000 1.438 1.438 1.500 1.500 1.563 1.563 1.625 1.625 Cable Acceptance Outer Sheath E Min Max 0.1250 0.2500 0.2500 0.3750 0.3750 0.5000 0.5000 0.6250 0.6250 0.7500 0.7500 0.8750 0.8750 1.0000 0.6250 0.7500 0.7500 0.8750 0.8750 1.0000 1.0000 1.1880 1.1880 1.3750 1.0000 1.1880 1.1880 1.3750 1.3750 1.6250 1.6250 1.8750 1.8750 2.1880 2.1880 2.5000 1.8750 2.1880 2.1880 2.5000 2.5000 3.0000 3.0000 3.5000 2.5000 3.0000 3.0000 3.5000 Gland Length F (less entry) 1.375 1.375 1.375 1.375 1.750 1.750 1.750 1.750 1.750 1.750 2.375 2.375 2.375 2.375 3.250 3.250 3.250 3.250 3.250 3.250 4.250 4.250 4.250 4.250 External Diameter G 1.281 1.281 1.281 1.281 1.781 1.781 1.781 1.781 1.781 1.781 2.250 2.250 2.250 2.250 3.250 3.250 3.875 3.875 3.875 3.875 5.500 5.500 5.500 5.500

All dimensions in inches unless otherwise noted.

96

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

NCG and NCGB


North American Standards General Purpose

cULus Listed NEMA 3, 4X (NCGB only)

4F

Gland Type:
Non-armoured

4F

Cable Type:
Non-armoured and tray cable

Certifications and Compliances:


cULus Listed - UL File E23223

SELECTION TABLE
Entry Thread Size A NPT Size NPT Catalog # 3 /8" NCG38 35 1 /2" NCG50 50 3 /4" NCG75 75 1" NCG100 100
All dimensions in inches unless otherwise noted.

NCG Features:
Outer Sheath E Min Max 0.10 0.35 0.20 0.50 0.35 0.75 0.55 1.00 Standard material is polyamide 6 Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads

POLYAMIDE LOCK NUT SELECTION TABLE


Size 3 /8"
1 3

Catalog # 10N 11N 12N 13N

/2" /4"

1"

Gland Type:
Non-armoured

Cable Type:
Non-armoured and tray cable

Certifications and Compliances:


cULus Listed - UL File E23223 NEMA 3, 4X

SELECTION TABLE
NPT Size 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" NPT Catalog # NCGB1231 NCGB1232 NCGB2233 NCGB2234 NCGB3235 NCGB3236 Cable Acceptance Range 'E' Min Max 0.25 0.42 0.40 0.57 0.54 0.68 0.64 0.78 0.76 0.91 0.89 1.03 Gland Length (Less Entry) 'F' 2.25 2.25 2.52 2.52 3.19 3.19 External Diameter 'G' 1.33 1.33 1.58 1.58 2.02 2.02

NCGB Features:
Standard material is thermoplastic polyester Tightens by hand to create a watertight seal Gasket on entry threads included Compact design allows close grouping of connectors Available with NPT threads

All dimensions in inches unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

97

4F

Accessories A Series

4F

A Series Lock Nut


Entry Thread M16 M20 M25 M32 M40 M50 M63 M75 A 3 3 3 3.5 4 5 6 8 B 18 23 28 36 44 54 70 85

Standard material is nickel-plated brass

METRIC SELECTION TABLE


Catalog # CAP221694 CAP222094 CAP222594 CAP223294 CAP224094 CAP225094 CAP226394 CAP227594
1

NPT SELECTION TABLE


Entry Thread /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" A 3.5 3.5 4.5 4.5 5 5.5 6.5 B 24 30 37 47 52 64 77 Catalog # CAP280124 CAP280134 CAP280144 CAP280154 CAP280164 CAP280174 CAP280184

* For stainless steel replace last digit with "9".

A Series Sealing Washer Standard material is neoprene METRIC SELECTION TABLE NPT SELECTION TABLE
Metric Metric Size Catalog # 10 12 16 20 25 32 40 50 63 CAP221049 CAP221249 CAP221649 CAP222049 CAP222549 CAP223249 CAP224049 CAP225049 CAP226349 Metric Diam. D 15.0 18.0 22.0 24.0 30.0 42.0 52.0 63.0 77.0 Metric Thickness E 1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.0 NPT Size /4" /8" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2"
1 3

NPT Catalog # CAP229014 CAP229038 CAP229012 CAP229034 CAP229010 CAP229114 CAP229112 CAP229020 CAP229212 CAP229300 CAP229312

NPT Diam. D 20.0 22.0 27.0 33.0 41.0 52.0 57.0 71.0 85.0 104.0 120.0

NPT Thickness E 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0

A Series Earth Tag Standard material is nickel-plated brass METRIC SELECTION TABLE
Entry Thread M16 M20 M25 M32 M40 M50 M63 M75 A 48.75 53.8 61.5 73 86.5 111.5 125.5 137.5 B 30 33 36 41 44.5 58 67 73 C 6.75 7 10.5 12.2 13.5 13.5 13.5 13.5 D 24.5 28.6 34 42 54 67 77 89 Catalog # CAP567034 CAP567054 CAP567074 CAP567094 CAP567124 CAP567154 CAP567184 CAP567194

NPT SELECTION TABLE


Entry Thread /2" 3 /4" 1" 11/4" 11/2" 2" 21/2"
1

A 61.5 73 73 86.5 111.5 125.5 137.5

B 36 41 41 44.5 58 67 73

C 10.5 12.2 12.2 13.5 13.5 13.5 13.5

D 34 42 42 54 67 77 89

Catalog # CAP567064 CAP567084 CAP567104 CAP567134 CAP567154 CAP567174 CAP567194

All dimensions in millimeters unless otherwise noted.

98

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Accessories A Series

4F

A Series Serrated Lock Washer


Standard material is stainless steel

A-Series Shroud
Standard material is PVC

4F

SELECTION TABLE
Gland Size Catalog # CAP506040 CAP506050 CAP506060 CAP506070 CAP506080 CAP506090 CAP506100 CAP506110 CAP506120 CAP506130 CAP506140 CAP506150 CAP506160

SELECTION TABLE
Metric Size 16 20 25 32 40 50 63 75 90 External Diameter 25.5 32.5 39.5 49.5 64.5 80.5 100 112 123 Catalog # CAP280069 CAP280029 CAP280259 CAP280329 CAP280409 CAP280509 CAP280639 CAP280759 CAP280099

4 5 6 7 8 9 10 11 12 13 14 15 16

A Series Clamping Module


Standard materials are nickel-plated brass body with stainless steel screws and washers

SELECTION TABLE
Cable Range Gland Size 4-8.5 6-11 8.5-16 12-21 16-27.5 21-34 27-41 33-48 40-56 47-65 54-74 63-83 72-93 4 5 6 7 8 9 10 11 12 13 14 15 16 Across Flats 15 19 24 30 41 48 55 64 72 85 95 110 120 Width 18 22 27.5 33.5 45 52 59 69 78 92 103 118 128 Thickness Catalog # 5 5 6 8 8 9.5 9.5 12 12 16 16 18 18 CAP810434 CAP810534 CAP810634 CAP810734 CAP810834 CAP810934 CAP811034 CAP811134 CAP811234 CAP811334 CAP811434 CAP811534 CAP811634

