4F
Description
Application Cable Glands - International Standards Quick Selection Guide Flameproof and Increased Safety
ADE 1F ADE 4F ADE 6F ADE 6FC TWAB TWAX TWAE Ex - e Ex - i Trumpet Enlargement and Multiple
Description
Cable Glands - Accessories
A Series B Series C Series D Series E Series Breathers and Drains
Page No.
4F
see see see see see see see see see see see
page page page page page page page page page page page
71 72 73 74 75 76 77 78 79 80 81
see page 98 see page 102 see page 103 see page 104 see page 105 see page 106
Grounding Conductor
TGC Series
Industrial
ADE 4I TWA TUA
see pages 6770 see see see see see page page page page page 85 86 87 88 88
General Pupose
TMC TECK CGB CGD CGE CGB1013 CGFP NCG NCGB
see page 89 see page 90 see pages 9192 see page 93 see page 94 see page 95 see page 96 see page 97 see page 97
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
65
4F
4F
Applications:
Cable glands and cord fittings: Provide means for passing a cord, cable (armored or unarmored) or flexible conduit into an enclosure, through a bulkhead or into a rigid conduit Form a mechanical grip and water and/or oil resistant seal for cord and unarmored or jacketed armored, round cables Form a non-slip connection or termination for flexible cord, cable (armored or unarmored), or flexible conduit Provide grounding continuity for cable armor and flexible conduit Cable glands with sealing fitting or epoxy are installed to: Provide means for passing armored, metal clad, jacketed or unjacketed and unarmored cables through a bulkhead or enclosure in hazardous areas. These fittings are suitable for use in Class I, Groups C, D, locations only when Chico A sealing compound or TSC epoxy (TMCX) is used to make the seal in the fitting.* Form a mechanical grip and water and/or oil-resistant termination Provide ground continuity of cable armor and flexible conduit TMC (non-hazardous) and TMCX (hazardous) fittings are designed for use with Type MC jacketed steel or aluminum metal clad cables with interlocked or corrugated armor and Type TC tray cable (TMCX). LCC cable tray conduit clamps are used for installation on cable tray side rails with inside flanges (requiring inside tray mounting) and outside flanges; LCCF clamps are for use exclusively on inside flanges. LCC/LCCF series cable tray conduit clamps are installed to: Provide a means of clamping metal conduit (rigid steel or aluminum, IMC and EMT) to cable tray for the exit of power and/or control cables from tray Provide a means to firmly bond exiting conduit to cable tray for best grounding continuity TW series THRU-WALL BARRIER cable/conduit sealing devices are installed to: Seal cables or conduits penetrating firerated walls, ceilings or floors Restrict entrance of water and dust and contain treated air Provide a seal for cable/conduit penetrations through steel, masonry or concrete; to restrict the entrance of contaminants through cable/conduit penetrations into clean areas TGC cable tray grounding conductor clamp provides a means for securely attaching a grounding conductor to cable tray to provide grounding continuity for the entire tray system. TGC cable tray grounding conductor clamps provide a reliable method for carrying ground fault current for equipment protection. TGC clamp may be installed on most types of cable trays with inside or outside flanges.
66
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4F
4F
CABLE GLAND
ILLUSTRATION
CABLE TYPE
GLAND TYPE
STANDARD MATERIAL
CERTIFICATION
PROTECTION TYPE
Non-armoured, armoured and tray Non-armoured Nickel-plated brass cable (does not terminate the armour)
Non-armoured, armoured and tray Non-armoured Nickel-plated brass cable (does not barrier terminate the armour)
SWA, SWB, STA, braided marine shipboard and lead sheathed (with addition of earthing washer)
Armoured
Nickel-plated brass
Armoured
Nickel-plated brass
SWA, SWB, STA, braided marine shipboard and lead sheathed (with addition of earthing washer)
Armoured barrier
Nickel-plated brass
SWA
Armoured barrier
Nickel-plated brass
Flameproof
SWA
Armoured
Nickel-plated brass
Flameproof
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
67
4F
CABLE GLAND
ILLUSTRATION
CABLE TYPE
GLAND TYPE
STANDARD MATERIAL
CERTIFICATION
PROTECTION TYPE
4F
SWA
Armoured
Nickel-plated brass
Increased Safety
Nonarmoured
Non-armoured
Polyamide
Increased Safety
Nonarmoured
Non-armoured
Polyamide
Increased Safety
Nonarmoured
Non-armoured
Polyamide
Increased Safety
Nonarmoured
Non-armoured
Polyamide
Increased Safety
SWA, SWB, STA, braided marine shipboard and lead Armoured sheathed (with addition of earthing washer)
Nickel-plated brass
Industrial
SWA
Armoured
Nickel-plated brass
Industrial
Nonarmoured
Non-armoured
Nickel-plated brass
Industrial
68
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4F
ILLUSTRATION
CERTIFICATION
PROTECTION TYPE
4F
Aluminum
Explosionproof
Non-armoured barrier
Nickel-plated brass
Armoured barrier
Nickel-plated brass
Explosionproof
Non-armoured
Aluminum
Explosionproof
Metal-clad with interlocked or continuously-welded corrugated, TECK armoured, non-armoured and tray cable
Armoured or non-armoured
Aluminum
General Purpose
TECK armoured
Armoured
Aluminum
General Purpose
Non-armoured
General Purpose
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
69
4F
CABLE GLAND
ILLUSTRATION
CABLE TYPE
GLAND TYPE
STANDARD MATERIAL
CERTIFICATION
PROTECTION TYPE
4F
Non-armoured
General Purpose
Non-armoured
General Purpose
General Purpose
Non-armoured
General Purpose
Non-armoured
Polyamide
General Purpose
Non-armoured
Thermoplastic polyester
General Purpose
70
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
ADE 1F
International Standards Flameproof and Increased Safety
Gland Type
Non-armoured
ATEX IECEx cULus Listed for Class I Zone 2 cULus Marine Listed for Class I Zone 2
4F
4F
Cable Type
Non-armoured, armoured and tray cable (does not terminate the armour)
Features:
Standard material is nickel-plated brass for superior corrosion resistance Provides a flameproof and weatherproof seal on the outer sheath of the cable Standard neoprene seal suitable for use in operating temperatures ATEX (-60C to 100C), IECEx and cULus (-40C to 100C) Available with optional silicone seal for extreme temperatures Available with metric or NPT threads See pages 98101 for related accessories
SELECTION TABLE
Entry Thread Size A Gland Size 4 4 5 4 5 6 5 6 7 7 8 8 9 9 10 11 12 12 13 14 15 16 Metric Size M12 M16 M16 M20 M20 M20 M25 M25 M25 M32 M32 M40 M40 M50 M50 M63 M63 M75 M75 M90 M90 M110 Metric Catalog # CAP816404 CAP816594 CAP816504 CAP816674 CAP816694 CAP816604 CAP816774 CAP816794 CAP816704 CAP816894 CAP816804 CAP816994 CAP816904 CAP817094 CAP817004 CAP817294 CAP817204 CAP817394 CAP817304 CAP817594 CAP817504 CAP817794 NPT Size 1 /4" 3 /8" 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" 3" 31/2"
NPT Catalog #
CAP818404 CAP818594 CAP818694 CAP818674 CAP818694 CAP818604 CAP818774 CAP818794 CAP818704 CAP818894 CAP818804 CAP818994 CAP818904 CAP819094 CAP819004 CAP819294 CAP819204 CAP819494 CAP819404 CAP819594 CAP819504 CAP819604
Thread Length B Metric (NPT) 15 (12.0) 15 (12.0) 15 (12.0) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (25.3) 15 (25.3) 15 (26.0) 15 (26.0) 15 (26.5) 15 (26.5) 17 (27.2) 17 (27.2) 18 (40.5) 18 (40.5) 22 (42.0) 22 (42.0) 22 (43.2)
Cable Acceptance Outer SheathE Min 4.0 4.0 6.0 4.0 6.0 8.5 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 33.0 40.0 40.0 47.0 54.0 63.0 72.0 Max 8.0 8.5 12.0 8.5 12.0 16.0 12.0 16.0 21.0 21.0 27.5 27.5 34.0 34.0 41.0 48.0 56.0 56.0 65.0 74.0 78.0 92.0
Hexagon Dimensions Across Flats Across Corners G 16.5 20.9 20.9 26.4 26.4 26.4 33 33 33 39.6 45.1 48.4 52.8 60.5 60.5 73.7 79.2 88 93.5 104.5 121 132
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
71
4F
ADE 4F
International Standards Flameproof and Increased Safety
CEPEL ATEX GOST-R IECEx NEPSI cULus listed for Class I Zone 2 cULus Marine listed for Class I, Zone 1 NEMA 4X and IP68
4F
Gland Type:
Armoured
Cable Type:
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard and lead sheathed (with addition of earthing washer)
Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping and bonding with no reversible components for easy installation, minimizing error Provides flameproof seal on inner jacket and weatherproof seal on outer sheath of cable Optional earthing washer for use with lead sheathed cable (see page 99) Standard neoprene seal suitable for use in operating temperatures ATEX (-60C to 100C), IECEx and cULus (-40C to 100C) Available with optional silicone seal for extreme temperatures Available with metric or NPT threads See pages 98101 for related accessories
SELECTION TABLE
Entry Thread Size A Thread Length B Metric NPT (NPT) Size NPT Catalog # 1 /4" CAP848404 15 (12.0) 3 /8" CAP848594 15 (12.0) 3 /8" CAP848504 15 (12.0) 1 /2" CAP848674 15 (20.2) 1 /2" CAP848694 15 (20.2) 1 /2" CAP848604 15 (20.2) 3 /4" CAP848774 15 (20.2) 3 /4" CAP848794 15 (20.2) 3 /4" CAP848704 15 (20.2) 1" CAP848894 15 (25.3) 1" CAP848804 15 (25.3) 15 (26.0) 11/4" CAP848994 11/4" CAP848904 15 (26.0) 11/2" CAP849094 15 (26.5) 15 (26.5) 11/2" CAP849004 2" CAP849294 17 (27.2) 2" CAP849204 17 (27.2) 21/2" CAP849494 18 (40.5) 21/2" CAP849404 18 (40.5) 3" CAP849594 22 (42.0) 3" CAP849504 22 (42.0) N/A (43.2) 31/2" CAP849604 4" CAP849704 22 (44.5) Cable Acceptance Inner Sheath Outer Sheath D E Min 4.0 4.0 6.0 4.0 6.0 8.5 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 40.0 47.0 54.0 63.0 63.0 72.0 Max 8.0 8.5 12.0 8.5 12.0 16.0 12.0 16.0 20.5 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 56.0 65.0 74.0 82.0 82.0 92.0 Min 6.0 6.0 8.5 6.0 8.5 12.0 8.5 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 33.0 47.0 47.0 54.0 63.0 72.0 72.0* 85.0 Max 12.0 12.0 16.0 12.0 16.0 21.0 16.0 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 48.0 56.0 65.0 74.0 83.0 93.0 93.0* 107.0 Hexagon Dimensions Gland Length Across Armour F (less Across Corners entry) Flats G (max) 0.9 36 20.9 0.9 36 20.9 1.25 42 26.4 0.9 36 26.4 1.25 42 26.4 1.25 46 33.0 1.25 42 33.0 1.25 46 33.0 1.6 56 45.1 1.6 56 45.1 1.6 63 52.8 1.6 63 52.8 2.0 68 60.5 2.0 68 60.5 2.5 74 70.4 2.5 77 79.2 2.5 85 93.5 2.5 85 93.5 2.5 92 104.5 3.15 104 121.0 3.15 108 132.0 3.15 108 132.0 3.15 115 148.5
Gland Metric Size Size 5 M12 5 M16 6 M16 5 M20 6 M20 7 M20 6 M25 7 M25 8 M25 8 M32 9 M32 9 M40 10 M40 10 M50 11 M50 12 M63 13 M63 13 M75 14 M75 15 M90 16 M90 16 M90 17 M110
Metric Catalog # CAP846404 CAP846594 CAP846504 CAP846674 CAP846694 CAP846604 CAP846774 CAP846794 CAP846704 CAP846894 CAP846804 CAP846994 CAP846904 CAP847094 CAP847004 CAP847294 CAP847204 CAP847394 CAP847304 CAP847794 CAP847504 CAP847574 CAP847794
All dimensions in millimeters unless otherwise noted * CAP849604 outer sheath min: 85 max: 107.
