Cisco Nexus 7000 Series Site Preparation Guide


October 29, 2011

Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 USA http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883

Text Part Number: OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

HE SPECIFICATIONS AND INFORMATION REGARDING THE PRODUCTS IN THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL STATEMENTS, INFORMATION, AND RECOMMENDATIONS IN THIS MANUAL ARE BELIEVED TO BE ACCURATE BUT ARE PRESENTED WITHOUT WARRANTY OF ANY KIND, EXPRESS OR IMPLIED. USERS MUST TAKE FULL RESPONSIBILITY FOR THEIR APPLICATION OF ANY PRODUCTS. THE SOFTWARE LICENSE AND LIMITED WARRANTY FOR THE ACCOMPANYING PRODUCT ARE SET FORTH IN THE INFORMATION PACKET THAT SHIPPED WITH THE PRODUCT AND ARE INCORPORATED HEREIN BY THIS REFERENCE. IF YOU ARE UNABLE TO LOCATE THE SOFTWARE LICENSE OR LIMITED WARRANTY, CONTACT YOUR CISCO REPRESENTATIVE FOR A COPY. The following information is for FCC compliance of Class A devices: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio-frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case users will be required to correct the interference at their own expense. The following information is for FCC compliance of Class B devices: The equipment described in this manual generates and may radiate radio-frequency energy. If it is not installed in accordance with Ciscos installation instructions, it may cause interference with radio and television reception. This equipment has been tested and found to comply with the limits for a Class B digital device in accordance with the specifications in part 15 of the FCC rules. These specifications are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. Modifying the equipment without Ciscos written authorization may result in the equipment no longer complying with FCC requirements for Class A or Class B digital devices. In that event, your right to use the equipment may be limited by FCC regulations, and you may be required to correct any interference to radio or television communications at your own expense. You can determine whether your equipment is causing interference by turning it off. If the interference stops, it was probably caused by the Cisco equipment or one of its peripheral devices. If the equipment causes interference to radio or television reception, try to correct the interference by using one or more of the following measures: Turn the television or radio antenna until the interference stops. Move the equipment to one side or the other of the television or radio. Move the equipment farther away from the television or radio. Plug the equipment into an outlet that is on a different circuit from the television or radio. (That is, make certain the equipment and the television or radio are on circuits controlled by different circuit breakers or fuses.) Modifications to this product not authorized by Cisco Systems, Inc. could void the FCC approval and negate your authority to operate the product. The Cisco implementation of TCP header compression is an adaptation of a program developed by the University of California, Berkeley (UCB) as part of UCBs public domain version of the UNIX operating system. All rights reserved. Copyright 1981, Regents of the University of California. NOTWITHSTANDING ANY OTHER WARRANTY HEREIN, ALL DOCUMENT FILES AND SOFTWARE OF THESE SUPPLIERS ARE PROVIDED AS IS WITH ALL FAULTS. CISCO AND THE ABOVE-NAMED SUPPLIERS DISCLAIM ALL WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, THOSE OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT OR ARISING FROM A COURSE OF DEALING, USAGE, OR TRADE PRACTICE. IN NO EVENT SHALL CISCO OR ITS SUPPLIERS BE LIABLE FOR ANY INDIRECT, SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGES, INCLUDING, WITHOUT LIMITATION, LOST PROFITS OR LOSS OR DAMAGE TO DATA ARISING OUT OF THE USE OR INABILITY TO USE THIS MANUAL, EVEN IF CISCO OR ITS SUPPLIERS HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. Cisco and the Cisco Logo are trademarks of Cisco Systems, Inc. and/or its affiliates in the U.S. and other countries. A listing of Cisco's trademarks can be found at www.cisco.com/go/trademarks. Third party trademarks mentioned are the property of their respective owners. The use of the word partner does not imply a partnership relationship between Cisco and any other company. (1005R) Any Internet Protocol (IP) addresses used in this document are not intended to be actual addresses. Any examples, command display output, and figures included in the document are shown for illustrative purposes only. Any use of actual IP addresses in illustrative content is unintentional and coincidental. Any Internet Protocol (IP) addresses used in this document are not intended to be actual addresses. Any examples, command display output, and figures included in the document are shown for illustrative purposes only. Any use of actual IP addresses in illustrative content is unintentional and coincidental. Cisco Nexus 7000 Series Site Preparation Guide 2008-2011 Cisco Systems, Inc. All rights reserved.