A Series Earthing Washer Standard material is brass METRIC SELECTION TABLE


Lead Sheath Sealing Range Gland Size 5 6 7 8 9 10 11 12 13 14 15 16 Min 4 6 9 12 16 21 28 33 40 46.5 54 63 Max 7.5 11 15 20 26.5 32.5 39.5 46.5 54.5 61 72.5 81.5 Cable Diameter 10 13.9 18.3 23.8 31 38.3 45.3 52.8 60.8 71 80.5 89.5 Catalog # CAP560530 CAP560630 CAP560730 CAP560830 CAP560930 CAP561030 CAP561130 CAP561230 CAP561330 CAP561430 CAP561530 CAP561630

All dimensions in millimeters unless otherwise noted.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

99

4F

Accessories A Series

Standard brass A Series Adaptors and Reducers ATEX Exe material is nickel-plated00010 Exd with LCIE 98 ATEX

4F

METRIC x METRIC SELECTION TABLE


Female Male
M12 M16 M20 M25 M32 M40 M50 M63 M75 M90 M110

M12
745834 745844

M16
745334

M20
740274

M25

M32

M40

M50

M63

M75

M80

M90

M110

740024 740034

740544 740294 740304 740814 740564 740574 741084 740834 740844 741354 741104 741114 741624 741374 741384 741894 741644 745864 745394

METRIC x NPT SELECTION TABLE


Female Male
1

/4"

/8"

/2"

/4"

1"

11/4"

11/2"

2"

21/2"

3"

31/2"

M12 744104 M16 M20 744204 M25 M32 M40 M50 M63 M75 M90 M110

744194 744214

744694 744704 744714 744724

744964 744974 744984 744994

745234 745244 745254 745264

745504 745514 745524

745774 745784 745794

746044 746054 746064

746314 746324

746584 744304

Size available no part number Size not available

NPT x METRIC SELECTION TABLE


Female Male 1 /4" 3 /8" 1 /2" 3 /4"
1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4"

M12
740614 740884 740914

M16
740624 740894 740194 740204

M20
740904 740454 740464 740474

M25

M32

M40

M50

M63

M75

M90

M100

M110

740714 740724 740734 740744

740984 740994 741004 741104

741264 741274 741284

741524 741534 741544 741554

741794 741804 741814 741824

742064

NPT x NPT SELECTION TABLE


Female Male 1 /4" 3 /8" 1 /2" 3 /4"
1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4"
1

/4"

/8"

/2"

/4"

1"

11/4"

11/2"

2"

21/2"

3"

31/2"

4"

745574 745594

744624 745134 744884 744894 745404 745154 745164 745674 745424 745434 745944 745694 745704 746214 745964 746234 746244 746484 746504

* For stainless steel replace last digit with "9".

100

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Accessories A Series

4F

A Series Stopping Plug Standard material is nickel-plated brass;


ATEX Exe Exd with LCIE 98 ATEX 00010

4F

METRIC SELECTION TABLE


Metric Size
12 16 20 25 32 40 50 63 75 80 90 100

Metric Catalog #*
CAP190124 CAP190164 CAP190204 CAP190254 CAP190324 CAP190404 CAP190504 CAP190634 CAP190754 CAP190804 CAP199904 CAP191004

Across Flats A
14 18 23 28 36 44 54 67 80 85 95 110

Hex Thickness B
2.8 3.0 3.0 3.5 4.0 4.0 5.0 5.5 6.0 7.0 8.0 10.0

Thread Length E
15 15 15 15 15 15 16 17 18 20 22 22

* For stainless steel replace last digit with "9".

NPT SELECTION TABLE


NPT Size NPT Catalog #* /4" 3 /8" 1 /2" 3 /4"
1

Across Flats A
14 18 22 28 36 44 50 64 75 90 110

Hex Thickness B
2.8 2.8 3.0 3.0 3.5 4.0 5.0 5.5 6.0 6.0 10.0

Thread Length E
12 12 16 16 20 20 20 20 28 30 32

1" 11/4" 11/2" 2" 21/2" 3" 31/2"

CAP190194 CAP109294 CAP190394 CAP190494 CAP190594 CAP190694 CAP190794 CAP190894 CAP190994 CAP191094 CAP191194

All dimensions in millimeters unless otherwise noted. *For stainless steel replace last digit with "9".

A Series Nonmetallic Stopping Plug

Standard material is polyamide 6; ATEX certified Ex e II with LCIE 97ATEX6007X

Washer and locknut are required for non-threaded holes (not included) see page 98

POLYAMIDE SELECTION TABLE


Metric Size
12 16 20 25 32 40 50 63

Metric Catalog #*
CAP191127 CAP191167 CAP191207 CAP191257 CAP191327 CAP191407 CAP191507 CAP191637

Across Flats A
15 19 23 28 36 44 54 67

Hex Thickness B
4 4 4 5 5.5 5.5 6 6.5

Thread Length E
15 15 15 15 15 15 16 17

*For stainless steel replace last digit with "9".

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

101

4F

Accessories B Series

4F

B Series Lock Nut Standard material is brass


METRIC SELECTION TABLE
Metric Entry Thread M16 M20 M25 M32 M40 M50 M63 M75 M80 M85 M90 M100 Catalog # BLN/M16 BLN/M20 BLN/M25 BLN/M32 BLN/M40 BLN/M50 BLN/M63 BLN/M75 BLN/M80 BLN/M85 BLN/M90 BLN/M100 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4"
1

NPT SELECTION TABLE


NPT Entry Thread Catalog # BLN/050NPT BLN/075NPT BLN/100NPT BLN/125NPT BLN/150NPT BLN/200NPT BLN/250NPT BLN/300NPT BLN/350NPT BLN/400NPT

B Series Sealing Washer Standard material is nylon


METRIC SELECTION TABLE
Metric Entry Thread M16 M20 M25 M32 M40 M50 M63 M75 M80 M85 M90 M100 Catalog # RNSW/M16 RNSW/M20 RNSW/M25 RNSW/M32 RNSW/M40 RNSW/M50 RNSW/M63 RNSW/M75 RNSW/M80 RNSW/M85 RNSW/M90 RNSW/M100 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4"
1

NPT SELECTION TABLE


NPT Entry Thread Catalog # RNSW/050NPT RNSW/075NPT RNSW/100NPT RNSW/125NPT RNSW/150NPT RNSW/200NPT RNSW/250NPT RNSW/300NPT RNSW/350NPT RNSW/400NPT

B Series Earth Tag Standard material is brass


METRIC SELECTION TABLE
Metric Entry Thread M16 M20 M25 M32 M40 M50 M63 M75 M80 M85 M90 M100 Catalog # BET/M16 BET/M20 BET/M25 BET/M32 BET/M40 BET/M50 BET/M63 BET/M75 BET/M80 BET/M85 BET/M90 BET/M100 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4"
1

NPT SELECTION TABLE


NPT Entry Thread Catalog # BET/050NPT BET/075NPT BET/100NPT BET/125NPT BET/150NPT BET/200NPT BET/250NPT BET/300NPT BET/350NPT BET/400NPT

B Series Shroud
PVC SELECTION TABLE
Size (Gland Size) L24 (16, 20s) L30 (20) L38 (25) L46 (32) L55 (40) L65 (50, 50s) L80 (63, 63s) L90 (75, 75s) L104 (80,85) L114 (90, 100) Catalog # PVC-L24 PVC-L30 PVC-L38 PVC-L46 PVC-L55 PVC-L65 PVC-L80 PVC-L90 PVC-L104 PVC-L114 Size L24 (16, 20s) L30 (20) L38 (25) L46 (32) L55 (40) L65 (50, 50s) L80 (63, 63s) L90 (75, 75s) L104 (80, 85)

PCP SELECTION TABLE


Catalog # PCP-L24 PCP-L30 PCP-L38 PCP-L46 PCP-L55 PCP-L65 PCP-L80 PCP-L90 PCP-L104

PVC

PCP

All dimensions in millimeters unless otherwise noted.