72
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
ADE 6F
International Standards Flameproof and Increased Safety
Gland Type
Armoured
ATEX IECEx cULus Listed for Class I Zone 2 cULus Marine Listed for Class I, Zone 2
4F
4F
Cable Type
Steel wire armoured, steel wire braided, steel tape armoured and braided marine shipboard
Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping and bonding with no reversible components for easy installation, minimizing error Provides fully inspectable inner seal after installation Flameproof diaphragm seal on inner jacket does not damage cables exhibiting cold-flow; weatherproof seal on outer sheath of cable Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures ATEX (-60C to 100C), IECEx and cULus (-40C to 100C) Available with metric or NPT threads See pages 98101 for related accessories
SELECTION TABLE
Entry Thread Size A Gland Size 5 5 6 7 7 8 8 9 9 10 10 11 Metric Size M16 M20 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 Metric Catalog # CAP965594 CAP965674 CAP965694 CAP965604 CAP965794 CAP965704 CAP965894 CAP965804 CAP965994 CAP965904 CAP966094 CAP966004 NPT Size 3 /8" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 2" NPT Catalog # CAP967594 CAP967674 CAP967694 CAP967604 CAP967794 CAP967704 CAP967894 CAP967804 CAP967994 CAP967904 CAP968094 CAP968294 Thread Length B Metric (NPT) 15 (12.0) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.2) 15 (25.3) 15 (25.3) 15 (26.0) 15 (26.0) 16 (26.5) 16 (27.2) Cable Acceptance Inner Outer Sheath D Sheath E Min 3.0 3.0 6.5 9.0 9.0 12.0 12.0 17.5 17.5 23.0 23.0 28.5 Max 7.5 7.5 11.0 14.5 14.5 19.5 19.5 26.0 26.0 33.0 33.0 41.0 Min 6.0 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 Max 12.0 12.0 16.0 21.0 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 Armour (max) 0.9 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 Gland Length F (less entry) 46.0 46.0 53.0 59.0 59.0 74.5 74.5 83.5 83.5 92.0 92.0 104.0 Hexagon Dimensions Across Across Corners Flats G 20.9 26.4 26.4 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4
Larger sizes available in ADE 4F design, please refer back to page see page 72. All dimensions in millimeters unless otherwise noted.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
73
4F
ADE 6FC
International Standards Flameproof and Increased Safety
ATEX IECEx cULus listed for Class I, Zone 2 cULus Marine listed for Class I, Div. 1
4F
Gland Type
Armoured barrier
Cable Type
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard and lead sheathed (with addition of earthing washer)
Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping with no reversible components for easy installation, minimizing error Provides exposionproof compound seal (denoted by red back nut) on conductors and weatherproof seal on outer sheath of cable Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures -60C to 80C Available with metric or NPT threads See pages 98-101 for related accessories
SELECTION TABLE
Entry Thread Size A Cable Acceptance Hexagon Dimensions Inner Sheath Outer and Cores Sheath E Thread Max Max Length Gland Across Over Inner Max B Length Metric Cores Sheath No. of Armour F (less Across Corners G 'C' 'D' Cores Min Max (max) Flats (NPT) entry) 15 (12.0) 0.9 46.0 20.9 6.5 7.5 6.0 6.0 12.0 15 (20.2) 15 (20.2) 15 (20.2) 15 (20.5) 15 (20.5) 15 (25.3) 15 (25.3) 15 (26.0) 15 (26.0) 16 (26.5) 16 (27.2) 6.5 9.5 12.0 12.0 17.0 17.0 23.0 23.0 29.0 29.0 36.5 7.5 11.0 14.5 14.5 19.5 19.5 28.0 28.0 33.0 33.0 41.0 6.0 6.0 10.0 10.0 21.0 21.0 42.0 42.0 60.0 60.0 80.0 6.0 8.5 12.0 12.0 16.0 16.0 21.0 21.0 27.0 27.0 33.0 12.0 16.0 21.0 21.0 27.5 27.5 34.0 34.0 41.0 41.0 48.0 0.9 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 46.0 53.0 59.0 59.0 74.5 74.5 83.5 83.5 92.0 92.0 104.0 26.4 26.4 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4
Gland Metric Size Size 5 M16 5 6 7 7 8 8 9 9 10 10 11 M20 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50
Metric Catalog # CAP969594 CAP969674 CAP969694 CAP969604 CAP969794 CAP969704 CAP969894 CAP969804 CAP969994 CAP969904 CAP970094 CAP970004
NPT Catalog # CAP974594 CAP971674 CAP971674 CAP971604 CAP971794 CAP971704 CAP971894 CAP971804 CAP971994 CAP971904 CAP972094 CAP972004
2"
Larger sizes available soon. All dimensions in millimeters unless otherwise noted.
74
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
TWAB
International Standards Flameproof and Increased Safety
Gland Type
Armoured barrier
IECEx
IP66 and 67
4F
4F
Cable Type
Steel wire armoured
Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armoured cable Provides flameproof compound seal on conductors and weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories
SELECTION TABLE
Entry Thread Size A Thread Length B Metric 14 14 16 20 20 20 22 22 Cable Acceptance Inner Sheath D Min 6.0 7.0 11.0 17.0 24.0 30.0 40.0 53.0 Max 8.0 12.0 18.0 25.0 31.0 41.0 54.0 65.0 Outer Sheath E Min 10.2 14.0 18.0 25.0 30.0 36.0 51.0 63.0 Max 15.8 20.8 27.2 33.5 35.9 52.6 65.3 78.0 Armour Range 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.5 - 3.5 Gland Length F (less entry) 58.0 58.0 60.0 72.0 74.0 82.0 90.0 98.0 Hexagon Dimensions Across Across Corners Flats G 27.0 31.0 30.4 34.0 38.1 43.0 47.6 53.0 55.0 63.5 70.0 78.0 80.0 88.0 101.0 112.0
Gland Size 20 20 25 32 40 50 63 75
Metric Size M20 M20 M25 M32 M40 M50 M63 M75
Metric Catalog # TWAB1M16 TWAB1M20 TWAB2M27 TWAB3M34 TWAB4M40 TWAB5M53 TWAB6M66 TWAB7M78
NPT Size 1 /2" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2"
NPT Catalog # TWAB1N16 TWAB1N20 TWAB2N27 TWAB3N34 TWAB4N40 TWAB5N53 TWAB6N66 TWAB7N78
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
75
4F
TWAX
International Standards Flameproof and Increased Safety
IECEx
IP66 and 67
4F
Gland Type:
Armoured
Cable Type:
Steel wire armoured
Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armour cable Flameproof seal on inner jacket and weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories
SELECTION TABLE
Entry Thread Size A Thread Length B Metric 14.0 14.0 14.0 16.0 16.0 20.0 20.0 20.0 20.0 20.0 22.0 22.0 22.0 22.0 22.0 Cable Acceptance Inner Outer Sheath D Sheath E Min 6.3 8.4 11.0 13.5 16.5 19.5 23.5 25.8 30.8 35.5 39.5 43.5 48.5 55.5 61.0 Max 8.6 11.6 13.9 16.9 19.9 23.9 26.2 31.2 36.2 40.0 44.0 49.0 55.9 61.9 67.9 Min 10.2 13.0 15.5 19.5 23.5 27.0 30.0 33.0 38.0 43.0 48.0 52.0 58.0 64.3 70.6 Max 13.2 15.8 19.8 23.8 27.2 30.5 33.5 38.5 43.5 48.5 52.6 58.9 65.3 71.6 78.0 Armour Range 0.9 - 1.25 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.0 - 2.5 2.0 - 2.5 2.0 - 2.5 2.5 - 3.15 2.5 - 3.15 Gland Length F (less entry) 58.0 58.0 58.0 60.0 60.0 72.0 72.0 74.0 82.0 82.0 82.0 90.0 90.0 98.0 98.0 Hexagon Dimensions Across Flats 23.3 27.0 30.5 33.3 38.1 42.2 47.0 55.0 57.0 63.5 70.0 76.0 80.0 89.0 101.0 Across Corners G 26.0 31.0 34.0 37.0 43.0 47.0 53.0 64.0 62.0 71.0 78.0 85.0 88.0 102.0 112.0
Gland Size 20 20 20 25 25 32 32 40 50 50 50 63 63 75 75
Metric Size M20 M20 M20 M25 M25 M32 M32 M40 M50 M50 M50 M63 M63 M75 M75
Metric Catalog # TWAX1M13 TWAX1M16 TWAX1M20 TWAX2M24 TWAX2M27 TWAX3M30 TWAX3M33 TWAX4M38 TWAX5M43 TWAX5M48 TWAX5M52 TWAX6M60 TWAX6M65 TWAX7M71 TWAX7M78
NPT Size 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/ 2" 11/2" 2" 2" 21/2" 21/2" 3"
NPT Catalog # TWAX1N13 TWAX1N16 TWAX1N20 TWAX2N24 TWAX2N27 TWAX3N30 TWAX3N33 TWAX4N38 TWAX5N43 TWAX5N48 TWAX6N52 TWAX6N60 TWAX7N65 TWAX7N71 TWAX8N78
76
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
TWAE
International Standards Flameproof and Increased Safety
IECEx
IP66 and 67
4F
Gland Type:
Armoured
4F
Cable Type:
Steel wire armoured
Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armour cable Forms weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads A captive sealing gasket on entry threads See page 103 for related accessories
SELECTION TABLE
Entry Thread Size A Gland Size 20 20 25 32 40 50 63 75 Metric Size M20 M20 M25 M32 M40 M50 M63 M75 Metric Catalog # TWAE1M16 TWAE1M20 TWAE2M27 TWAE3M34 TWAE4M40 TWAE5M53 TWAE6M66 TWAE7M78 NPT Size (in.) 1 /2" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" NPT Catalog # TWAE1N16 TWAE1N20 TWAE2N27 TWAE3N34 TWAE4N40 TWAE5N53 TWAE6N66 TWAE7N78 Thread Length B Metric 14.0 14.0 16.0 20.0 20.0 20.0 22.0 22.0 Cable Acceptance Outer Inner Sheath E Sheath D Min 6.0 7.0 11.0 17.0 24.0 30.0 40.0 53.0 Max 11.0 13.0 19.0 25.0 31.0 41.0 54.0 65.0 Min 10.2 14.0 18.0 25.0 30.0 36.0 51.0 63.0 Max 15.8 20.8 27.2 33.5 39.5 52.6 65.3 78.0 Armour Range 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.5 - 3.5 Gland Length F (less entry) 58.0 58.0 60.0 72.0 74.0 82.0 90.0 98.0 Hexagon Dimensions Across Across Corners Flats G 27.0 31.0 30.4 34.0 38.5 43.0 47.2 53.0 55.0 62.0 70.0 78.0 80.0 88.0 101.0 112.0
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
77
4F
Ex-e
International Standards Flameproof and Increased Safety
Sizes M12-M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X IECEx
IP66
4F
Gland Type:
Non-armoured
Cable Type:
Non-armoured
Features:
Standard material is high-impact resistant polyamide Forms weatherproof seal on outer sheath of cable Standard silicone seal suitable for use in operating temperatures -55 to 70C (M12 and M16 for use in operating temperatures -20 to 70C) Available with optional silicone seal for extreme temperatures Available with metric threads See page 104 for related accessories
78
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Ex-i
International Standards Flameproof and Increased Safety
Sizes M12-M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X IECEx
IP66
4F
Gland Type:
Non-armoured
4F
Cable Type:
Non-armoured
Features:
Standard material is high-impact resistant polyamide (gland nut is blue for intrinsically safe circuits) Forms weatherproof seal on outer sheath of cable Standard silicone seal suitable for use in operating temperatures -55 to 70C (M12 and M16 for use in operating temperatures -20 to 70C) Available with metric threads See page 104 for related accessories
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
79
4F
Trumpet
International Standards Flameproof and Increased Safety
ATEX
IP66
4F
Gland Type:
Non-armoured
Cable Type:
Non-armoured
Features:
Standard material is high-impact resistant polyamide Forms weatherproof seal on outer sheath of cable Flared rear seal provides protection for cable Standard neoprene seal suitable for use in operating temperatures -40 to 85C Available with metric threads See page 104 for related accessories