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

CONTENTS
New and Changed Information Preface
vii vii vii vii viii viii v

Audience

Document Organization Document Conventions Related Documentation

Obtaining Documentation and Submitting a Service Request


1

CHA PTER

Overview

1-1

CHA PTER

Preparing the Site Temperature Humidity Altitude Corrosion


2-2 2-3

2-1 2-1

Information About the Site Requirements


2-2

Dust and Particles


2-3

2-3

Electromagnetic and Radio Frequency Interference Shock and Vibration Grounding


2-4 2-4 2-4

2-3

Power Source
3

CHA PTER

Technical Specifications

3-1 3-1

Environmental Specifications for Cisco Nexus 7000 Series Switches Physical Specifications for the Cisco Nexus 7000 Series Chassis Power Specifications for Cisco Nexus 7000 Series Switches Power Requirements for Switch Components 3-5 Power Supply Configuration Modes 3-6 Power Supply Cable Specifications
3-9 3-5 3-2

Chassis Clearances 3-15 Cisco Nexus 7009 Chassis Clearances Cisco Nexus 7010 Chassis Clearances

3-15 3-16

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

iii

Contents

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Cisco Nexus 7018 Chassis Clearances Facility Cooling Requirements Chassis Airflow
A
3-16 3-16 3-16

APPENDIX

Site Preparation and Maintenance Records Site Preparation Checklist Contact and Site Information
A-1 A-3 A-3

A-1

Chassis and Module Information


B

APPENDIX

Cabinet and Rack Requirements Cabinet and Rack Vendors

B-1 B-1

General Requirements for Cabinets and Racks


B-3

INDEX

Cisco Nexus 7000 Series Site Preparation Guide

iv

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

New and Changed Information


This chapter provides release-specific information for each new and changed feature in the Cisco Nexus 7000 Series Site Preparation Guide . The latest version of this document is available at the following Cisco website: http://www.cisco.com/en/US/docs/switches/datacenter/hw/nexus7000/site_prep/guide/nexus7k_sitepre p_book.html Table 1 summarizes the new and changed features for the Cisco Nexus 7000 Series Site Preparation Guide , and tells you where they are documented.
Table 1 New and Changed Features for Release 6.0(1)

Feature

Description

Changed in Release Where Documented 6.0(1) Chapter 1, Overview Chapter 3, Technical Specifications Chapter 1, Overview Chapter 3, Technical Specifications Chapter 3, Technical Specifications

48-port 1- and 10-Gigabit Introduced the F2 48-port 1- and 10-Gigabit Ethernet SFP+ I/O Ethernet SFP+ I/O module for use with Series module 2 fabric modules on the Cisco Nexus 7000 Series switches.

Series 2 fabric modules Introduced the Series 2 fabric module for the 6.0(1) for Cisco Nexus 7010 and Cisco Nexus 7010 and 7018 switches (the 7018 Cisco 7009 switch was introduced earlier with its own Series 2 fabric module). Cisco Nexus 7010 and 7018 chassis Modified the rear clearance from 30 inches (76 6.0(1) cm) to 26 inches (66 cm)

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

New and Changed Information

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Cisco Nexus 7000 Series Site Preparation Guide

vi

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Preface
This preface describes the audience, organization, and conventions of the Cisco Nexus 7000 Series Site Preparation Guide . It also provides information on how to obtain related documentation.

Audience
This guide is intended for anyone who plans the facilities, including space, floor weighting, power, cooling, cabling, delivery, and storage for the installation of the Cisco Nexus 7000 Series switches.

Document Organization
This document is organized into the following chapters: Chapter Chapter 1, Overview Chapter 2, Preparing the Site Chapter 3, Technical Specifications Chapter A, Site Preparation and Maintenance Records Chapter B, Cabinet and Rack Requirements Description Provides an overview of the Cisco Nexus 7000 Series and its switches. Describes the basic site requirements for installing the Cisco Nexus 7000 Series switches. Describes the technical specifications for the Cisco Nexus 7000 Series switches. Provides a site planning list to prepare your site for the Cisco Nexus 7000 Series switches. Describes the cabinet and rack requirements for the Cisco Nexus 7000 Series switches.

Document Conventions
Notes use the following conventions:
Note

Means reader take note . Notes contain helpful suggestions or references to material not covered in the publication.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

vii

Preface

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Caution

Means reader be careful . In this situation, you might do something that could result in equipment damage or loss of data.