102

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Accessories C Series

4F

C Series Lock Nut


Metric Entry Diameter 20 25 32 40 50 63 75 80

Standard material is brass

4F

METRIC SELECTION TABLE


Catalog # LNM1 LNM2 LNM3 LNM4 LNM5 LNM6 LNM7 LNM8 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3"
1

NPT SELECTION TABLE


NPT Entry Diameter Catalog # LNN1 LNN2 LNN3 LNN4 LNN5 LNN6 LNN7 LNN8

C Series Sealing Washer/Gaskets


METRIC SELECTION TABLE
Metric Entry Diameter 20 25 32 40 50 63 75 80 Catalog # SGM1 SGM2 SGM3 SGM4 SGM5 SGM6 SGM7 SGM8

Standard material is nylon

NPT SELECTION TABLE


NPT Entry Diameter /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3"
1

Catalog # SGN1 SGN2 SGN3 SGN4 SGN5 SGN6 SGN7 SGN8

C Series Earth Tag


Metric Entry Diameter 20 25 32 40 50 63 75 80

Standard material is nickel-plated brass

SELECTION TABLE
NPT Entry Thread /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3"
1

Catalog # ET1 ET2 ET3 ET4 ET5 ET6 ET7 ET8

C Series Shroud
Catalog Number SH1 SH2 SH3 SH4 SH5 SH6 SH7 SH8 SH9 SH10 SH11 SH12 SH13 SH14

Standard material is PVC

SELECTION TABLE
To Suit Gland TUA1M10 TUA1M12 TUA1M15 TUA2M18 TUA3M23 TUA3M25 TUA5M34 TUA5M38 TUA5M42 TUA6M48 TUA6M54 TUA7M60 TUA7M66 TWA1M13 TWA1M16 TWA1M20 TWA2M27 TWA3M34 TWA4M40 TWA5M53 TWA6M66 TWA7M78 TWAE1M16 TWAE1M20 TWAE2M27 TWAE3M34 TWAE4M40 TWAE5M53 TWAE6M66 TWAE7M78 TWAX1M13 TWAX1M16 TWAX1M20 TWAX2M24 TWAX2M27 TWAX3M30 TWAX3M33 TWAX4M38 TWAX5M43 TWAX5M48 TWAX5M52 TWAX6M60 TWAX6M65 TWAX7M71 TWAX7M78 TWAB1M16 TWAB1M20 TWAB2M27 TWAB3M34 TWAB4M40 TWAB5M53 TWAB6M66 TWAB7M78

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

103

4F

Accessories D Series

4F

D Series Lock Nut


Metric Entry Diameter M12 M16 M20 M25 M32 M40 M50 M63 x x x x x x x x 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

Standard material is polyamide

SELECTION TABLE
Width 17.00 22.00 26.00 32.00 41.00 50.00 60.00 75.00 Thickness 5.00 5.00 6.00 6.00 7.00 7.00 8.00 8.00 Catalog # GHG GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 960 1941 1941 1941 1941 1941 1941 1941 1941 R0031 R0032 R0033 R0034 R0035 R0036 R0037 R0038

D Series Reducing Ring

Standard material is polyamide

SELECTION TABLE
Thread 1 Thread 2 20 25 32 32 40 40 50 50 63 63 x x x x x x x x x x 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 M16 M20 M20 M25 M25 M32 M32 M40 M40 M50 x x x x x x x x x x 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 Length 1 12.00 14.00 16.00 16.00 16.00 16.00 18.00 18.00 18.00 18.00 Length 2 8.00 8.00 10.00 10.00 10.00 10.00 12.00 12.00 12.00 12.00 Length 3 8.00 8.00 6.00 10.00 8.00 10.00 10.00 10.00 10.00 12.00 Across Flats 24.00 29.00 36.00 36.00 46.00 46.00 55.00 68.00 68.00 68.00 Catalog # GHG GHG GHG GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 960 960 960 1946 1946 1946 1946 1946 1946 1946 1946 1946 1946 R0071 R0072 R0056 R0074 R0059 R0077 R0062 R0080 R0065 R0083

D Series Screw Plug


Thread 1 16 20 25 32 40 50 63 x x x x x x x 1.5 1.5 1.5 1.5 1.5 1.5 1.5 Diameter 21.50 25.50 30.50 37.50 45.50 55.50 85.00

Standard material is polyamide

SELECTION TABLE
Length 1 4.00 4.00 4.00 5.50 5.50 5.50 6.50 Length 2 12.00 13.00 13.00 15.00 15.00 16.00 16.00 Catalog # GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 1952 1952 1952 1952 1952 1952 1952 R0111 R0112 R0113 R0114 R0115 R0116 R0117

D Series Blanking Plug


Thread 1 12 16 20 25 32 40 50 63 Diameter 6.00 7.00 8.50 11.00 14.00 20.00 26.00 34.00

For sealing unused cable glands; Standard material is polyamide

SELECTION TABLE
Length 1 30.30 33.00 34.50 36.00 39.50 42.00 44.00 45.00 Catalog # GHG GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 960 1944 1944 1944 1944 1944 1944 1944 1944 R0101 R0102 R0103 R0104 R0105 R0106 R0107 R0108

All dimensions in millimeters unless otherwise noted.

104

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Accessories E Series

4F

E Series TSC Epoxy Sealing Compound SELECTION TABLE


Std. Carton Qty. 10 10 5 Tube Size 0.5 oz. 1.0 oz. 4.0 oz. Catalog # TSC05 TSC1 TSC4

4F

E Series Wire Mesh Grip SELECTION TABLE


Cord Range Diameter .375 to .500 .500 to .625 .500 to .625 .625 to .750 .750 to .875 .875 to 1.000 .875 to 1.000 .875 to 1.000 .875 to 1.000 1.000 to 1.188 1.188 to 1.375 1.375 to 1.625 1.625 to 1.875 Gland Nut NUT94 NUT94 NUT95 NUT95 NUT95 NUT98 NUT98 NUT95 NUT98 NUT98 NUT98 NUT913 NUT913 Wire Mesh Grip Catalog # RPE417-115 RPE417-116 RPE417-129 RPE417-117 RPE421-119 16676N 16676N RPE421-120 16676N RPE421-121 RPE433-122 RPE433-123 17317N

E Series Cold Shrink Kit SELECTION TABLE


Entry Thread /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4"
1

Catalog # TMC-K1 TMC-K2 TMC-K3 TMC-K4 TMC-K5 TMC-K6 TMC-K7 TMC-K8 TMC-K9 TMC-K10

All dimensions in inches unless otherwise noted.