SELECTION TABLE
Gland Size 20 25 32 40 50 60 Entry Metric Size M20 M25 M32 M40 M50 M60 Thread Size A Metric Catalog # GHG 960 1949 GHG 960 1949 GHG 960 1949 GHG 960 1949 GHG 960 1949 GHG 960 1949 Thread Length B Metric 15.0 15.0 15.0 15.0 16.0 16.0 Cable Acceptance Outer Sheath E Min Max 8.0 13.0 11.0 16.0 15.0 20.0 19.0 27.0 26.0 34.0 35.0 46.0 Gland Length F (less entry) 49.0 50.0 65.0 71.0 79.0 89.0 Hexagon Dimensions Across Across Flats Corners G 26.0 28.6 32.0 35.2 41.0 45.1 50.0 55.0 60.0 66.0 75.0 82.5
80
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Sizes M16: PTB 99 ATEX 3101 X Sizes M20-M63: PTB 99 ATEX 3128 X IECEx
IP66
4F
Gland Type:
Non-armoured
4F
Cable Type:
Non-armoured
Features:
Standard material is high-impact resistant polyamide Forms weatherproof seal on outer sheath of cable Provides reduced entry threads for larger gland size Standard silicone seal suitable for use in operating temperatures -55 to 70C (M16 for use in operating temperatures -20 to 70C) Available with metric threads See page 104 for related accessories
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
81
4F
ADE 4I
International Standards Industrial
4F
Gland Type
Armoured
Cable Type
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard lead sheathed (with addition of earthing washer) and tray cable
Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping and bonding with no reversible components for easy installation, minimizing error Provides seal on inner jacket and weatherproof seal on outer sheath of the cable An optional earthing washer for use with lead sheathed cable (see page 99) Standard neoprene seal suitable for use in operating temperatures of -60C to 100C Available with optional silicone seal for extreme temperatures Available with metric or NPT threads See pages 98101 for related accessories
SELECTION TABLE
Entry Thread Size A Cable Acceptance Thread Length Inner Sheath Outer Sheath E D B Metric Min Max Min Max (NPT) 15 (12.0) 4.0 8.0 6.0 12.0 15 (12.0) 4.0 8.5 6.0 12.0 15 (12.0) 6.0 12.0 8.5 16.0 15 (20.2) 4.0 8.5 6.0 12.0 15 (20.2) 6.0 12.0 8.5 16.0 15 (20.2) 8.5 16.0 12.0 21.0 15 (20.2) 6.0 12.0 8.5 16.0 15 (20.2) 8.5 16.0 12.0 21.0 15 (20.2) 12.0 20.5 16.0 27.5 15 (25.3) 12.0 21.0 16.0 27.5 15 (25.3) 16.0 27.5 21.0 34.0 15 (26.0) 16.0 27.5 21.0 34.0 15 (26.0) 21.0 34.0 27.0 41.0 16 (26.5) 21.0 34.0 27.0 41.0 16 (26.5) 27.0 41.0 33.0 48.0 17 (27.2) 27.0 41.0 33.0 48.0 17 (27.2) 33.0 48.0 40.0 56.0 18 (40.5) 40.0 56.0 47.0 65.0 18 (40.5) 47.0 65.0 54.0 74.0 22 (42.0) 54.0 74.0 63.0 83.0 22 (42.0) 63.0 82.0 72.0 93.0 (43.2) 63.0 82.0 72.0 93.0 22 (44.5) 72.0 92.0 85.0 107.0 Gland Length F (less entry) 36.0 36.0 42.0 36.0 42.0 46.0 42.0 46.0 56.0 56.0 63.0 63.0 68.0 68.0 74.0 77.0 85.0 85.0 92.0 104.0 108.0 108.0 115.0 Hexagon Dimensions Across Flats Across Corners G 20.9 20.9 26.4 26.4 26.4 33.0 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4 79.2 93.5 93.5 104.5 121.0 132.0 132.0 148.5
Gland Size 5 5 6 5 6 7 6 7 8 8 9 9 10 10 11 12 13 13 14 15 16 16 17
Metric Size M12 M16 M16 M20 M20 M20 M25 M25 M25 M32 M32 M40 M40 M50 M50 M63 M63 M75 M75 M90 M90 M110
Metric Catalog # CAP946404 CAP946594 CAP946504 CAP946674 CAP946694 CAP946604 CAP946774 CAP946794 CAP946704 CAP946894 CAP946804 CAP946994 CAP946904 CAP947094 CAP947004 CAP947294 CAP947204 CAP947394 CAP947304 CAP947594 CAP947504 CAP947794
NPT Size 1 /4" 3 /8" 3 /8" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" 3" 31/2" 4"
NPT Catalog # CAP948404 CAP948594 CAP948504 CAP948674 CAP948694 CAP948604 CAP948774 CAP948795 CAP948704 CAP948894 CAP948804 CAP948994 CAP948904 CAP949904 CAP949004 CAP949294 CAP949204 CAP949949 CAP949404 CAP949564 CAP949504 CAP949604 CAP949704
Armour (max) 0.9 0.9 1.25 0.9 1.25 1.25 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.15 3.15 3.15 3.15
82
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
TWA
International Standards Industrial
Gland Type
Armoured
IP66 and 67
4F
4F
Cable Type
Steel wire armoured
Features:
Standard material is nickel-plated brass Armour clamping and bonding for steel wire armoured cable Forms weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories
SELECTION TABLE
Entry Thread Size A Gland Size 20 20 20 25 32 40 50 63 75 Metric Size M20 M20 M20 M25 M32 M40 M50 M63 M75 Metric Catalog # TWA1M13 TWA1M16 TWA1M20 TWA2M27 TWA3M34 TWA4M40 TWA5M53 TWA6M66 TWA7M78 NPT Size 1 /2" 1 /2" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" NPT Catalog # TWA1N13 TWA1N16 TWA1N20 TWA2N27 TWA3N34 TWA4N40 TWA5N53 TWA6N66 TWA7N78 Thread Length B Metric 14.0 14.0 14.0 16.0 20.0 20.0 20.0 22.0 22.0 Cable Acceptance Inner Sheath D Min Max 3.0 8.0 6.0 11.0 7.0 13.0 11.0 19.0 17.0 25.0 24.0 31.0 30.0 41.0 40.0 54.0 53.0 65.0 Outer Sheath E Min Max 8.0 13.0 10.2 15.8 14.0 20.8 18.0 27.2 25.0 33.5 30.0 39.5 36.0 52.6 51.0 65.3 63.0 78.0 Armour Range 0.5 - 0.9 0.9 - 1.25 0.9 - 1.25 1.25 - 1.6 1.6 - 2.0 1.6 - 2.0 2.0 - 2.5 2.0 - 2.5 2.5 - 3.5 Gland Length F (less entry) 56.0 58.0 58.0 60.0 72.0 74.0 82.0 90.0 98.0 Hexagon Dimensions Across Across Corners G Flats 27.0 31.0 27.0 31.0 30.4 34.0 38.5 43.0 47.2 53.0 57.0 64.0 70.0 78.0 80.0 88.0 101.0 112.0
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
83
4F
TUA
International Standards Industrial
IP66 and 67
4F
Gland Type
Non-armoured
Cable Type
Non-armoured
Features:
Standard material is nickel-plated brass Forms weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -20 to 40C Available with metric, NPT or BSP threads See page 103 for related accessories
SELECTION TABLE
Entry Thread Size A Gland Size 16 20 20 20 25 32 32 40 50 50 50 63 63 75 75 Metric Size M16 M20 M20 M20 M25 M32 M32 M40 M50 M50 M50 M63 M63 M75 M75 Metric Catalog # TUA16M7 TUA1M10 TUA1M12 TUA1M15 TUA2M18 TUA3M23 TUA3M25 TUA4M29 TUA5M34 TUA5M38 TUA5M42 TUA6M48 TUA6M54 TUA7M60 TUA7M66 NPT Size N/A 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" NPT Catalog # N/A TUA1N10 TUA1N12 TUA1N15 TUA2N18 TUA3N23 TUA3N25 TUA4N29 TUA5N34 TUA5N38 TUA5N42 TUA6N48 TUA7N54 TUA7N60 TUA8N66 Thread Length B Metric 14.0 14.0 14.0 16.0 16.0 20.0 20.0 20.0 20.0 20.0 22.0 22.0 22.0 22.0 22.0 Cable Acceptance Outer Sheath E Min 10.2 13.0 15.5 19.5 23.5 27.0 30.0 33.0 38.0 43.0 48.0 52.0 58.0 64.3 70.6 Max 13.2 15.8 19.8 23.8 27.2 30.5 33.5 38.5 43.5 48.5 52.6 58.9 65.3 71.6 78.0 Gland Length F (less entry) 58.0 58.0 58.0 60.0 60.0 72.0 72.0 74.0 82.0 82.0 82.0 90.0 90.0 98.0 98.0 Hexagon Dimensions Across Flats 23.3 27.0 30.5 33.3 38.1 42.2 47.0 55.0 57.0 63.5 70.0 76.0 80.0 89.0 101.0 Across Corners G 26.0 31.0 34.0 37.0 43.0 47.0 53.0 64.0 62.0 71.0 78.0 85.0 88.0 102.0 112.0
84
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
TMCX
North American Standards Explosionproof
Gland Type
UL Listed CSA Certified Class I, Div. 1 Groups, A, B, C, D Class II; Class III
4F
4F
Cable Type
Metal-clad (interlocked or continuously welded corrugated armoured), non-armoured and tray cable
Features:
Standard material is aluminum Stainless steel copper-plated spring provides grounding continuity of cable armour (MC cable only) Provides explosionproof compound seal on conductors and watertight seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 60C Cold Shrink Kit is available for extra protection in aggressive environments (see page 105) Available with NPT threads See page 105 for related accessories
SELECTION TABLE
Entry Thread Size A NPT Size 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4" NPT Catalog # TMCX165 TMCX285 TMCX3112 TMCX4140 TMCX5161 TMCX6206 TMCX7247 TMCX8302 TMCX9352 TMCX10402 Thread Length B NPT 0.750 0.781 0.938 0.969 0.969 1.000 1.438 1.438 1.625 1.625 Min 0.440 0.600 0.800 1.100 1.330 1.570 1.930 2.450 2.950 3.500 Cable Acceptance Armour Range H Max 0.650 0.850 1.120 1.400 1.610 2.060 2.470 3.020 3.520 4.020 Outer Sheath E Min 0.490 0.650 0.850 1.150 1.380 1.630 1.990 2.525 3.025 3.585 Max 0.781 1.000 1.313 1.625 1.781 2.313 2.719 3.281 3.781 4.281 Gland Length F (less entry) 2.625 2.875 3.125 3.125 3.375 5.313 6.063 6.063 7.750 8.313 Hexagon Dimensions Across Flats 1.250 1.500 1.875 2.250 2.500 3.250 3.750 4.500 5.000 5.500 Across Corners G 1.375 1.625 2.000 2.438 2.750 3.500 4.000 4.875 5.375 5.875
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
85
4F
ADE 6FC
North American Standards Explosionproof
CEPEL ATEX GOST-R IECEx NEMA 4X and IP68 cULus listed for Class I, Zone 2 cULus Marine listed for Class I, Div. 1
4F
Gland Type
Armoured barrier
Cable Type
Steel wire armoured, steel wire braided, steel tape armoured, braided marine shipboard and lead sheathed (with addition of earthing washer)
Features:
Standard material is nickel-plated brass for superior corrosion resistance Armour clamping with no reversible components for easy installation, minimizing error Provides exposionproof compound seal (denoted by red back nut) on conductors and weatherproof seal on outer sheath of cable Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures -60C to 80C Available with metric or NPT threads See pages 98101 for related accessories
SELECTION TABLE
Entry Thread Size A Cable Acceptance Inner Sheath and Cores Thread Max Max Length Over Inner Max B Metric Cores Sheath No. of 'C' 'D' Cores (NPT) 15 (12.0) 6.5 7.5 6 15 (20.2) 6.5 7.5 6 15 (20.2) 9.5 11.0 6 15 (20.2) 12.0 14.5 10 15 (20.5) 12.0 14.5 10 15 (20.5) 17.0 19.5 21 15 (25.3) 17.0 19.5 21.0 15 (25.3) 23.0 28.0 42.0 15 (26.0) 23.0 28.0 42.0 15 (26.0) 29.0 33.0 60.0 16 (26.5) 29.0 33.0 60.0 16 (27.2) 36.5 41.0 80.0 Outer Sheath E Hexagon Dimensions
Gland Metric Metric NPT NPT Size Size Catalog # Size Catalog # 5 M16 CAP969594 3/8" CAP974594 5 M20 CAP969674 1/2" CAP971674 6 M20 CAP969694 1/2" CAP971674 7 M20 CAP969604 1/2" CAP971604 7 M25 CAP969794 3/4" CAP971794 8 M25 CAP969704 3/4" CAP971704 8 M32 CAP969894 1" CAP971894 9 M32 CAP969804 1" CAP971804 9 M40 CAP969994 11/4" CAP971994 10 M40 CAP969904 11/4" CAP971904 10 M50 CAP970094 11/2" CAP972094 11 M50 CAP970004 2" CAP972004
Gland Length F Armour (less Across Min Max (max) entry) Flats 6.0 12.0 0.9 46 6.0 12.0 0.9 46 8.5 16.0 1.25 53 12.0 21.0 1.25 59 12.0 21.0 1.25 59 16.0 27.5 1.6 74.5 16.0 27.5 1.6 74.5 21.0 34.0 1.6 83.5 21.0 34.0 1.6 83.5 27.0 41.0 2.0 92 27.0 41.0 2.0 92 33.0 48.0 2.5 104
Across Corners G 20.9 26.4 26.4 33 33 45.1 45.1 52.8 52.8 60.5 60.5 70.4
Larger sizes available soon. All dimensions in millimeters unless otherwise noted.