Related Documentation
Cisco Nexus 7000 Series documentation includes the following documents:

Hardware Documents
Cisco Nexus 7000 Series Site Preparation Guide Cisco Nexus 7000 Series Hardware Installation and Reference Guide Cisco Nexus 7000 Series Regulatory Compliance and Safety Information Cisco Nexus 7000 Series Connectivity Management Processor Configuration Guide

Software Documents
The Cisco Nexus 7000 Series switches ship with the Cisco NX-OS software. You can find software documentation for the Cisco NX-OS software at the following URL: http://www.cisco.com/en/US/products/ps9402/tsd_products_support_series_home.html The Cisco Data Center Network Manager (DCNM) supports the Cisco Nexus 7000 Series. You can find documentation for DCNM at the following URL: http://www.cisco.com/en/US/products/ps9369/tsd_products_support_series_home.html

Obtaining Documentation and Submitting a Service Request


For information on obtaining documentation, submitting a service request, and gathering additional information, see the monthly Whats New in Cisco Product Documentation, which also lists all new and revised Cisco technical documentation, at: http://www.cisco.com/en/US/docs/general/whatsnew/whatsnew.html Subscribe to the Whats New in Cisco Product Documentation as a Really Simple Syndication (RSS) feed and set content to be delivered directly to your desktop using a reader application. The RSS feeds are a free service and Cisco currently supports RSS version 2.0.

Cisco Nexus 7000 Series Site Preparation Guide

viii

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

C H A P T E R

Overview
This chapter provides an overview of the Cisco Nexus 7000 Series switches, which support end-to-end data center connectivity, consolidating IP, storage, and interprocess communication (IPC) networks onto a single Ethernet fabric. The Cisco Nexus 7000 Series includes the following switches:

Cisco Nexus 7009 switchProvides nine slots that include two supervisor modules and up to seven I/O modules with 8.8 Terrabytes per second (Tbps) of forwarding capacity. You can access the supervisor, I/O module, and fabric modules from the front, and you can access the power supply and fan modules from the rear. This switch uses side-to-side airflow. Cisco Nexus 7010 switchProvides 10 slots that include two supervisor modules and up to eight I/O modules with 4.1 Tbps of forwarding capacity. You can access the supervisor and I/O modules from the front, and you can access the fabric modules, power supply, and fan modules from the rear. This switch uses front-to-back airflow Cisco Nexus 7018 switchProvides 18 slots that include two supervisor modules and up to 16 I/O modules with 7.8 Tbps of forwarding capacity. You can access the supervisor and I/O modules from the front, and you can access the fabric, power supply, and fan modules from the rear. This switch uses side-to-side airflow.

Both switches use the same supervisor modules, I/O modules, and power supply units (AC and DC models). The fan trays and fabric modules are unique to each type of chassis. To compare the features of these two switches, see Table 1-1.
Table 1-1 Cisco Nexus 7000 Series Switch Features

Feature Chassis Supervisor Modules

Cisco Nexus 7009 9-slot chassis

Cisco Nexus 7010 1 10-slot chassis

Cisco Nexus 7018 1 18-slot chassis

1 to 2 modules (N7K-SUP1) shipped in the chassis.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

1-1

Chapter 1

Overview

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table 1-1 Cisco Nexus 7000 Series Switch Features (continued)

Feature I/O Modules

Cisco Nexus 7009 1 to 7 modules shipped in the chassis.


Cisco Nexus 7010 1 1 to 8 modules shipped in the chassis.

Cisco Nexus 7018 1 1 to 16 modules shipped in the chassis.

48-port 10/100/1000 Ethernet (N7K-M148GT-11) 48-port 10/100/1000 Ethernet (N7K-M148GT-11L) 48-port 1-Gigabit Ethernet (N7K-M148GS-11) 48-port 1-Gigabit Ethernet XL (N7K-M148GS-11L) 48-port 1- and 10-Gigabit Ethernet (N7K-F248XP-25) 32-port 10-Gigabit Ethernet (N7K-M132XP-12) 32-port 10-Gigabit Ethernet XL (N7K-M132XP-12L) 32-port 1- and 10-Gigabit Ethernet (N7K-F132XP-15) 8-port 10-Gigabit Ethernet XL (N7K-M108X2-12L) 2 fan trays (N7K-C7010-FAN-S) shipped in the chassis. 2 fan trays (N7K-C7010-FAN-F) shipped in the chassis. 3 to 5 modules (N7K-C7010-FAB-1) shipped in the chassis. These modules deliver 230 Gbps per slot for up to 4.1 Tbps of forwarding capacity. 3 to 5 modules (N7K-C7010-FAB-2). These modules deliver 550 Gbps per slot for up to 8.8 Tbps of forwarding capacity. 2 to 3 power supply units shipped with the chassis but boxed separately. 2 fan trays (N7K-C7018-FAN) shipped in the chassis. 3 to 5 modules ((N7K-C7018-FAB-1) shipped in the chassis. These modules deliver 230 Gbps per slot for up to 7.8 Tbps of forwarding capacity. 3 to 5 modules (N7K-C7018-FAB-2). These modules deliver 550 Gbps per slot for up to 8.8 Tbps of forwarding capacity. 2 to 4 power supply units shipped with the chassis but boxed separately.

