OWNER'S CONSULTANT :
PROJECT:
TITLE:
28.05.2012
DESIGNED
V.K.K
28.05.2012
CHECKED
R.K
APPROVED
SSD
FOR APPROVAL
SSD
28.05.2012
REV. No.
DESCRIPTION
APPD.
DATE
Doc. No.
PS048-EL-A4-018
SHEET
1
NO OF SHEET
6
REV
'0'
R/LD-40
29 May, 2012
Project Name: 1x50MW SOLAR THERMAL POWER PLANT, RAJASTHAN.
Project Model: 132kV Switchyard
Luminaire Type
Catalogue Number
FLOODLIGHT
All calculation results are based on the nominal values of lamps, ballasts, luminaires and other design
assumptions (M.F. / R.F.). Any deviations in these parameters may affect the illumination design.
Crompton Greaves
Luminaire Division
R/LD-40
29 May, 2012
Project Name: 1x50MW SOLAR THERMAL POWER PLANT, RAJASTHAN.
Project Model: 132kV Switchyard
FLOODLIGHT
FAD1314 - 400 W MH/T
0.390 m
0.150 m
0.228 m
Lamp Type:
No. of Lamps:
Lumens per Lamp:
Light Output Ratio:
Rated Power:
400 W MH/T
1
32000.0 lm
71.7 %
443.0 W
Luminaire Layout
#
Type
X (m)
Y (m)
H (m)
O ()
T ()
1
2
3
4
1
1
1
1
13.00
13.00
13.00
48.00
3.80
3.80
15.80
3.80
12.30
12.30
12.30
12.30
-140.53
91.70
81.70
-138.00
33.98
55.10
54.00
51.20
Crompton Greaves
Luminaire Division
R/LD-40
29 May, 2012
Project Name: 1x50MW SOLAR THERMAL POWER PLANT, RAJASTHAN.
Project Model: 132kV Switchyard
(0.0, 0.0)
48.0, 0.0)
3
4
(0.0, 19.6)
(48.0, 19.6)
Crompton Greaves
Luminaire Division
R/LD-40
29 May, 2012
Project Name: 1x50MW SOLAR THERMAL POWER PLANT, RAJASTHAN.
Project Model: 132kV Switchyard
Average = 33.6 lx
Max / Min: 18.652
Maximum = 64.4 lx
Ave / Min: 9.749
Minimum = 3.45 lx
Distance (m)
2.97
0.50
7.92
5.45
12.9
10.4
17.8
15.3
22.8
20.3
27.7
25.2
32.7
30.2
37.6
35.1
42.6
40.1
47.5
45.0
0.50
21.4
27.8
27.5
21.2
15.0
8.21
10.8
18.9
28.7
40.1
40.5
33.5
27.5
24.3
22.9
19.8
16.2
12.1
6.51
3.45
1.48
24.5
33.5
35.4
28.6
20.1
11.9
13.6
20.8
31.8
44.5
43.7
36.2
30.5
28.3
26.6
23.6
19.5
14.7
8.49
3.55
2.46
25.7
38.4
44.2
37.3
25.4
16.3
18.0
24.0
36.1
49.2
46.4
38.2
33.1
31.3
30.0
27.3
22.8
17.4
10.9
4.04
3.44
26.3
41.6
51.8
46.5
32.2
21.1
22.4
28.5
41.5
52.4
48.8
40.1
34.8
33.6
33.4
31.4
26.2
20.9
13.6
5.58
4.42
26.0
41.5
54.9
54.0
39.1
26.5
26.9
34.0
46.9
55.7
50.7
41.2
35.9
35.5
36.6
35.6
30.8
24.2
16.4
8.38
5.39
25.2
39.2
53.9
57.8
47.1
32.2
31.9
39.3
50.3
58.0
52.2
41.8
36.5
36.7
38.8
39.7
35.2
27.2
19.7
11.6
6.37
23.9
34.9
48.5
57.2
54.2
38.0
36.8
43.4
53.6
59.9
53.2
42.3
36.7
37.1
40.4
42.1
38.8
30.7
22.5
14.5
7.35
22.4
30.6
41.5
54.3
58.6
45.4
42.7
47.2
56.2
61.5
54.1
42.6
36.6
36.6
40.3
42.8
41.0
33.6
25.2
17.2
8.33
20.5
27.2
35.7
48.6
58.1
53.7
49.5
49.7
58.3
63.5
55.0
42.7
36.0
35.6
38.5
41.6
42.1
36.7
27.9
19.6
9.31
18.8
24.3
31.3
42.5
54.9
59.8
56.5
52.5
59.5
64.3
55.5
42.8
35.5
33.8
36.1
39.4
42.0
39.0
30.0
21.4
10.3
17.2
21.8
28.0
37.3
49.2
60.9
61.4
55.0
59.2
64.4
55.6
43.0
34.8
32.1
33.2
36.6
40.4
40.4
33.0
23.5
11.3
15.6
19.8
25.1
32.5
42.7
57.8
64.0
57.3
57.7
63.9
55.4
42.7
34.0
30.4
30.6
33.6
38.1
40.5
35.0
25.7
12.2
13.7
17.9
22.7
28.7
37.2
51.2
62.5
57.9
56.0
62.0
54.8
42.1
33.3
29.0
28.4
30.8
35.9
39.0
36.6
28.3
13.2
12.1
16.1
20.6
25.6
32.6
43.6
58.9
56.1
54.1
59.9
53.1
41.5
32.4
27.8
26.6
28.3
32.9
36.7
37.1
30.3
14.2
10.7
14.2
18.6
22.9
28.8
37.1
52.1
52.5
51.8
57.5
51.3
40.0
31.5
26.7
25.1
26.3
29.8
34.2
36.3
31.4
15.2
9.44
12.5
16.5
20.4
25.3
31.4
44.9
48.1
48.6
55.1
49.2
38.6
30.3
25.7
23.8
24.4
26.9
31.4
34.7
31.9
16.2
8.37
11.0
14.4
18.2
22.1
26.7
38.8
42.7
45.8
52.6
47.2
37.2
29.1
24.6
22.7
22.7
24.7
28.4
32.6
31.1
17.1
7.44
9.70
12.6
16.1
19.5
22.7
33.0
37.6
41.9
50.0
45.2
35.8
28.0
23.6
21.6
21.2
22.7
25.7
30.1
29.6
18.1
6.63
8.55
11.0
14.0
17.1
19.2
28.0
33.1
38.1
46.9
43.8
34.8
27.0
22.6
20.6
19.9
20.8
23.4
27.1
27.8
19.1
5.88
7.54
9.62
12.2
15.0
16.5
24.2
29.3
35.0
43.8
42.4
33.9
26.2
21.7
19.6
18.8
19.3
21.4
24.2
25.3
Distance
(m)
Crompton Greaves
Luminaire Division
R/LD-40
29 May, 2012
Project Name: 1x50MW SOLAR THERMAL POWER PLANT, RAJASTHAN.
Project Model: 132kV Switchyard
Distance
(m)
0.0
4.9
60% 50%40%
9.8
90%
14.7
80%
70%
0.0
12.0
24.0
36.0
19.6
48.0
Distance (m)
90% Maximum
80% Maximum
70% Maximum
60% Maximum
50% Maximum
40% Maximum
Crompton Greaves
Luminaire Division