Cold ShrinkTM Corrosion Protection Kits are specially designed for Cooper Crouse-Hinds TMC, TMCX and TECK fittings to provide protection against corrosive elements like salt spray and moisture. The TMC-K kit is made of a Cold Shrink material that is quick and easy to install on the gland. The Cold Shrink material is made of EPDM rubber that contains no chlorides or sulfurs. The protection kit installs easily over the gland without the use of a heat source to shrink the material tightly over the seal. The Cold Shrink material can be removed easily from the gland by simply cutting it off. See ordering information for complete offering of TMC-K Cold Shrink kits for corrosion protection. Cold Shrink is a registered trademark of the 3M Company.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

105

4F

Accessories Breathers & Drains

4F

Breather Drain SIRA 99 ATEX 3050 U

I M2 II, 2GD, EExe I & II (Stainless steel & brass only) II 2GD, EExe II (Nylon only) Enclosure type 4X IP66

SELECTION TABLE
Entry Thread M20 M20 M20 M25 M25 M25 1 /2" 1 /2" 3 /4" 3 /4" Material Brass Stainless Nylon Brass Stainless Nylon Brass Stainless Brass Stainless Steel Steel Steel Steel Catalog # ACDPEB/M20/15 ACDPES/M20/15 ACDPEN/M20/15 ACDPEB/M25/15 ACDPES/M25/15 ACDPEN/M25/15 ACDPEB/050NPT/15 ACDPES/050NPT/15 ACDPEB/075NPT/15 ACDPES/075NPT/15

Drainage Plug Standard material is polyamide; PTB01 ATEX 1128X Ex 1126 Exe II SELECTION TABLE
Thread 1 M25 x 1.5 Diameter 30.00 Length 1 19.00 Length 2 4.50 Catalog # GHG 960 1927 R0105

Breathing and Drainage Plug Standard material is glass-filled polyamide;


SIRA 99 ATEX 3050 U Ex 1126 Exe II

SELECTION TABLE
Thread 1 M25 x 1.5 Catalog # GHG 960 1954 R0002
All dimensions in millimeters unless otherwise noted.

Please refer to section 6F for additional breather and drain options.

106

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

LCC Series Cable Tray Conduit Clamps

4F

Applications:
LCC cable tray conduit clamps are used for installation on cable tray side rails with inside flanges (requiring inside tray mounting) and outside flanges; LCCF clamps are for use exclusively on inside flanges. LCC/LCCF cable tray conduit clamps: Provide a means of clamping metal conduit (rigid steel or aluminum, IMC and EMT) to cable tray to provide for the exit of power and/or control cables from tray Provide a means to firmly bond exit conduit to cable tray for best grounding continuity Provide strong mechanical support for exit conduits and cables Can be used indoors or outdoors, wherever cable tray systems are installed Facilitate the safe exit of cables from tray insure protection of cables from damage

4F

LCC

LCCF

For use with outside rail tray

For use with inside rail tray

Ordering Information
Conduit Size /2 3 /4 1 11/4 11/2 2 21/2 3 31/2 4
1

Cat. # LCC1 LCC2 LCC3 LCC4 LCC5 LCC6 LCC7 LCC8 LCC9 LCC010

Cat. # LCCF1 LCCF2 LCCF3 LCCF4 LCCF5 LCCF6 LCCF7 LCCF8 LCCF9 LCCF010

Features:
Quick and easy installation low installed cost. Merely tighten clamp nut and/or set screw(s) Swivel hook clears conduit. No disassembly required for installation No drilling or welding necessary for installation Provides superior ground continuity between conduit and cable tray Clamps conduit at any angle with relation to tray facilitates wire pulling, minimizes conduit bending Malleable iron body provides great strength Knurled body has no-slip surface for conduit and tray positive grip assured Compact design has low profile minimum tray space required for assembly Design accommodates all popular types of cable tray Accommodates wide range of conduit sizes 1/2" through 4" LCCF features: Outside mounting facilitates inside rail installation Adjustable hook assures positive grip on inside rail Accommodates 3/4" through 13/4" wide flange

Dimensions
In Inches:

Certifications and Compliances:


UL Standard: 467 (Grounding and Bonding Equipment)

Standard Materials:
Body cast iron Hook steel Set screws and clamping nut steel Hook cap vinyl Conduit Size 1 /2 3 /4 1 11/4 11/2 2 21/2 3 31/2 4 LCC a 33/16 37/16 39/16 4 413/16 55/16 513/16 613/16 75/16 713/16 b 111/16 111/16 111/16 111/16 211/16 211/16 211/16 33/4 33/4 33/4 LCCF a 31/8 311/32 319/32 315/16 43/4 51/4 53/4 63/4 71/4 73/4 b 15/8 15/8 15/8 15/8 23/4 23/4 23/4 311/16 311/16 311/16 c 111/32 111/32 111/32 111/32 111/16 111/16 111/16 23/16 23/16 23/16 LCC LCCF

Standard Finishes:
Cast iron electrogalvanized and aluminum acrylic paint Steel zinc electroplate Vinyl natural

Conduit Size Ranges:


1/2" to 4"

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

107

4F

TGC Cable Tray Ground Conductor Clamp

4F

Applications:
Cable tray grounding conductor clamps are designed for use in heavy industrial applications: To provide a means for securely attaching a grounding conductor to cable tray to maintain grounding continuity for the entire cable tray system To provide protection of equipment through a reliable method for carrying ground fault currents To meet UL and NEC Code requirements For installation indoors or outdoors, with most types of cable trays with inside or outside flanges

Ordering Information

Ground Wire Size #6 to 2/ 0

Cat. # TGC40

TGC Clamp installs on cable trays with inside or outside flanges

Features:
Meets requirements of NEC Code Article 318-7 for grounding and bonding Quick and easy installation low installed cost. No drilling or special tools required. Accommodates solid (where suitable) or stranded aluminum or copper grounding conductors in sizes from #6 to 2/0 Set screw bonds the clamp to the tray and another set screw securely attaches the grounding conductor to the clamp outstanding pull-out and vibration resistance Design accommodates most popular types of cable tray Mechanical device can be easily inspected Malleable iron body provides high strength

Dimensions
In Inches:

Certifications and Compliances:


UL Standard: 467 (Grounding and Bonding Equipment)

Standard Materials:
Body malleable iron Set screws steel

Standard Finishes:
Malleable iron and steel electrogalvanized

108

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

TW Series THRU-WALL BARRIER Cable/Conduit Sealing Device

4F

4F

Applications:
THRU-WALL BARRIER cable/conduit sealing device is used wherever there is a need to seal cables or conduits penetrating fireor non-fire-rated walls, ceilings, floors, bulkheads or decks. For nonfire-rated walls, ceilings, floors, bulkheads or decks, THRU-WALL BARRIER also restricts water and dust and will help contain treated air. THRU-WALL BARRIER is designed: To provide a seal for cable/conduit penetrations through masonry, concrete or steel; to restrict the entrance of contaminants through cable/conduit penetrations into clean areas For use with most types of power, instrument and control cables as well as conduits To be used indoors or outdoors, in new construction or existing structures

Certifications and Compliances:


ASTM Standard E-119 NFPA 251 UL Classification per UL Standard 1479 USCG Acceptance consult Cooper Crouse-Hinds NAVSEA Approval Electric Plant Installation Standard Methods No. S9300- AW-EDG-010/EPISM TWFS/TWBS assemblies

