Start-Up Date:
Contact Phone
3-11-13
Rick Haley
City
4136369761
State Zip Code Country
Springfield
Supplier Type:
State Contact Name
MA
Contact Phone
USA
Flow Tech
Model Number (Type Code)
South Windsor
CT
Serial Number
Jim Lewis
860-291-8886
Software Revision code
2131002575
313D HEX
Fan
Speed Control
Scalar
Installation Checks - Mechanical Mechanical Installation Cable Connections Proper Grounding Input Fuses Wire run to/from motor Motor cable length Installation Checks - Electrical Drive disconnected - Megger Cable/Motor: Megger test voltage = Input Voltage @ Base Spd L1-L2= L2-L3= L3-L1= T1-T2= T2-T3= T3-T1= 482 484 481 452 453 451
Control (I/O, Feedback) Ambient Temperature Drive Unit cooling / Air flow Motor disengaged Safe to operate machine AutoTune completed
Reading
60-70F
Reading
T1-PE = T2-PE =
T3-PE =
L1 = L2 = L3 = T1 = T2 = T3 =
40 41 42 49 49 50
Additional Comments:
AHU-4-SF readings recorded at 60hz. Input fuses changed, original VFD is NG, sent back for warranty Fuses=JJS-100
Performed by:
Derek Labbie
By submittal of this form you commit that all information provided is accurate to the best of your ability, provided to the customer, and the requirements as listed here and in the product user Manual have been completed.