86
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
ADE 1FC
North American Standards Explosionproof
Gland Type
Non-armoured barrier
ATEX IECEx cULus listed for Class I, Zone 2 cULus Marine listed for Class I, Div. 1
4F
4F
Cable Type
Non-armoured, armoured and tray cable (does not terminate the armour)
Features:
Standard material is nickel-plated brass for superior corrosion resistance Provides a flameproof and weatherproof seal on outer sheath of cable Provides explosionproof compound seal (denoted by red back nut) on conductors Deluge boot provides enhanced protection from water ingress Standard neoprene seal suitable for use in operating temperatures -60C to 80C Available with metric or NPT threads See pages 98101 for related accessories
SELECTION TABLE
Entry Thread Size A Gland Size 4 4 5 6 6 7 7 8 8 9 9 10 10 Metric Size M16 M20 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 M63 Metric Catalog # CAP019594 CAP019674 CAP019694 CAP019604 CAP019794 CAP019704 CAP019894 CAP019804 CAP019994 CAP019904 CAP019094 CAP019004 CAP019204 NPT Size 3 /8" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/2" 2" --NPT Catalog # CAP011594 CAP971674 CAP011674 CAP011604 CAP011794 CAP011704 CAP011894 CAP011804 CAP011994 CAP011904 CAP011094 CAP011004 --Thread Cable Acceptance Length B Outer Sheath E Metric (NPT) Max Min 15 (12.0) 4.0 7.5 15 (22.2) 4.0 7.5 15 (22.2) 6.5 11.0 15 (22.2) 9.0 14.5 15 (22.5) 9.0 14.5 15 (22.5) 12.0 19.5 15 (27.3) 12.0 19.5 15 (27.3) 17.5 26.0 15 (28.0) 17.5 26.0 15 (28.0) 23.0 33.0 16 (28.5) 23.0 33.0 16 (29.2) 28.5 41.0 16 28.5 41.0 Max No. Cores 6.0 6.0 6.0 10.0 10.0 21.0 21.0 42.0 42.0 60.0 60.0 80.0 80.0 Gland Length F (less entry) 46.0 46.0 53.0 59.0 59.0 74.5 74.5 83.5 83.5 92.0 92.0 104.0 Hexagon Dimensions Across Across Flats Corners G 20.9 26.4 26.4 33.0 33.0 45.1 45.1 52.8 52.8 60.5 60.5 70.4 73.7
Larger sizes available soon. All dimensions in millimeters unless otherwise noted.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
87
4F
CGBS: CSA Certified Class I, Div 1. Groups C, D Class II, Div. 1 & 2, Groups E, F, G Class III
EBY: UL, cUL Listed Class I, Div. 1 Groups, B, C, D Class II, Div. 1 Groups, F, G
4F
Gland Type
Portable cord connector
Cable Type
Non-armoured and tray cable
CGBS Features:
Body steel with zinc electroplate and chromate finish coat Gland nut aluminum Body well for Chico A sealing compound (for ordering information please contact customer service) Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads
SELECTION TABLE
Entry NPT Size 1 /2" 3 /4" 3 /4" 1" 1" 11/4" 11/4" 11/4" Thread Size A NPT Catalog # CGBS1013 CGBS2013 CGBS2014 CGBS3015 CGBS3016 CGBS4017 CGBS4018 CGBS4019 Form A A A B B B B B Outer Sheath E Min 0.312 0.312 0.375 0.500 0.625 0.750 0.875 1.000 Max 0.437 0.437 0.500 0.625 0.750 0.875 1.000 1.188 Gland Length F (less entry) 51/4" 51/4" 51/4" 27/8" 215/16" 213/16" 31/2" 39/16"
Gland Type
Portable cord connector
Cable Type
Non-armoured
EBY Features:
Standard material is aluminum Factory sealed conductors and seal on outer sheath of cable Three, 12-inch long, #12 type SF-2 (150C rating) stranded pigtails; two circuit wires and one identified grounding wire Three pressure connectors for 3-conductor cord, range #18 to #12 AWG Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads
SELECTION TABLE
Entry Thread Size A NPT Size 3 /4" 3 /4" 3 /4" NPT Catalog # EBY2672 EBY2682 EBY26102 Outer Sheath E Min Max 0.250 0.437 0.375 0.500 0.500 0.625
88
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
TMC
North American Standards General Purpose
Gland Type
Armoured, TECK armoured and non-armoured
4F
4F
Cable Type
Metal-clad (interlocked or continuously welded corrugated armoured), non-armoured and tray cable
Features:
Standard material is aluminum Stainless steel copper-plated spring provides grounding continuity of cable armour (MC cable only) Watertight seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 60C Cold Shrink Kit is available for extra protection in aggressive environments (see page 105) Available with NPT threads See page 105 for related accessories
SELECTION TABLE
Entry Thread Size A NPT Size 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2" 4" NPT Catalog # TMC165 TMC285 TMC3112 TMC4140 TMC5161 TMC6206 TMC7247 TMC8302 TMC9352 TMC10402 Thread Length B NPT 0.750 0.781 0.938 0.969 0.969 1.000 1.438 1.438 1.625 1.625 Cable Acceptance Armour Range H Min Max 0.440 0.650 0.600 0.850 0.800 1.120 1.100 1.400 1.330 1.610 1.570 2.060 1.930 2.470 2.450 3.020 2.950 3.520 3.500 4.020 Outer Sheath E Min Max 0.490 0.781 0.650 1.000 0.850 1.313 1.150 1.625 1.380 1.781 1.630 2.313 1.990 2.719 2.525 3.281 3.025 3.781 3.585 4.281 Gland Length F (less entry) 2.375 2.625 2.625 2.750 2.750 4.500 4.750 4.875 5.375 5.500 Hexagon Dimensions Across Flats 1.250 1.500 1.875 2.250 2.500 3.250 3.750 4.500 5.000 5.500 Across Corners G 1.375 1.625 2.000 2.438 2.75 3.500 4.000 4.875 5.375 5.875
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
89
4F
TECK
North American Standards General Purpose
CSA Certified Class II, Div. 1, Div 2 Groups, E, F, G Type 4 and IP56 Class III - CSA Wet locations
4F
Gland Type
Armoured
Cable Type
TECK armoured
Features:
Standard material is aluminum Stainless steel copper-plated spring provides grounding continuity of cable armour (TECK cable only) Watertight seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 60C Cold Shrink Kit is available for extra protection in aggressive environments ( see page 105) An integral o-ring seal on entry threads Available with NPT threads See page 105 for related accessories
SELECTION TABLE
Stainless Steel Catalog # TECK050 1SS TECK050 2SS TECK050 3SS TECK050 4SS TECK075 5SS TECK075 6SS TECK100 7SS Hexagon Gland Entry Cable Acceptance Dimensions Length Thread F Across Size A Thread Armour Range H Outer Sheath E (less Across Corners NPT Length Min Max Min Max entry) Size B NPT G Flats 1 /2" 0.630 0.415 0.570 0.525 0.650 2.300 1.250 1.350 1 /2" 0.630 0.490 0.680 0.600 0.760 2.300 1.375 1.500 1 /2" 0.630 0.615 0.805 0.725 0.885 2.300 1.500 1.600 1 /2" 0.630 0.715 0.905 0.825 0.985 2.300 1.500 1.600 3 /4" 0.630 0.770 0.985 0.880 1.065 2.500 2.000 2.125 3 /4" 0.630 0.915 1.125 1.025 1.205 2.500 2.000 2.125 1" 0.750 1.077 1.295 1.187 1.375 2.625 2.250 2.400 0.800 1.240 1.545 1.350 1.625 3.500 3.000 3.125 11/4" 0.800 1.390 1.545 1.500 1.625 3.400 3.000 3.125 11/4" 0.800 1.490 1.795 1.600 1.875 3.500 3.000 3.125 11/4" 0.800 1.590 1.885 1.700 1.965 3.800 3.750 3.600 11/2" 0.800 1.790 2.107 1.900 2.187 3.900 3.500 3.750 11/2" 2" 0.825 1.790 2.107 1.900 2.187 4.000 3.750 4.000 2" 0.825 1.990 2.280 2.100 2.375 4.000 3.750 4.000 2" 0.875 2.190 2.485 2.300 2.565 4.000 4.125 4.400 2" 0.875 2.390 2.656 2.500 2.750 4.000 4.125 4.400 1.300 2.240 2.560 2.380 2.640 5.000 4.500 4.750 21/2" 1.300 2.440 2.750 2.580 2.840 5.000 4.500 4.750 21/2" 3" 1.400 2.640 2.970 2.790 3.060 5.000 4.600 4.900 3" 1.400 2.870 3.190 3.000 3.270 5.000 4.900 5.250 3" 1.400 3.042 3.390 3.210 3.480 5.000 5.000 5.250 1.400 3.270 3.590 3.420 3.690 5.000 5.600 5.900 31/2" 31/2" 1.400 3.440 3.770 3.610 3.870 5.000 5.500 5.900 4" 1.400 3.600 3.930 3.810 4.030 5.000 6.125 6.500 4" 1.400 3.755 4.065 3.965 4.185 5.000 6.125 6.500 4" 1.400 3.910 4.220 4.120 4.340 5.000 6.125 6.500
Aluminum Catalog # TECK050 1 TECK050 2 TECK050 3 TECK050 4 TECK075 5 TECK075 6 TECK100 7 TECK125 8 TECK125 9 TECK125 10 TECK150 11 TECK150 12 TECK200 13 TECK200 14 TECK200 15 TECK200 16 TECK250 17 TECK250 18 TECK300 19 TECK300 20 TECK300 21 TECK350 22 TECK350 23 TECK400 24 TECK400 25 TECK400 26
Steel Catalog # TECK050 1S TECK050 2S TECK050 3S TECK050 4S TECK075 5S TECK075 6S TECK100 7S TECK125 8S TECK125 9S TECK125 10S TECK150 11S TECK150 12S TECK200 13S TECK200 14S TECK200 15S TECK200 16S TECK250 17S TECK250 18S TECK300 19S TECK300 20S TECK300 21S TECK350 22S TECK350 23S TECK400 24S TECK400 25S TECK400 26S
PVC Catalog # TECK050 1PVC TECK050 2 PVC TECK0503PVC TECK050 4PVC TECK075 5PVC TECK075 6PVC TECK1007PVC TECK125 8PVC TECK125 9PVC TECK125 10PVC TECK150 11PVC TECK150 12PVC TECK200 13PVC TECK200 14PVC TECK200 15PVC TECK200 16PVC TECK250 17PVC TECK250 18PVC TECK300 19PVC TECK300 20PVC TECK300 21PVC TECK350 22PVC TECK350 23PVC
90
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
CGB
North American Standards General Purpose
Gland Type
Non-armoured
cULus Listed
4F
4F
Cable Type