Features:
System Few parts required to seal a wide range of diameters of cables or conduits Easy and fast installation, using factory assembled components High degree of flexibility with interchangeable sealing block assemblies and a selection of different sizes of frames Mounting frame One-piece cast malleable iron or steel mounting frame can be cast into concrete during wall construction, grouted in masonry surfaces or welded into steel bulkheads at any time Retrofit frame allows for easy installation of frame where cables/conduit are already installed Available in sizes to accommodate a wide range of cable tray sizes and loadings including single and multiple layers of cables for power or instrument applications Cast keyways in mounting frame align and position sealing block assemblies Frames can be installed in wall such that sealing block assemblies can be inserted in either horizontal or vertical position Sealing block assembly Specially formulated elastomeric material between cast malleable iron pressure plates protects cable from mechanical damage; provides high pull-out resistance and positive cable separation; expands during fire to seal any voids left by burned cable insulation Interchangeable sealing block assemblies fit all THRU-WALL BARRIER mounting frames Cast stops on front pressure plate prevent sealing block assembly from slipping through mounting frame during installation Assemblies are offered for all cable/conduit outside diameters from .250" to 4.500" (6.4 mm to 114.3 mm). Cables with diameters less than .250" can be accommodated consult Cooper Crouse-Hinds. Sealing block openings will accommodate undersize and out-of-round cable Each sealing block assembly seals multiple cables/conduits. Compact design permits close nesting of cables, saving space. Reducers permit sealing block assemblies to accept cables with smaller O.D. than the specified range Plugs are used to fill unused openings in sealing block assemblies. Blank sealing block assemblies fill unused spaces in mounting frames, providing for future expansion.

Standard Materials:
Mounting frame: TWF, TWFR cast malleable iron TWFS cast carbon steel, ASTM A27 Grade 60-30 Pressure plate cast malleable iron Sealing material special elastomeric material Clamping hardware steel

Standard Finishes:
Malleable iron and hardware electrogalvanized Steel aluminized weldable paint Special elastomeric material natural

Easy three step installation

1. Cast, grout or weld the onepiece mounting frame into masonry or steel surface.

2. Feed cables/conduit through the frame.

3. Position cables/conduit, insert factory assembled sealing blocks into keyways in mounting frame, and tighten nuts on clamping hardware to effect the seal.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

109

4F

TW Series THRU-WALL BARRIER Cable/Conduit Sealing Device


Sealing Block Assemblies & Mounting Frames Ordering Information

4F

TWB Sealing Block Assemblies


TWB sealing block assemblies are offered for cable/conduit outside diameters (O.D.) from .250" to 4.500" (6.4 mm to 114.3 mm). Cables with diameters less than .250" can be accommodated consult Cooper Crouse-Hinds. Each assembly opening will accommodate a .250" (6.4 mm) O.D. range. When clamping hardware is tightened, the elastomeric material is uniformly compressed around all cable/conduits for a completely tight fit. Sealing block assemblies are offered for use in marine applications. Each assembly has the required lubrication and sealing gaskets to meet U.S. Navy Hydrostatic Pressure Test Requirements. Assemblies for marine applications are available for cable/conduit outside diameters (O.D.) from .250" (6.4 mm) through 3.500" (88.9 mm). To order, add suffix S to TWB sealing block assembly Cat. No. Example: TWBS4036.

TWB2063 Depending on opening size range, a standard sealing block assembly will seal from one to eleven cables

Opening Size Range No. Openings In Block

In. .250.500 mm 6.412.7 11

.500.750 .7501.000 1.0001.250 1.2501.500 1.5001.750 1.7502.000 2.0002.250 2.2502.500 12.719.1 19.125.4 25.431.8 5 31.838.1 4 38.144.5 3 44.550.8 3 50.857.2 3 57.263.5 2

11 11 6 6 Added* Added*

Sealing Block Assembly Cat. # Frame Spaces Required Plug Cat. # Reducer Cat. #

TWB2111 TWB1111

TWB2062 TWB2112 TWB2063 TWB3054 TWB3045 TWB30355 TWB4036 TWB40366 TWB5027

2 2

2 TWP3

3 TWP5

4 TWP6

5 TWP7

TWP1 TWR2

TWR3

TWR4

TWR5

TWR55

TWR6

TWR66

TWR7

TWF Mounting Frames


TWF(S) mounting frames may be installed either horizontally or vertically. TWFR retrofit frames are used wherever cables/conduits are already installed through a fire- or nonfire-rated wall, floor or ceiling. They are designed with a removable section to permit installation around cables/conduits. TWFR retrofit frames can be grouted into walls, floors, or ceilings, or welded into steel bulkheads or decks. TWFR retrofit frames will perform in the same manner as the onepiece TWF(S) frames. TWFS steel mounting frames are welded directly into steel bulkheads, decks and prepared sleeves. For marine applications, keeper bars are provided to securely hold TWBS sealing block assemblies in position when installed.

TWF6 TWF12 No. of Spaces Available 6 10 12 20 24 30


Includes removable partition.

TWF10 Retrofit Frame Cat. # TWFR6 TWFR10 TWFR12 TWFR20 TWFR24 TWFR30

TWFS10 Cast Steel Frame Cat. # TWFS10 TWFS20 TWFS30

Frame Cat. # TWF6 TWF10 TWF12J TWF20 TWF24 TWF30

For 3.5" - 4" cable/conduit use TWB7011010 assembly and reduce down using TWR reducers. *Catalog # TWB1111 and TWB2112 are used between TWB2111 and TWB2062 in cases where the number of cables to be sealed in .250-.750 range exceeds the number of openings in standard assemblies. Use as many of these higher density assemblies as needed, sandwiched between halves of a standard assembly. TWR reducers match TWB sealing block assemblies shown in column above Cat. No. and reduce openings to accept cable size ranges shown in adjacent column to the left (in direction of arrow).

110

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

TW Series THRU-WALL BARRIER Cable/Conduit Sealing Device


Plugs, Reducers, Closure Cover Kits, Anchors & Lubricant Ordering Information
TWP Plugs TWR Reducers

4F

4F

TWP plugs will close any unused openings in sealing block assemblies. See table for plug catalog numbers which match specific sealing block assemblies. TWB2112 TWB2062

TWR reducers will reduce openings by .250" (6.4 mm) in sealing block assemblies. See table for reducer catalog numbers which match specific sealing block assemblies. More than one reducer can be used in a single opening.

It is possible to increase cable fill density with double-sided sealing block assemblies (TWB1111 and TWB2112) sandwiched between halves of a standard assembly. 2.5002.750 63.569.9 2 2.7503.000 69.976.2 2 3.0003.250 76.282.6 2 3.2503.500 82.688.9 2 3.5004.250 101.6108.0 1 4.2504.500 108.0114.3 1

Blank No Openings None None

TWB50277

TWB5028

TWB60288

TWB6029

TWB7011010

TWB70111

TWB1

TWB3

5 TWP7 TWR77

5 TWP8 TWR8

6 TWP9

7 TWP10 TWR1010 TWR10

7 TWP11 TWR11

TWR88

TWR9 TWR99

TWB Closure Cover Kits


TWB closure cover kits offer an optional method to close TWF frames installed for future expansion or those that are abandoned. Closure cover kits include two covers clamped to opposite sides of the frame with hardware provided. The insulating material provided is sandwiched between the two covers to maintain the fire rating of the assembly. See table below for closure kit catalog numbers. No. of Spaces Available 6 10 12 20 24 30 Closure Cover Kit Cat. #* TWB600 TWB1000 TWB600 TWB2000 TWB2400 TWB3000