Fan Tray System Fan Tray Fabric Fan Tray Fabric-1 Modules

1 fan tray (N7K-C7009-FAN) shipped in chassis.

Fabric-2 Modules

3 to 5 modules (N7K-C7009-FAB-2) shipped in the chassis. These modules deliver 550 Gbps per slot for up to 8.8 Tbps of forwarding capacity. 1 or 2 power supply units shipped with the chassis but boxed separately.

Power Supplies

6-kW AC power supply unit (N7K-AC-6.0KW) 7.5-kW AC power supply unit (N7K-AC-7.5KW-INT and N7K-AC-7.5KW-US) 6-kW DC power supply unit (N7K-DC-6.0KW)

DC Power 1 or 2 used when the DC power source is more than 15 feet (4.6 m) away from the DC power supply units. Interface Unit
1. The quantity of supervisor, I/O, and fabric modules, and power supply units shipped with the chassis will vary depending on your order.

For information about preparing your site for the Nexus 7000 Series switches, see Chapter 2, Preparing the Site.

Cisco Nexus 7000 Series Site Preparation Guide

1-2

OL-23070-05

Chapter 1

Overview

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
For information about installing the Cisco Nexus 7000 Series switches, see the Cisco Nexus 7000 Series Hardware Installation and Reference Guide . For translations of the warnings in that guide, see the Cisco Nexus 7000 Series Regulatory Compliance and Safety Information document.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

1-3

Chapter 1

Overview

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Cisco Nexus 7000 Series Site Preparation Guide

1-4

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

C H A P T E R

Preparing the Site


This chapter describes the basic site requirements that you should be aware of as you prepare to install your Cisco Nexus 7000 Series switches. This chapter includes the following sections:

Information About the Site Requirements, page 2-1 Temperature, page 2-2 Humidity, page 2-2 Altitude, page 2-3 Dust and Particles, page 2-3 Corrosion, page 2-3 Electromagnetic and Radio Frequency Interference, page 2-3 Shock and Vibration, page 2-4 Grounding, page 2-4 Power Source, page 2-4

Information About the Site Requirements


Environmental factors can adversely affect the performance and life span of your switch. The Cisco Nexus 7000 Series switches require a dry, clean, well-ventilated, and air-conditioned environment. To ensure normal operation, you must maintain ambient airflow. If the airflow is blocked or restricted, or if the intake air is too warm, an overtemperature condition can occur and the environmental monitor on the switch will shut down to protect the switch components. In a 42-rack unit (RU) rack, you can mount up to three Cisco Nexus 7009 chassis or two Cisco Nexus 7010 chassis or one Cisco Nexus 7018 chassis. You must also allow enough room in front for loading the chassis using a mechanical lift and enough room in the rear for removing the switch components. When mounting the Cisco Nexus 7000 Series chassis in a rack with other equipment, ensure that the exhaust from the other equipment does not blow into the air intake vent of the Cisco Nexus 7000 Series chassis. If your site has hot and cold aisles, align the rack or cabinet air intake to a cold aisle and exhaust to a hot aisle.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

2-1

Chapter 2 Temperature

Preparing the Site

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Temperature
Temperature extremes can cause the Cisco Nexus 7000 Series switches to operate at reduced efficiency and cause a variety of problems, including premature aging, failure of chips, and failure of switches. In addition, extreme temperature fluctuations can cause chips to become loose in their sockets. The Cisco Nexus 7000 Series switches should operate in an environment that is not colder than 32F (0C) or hotter than 104F (40C). To control the switch temperature, you must make sure that the switch has adequate airflow, as follows:

The Cisco Nexus 7009 switch requires side-to-side airflow, which requires that you leave at least 11 inches (27.9 cm) free on both sides of the chassis (or 22 inches [55.8 cm] between two Cisco Nexus 7009 or 7018 switches]), and you must be sure that cables do not block the airflow from the lower right front of the chassis (for more information, see the Chassis Clearances section on page 3-15). The Cisco Nexus 7010 switch requires front-to-back airflow, which requires that you not block the front air intake or the rear exhaust areas (for more information, see the Chassis Clearances section on page 3-15). The Cisco Nexus 7018 switch requires side-to-side airflow, which requires that you leave at least 11 inches (27.9 cm) free on both sides of the chassis (or 22 inches [55.8 cm] between two Cisco Nexus 7009 or 7018 switches]), and you must be sure that cables do not block the airflow from the lower right front of the chassis (for more information, see the Chassis Clearances section on page 3-15).