Non-armoured and tray cable
Features:
Form A - D bodies and gland nuts steel with zinc electroplate and chromate finish coat Form E - F bodies and gland nuts Feraloy iron alloy with electrogalvanized and aluminum acrylic paint Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads Available in all aluminum construction See page 105 for related accessories
SELECTION TABLE
Entry Thread Size A NPT Size 3 /8" 3 /8" 3 /8" 3 /8" 3 /8" 3 /8" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 1" 1" 1" 1" 1" 1" 1" 1" 1" NPT Catalog # CGB3814 CGB3816 CGB3817 CGB3892 CGB3893 CGB3894 CGB114 CGB116 CGB117 CGB192* CGB193* CGB194* CGB195* CGB196* CGB197* CGB292 CGB293 CGB294 CGB295 CGB296* CGB297* CGB298* CGB393 CGB394 CGB395* CGB396* CGB397* CGB3239 CGB398* CGB399* CGB3911* Form A A A B B B A A A B B B B C C B B B B C C D B B C C C C D D D Thread Length B NPT 0.438 0.438 0.438 0.438 0.438 0.438 0.625 0.625 0.625 0.750* 0.750* 0.750* 0.750* 0.625* 0.625* 0.625 0.625 0.625 0.625 0.625* 0.625* 0.625* 0.688 0.688 0.688* 0.688* 0.688* 0.688 0.625* 0.625* 0.625* Cable Acceptance Outer Sheath E Min 0.125 0.250 0.375 0.125 0.250 0.375 0.125 0.250 0.375 0.125 0.250 0.375 0.500 0.625 0.750 0.125 0.250 0.375 0.500 0.625 0.750 0.875 0.250 0.375 0.500 0.625 0.750 0.875 0.875 1.000 1.188 Max 0.250 0.375 0.437 0.250 0.375 0.500 0.250 0.375 0.437 0.250 0.375 0.500 0.625 0.750 0.875 0.250 0.375 0.500 0.625 0.750 0.875 1.000 0.375 0.500 0.625 0.750 0.875 1.000 1.000 1.188 1.375 Gland Length F (less entry) 1.063 1.063 1.063 1.313 1.313 1.313 1.000 1.000 1.000 1.313 1.313 1.313 1.313 1.750 1.750 1.375 1.375 1.375 1.375 1.750 1.750 2.500 1.375 1.375 1.688 1.688 1.688 1.688 2.375 2.375 2.375 External Diameter G 2.250 2.375 2.375 2.375 Hexagon Dimensions Across Flats 0.750 0.750 0.750 1.000 1.000 1.000 0.875 0.875 0.875 1.000 1.000 1.000 1.000 1.500 1.500 1.060 1.060 1.060 1.060 1.630 1.630 1.375 1.375 1.500 1.500 1.500 Across Corners G 0.875 0.875 0.875 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.188 1.656 1.656 1.250 1.250 1.250 1.250 1.656 1.656 1.625 1.625 1.875 1.875 1.875 1.875
All dimensions in inches unless otherwise noted. *With optional Sealing Gasket. With optional Aluminum Construction.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
91
4F
CGB
North American Standards General Purpose
cULus Listed
4F
Entry Thread Size A NPT Size 11/4" 11/4" 11/4" 11/4" 11/4" 11/2" 11/2" 11/2" 11/2" 11/2" 2" 2" 2" 2" 21/2" 21/2" 21/2" 21/2" 3" 3" NPT Catalog # CGB498 CGB499 CGB4911 CGB4913 CGB4915 CGB598 CGB599 CGB5911 CGB5913 CGB5915 CGB6913 CGB6915 CGB6917 CGB6920 CGB7913 CGB7915 CGB7917 CGB7920 CGB8917 CGB8920 Form D D D E E D D D E E E E F F E E F F F F
Thread Length B NPT 0.688 0.688 0.688 0.688 0.688 0.813 0.813 0.813 0.813 0.813 0.813 0.813 0.813 0.813 1.000 1.000 1.000 1.000 1.000 1.000
Cable Acceptance Outer Sheath E Min 0.875 1.000 1.188 1.375 1.625 0.875 1.000 1.188 1.375 1.625 1.375 1.625 1.875 2.188 1.375 1.625 1.875 2.188 1.875 2.188 Max 1.000 1.188 1.375 1.625 1.875 1.000 1.188 1.375 1.625 1.875 1.625 1.875 2.188 2.500 1.625 1.875 2.188 2.500 2.188 2.500
Gland Length F (less entry) 2.313 2.313 2.313 2.625 2.625 2.313 2.313 2.313 2.625 2.625 2.625 2.625 2.563 2.563 2.625 2.625 2.625 2.625 2.625 2.625
External Diameter G 2.250 2.250 2.250 3.000 3.000 2.250 2.250 2.250 3.000 3.000 3.000 3.000 3.750 3.750 3.125 3.125 3.750 3.750 3.750 3.750
92
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
CGD
North American Standards General Purpose
cULus Listed
4F
Gland Type
Non-armoured
4F
Cable Type
Non-armoured and tray cable
Features:
45 angle with male thread Standard body material is Feraloy iron alloy Standard gland nut material is steel Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories
SELECTION TABLE
Entry Thread Size A NPT Size NPT Catalog # 1 /2" CGD192 /2" /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4"
1 1
Thread Length B NPT 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630 0.630
Cable Acceptance Outer Sheath E Min Max 0.125 0.250 0.250 0.375 0.500 0.625 0.750 0.125 0.250 0.375 0.500 0.625 0.750 0.375 0.500 0.625 0.750 0.875 0.250 0.375 0.500 0.625 0.750 0.875
Gland Length F (less entry) 1.688 1.688 1.688 1.688 2.063 2.063 1.938 1.938 1.938 1.938 2.000 2.000
External Diameter G 1.188 1.188 1.188 1.188 1.625 1.625 1.141 1.141 1.125 1.125 1.625 1.625
CGD193 CGD194 CGD195 CGD196 CGD197 CGD292 CGD293 CGD294 CGD295 CGD296 CGD297
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
93
4F
CGE
North American Standards General Purpose
cULus Listed
4F
Gland Type
Non-armoured
Cable Type
Non-armoured and tray cable
Features:
90 angle with male thread Standard body material is Feraloy iron alloy Standard gland nut material is steel Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories
SELECTION TABLE
Entry Thread Size A NPT Size /2" /2" 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 3 /4" 1" 1" 1" 1" 1" 1" 1"
1 1
NPT Catalog # CGE192 CGE193 CGE194 CGE195 CGE196 CGE197 CGE292 CGE293 CGE294 CGE295 CGE296 CGE297 CGE395 CGE396 CGE397 CGE3239 CGE398 CGE399 CGE3911
Thread Length B NPT 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710 0.710
Cable Acceptance Outer Sheath E Min 0.1250 0.2500 0.3750 0.5000 0.6250 0.7500 0.1250 0.2500 0.3750 0.5000 0.6250 0.7500 0.5000 0.6250 0.7500 0.8750 0.8750 1.0000 1.1880 Max 0.2500 0.3750 0.5000 0.6250 0.7500 0.8750 0.2500 0.3750 0.5000 0.6250 0.7500 0.8750 0.6250 0.7500 0.8750 1.0000 1.0000 1.1880 1.3750
Gland Length F (less entry) 1.438 1.438 1.438 1.438 2.000 2.000 1.406 1.406 1.406 1.406 1.875 1.875 2.063 2.094 2.094 2.094 2.656 2.656 2.656
External Diameter G 1.188 1.188 1.188 1.188 1.625 1.625 1.188 1.188 1.188 1.188 1.625 1.625 1.625 1.625 1.625 2.250 2.250 1.625 2.250
94
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
CGB1013
North American Standards General Purpose
cULus Listed
4F
Gland Type
Portable cord connector
4F
Cable Type
Non-armoured and tray cable
Features:
Body steel with zinc electroplate and chromate finish coat Gland nut material is aluminum Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories
SELECTION TABLE
Entry Thread Size A NPT Size NPT Catalog # 1 /2" CGB1013 1 /2" CGB1014 1 /2" CGB1015 3 /4" CGB2013 3 /4" CGB2014 3 /4" CGB2015
All dimensions in inches unless otherwise noted.
Outer Sheath E Min 0.312 0.375 0.500 0.312 0.375 0.500 Max 0.437 0.500 0.625 0.437 0.500 0.625
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
95
4F
CGFP
North American Standards General Purpose
4F
Gland Type:
Non-armoured
Cable Type:
Non-armoured and tray cable
Features:
Form B - C standard body and gland nut are turned steel Form D - G standard body and gland nut are Feraloy iron alloy Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads See page 105 for related accessories
SELECTION TABLE
Entry Thread Size A NPT Size 1 /2" 1 /2" 1 /2" 1 /2" 3 /4" 3 /4" 3 /4" 1" 1" 1" 11/4" 11/4" 11/2" 11/2" 2" 2" 21/2" 21/2" 3" 3" 31/2" 31/2" 4" 4" NPT Catalog # CGFP192 CGFP193 CGFP194 CGFP195 CGFP296 CGFP297 CGFP2239 CGFP396 CGFP397 CGFP3239 CGFP499 CGFP4911 CGFP599 CGFP5911 CGFP6913 CGFP6915 CGFP7917 CGFP7920 CGFP8917 CGFP8920 CGFP923 CGFP927 CGFP1023 CGFP1027 Form B B B B C C C C C C D D D D E E F F F F G G G G Thread Length B NPT 0.750 0.750 0.750 0.750 0.750 0.750 0.750 0.938 0.938 0.938 0.938 0.938 0.938 0.938 1.000 1.000 1.438 1.438 1.500 1.500 1.563 1.563 1.625 1.625 Cable Acceptance Outer Sheath E Min Max 0.1250 0.2500 0.2500 0.3750 0.3750 0.5000 0.5000 0.6250 0.6250 0.7500 0.7500 0.8750 0.8750 1.0000 0.6250 0.7500 0.7500 0.8750 0.8750 1.0000 1.0000 1.1880 1.1880 1.3750 1.0000 1.1880 1.1880 1.3750 1.3750 1.6250 1.6250 1.8750 1.8750 2.1880 2.1880 2.5000 1.8750 2.1880 2.1880 2.5000 2.5000 3.0000 3.0000 3.5000 2.5000 3.0000 3.0000 3.5000 Gland Length F (less entry) 1.375 1.375 1.375 1.375 1.750 1.750 1.750 1.750 1.750 1.750 2.375 2.375 2.375 2.375 3.250 3.250 3.250 3.250 3.250 3.250 4.250 4.250 4.250 4.250 External Diameter G 1.281 1.281 1.281 1.281 1.781 1.781 1.781 1.781 1.781 1.781 2.250 2.250 2.250 2.250 3.250 3.250 3.875 3.875 3.875 3.875 5.500 5.500 5.500 5.500
96
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4F
Gland Type:
Non-armoured
4F
Cable Type:
Non-armoured and tray cable
SELECTION TABLE
Entry Thread Size A NPT Size NPT Catalog # 3 /8" NCG38 35 1 /2" NCG50 50 3 /4" NCG75 75 1" NCG100 100
All dimensions in inches unless otherwise noted.