TWK Anchors
TWK anchor assemblies are used to attach mounting frames to wall, ceiling or floor when grouting in frames. Mounting Type Flush Recessed Cat. # TWK1 TWK2

*TWB closure cover kits are not designed to provide a watertight seal in marine/shipboard applications or washdown areas. One kit seals one unused frame opening of same size. Example: use one TWB2000 kit to seal one TWF20, or TWFR20 frame. Use two TWB600 kits to seal one TWF12 or TWFR12 frame opening.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

111

4F

TW Series THRU-WALL BARRIER Cable/Conduit Sealing Device


Ordering Example A

4F

Product Information
Selecting and specifying THRU-WALL BARRIER components is a simple procedure. Primary components for the THRU-WALL BARRIER consist of TWF mounting frames in various sizes and TWB sealing block assemblies for cable/conduit outside diameters (O.D.) in 1/4-inch increments from .250" to 4.500" (6.4 mm to 114.3 mm). Cables with diameters less than .250" can be accommodated consult Cooper Crouse-Hinds. Cable/conduit sizes can be mixed within a sealing block assembly by inserting TWR reducers to accommodate smaller diameters. The use of reducers can decrease the number of sealing block assemblies required. More than one reducer can be used in a single opening. Another way to increase density is to use TWB1111 and TWB2112 sealing block assemblies wherever there is a large number of cables/conduits in sizes ranging from .250" to .750". TWB2112

Specifying & Ordering


The selection of components is based on the quantity and sizes of cables or conduits going through the penetrations. Once these are known, the sealing block assemblies and frames can be selected. Step 1. Group cables/conduits by outside diameter (O.D.) and rank from the largest to the smallest. Step 2. Keeping in mind that sealing block assemblies are available in one-quarter inch increments, group cables/conduits that fall within the same sealing block assembly O.D. size range. Step 3. Starting with the largest cable/ conduit O.D., select the sealing block assemblies required. All openings in each sealing block assembly must be filled. Specify TWR reducers to accommodate smaller diameter cables where possible and TWP plugs to fill openings not used. Step 4. Total the frame spaces required for the specified sealing block assemblies and select an appropriate mounting frame(s). Frames are available in 6-, 10-, 12-, 20-, 24- and 30-space sizes. Keep future expansion requirements in mind when specifying frame. Specify blank sealing block assemblies to fill unused mounting frame space and TWB closure cover kits to fill unused frames. Step 5. Check specification/order to be sure it includes 1) frames, 2) sealing block assemblies, 3) plugs and 4) reducers.

Ordering Example A:
Cable tray size: 24" Cables specified: 5 power cables sizes ranging from 1.960" to 2.200" O.D. Spare capacity required: 50% Step 1. Group cables by O.D. and rank from largest to smallest. Cable Cable Qty. O.D. 4 2.200 1 1.960 Total 5 Step 2. Group cables that fall within the same sealing block assembly size. Sealing Block Cable Qty. O.D. Range diameter cables where possible and TWP plugs to fill openings not used. (See Example A diagram.)
Note: In the example, one TWR66 reducer is required to accommodate the cable with 1.960 O.D. and one TWP6 plug is required for the unused opening.

Step 4. Total the frame spaces required for sealing block assemblies and select appropriate size mounting frame. Factor in spare capacity required for future expansion. Total frame spaces required Specification requires 50% spare capacity Total spaces 8 4 12

TWB2062

TWB2062

Shown here is a double-sided sealing block assembly (TWB2112) sandwiched between halves of a standard sealing block assembly (TWB2062). Additional double-sided sealing block assemblies may be used to accommodate larger quantities of cables or conduits. Unused sealing block openings must be closed with TWP plugs. Blank sealing block assemblies TWB1 and TWB3 are used to fill each unused space in the mounting frame and permit future expansion of the system. Typical practice is to include space allowance of 20 to 50% for future expansion. TWB closure kits are used to seal entire frames and permit future system expansion.

4 2.0002.250 1 1.7502.000 Total 5 Step 3. Starting with the largest cable O.D., select the quantity of sealing block assemblies required. Specify TWR reducers to accommodate smaller Sealing Block Assy Cat. # TWB40366 TWB40366 Number of Openings 3 3 66

Selection: One TWF12 mounting frame with capacity of 12 spaces. Four TWB1 blank sealing block assemblies to fill unused frame space. (Choice of frame could vary based on future expansion needs and/or specific cable arrangement.)

O.D. Range 2.0002.250 2.0002.250 Totals

Cables to be Sealed 3 2 5

Number of Openings 1 1

Cables to be Sealed 4 4 8

Step 5. Bill of materials for specification/order should read: (1) TWF12 (2) TWB40366 (4) TWB1 (1) TWR66 (1) TWP6

Example A diagram 112


www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2010 Cooper Crouse-Hinds

TW Series THRU-WALL BARRIER Cable/Conduit Sealing Device


Ordering Example B Dimensions
Ordering Example B:
Cable tray size: 24" Cables specified: 6 power cables sizes ranging from 2.140" to 2.180" O.D. 31 control cables sizes ranging from .550" to .945" O.D. Spare capacity required: 25% Step 1. Group cables by O.D. and rank from largest to smallest. Cable Qty. Cable O.D. 4 2 1 4 7 9 10 37 2.180 2.140 .945 .890 .700 .637 .550

4F

4F

Sealing Block Assy Cat. # TWB40366 TWB40366 TWB2063 TWB2062 TWB2112 TWB2112

Number of O.D. Range Openings 2.0002.250 2.0002.250 .7501.000 .500.750 .500.750 .500.750 Totals 3 3 6 6 11 11 40

Cables to be Sealed 3 3 5 6 11 9 37

Openings Not Used 1 2 3

Frame Spaces Required 4 4 2 2 2 2 16

Note: In this example, two TWB2112 sealing block assemblies are sandwiched between two halves of a TWB2062. This dramatically increases cable density in minimum frame space. One TWP3 plug is required for unused opening in TWB2063 and two TWP1 plugs are required for unused openings in the TWB2112.

Total

Step 4. Total the frame spaces required for sealing block assemblies and select appropriate size mounting frame(s). Factor in spare capacity required for future expansion. Total frame spaces required Specification requires 25% spare capacity Total 16 4 20

Step 5. Bill of materials for specification/order should read: (2) TWF10 or (1) TWF20 (2) TWB40366 (1) TWB2063 (1) TWB2062 (2) TWB2112 (1) TWP3 (2) TWP1 (1) TWB3 (1) TWB1

Step 2. Group cables that fall within the same sealing block assembly size. Sealing Block Cable Qty. O.D. Range 6 2.0002.250 5 .7501.000 26 .500.750 Total 37 Step 3. Starting with the largest cable O.D., select the quantity of sealing block assemblies required. Specify TWR reducers to accommodate smaller diameter cables where possible and TWP plugs to fill openings not used. (See Example B diagram.)

Selection: Two TWF10 (or one TWF20) mounting frames with total capacity of 20 spaces. One TWB3 and one TWB1 blank sealing block assembly to fill unused frame space. (Choice of frame could vary based on future expansion needs and/or specific cable/conduit arrangement.) Example B diagram
*For TWFS mounting frame hole dimensions, contact Cooper Crouse-Hinds ECM field representative or headquarters.

Dimensions
In Inches:

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

113

4F

TW Series THRU-WALL BARRIER Cable/Conduit Sealing Device


Dimensions*

4F

Dimensions
In Inches:

TWF6 (20 lbs.)