To prevent overheating and to minimize the energy spent to cool the Cisco Nexus 7000 Series switch, do not place the chassis next to a heat source of any kind, including heating vents during cold weather. Adequate ventilation is particularly important if you are operating a Cisco Nexus 7000 Series switch at high altitudes. Make sure that all slots and openings on the chassis remain unobstructed, especially the fan vents. Clean the installation site at regular intervals to avoid buildup of dust and debris, which can cause a switch to overheat. If the Cisco Nexus 7000 Series switch is exposed to abnormally cold temperatures, allow a 2-hour warm-up period to bring it up to a normal operating temperature before you turn the switch on.

Caution

If you do not allow a 2-hour warm-up period when temperatures are abnormally cold, you can damage the internal components.

Note

The Cisco Nexus 7000 Series switches are equipped with internal air temperature sensors that trigger a minor alarm at 104F (40C) and a major alarm at 131F (55C).

Humidity
High humidity can cause moisture to seep into the Cisco Nexus 7000 Series switches. Moisture can cause corrosion of internal components and degradation of properties such as electrical resistance, thermal conductivity, physical strength, and size. The Cisco Nexus 7000 Series is rated to operate at 8 to 80 percent relative humidity, with a humidity gradation of 10 percent per hour.

Cisco Nexus 7000 Series Site Preparation Guide

2-2

OL-23070-05

Chapter 2

Preparing the Site Altitude

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
The Cisco Nexus 7000 Series switches can withstand from 5 to 90 percent relative humidity. Buildings in which the climate is controlled by air-conditioning in the warmer months and by heat during the colder months usually maintain an acceptable level of humidity for the switch equipment. However, if a Cisco Nexus 7000 Series switch is located in an unusually humid location, you should use a dehumidifier to maintain the humidity within an acceptable range.

Altitude
If you operate a Cisco Nexus 7000 Series switch at a high altitude (low pressure), the efficiency of forced and convection cooling is reduced and can result in electrical problems that are related to arcing and corona effects. This condition can also cause sealed components with internal pressure, such as electrolytic capacitors, to fail or to perform at a reduced efficiency. The Cisco Nexus 7000 Series is rated to operate at altitudes from 500 to 13,123 feet (152 to 4,000 meters). You can store the switch at altitudes of 1,000 to 30,000 feet (305 to 9,144 meters).

Dust and Particles


Exhaust fans cool power supplies and system fan trays cool switches by drawing in air and exhausting air out through various openings in the chassis. However, fans also ingest dust and other particles, causing contaminant buildup in the switch and increased internal chassis temperature. A clean operating environment can greatly reduce the negative effects of dust and other particles, which act as insulators and interfere with the mechanical components in the switch.

Note

In the Cisco Nexus 7010 switch, you can install an optional air filter in a nonclean environment. In addition to regular cleaning, follow these precautions to avoid contamination of your equipment:

Do not permit smoking near the Cisco Nexus 7000 Series switch. Do not permit food or drink near the Cisco Nexus 7000 Series switch.

Corrosion
The corrosion of switch connectors is a gradual process that can eventually lead to intermittent failures of electrical circuits. The oil from your fingers or prolonged exposure to high temperature or humidity can corrode the gold-plated edge connectors and pin connectors on various components in the Cisco Nexus 7000 Series switches. To prevent corrosion, avoid touching contacts on modules and protect the switch from extreme temperatures and moist, salty environments.