NCG Features:
Outer Sheath E Min Max 0.10 0.35 0.20 0.50 0.35 0.75 0.55 1.00 Standard material is polyamide 6 Weatherproof seal on outer sheath of cable Standard neoprene seal suitable for use in operating temperatures -25 to 40C Available with NPT threads
/2" /4"
1"
Gland Type:
Non-armoured
Cable Type:
Non-armoured and tray cable
SELECTION TABLE
NPT Size 1 /2" 1 /2" 3 /4" 3 /4" 1" 1" NPT Catalog # NCGB1231 NCGB1232 NCGB2233 NCGB2234 NCGB3235 NCGB3236 Cable Acceptance Range 'E' Min Max 0.25 0.42 0.40 0.57 0.54 0.68 0.64 0.78 0.76 0.91 0.89 1.03 Gland Length (Less Entry) 'F' 2.25 2.25 2.52 2.52 3.19 3.19 External Diameter 'G' 1.33 1.33 1.58 1.58 2.02 2.02
NCGB Features:
Standard material is thermoplastic polyester Tightens by hand to create a watertight seal Gasket on entry threads included Compact design allows close grouping of connectors Available with NPT threads
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
97
4F
Accessories A Series
4F
A Series Sealing Washer Standard material is neoprene METRIC SELECTION TABLE NPT SELECTION TABLE
Metric Metric Size Catalog # 10 12 16 20 25 32 40 50 63 CAP221049 CAP221249 CAP221649 CAP222049 CAP222549 CAP223249 CAP224049 CAP225049 CAP226349 Metric Diam. D 15.0 18.0 22.0 24.0 30.0 42.0 52.0 63.0 77.0 Metric Thickness E 1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.0 NPT Size /4" /8" 1 /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3" 31/2"
1 3
NPT Catalog # CAP229014 CAP229038 CAP229012 CAP229034 CAP229010 CAP229114 CAP229112 CAP229020 CAP229212 CAP229300 CAP229312
NPT Diam. D 20.0 22.0 27.0 33.0 41.0 52.0 57.0 71.0 85.0 104.0 120.0
NPT Thickness E 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0
A Series Earth Tag Standard material is nickel-plated brass METRIC SELECTION TABLE
Entry Thread M16 M20 M25 M32 M40 M50 M63 M75 A 48.75 53.8 61.5 73 86.5 111.5 125.5 137.5 B 30 33 36 41 44.5 58 67 73 C 6.75 7 10.5 12.2 13.5 13.5 13.5 13.5 D 24.5 28.6 34 42 54 67 77 89 Catalog # CAP567034 CAP567054 CAP567074 CAP567094 CAP567124 CAP567154 CAP567184 CAP567194
B 36 41 41 44.5 58 67 73
D 34 42 42 54 67 77 89
98
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Accessories A Series
4F
A-Series Shroud
Standard material is PVC
4F
SELECTION TABLE
Gland Size Catalog # CAP506040 CAP506050 CAP506060 CAP506070 CAP506080 CAP506090 CAP506100 CAP506110 CAP506120 CAP506130 CAP506140 CAP506150 CAP506160
SELECTION TABLE
Metric Size 16 20 25 32 40 50 63 75 90 External Diameter 25.5 32.5 39.5 49.5 64.5 80.5 100 112 123 Catalog # CAP280069 CAP280029 CAP280259 CAP280329 CAP280409 CAP280509 CAP280639 CAP280759 CAP280099
4 5 6 7 8 9 10 11 12 13 14 15 16
SELECTION TABLE
Cable Range Gland Size 4-8.5 6-11 8.5-16 12-21 16-27.5 21-34 27-41 33-48 40-56 47-65 54-74 63-83 72-93 4 5 6 7 8 9 10 11 12 13 14 15 16 Across Flats 15 19 24 30 41 48 55 64 72 85 95 110 120 Width 18 22 27.5 33.5 45 52 59 69 78 92 103 118 128 Thickness Catalog # 5 5 6 8 8 9.5 9.5 12 12 16 16 18 18 CAP810434 CAP810534 CAP810634 CAP810734 CAP810834 CAP810934 CAP811034 CAP811134 CAP811234 CAP811334 CAP811434 CAP811534 CAP811634
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
99
4F
Accessories A Series
Standard brass A Series Adaptors and Reducers ATEX Exe material is nickel-plated00010 Exd with LCIE 98 ATEX
4F
M12
745834 745844
M16
745334
M20
740274
M25
M32
M40
M50
M63
M75
M80
M90
M110
740024 740034
740544 740294 740304 740814 740564 740574 741084 740834 740844 741354 741104 741114 741624 741374 741384 741894 741644 745864 745394
/4"
/8"
/2"
/4"
1"
11/4"
11/2"
2"
21/2"
3"
31/2"
M12 744104 M16 M20 744204 M25 M32 M40 M50 M63 M75 M90 M110
744194 744214
746314 746324
746584 744304
M12
740614 740884 740914
M16
740624 740894 740194 740204
M20
740904 740454 740464 740474
M25
M32
M40
M50
M63
M75
M90
M100
M110
742064
/4"
/8"
/2"
/4"
1"
11/4"
11/2"
2"
21/2"
3"
31/2"
4"
745574 745594
744624 745134 744884 744894 745404 745154 745164 745674 745424 745434 745944 745694 745704 746214 745964 746234 746244 746484 746504
100
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Accessories A Series
4F
4F
Metric Catalog #*
CAP190124 CAP190164 CAP190204 CAP190254 CAP190324 CAP190404 CAP190504 CAP190634 CAP190754 CAP190804 CAP199904 CAP191004
Across Flats A
14 18 23 28 36 44 54 67 80 85 95 110
Hex Thickness B
2.8 3.0 3.0 3.5 4.0 4.0 5.0 5.5 6.0 7.0 8.0 10.0
Thread Length E
15 15 15 15 15 15 16 17 18 20 22 22
Across Flats A
14 18 22 28 36 44 50 64 75 90 110
Hex Thickness B
2.8 2.8 3.0 3.0 3.5 4.0 5.0 5.5 6.0 6.0 10.0
Thread Length E
12 12 16 16 20 20 20 20 28 30 32
CAP190194 CAP109294 CAP190394 CAP190494 CAP190594 CAP190694 CAP190794 CAP190894 CAP190994 CAP191094 CAP191194
All dimensions in millimeters unless otherwise noted. *For stainless steel replace last digit with "9".
Washer and locknut are required for non-threaded holes (not included) see page 98
Metric Catalog #*
CAP191127 CAP191167 CAP191207 CAP191257 CAP191327 CAP191407 CAP191507 CAP191637
Across Flats A
15 19 23 28 36 44 54 67
Hex Thickness B
4 4 4 5 5.5 5.5 6 6.5
Thread Length E
15 15 15 15 15 15 16 17
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
101
4F
Accessories B Series
4F
B Series Shroud
PVC SELECTION TABLE
Size (Gland Size) L24 (16, 20s) L30 (20) L38 (25) L46 (32) L55 (40) L65 (50, 50s) L80 (63, 63s) L90 (75, 75s) L104 (80,85) L114 (90, 100) Catalog # PVC-L24 PVC-L30 PVC-L38 PVC-L46 PVC-L55 PVC-L65 PVC-L80 PVC-L90 PVC-L104 PVC-L114 Size L24 (16, 20s) L30 (20) L38 (25) L46 (32) L55 (40) L65 (50, 50s) L80 (63, 63s) L90 (75, 75s) L104 (80, 85)
PVC
PCP
102
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Accessories C Series
4F
4F
SELECTION TABLE
NPT Entry Thread /2" 3 /4" 1" 11/4" 11/2" 2" 21/2" 3"
1
C Series Shroud
Catalog Number SH1 SH2 SH3 SH4 SH5 SH6 SH7 SH8 SH9 SH10 SH11 SH12 SH13 SH14
SELECTION TABLE
To Suit Gland TUA1M10 TUA1M12 TUA1M15 TUA2M18 TUA3M23 TUA3M25 TUA5M34 TUA5M38 TUA5M42 TUA6M48 TUA6M54 TUA7M60 TUA7M66 TWA1M13 TWA1M16 TWA1M20 TWA2M27 TWA3M34 TWA4M40 TWA5M53 TWA6M66 TWA7M78 TWAE1M16 TWAE1M20 TWAE2M27 TWAE3M34 TWAE4M40 TWAE5M53 TWAE6M66 TWAE7M78 TWAX1M13 TWAX1M16 TWAX1M20 TWAX2M24 TWAX2M27 TWAX3M30 TWAX3M33 TWAX4M38 TWAX5M43 TWAX5M48 TWAX5M52 TWAX6M60 TWAX6M65 TWAX7M71 TWAX7M78 TWAB1M16 TWAB1M20 TWAB2M27 TWAB3M34 TWAB4M40 TWAB5M53 TWAB6M66 TWAB7M78
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
103
4F
Accessories D Series
4F
SELECTION TABLE
Width 17.00 22.00 26.00 32.00 41.00 50.00 60.00 75.00 Thickness 5.00 5.00 6.00 6.00 7.00 7.00 8.00 8.00 Catalog # GHG GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 960 1941 1941 1941 1941 1941 1941 1941 1941 R0031 R0032 R0033 R0034 R0035 R0036 R0037 R0038
SELECTION TABLE
Thread 1 Thread 2 20 25 32 32 40 40 50 50 63 63 x x x x x x x x x x 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 M16 M20 M20 M25 M25 M32 M32 M40 M40 M50 x x x x x x x x x x 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 Length 1 12.00 14.00 16.00 16.00 16.00 16.00 18.00 18.00 18.00 18.00 Length 2 8.00 8.00 10.00 10.00 10.00 10.00 12.00 12.00 12.00 12.00 Length 3 8.00 8.00 6.00 10.00 8.00 10.00 10.00 10.00 10.00 12.00 Across Flats 24.00 29.00 36.00 36.00 46.00 46.00 55.00 68.00 68.00 68.00 Catalog # GHG GHG GHG GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 960 960 960 1946 1946 1946 1946 1946 1946 1946 1946 1946 1946 R0071 R0072 R0056 R0074 R0059 R0077 R0062 R0080 R0065 R0083
SELECTION TABLE
Length 1 4.00 4.00 4.00 5.50 5.50 5.50 6.50 Length 2 12.00 13.00 13.00 15.00 15.00 16.00 16.00 Catalog # GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 1952 1952 1952 1952 1952 1952 1952 R0111 R0112 R0113 R0114 R0115 R0116 R0117
SELECTION TABLE
Length 1 30.30 33.00 34.50 36.00 39.50 42.00 44.00 45.00 Catalog # GHG GHG GHG GHG GHG GHG GHG GHG 960 960 960 960 960 960 960 960 1944 1944 1944 1944 1944 1944 1944 1944 R0101 R0102 R0103 R0104 R0105 R0106 R0107 R0108
104
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Accessories E Series
4F
4F
Catalog # TMC-K1 TMC-K2 TMC-K3 TMC-K4 TMC-K5 TMC-K6 TMC-K7 TMC-K8 TMC-K9 TMC-K10
Cold ShrinkTM Corrosion Protection Kits are specially designed for Cooper Crouse-Hinds TMC, TMCX and TECK fittings to provide protection against corrosive elements like salt spray and moisture. The TMC-K kit is made of a Cold Shrink material that is quick and easy to install on the gland. The Cold Shrink material is made of EPDM rubber that contains no chlorides or sulfurs. The protection kit installs easily over the gland without the use of a heat source to shrink the material tightly over the seal. The Cold Shrink material can be removed easily from the gland by simply cutting it off. See ordering information for complete offering of TMC-K Cold Shrink kits for corrosion protection. Cold Shrink is a registered trademark of the 3M Company.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
105
4F
4F
I M2 II, 2GD, EExe I & II (Stainless steel & brass only) II 2GD, EExe II (Nylon only) Enclosure type 4X IP66
SELECTION TABLE
Entry Thread M20 M20 M20 M25 M25 M25 1 /2" 1 /2" 3 /4" 3 /4" Material Brass Stainless Nylon Brass Stainless Nylon Brass Stainless Brass Stainless Steel Steel Steel Steel Catalog # ACDPEB/M20/15 ACDPES/M20/15 ACDPEN/M20/15 ACDPEB/M25/15 ACDPES/M25/15 ACDPEN/M25/15 ACDPEB/050NPT/15 ACDPES/050NPT/15 ACDPEB/075NPT/15 ACDPES/075NPT/15
Drainage Plug Standard material is polyamide; PTB01 ATEX 1128X Ex 1126 Exe II SELECTION TABLE
Thread 1 M25 x 1.5 Diameter 30.00 Length 1 19.00 Length 2 4.50 Catalog # GHG 960 1927 R0105
SELECTION TABLE
Thread 1 M25 x 1.5 Catalog # GHG 960 1954 R0002
All dimensions in millimeters unless otherwise noted.