TWF12 (38 lbs.)

TWF10 (25 lbs.)

TWF20 (82 lbs.)

TWB TWF24 (88 lbs.)

TWK
1. Dimensions are shown as inches (mm). 2. Dimensions shown for TWF frames also apply for TWFR retrofit frames.

TWF30 (97 lbs.) *For TWF mounting frame hole dimensions, contact Cooper Crouse-Hinds ECM field representative or headquarters.

114

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Link-Seal Devices
Environmental Seal for Conduit passing through Concrete Walls, Floors or Ceilings
Link-Seal Devices Applications:
Cooper Crouse-Hinds Link-Seal is the quick, economical way to seal around conduit in concrete walls, floors and casings. Link-Seal is a modular mechanical seal used for any type of penetration.

Wet Locations Corrosive Environments

4F

Environmental Conduit Seal Ordering Information:


Its easy. Locate the conduit size and type you are installing in the columns on the left. Then locate the seal and sleeve part numbers under the installation method youve selected. No sleeve is needed for cored or cast hole installation.

4F

Features and Benefits:


Saves time and money Link-Seal installs in up to 75% less time than competition products Positive Hydrostatic Sealing properly installed, Link-Seal is rated at 20 psig (40 feet of head), which exceeds the performance requirements of most applications Environment Seals Link-Seal environmental seal is designed for long life and use as a permanent seal. Seal elements are specially compounded to resist aging, ozone, sunlight, water and a wide range of chemicals Fire Seals for fire protection in floor and wall penetrations Link-Seal is Factory Mutual approved Resistance to high and low temperatures Link-Seal environmental seal is manufactured from special compounds that resist temperatures from 40F to +250F. Link-Seal Fire Seal is manufactured from a silicone material that resists temperatures from 67F to +400F Corrosion protection where installation against galvanic corrosion (or electrolysis) is required, Link-Seal provides complete separation pipe and casing. Metal-to-metal contact is eliminated Compensates for misalignment Link-Seal allows for some angular and off-center conduit conditions and still seals effectively Absorbs shock, sound and vibration this inherent benefit of Link-Seal helps reduce conduit failure due to fatigue and threaded connections

Cored or Cast Hole Method:


Note the appropriate hole diameter and select the seal part number. Example: For 3/4" EMT conduit through a cored hole Core a 2" diameter hole and install the conduit using Link-Seal Part number LSA200-C-04.

Materials:
The standard product for environmental conduit seals is made from EPDM supplied with steel bolts and nuts with a zinc dichromate finish. These seals are suitable for use in water, direct ground burial and atmospheric conditions. They provide electrical insulation where cathodic protection is required. EPDM rubber is resistant to most inorganic acids and alkalis, and some organic chemicals (acetone, alcohol, ketones).

Sleeve Methods:
Select either the plastic or metal sleeve. Both types of sleeves are designed to be cast into concrete walls or floors. Sleeves are ordered separately. Remember to add the wall or floor thickness to the steel sleeve part number to insure the sleeve is provided in the proper length. Plastic sleeves are a standard 16 long and can be modified in the field.

Options:
To order the standard product with 316 stainless steel bolts and nuts, for corrosive environments, replace the "C" in the seal catalog number with "S316". For example, a 1/2" seal for rigid steel conduit for a cored hole is an LSA200-C-04; ordered with stainless steel bolts and nuts the catalog number becomes LSA200-S316-04.

Standard Materials:
Rubber Seal Elements: EPDM (Black) Environmental Seals Silicone (Grey) Fire Seals Pressure Plates: Glass Reinforced Nylon Environmental Seals Steel w/Zinc Dichromate Plate Fire Seals Fasteners: Carbon Steel, Zinc Dichromate Plate Environmental Seals 316 Stainless Steel Environmental with Option S316 Carbon Steel w/Zinc Dichromate Fire Seals

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

115

4F

Link-Seal Devices
Environmental Seal for Conduit passing through Concrete Walls, Floors or Ceilings

Wet Locations Corrosive Environments

4F

Ordering Information - Environmental Conduit Seal


Conduit Nominal Size /2" /2" 1 /2"
1 1 3 3 3

Conduit Type* EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT/RSC IMC EMT/RSC IMC EMT/RSC IMC EMT/RSC IMC RSC RSC

Conduit Actual O.D. (inches) .706 .815 .840 .922 1.029 1.050 1.163 1.290 1.315 1.510 1.638 1.660 1.740 1.883 1.900 2.197 2.360 2.375 2.875 2.857 3.500 3.476 4.000 3.971 4.500 4.466 5.563 6.625

Cast/Cored Hole Dia. (inches) 2.000 2.000 2.000 2.000 2.500 2.500 2.500 3.000 3.000 3.000 3.000 3.000 3.500 3.500 3.500 4.000 4.000 4.000 4.000 4.000 5.000 5.000 6.000 6.000 6.000 6.000 8.000 10.000

Seal for Cast/Cored Hole Cat. # LSA275 C 04 LSA200 C 04 LSA200 C 04 LSA200 C 04 LSA275 C 06 LSA275 C 06 LSA315 C 04 LSA300 C 04 LSA300 C 04 LSA300 C 04 LSA275 C 07 LSA275 C 07 LSA315 C 05 LSA300 C 05 LSA300 C 05 LSA315 C 06 LSA300 C 06 LSA300 C 06 LSA200 C 09 LSA200 C 09 LSA300 C 08 LSA300 C 08 LSA325 C 05 LSA325 C 05 LSA300 C 10 LSA300 C 10 LSA425 C 06 LSA475 C 10

Plastic Sleeve Cat. # LS CS 2 16 LS CS 2 16 LS CS 2 16 LS CS 3 16 LS CS 3 16 LS CS 3 16 LS CS 3 16 LS CS 3 16 LS CS 3 16

Seal for Plastic Sleeve Cat. # LSA200 C 04 LSA200 C 04 LSA200 C 04 LSA315 C 04 LSA315 C 04 LSA315 C 04 LSA300 C 04 LSA300 C 04 LSA300 C 04

Steel Sleeve Cat. # WS2 15 WS2 21 WS2 21

Seal for Steel Sleeve Cat. # LSA275 C 04 LSA200 C 04 LSA200 C 04

/4" /4" /4"

WS2 15 LSA200 C 04 WS2 15 LSA200 C 04 WS2.5 20 LSA275 C 06 WS2.5 20 LSA275 C 06 WS2.5 10 LSA275 C 06 WS2.5 20 LSA200 C 05 WS3.5 22 LSA315 C 05 WS3.5 22 LSA315 C 05 WS3.5 22 LSA315 C 05 WS3.5 32 LSA315 C 05 WS3.5 22 LSA300 C 05 WS3.5 22 LSA300 C 05 WS4 23 WS4 23 WS4 23 WS4 23 WS4 23 WS5 25 WS5 25 WS6 28 WS6 28 WS6 28 WS6 28 WS8 32 WS8 18 LSA315 C 06 LSA300 C 06 LSA300 C 06 LSA200 C 09 LSA200 C 09 LSA300 C 08 LSA300 C 08 LSA325 C 05 LSA325 C 05 LSA300 C 10 LSA300 C 10 LSA425 C 06 LSA300 C 15

1" 1" 1" 11/4" 11/4" 11/4" 11/2" 11/2" 11/2" 2" 2" 2" 21/2" 21/2" 3" 3" 31/2" 31/2" 4" 4" 5" 6"