106
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4F
Applications:
LCC cable tray conduit clamps are used for installation on cable tray side rails with inside flanges (requiring inside tray mounting) and outside flanges; LCCF clamps are for use exclusively on inside flanges. LCC/LCCF cable tray conduit clamps: Provide a means of clamping metal conduit (rigid steel or aluminum, IMC and EMT) to cable tray to provide for the exit of power and/or control cables from tray Provide a means to firmly bond exit conduit to cable tray for best grounding continuity Provide strong mechanical support for exit conduits and cables Can be used indoors or outdoors, wherever cable tray systems are installed Facilitate the safe exit of cables from tray insure protection of cables from damage
4F
LCC
LCCF
Ordering Information
Conduit Size /2 3 /4 1 11/4 11/2 2 21/2 3 31/2 4
1
Cat. # LCC1 LCC2 LCC3 LCC4 LCC5 LCC6 LCC7 LCC8 LCC9 LCC010
Cat. # LCCF1 LCCF2 LCCF3 LCCF4 LCCF5 LCCF6 LCCF7 LCCF8 LCCF9 LCCF010
Features:
Quick and easy installation low installed cost. Merely tighten clamp nut and/or set screw(s) Swivel hook clears conduit. No disassembly required for installation No drilling or welding necessary for installation Provides superior ground continuity between conduit and cable tray Clamps conduit at any angle with relation to tray facilitates wire pulling, minimizes conduit bending Malleable iron body provides great strength Knurled body has no-slip surface for conduit and tray positive grip assured Compact design has low profile minimum tray space required for assembly Design accommodates all popular types of cable tray Accommodates wide range of conduit sizes 1/2" through 4" LCCF features: Outside mounting facilitates inside rail installation Adjustable hook assures positive grip on inside rail Accommodates 3/4" through 13/4" wide flange
Dimensions
In Inches:
Standard Materials:
Body cast iron Hook steel Set screws and clamping nut steel Hook cap vinyl Conduit Size 1 /2 3 /4 1 11/4 11/2 2 21/2 3 31/2 4 LCC a 33/16 37/16 39/16 4 413/16 55/16 513/16 613/16 75/16 713/16 b 111/16 111/16 111/16 111/16 211/16 211/16 211/16 33/4 33/4 33/4 LCCF a 31/8 311/32 319/32 315/16 43/4 51/4 53/4 63/4 71/4 73/4 b 15/8 15/8 15/8 15/8 23/4 23/4 23/4 311/16 311/16 311/16 c 111/32 111/32 111/32 111/32 111/16 111/16 111/16 23/16 23/16 23/16 LCC LCCF
Standard Finishes:
Cast iron electrogalvanized and aluminum acrylic paint Steel zinc electroplate Vinyl natural
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
107
4F
4F
Applications:
Cable tray grounding conductor clamps are designed for use in heavy industrial applications: To provide a means for securely attaching a grounding conductor to cable tray to maintain grounding continuity for the entire cable tray system To provide protection of equipment through a reliable method for carrying ground fault currents To meet UL and NEC Code requirements For installation indoors or outdoors, with most types of cable trays with inside or outside flanges
Ordering Information
Cat. # TGC40
Features:
Meets requirements of NEC Code Article 318-7 for grounding and bonding Quick and easy installation low installed cost. No drilling or special tools required. Accommodates solid (where suitable) or stranded aluminum or copper grounding conductors in sizes from #6 to 2/0 Set screw bonds the clamp to the tray and another set screw securely attaches the grounding conductor to the clamp outstanding pull-out and vibration resistance Design accommodates most popular types of cable tray Mechanical device can be easily inspected Malleable iron body provides high strength
Dimensions
In Inches:
Standard Materials:
Body malleable iron Set screws steel
Standard Finishes:
Malleable iron and steel electrogalvanized
108
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4F
4F
Applications:
THRU-WALL BARRIER cable/conduit sealing device is used wherever there is a need to seal cables or conduits penetrating fireor non-fire-rated walls, ceilings, floors, bulkheads or decks. For nonfire-rated walls, ceilings, floors, bulkheads or decks, THRU-WALL BARRIER also restricts water and dust and will help contain treated air. THRU-WALL BARRIER is designed: To provide a seal for cable/conduit penetrations through masonry, concrete or steel; to restrict the entrance of contaminants through cable/conduit penetrations into clean areas For use with most types of power, instrument and control cables as well as conduits To be used indoors or outdoors, in new construction or existing structures
Features:
System Few parts required to seal a wide range of diameters of cables or conduits Easy and fast installation, using factory assembled components High degree of flexibility with interchangeable sealing block assemblies and a selection of different sizes of frames Mounting frame One-piece cast malleable iron or steel mounting frame can be cast into concrete during wall construction, grouted in masonry surfaces or welded into steel bulkheads at any time Retrofit frame allows for easy installation of frame where cables/conduit are already installed Available in sizes to accommodate a wide range of cable tray sizes and loadings including single and multiple layers of cables for power or instrument applications Cast keyways in mounting frame align and position sealing block assemblies Frames can be installed in wall such that sealing block assemblies can be inserted in either horizontal or vertical position Sealing block assembly Specially formulated elastomeric material between cast malleable iron pressure plates protects cable from mechanical damage; provides high pull-out resistance and positive cable separation; expands during fire to seal any voids left by burned cable insulation Interchangeable sealing block assemblies fit all THRU-WALL BARRIER mounting frames Cast stops on front pressure plate prevent sealing block assembly from slipping through mounting frame during installation Assemblies are offered for all cable/conduit outside diameters from .250" to 4.500" (6.4 mm to 114.3 mm). Cables with diameters less than .250" can be accommodated consult Cooper Crouse-Hinds. Sealing block openings will accommodate undersize and out-of-round cable Each sealing block assembly seals multiple cables/conduits. Compact design permits close nesting of cables, saving space. Reducers permit sealing block assemblies to accept cables with smaller O.D. than the specified range Plugs are used to fill unused openings in sealing block assemblies. Blank sealing block assemblies fill unused spaces in mounting frames, providing for future expansion.
Standard Materials:
Mounting frame: TWF, TWFR cast malleable iron TWFS cast carbon steel, ASTM A27 Grade 60-30 Pressure plate cast malleable iron Sealing material special elastomeric material Clamping hardware steel
Standard Finishes:
Malleable iron and hardware electrogalvanized Steel aluminized weldable paint Special elastomeric material natural
1. Cast, grout or weld the onepiece mounting frame into masonry or steel surface.
3. Position cables/conduit, insert factory assembled sealing blocks into keyways in mounting frame, and tighten nuts on clamping hardware to effect the seal.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
109
4F
4F
TWB2063 Depending on opening size range, a standard sealing block assembly will seal from one to eleven cables
.500.750 .7501.000 1.0001.250 1.2501.500 1.5001.750 1.7502.000 2.0002.250 2.2502.500 12.719.1 19.125.4 25.431.8 5 31.838.1 4 38.144.5 3 44.550.8 3 50.857.2 3 57.263.5 2
11 11 6 6 Added* Added*
Sealing Block Assembly Cat. # Frame Spaces Required Plug Cat. # Reducer Cat. #
TWB2111 TWB1111
2 2
2 TWP3
3 TWP5
4 TWP6
5 TWP7
TWP1 TWR2
TWR3
TWR4
TWR5
TWR55
TWR6
TWR66
TWR7
TWF10 Retrofit Frame Cat. # TWFR6 TWFR10 TWFR12 TWFR20 TWFR24 TWFR30
For 3.5" - 4" cable/conduit use TWB7011010 assembly and reduce down using TWR reducers. *Catalog # TWB1111 and TWB2112 are used between TWB2111 and TWB2062 in cases where the number of cables to be sealed in .250-.750 range exceeds the number of openings in standard assemblies. Use as many of these higher density assemblies as needed, sandwiched between halves of a standard assembly. TWR reducers match TWB sealing block assemblies shown in column above Cat. No. and reduce openings to accept cable size ranges shown in adjacent column to the left (in direction of arrow).
110
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
4F
4F
TWP plugs will close any unused openings in sealing block assemblies. See table for plug catalog numbers which match specific sealing block assemblies. TWB2112 TWB2062
TWR reducers will reduce openings by .250" (6.4 mm) in sealing block assemblies. See table for reducer catalog numbers which match specific sealing block assemblies. More than one reducer can be used in a single opening.
It is possible to increase cable fill density with double-sided sealing block assemblies (TWB1111 and TWB2112) sandwiched between halves of a standard assembly. 2.5002.750 63.569.9 2 2.7503.000 69.976.2 2 3.0003.250 76.282.6 2 3.2503.500 82.688.9 2 3.5004.250 101.6108.0 1 4.2504.500 108.0114.3 1
TWB50277
TWB5028
TWB60288
TWB6029
TWB7011010
TWB70111
TWB1
TWB3
5 TWP7 TWR77
5 TWP8 TWR8
6 TWP9
7 TWP11 TWR11
TWR88
TWR9 TWR99
TWK Anchors
TWK anchor assemblies are used to attach mounting frames to wall, ceiling or floor when grouting in frames. Mounting Type Flush Recessed Cat. # TWK1 TWK2
*TWB closure cover kits are not designed to provide a watertight seal in marine/shipboard applications or washdown areas. One kit seals one unused frame opening of same size. Example: use one TWB2000 kit to seal one TWF20, or TWFR20 frame. Use two TWB600 kits to seal one TWF12 or TWFR12 frame opening.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
111
4F
4F
Product Information
Selecting and specifying THRU-WALL BARRIER components is a simple procedure. Primary components for the THRU-WALL BARRIER consist of TWF mounting frames in various sizes and TWB sealing block assemblies for cable/conduit outside diameters (O.D.) in 1/4-inch increments from .250" to 4.500" (6.4 mm to 114.3 mm). Cables with diameters less than .250" can be accommodated consult Cooper Crouse-Hinds. Cable/conduit sizes can be mixed within a sealing block assembly by inserting TWR reducers to accommodate smaller diameters. The use of reducers can decrease the number of sealing block assemblies required. More than one reducer can be used in a single opening. Another way to increase density is to use TWB1111 and TWB2112 sealing block assemblies wherever there is a large number of cables/conduits in sizes ranging from .250" to .750". TWB2112
Ordering Example A:
Cable tray size: 24" Cables specified: 5 power cables sizes ranging from 1.960" to 2.200" O.D. Spare capacity required: 50% Step 1. Group cables by O.D. and rank from largest to smallest. Cable Cable Qty. O.D. 4 2.200 1 1.960 Total 5 Step 2. Group cables that fall within the same sealing block assembly size. Sealing Block Cable Qty. O.D. Range diameter cables where possible and TWP plugs to fill openings not used. (See Example A diagram.)
Note: In the example, one TWR66 reducer is required to accommodate the cable with 1.960 O.D. and one TWP6 plug is required for the unused opening.
Step 4. Total the frame spaces required for sealing block assemblies and select appropriate size mounting frame. Factor in spare capacity required for future expansion. Total frame spaces required Specification requires 50% spare capacity Total spaces 8 4 12
TWB2062
TWB2062
Shown here is a double-sided sealing block assembly (TWB2112) sandwiched between halves of a standard sealing block assembly (TWB2062). Additional double-sided sealing block assemblies may be used to accommodate larger quantities of cables or conduits. Unused sealing block openings must be closed with TWP plugs. Blank sealing block assemblies TWB1 and TWB3 are used to fill each unused space in the mounting frame and permit future expansion of the system. Typical practice is to include space allowance of 20 to 50% for future expansion. TWB closure kits are used to seal entire frames and permit future system expansion.
4 2.0002.250 1 1.7502.000 Total 5 Step 3. Starting with the largest cable O.D., select the quantity of sealing block assemblies required. Specify TWR reducers to accommodate smaller Sealing Block Assy Cat. # TWB40366 TWB40366 Number of Openings 3 3 66
Selection: One TWF12 mounting frame with capacity of 12 spaces. Four TWB1 blank sealing block assemblies to fill unused frame space. (Choice of frame could vary based on future expansion needs and/or specific cable arrangement.)
Cables to be Sealed 3 2 5
Number of Openings 1 1
Cables to be Sealed 4 4 8
Step 5. Bill of materials for specification/order should read: (1) TWF12 (2) TWB40366 (4) TWB1 (1) TWR66 (1) TWP6
4F
4F
Sealing Block Assy Cat. # TWB40366 TWB40366 TWB2063 TWB2062 TWB2112 TWB2112
Number of O.D. Range Openings 2.0002.250 2.0002.250 .7501.000 .500.750 .500.750 .500.750 Totals 3 3 6 6 11 11 40
Cables to be Sealed 3 3 5 6 11 9 37
Note: In this example, two TWB2112 sealing block assemblies are sandwiched between two halves of a TWB2062. This dramatically increases cable density in minimum frame space. One TWP3 plug is required for unused opening in TWB2063 and two TWP1 plugs are required for unused openings in the TWB2112.