LS CS 3.5 16 LSA315 C 05 LS CS 3.5 16 LSA300 C 05 LS CS 3 16 LSA200 C 06 LS CS 3.5 16 LSA300 C 05 LS CS 3.5 16 LSA275 C 08 LS CS 3.5 16 LSA275 C 08 LS CS 4 16 LS CS 4 16 LS CS 4 16 LS CS 4 16 LS CS 4 16 LS CS 5 16 LS CS 5 16 LS CS 6 16 LS CS 6 16 LS CS 6 16 LS CS 6 16 LS CS 8 16 LS CS 10 16 LSA315 C 06 LSA300 C 06 LSA300 C 06 LSA200 C 09 LSA200 C 09 LSA300 C 08 LSA300 C 08 LSA325 C 05 LSA325 C 05 LSA300 C 10 LSA300 C 10 LSA425 C 06 LSA475 C 10

*EMT Electrical Metallic Tubing; IMC Intermediate Metal Conduit; RSC Rigid Steel Conduit Specify length of steel sleeve in inches. Example: S6-28-08 is 8" long. All plastic sleeves come in standard 16" lengths and can be field cut to desired length. The last two digits of the seal part number indicate the number of links (and the number of bolts) per seal.

116

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Link-Seal Devices
Fire Seal for Conduit passing through Concrete Walls, Floors or Ceilings
Fire Conduit Seal Ordering Information:
Locate the conduit size and type you are installing in the columns on the left. Then locate the seal and sleeve part number under the installation method you've selected. No sleeve is needed for cored or cast hole installation.

Fire Rated

4F

4F

Sleeve Methods:
Select the appropriate metal sleeve for the size and type of conduit being installed. The sleeve should be ordered separately. Remember to add the wall or floor thickness to the steel sleeve part number to insure the sleeve is provided in the proper length.

Options:
To order the fire seal for a 3-hour rating, replace the "T" in the seal catalog number with a "FS". For example, a 1/ 2" seal for rigid steel conduit for a cored hole is an LSA200-T-04; ordered with option FS the catalog number becomes LSA200-FS-04. A 3-hour fire seal can also be made by using two Model Ts back-to-back. The Model FS is basically two Model T's back-to-back. In Model FS, a tie rod tightens both seals simultaneously for use when only one side of an opening is accessible.

Cored or Cast Hole Method:


Note the appropriate hole diameter and select the seal part number. Example: For 3 / 4" EMT conduit through a cored hole Core a 2" diameter hole and install the conduit using Link-Seal Part number LSA200-T-04.

Materials:
The standard product for fire conduit seals is made from grey silicone supplied with steel bolts and nuts with a zinc dichromate finish. These seals are Factory Mutual approved for use as a 1-hour fire stop and can handle temperature extremes of 67F to +400F.

Fire Conduit Seal - Ordering Information


Conduit Nominal Size
1 1

Conduit Type*

Conduit Actual O.D. (inches) 0.706 0.815 0.840 0.922 1.029 1.050 1.163 1.290 1.315 1.510 1.638 1.660 1.740 1.883 1.900 2.197 2.360 2.375 2.875 2.857 3.500 3.476 4.000 3.971 4.500 4.466 5.563 6.625

Cast/Cored Hole Dia. (inches) 2.000 2.000 2.000 2.000 2.500 2.500 3.000 3.000 3.000 3.000 3.000 3.000 3.500 3.500 3.500 4.000 4.000 4.000 4.000 4.000 5.000 5.000 6.000 6.000 6.000 6.000 8.000 10.000

Seal for Cast/Cored Hole Cat. # LSA275 LSA200 LSA200 LSA200 LSA275 LSA275 LSA315 LSA300 LSA300 LSA300 LSA275 LSA275 LSA315 LSA300 LSA300 LSA315 LSA300 LSA300 LSA200 LSA200 LSA300 LSA300 LSA325 LSA325 LSA300 LSA300 LSA425 LSA475 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 04 04 04 04 06 06 04 04 04 04 07 07 05 05 05 06 06 06 09 09 08 08 05 05 10 10 06 10

Steel Sleeve Cat. # WS2 15 WS2 21 WS2 21 WS2 15 WS2 15 WS2.5 20 WS2.5 20 WS2.5 10 WS2.5 20 WS3.5 22 WS3.5 22 WS3.5 22 WS3.5 32 WS3.5 22 WS3.5 22 WS4 23 WS4 23 WS4 23 WS4 23 WS4 23 WS5 25 WS5 25 WS6 28 WS6 28 WS6 28 WS6 28 WS8 32 WS8 18

Seal for Steel Sleeve Cat. # LSA275 LSA200 LSA200 LSA200 LSA200 LSA275 LSA275 LSA275 LSA200 LSA315 LSA315 LSA300 LSA300 LSA300 LSA275 LSA315 LSA300 LSA300 LSA200 LSA200 LSA300 LSA300 LSA325 LSA325 LSA300 LSA300 LSA425 LSA300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 04 04 04 04 04 06 06 06 05 05 05 05 05 05 08 06 06 06 09 09 08 08 05 05 10 10 06 15

Example: WS6-28-08 is 8" long. *EMT Electrical Metallic Tubing; IMC Intermediate Metal Conduit; RSC Rigid Steel Conduit The last two digits of the seal part number indicate the number of links (and the number of bolts) per seal.

EMT /2" IMC /2" 1 RSC /2" 3 EMT /4" 3 /4" IMC 3 /4" RSC 1" EMT 1" IMC 1" RSC 11/4" EMT 11/4" IMC 11/4" RSC 11/2" EMT 11/2" IMC 11/2" RSC 2" EMT 2" IMC 2" RSC 21/2" EMT/RSC 21/2" IMC 3" EMT/RSC 3" IMC EMT/RSC 31/2" 31/2" IMC 4" EMT/RSC 4" IMC 5" RSC 6" RSC Specify length of steel sleeve in inches.

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

117

4F

Link-Seal Devices

Dimensions

4F

Dimensions
In Inches:

Technical Information
Link-Seal Cat. # LSA200 C LSA275 C LSA300 C LSA315 C LSA325 C LSA425 C LSA475 C Actual Thickness (inches) .478 .607 .687 .807 .875 1.062 1.562 Rubber Sealing Element Free Avg. Length After Length Tightening (inches) (inches) 13/4 13/4 21/2 21/2 3 31/2 31/2 13/8 13/8 2 2 2 /8
3

Pressure Plate A (inches) 11/6


7

Bolt Hex Across Flats M5 slotted hex M5 slotted hex


1 1 1 9 9

R (inches) 21/4 17/8 21/2 21/2 2 3 31/2

T (inches)
5

H (inches) .180 .180


7 7 7 1 1

Thread Size (inches) M5 M5 5/165/18 5/165/18 5/165/18 3/83/16 3/83/16

L 21/2 21/2 31/2 31/2 4 5 41/2

/16 /16 /16 /16 /2 /4 /2

/8

11/2 17/16 3 /8
1

7 7

/2 /2 /2 /16 /16

/32 /32 /32 /4 /4

1 3 1

23/4 23/4

31/2 31/2

118

www.crouse-hinds.com

US: 1-866-764-5454

CAN: 1-800-265-0502

Copyright 2010 Cooper Crouse-Hinds

Anda mungkin juga menyukai