Total
Step 4. Total the frame spaces required for sealing block assemblies and select appropriate size mounting frame(s). Factor in spare capacity required for future expansion. Total frame spaces required Specification requires 25% spare capacity Total 16 4 20
Step 5. Bill of materials for specification/order should read: (2) TWF10 or (1) TWF20 (2) TWB40366 (1) TWB2063 (1) TWB2062 (2) TWB2112 (1) TWP3 (2) TWP1 (1) TWB3 (1) TWB1
Step 2. Group cables that fall within the same sealing block assembly size. Sealing Block Cable Qty. O.D. Range 6 2.0002.250 5 .7501.000 26 .500.750 Total 37 Step 3. Starting with the largest cable O.D., select the quantity of sealing block assemblies required. Specify TWR reducers to accommodate smaller diameter cables where possible and TWP plugs to fill openings not used. (See Example B diagram.)
Selection: Two TWF10 (or one TWF20) mounting frames with total capacity of 20 spaces. One TWB3 and one TWB1 blank sealing block assembly to fill unused frame space. (Choice of frame could vary based on future expansion needs and/or specific cable/conduit arrangement.) Example B diagram
*For TWFS mounting frame hole dimensions, contact Cooper Crouse-Hinds ECM field representative or headquarters.
Dimensions
In Inches:
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
113
4F
4F
Dimensions
In Inches:
TWK
1. Dimensions are shown as inches (mm). 2. Dimensions shown for TWF frames also apply for TWFR retrofit frames.
TWF30 (97 lbs.) *For TWF mounting frame hole dimensions, contact Cooper Crouse-Hinds ECM field representative or headquarters.
114
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Link-Seal Devices
Environmental Seal for Conduit passing through Concrete Walls, Floors or Ceilings
Link-Seal Devices Applications:
Cooper Crouse-Hinds Link-Seal is the quick, economical way to seal around conduit in concrete walls, floors and casings. Link-Seal is a modular mechanical seal used for any type of penetration.
4F
4F
Materials:
The standard product for environmental conduit seals is made from EPDM supplied with steel bolts and nuts with a zinc dichromate finish. These seals are suitable for use in water, direct ground burial and atmospheric conditions. They provide electrical insulation where cathodic protection is required. EPDM rubber is resistant to most inorganic acids and alkalis, and some organic chemicals (acetone, alcohol, ketones).
Sleeve Methods:
Select either the plastic or metal sleeve. Both types of sleeves are designed to be cast into concrete walls or floors. Sleeves are ordered separately. Remember to add the wall or floor thickness to the steel sleeve part number to insure the sleeve is provided in the proper length. Plastic sleeves are a standard 16 long and can be modified in the field.
Options:
To order the standard product with 316 stainless steel bolts and nuts, for corrosive environments, replace the "C" in the seal catalog number with "S316". For example, a 1/2" seal for rigid steel conduit for a cored hole is an LSA200-C-04; ordered with stainless steel bolts and nuts the catalog number becomes LSA200-S316-04.
Standard Materials:
Rubber Seal Elements: EPDM (Black) Environmental Seals Silicone (Grey) Fire Seals Pressure Plates: Glass Reinforced Nylon Environmental Seals Steel w/Zinc Dichromate Plate Fire Seals Fasteners: Carbon Steel, Zinc Dichromate Plate Environmental Seals 316 Stainless Steel Environmental with Option S316 Carbon Steel w/Zinc Dichromate Fire Seals
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
115
4F
Link-Seal Devices
Environmental Seal for Conduit passing through Concrete Walls, Floors or Ceilings
4F
Conduit Type* EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT IMC RSC EMT/RSC IMC EMT/RSC IMC EMT/RSC IMC EMT/RSC IMC RSC RSC
Conduit Actual O.D. (inches) .706 .815 .840 .922 1.029 1.050 1.163 1.290 1.315 1.510 1.638 1.660 1.740 1.883 1.900 2.197 2.360 2.375 2.875 2.857 3.500 3.476 4.000 3.971 4.500 4.466 5.563 6.625
Cast/Cored Hole Dia. (inches) 2.000 2.000 2.000 2.000 2.500 2.500 2.500 3.000 3.000 3.000 3.000 3.000 3.500 3.500 3.500 4.000 4.000 4.000 4.000 4.000 5.000 5.000 6.000 6.000 6.000 6.000 8.000 10.000
Seal for Cast/Cored Hole Cat. # LSA275 C 04 LSA200 C 04 LSA200 C 04 LSA200 C 04 LSA275 C 06 LSA275 C 06 LSA315 C 04 LSA300 C 04 LSA300 C 04 LSA300 C 04 LSA275 C 07 LSA275 C 07 LSA315 C 05 LSA300 C 05 LSA300 C 05 LSA315 C 06 LSA300 C 06 LSA300 C 06 LSA200 C 09 LSA200 C 09 LSA300 C 08 LSA300 C 08 LSA325 C 05 LSA325 C 05 LSA300 C 10 LSA300 C 10 LSA425 C 06 LSA475 C 10
Seal for Plastic Sleeve Cat. # LSA200 C 04 LSA200 C 04 LSA200 C 04 LSA315 C 04 LSA315 C 04 LSA315 C 04 LSA300 C 04 LSA300 C 04 LSA300 C 04
WS2 15 LSA200 C 04 WS2 15 LSA200 C 04 WS2.5 20 LSA275 C 06 WS2.5 20 LSA275 C 06 WS2.5 10 LSA275 C 06 WS2.5 20 LSA200 C 05 WS3.5 22 LSA315 C 05 WS3.5 22 LSA315 C 05 WS3.5 22 LSA315 C 05 WS3.5 32 LSA315 C 05 WS3.5 22 LSA300 C 05 WS3.5 22 LSA300 C 05 WS4 23 WS4 23 WS4 23 WS4 23 WS4 23 WS5 25 WS5 25 WS6 28 WS6 28 WS6 28 WS6 28 WS8 32 WS8 18 LSA315 C 06 LSA300 C 06 LSA300 C 06 LSA200 C 09 LSA200 C 09 LSA300 C 08 LSA300 C 08 LSA325 C 05 LSA325 C 05 LSA300 C 10 LSA300 C 10 LSA425 C 06 LSA300 C 15
1" 1" 1" 11/4" 11/4" 11/4" 11/2" 11/2" 11/2" 2" 2" 2" 21/2" 21/2" 3" 3" 31/2" 31/2" 4" 4" 5" 6"
LS CS 3.5 16 LSA315 C 05 LS CS 3.5 16 LSA300 C 05 LS CS 3 16 LSA200 C 06 LS CS 3.5 16 LSA300 C 05 LS CS 3.5 16 LSA275 C 08 LS CS 3.5 16 LSA275 C 08 LS CS 4 16 LS CS 4 16 LS CS 4 16 LS CS 4 16 LS CS 4 16 LS CS 5 16 LS CS 5 16 LS CS 6 16 LS CS 6 16 LS CS 6 16 LS CS 6 16 LS CS 8 16 LS CS 10 16 LSA315 C 06 LSA300 C 06 LSA300 C 06 LSA200 C 09 LSA200 C 09 LSA300 C 08 LSA300 C 08 LSA325 C 05 LSA325 C 05 LSA300 C 10 LSA300 C 10 LSA425 C 06 LSA475 C 10
*EMT Electrical Metallic Tubing; IMC Intermediate Metal Conduit; RSC Rigid Steel Conduit Specify length of steel sleeve in inches. Example: S6-28-08 is 8" long. All plastic sleeves come in standard 16" lengths and can be field cut to desired length. The last two digits of the seal part number indicate the number of links (and the number of bolts) per seal.
116
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Link-Seal Devices
Fire Seal for Conduit passing through Concrete Walls, Floors or Ceilings
Fire Conduit Seal Ordering Information:
Locate the conduit size and type you are installing in the columns on the left. Then locate the seal and sleeve part number under the installation method you've selected. No sleeve is needed for cored or cast hole installation.
Fire Rated
4F
4F
Sleeve Methods:
Select the appropriate metal sleeve for the size and type of conduit being installed. The sleeve should be ordered separately. Remember to add the wall or floor thickness to the steel sleeve part number to insure the sleeve is provided in the proper length.
Options:
To order the fire seal for a 3-hour rating, replace the "T" in the seal catalog number with a "FS". For example, a 1/ 2" seal for rigid steel conduit for a cored hole is an LSA200-T-04; ordered with option FS the catalog number becomes LSA200-FS-04. A 3-hour fire seal can also be made by using two Model Ts back-to-back. The Model FS is basically two Model T's back-to-back. In Model FS, a tie rod tightens both seals simultaneously for use when only one side of an opening is accessible.
Materials:
The standard product for fire conduit seals is made from grey silicone supplied with steel bolts and nuts with a zinc dichromate finish. These seals are Factory Mutual approved for use as a 1-hour fire stop and can handle temperature extremes of 67F to +400F.
Conduit Type*
Conduit Actual O.D. (inches) 0.706 0.815 0.840 0.922 1.029 1.050 1.163 1.290 1.315 1.510 1.638 1.660 1.740 1.883 1.900 2.197 2.360 2.375 2.875 2.857 3.500 3.476 4.000 3.971 4.500 4.466 5.563 6.625
Cast/Cored Hole Dia. (inches) 2.000 2.000 2.000 2.000 2.500 2.500 3.000 3.000 3.000 3.000 3.000 3.000 3.500 3.500 3.500 4.000 4.000 4.000 4.000 4.000 5.000 5.000 6.000 6.000 6.000 6.000 8.000 10.000
Seal for Cast/Cored Hole Cat. # LSA275 LSA200 LSA200 LSA200 LSA275 LSA275 LSA315 LSA300 LSA300 LSA300 LSA275 LSA275 LSA315 LSA300 LSA300 LSA315 LSA300 LSA300 LSA200 LSA200 LSA300 LSA300 LSA325 LSA325 LSA300 LSA300 LSA425 LSA475 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 04 04 04 04 06 06 04 04 04 04 07 07 05 05 05 06 06 06 09 09 08 08 05 05 10 10 06 10
Steel Sleeve Cat. # WS2 15 WS2 21 WS2 21 WS2 15 WS2 15 WS2.5 20 WS2.5 20 WS2.5 10 WS2.5 20 WS3.5 22 WS3.5 22 WS3.5 22 WS3.5 32 WS3.5 22 WS3.5 22 WS4 23 WS4 23 WS4 23 WS4 23 WS4 23 WS5 25 WS5 25 WS6 28 WS6 28 WS6 28 WS6 28 WS8 32 WS8 18
Seal for Steel Sleeve Cat. # LSA275 LSA200 LSA200 LSA200 LSA200 LSA275 LSA275 LSA275 LSA200 LSA315 LSA315 LSA300 LSA300 LSA300 LSA275 LSA315 LSA300 LSA300 LSA200 LSA200 LSA300 LSA300 LSA325 LSA325 LSA300 LSA300 LSA425 LSA300 T T T T T T T T T T T T T T T T T T T T T T T T T T T T 04 04 04 04 04 06 06 06 05 05 05 05 05 05 08 06 06 06 09 09 08 08 05 05 10 10 06 15
Example: WS6-28-08 is 8" long. *EMT Electrical Metallic Tubing; IMC Intermediate Metal Conduit; RSC Rigid Steel Conduit The last two digits of the seal part number indicate the number of links (and the number of bolts) per seal.
EMT /2" IMC /2" 1 RSC /2" 3 EMT /4" 3 /4" IMC 3 /4" RSC 1" EMT 1" IMC 1" RSC 11/4" EMT 11/4" IMC 11/4" RSC 11/2" EMT 11/2" IMC 11/2" RSC 2" EMT 2" IMC 2" RSC 21/2" EMT/RSC 21/2" IMC 3" EMT/RSC 3" IMC EMT/RSC 31/2" 31/2" IMC 4" EMT/RSC 4" IMC 5" RSC 6" RSC Specify length of steel sleeve in inches.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
117
4F
Link-Seal Devices
Dimensions
4F
Dimensions
In Inches:
Technical Information
Link-Seal Cat. # LSA200 C LSA275 C LSA300 C LSA315 C LSA325 C LSA425 C LSA475 C Actual Thickness (inches) .478 .607 .687 .807 .875 1.062 1.562 Rubber Sealing Element Free Avg. Length After Length Tightening (inches) (inches) 13/4 13/4 21/2 21/2 3 31/2 31/2 13/8 13/8 2 2 2 /8
3
T (inches)
5
/8
11/2 17/16 3 /8
1
7 7
/2 /2 /2 /16 /16
1 3 1
23/4 23/4
31/2 31/2
118
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502