Electromagnetic and Radio Frequency Interference


Electromagnetic interference (EMI) and radio frequency interference (RFI) from the Cisco Nexus 7000 Series switch can adversely affect switches such as radio and television (TV) receivers operating near the switch. Radio frequencies that emanate from the Cisco Nexus 7000 Series switch can also interfere with cordless and low-power telephones. Conversely, RFI from high-power telephones can cause spurious characters to appear on the switch monitor.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

2-3

Chapter 2 Shock and Vibration

Preparing the Site

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
RFI is defined as any EMI with a frequency above 10 kHz. This type of interference can travel from the switch to other devices through the power cable and power source or through the air like transmitted radio waves. The Federal Communications Commission (FCC) publishes specific regulations to limit the amount of EMI and RFI that can be emitted by computing equipment. Each Cisco Nexus 7000 Series switch meets these FCC regulations. To reduce the possibility of EMI and RFI, follow these guidelines:

Cover all open expansion slots with a metal filler. Always use shielded cables with metal connector shells for attaching peripherals to the switch.

When wires are run for any significant distance in an electromagnetic field, interference can occur between the field and the signals on the wires and cause the following implications:

Bad wiring can result in radio interference emanating from the plant wiring. Strong EMI, especially when it is caused by lightning or radio transmitters, can destroy the signal drivers and receivers in the chassis and even create an electrical hazard by conducting power surges through lines into equipment.

Note

To predict and prevent strong EMI, you might need to consult experts in radio frequency interference (RFI). The wiring is unlikely to emit radio interference if you use twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. If the wires exceed the recommended distances, or if wires pass between buildings, give special consideration to the effect of a lightning strike in your vicinity. The electromagnetic pulse caused by lightning or other high-energy phenomena can easily couple enough energy into unshielded conductors to destroy electronic switches. You may want to consult experts in electrical surge suppression and shielding if you had similar problems in the past.

Shock and Vibration


The Cisco Nexus 7000 Series switch has been shock- and vibration-tested for operating ranges, handling, and earthquake standards to Network Equipment Building Standards (NEBS) Zone 4 per GR-63-Core.

Grounding
The Cisco Nexus 7000 Series switch is sensitive to variations in voltage supplied by the AC-power source. Overvoltage, undervoltage, and transients (or spikes) can erase data from the memory or cause components to fail. To protect against these types of problems, you should always properly ground power cables.

Power Source
You should use dedicated power circuits (rather than sharing circuits with other heavy electrical equipment). For input-source redundancy, we recommend that you use two dedicated power sources, each of which powers half of each power supply unit in the switch chassis. For 6-kW AC power supply

Cisco Nexus 7000 Series Site Preparation Guide

2-4

OL-23070-05

Chapter 2

Preparing the Site Power Source

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
units (N7K-AC-6.0KW), the circuits must be rated for 20 A, 110 VAC or 220 VAC. For 7.5-kW power supply units (N7K-AC-7.5KW-INT and N7K-AC-7.5KW-US), the circuits must be rated for 30 A, 220 VAC. For 6-kW DC power supply units (N7K-DC-6.0KW), the circuits must be rated for 40 A , 48V-48V. The receptacles for AC circuits must be within 12 feet (3.6 m) of each power supply unit when it is installed in the switch chassis. The DC power supply connection must be within 15 feet (4.6 m) or you must install a DC Power Interface Unit (PIU) within that distance to connect to a distant power supply connection. If you are installing a DC PIU, you should install it in the same rack that holds the DC power supply units. Before you connect the power supply units to the AC or DC power, you must install the power supplies in the Cisco Nexus 7000 Series chassis.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

2-5

Chapter 2 Power Source

Preparing the Site

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Cisco Nexus 7000 Series Site Preparation Guide

2-6

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

C H A P T E R

Technical Specifications
This chapter describes the technical specifications for the Cisco Nexus 7000 Series switches and includes these sections:

Environmental Specifications for Cisco Nexus 7000 Series Switches, page 3-1 Physical Specifications for the Cisco Nexus 7000 Series Chassis, page 3-2 Power Specifications for Cisco Nexus 7000 Series Switches, page 3-5 Power Supply Cable Specifications, page 3-9 Chassis Clearances, page 3-15 Facility Cooling Requirements, page 3-16 Chassis Airflow, page 3-16

Environmental Specifications for Cisco Nexus 7000 Series Switches


Table 3-1 lists the environmental specifications for the Cisco Nexus 7000 Series switches.
Table 3-1 Environmental Specifications for the Cisco Nexus 7000 Series Switches

Description Temperature Ambient operating Ambient nonoperating Relative humidity Ambient (noncondensing) operating Ambient (noncondensing) nonoperating and storage Altitude Operating Storage

Cisco Nexus 7009

Cisco Nexus 7010

Cisco Nexus 7018

32 to 104F (0 to 40C) 40 to 158F (40 to 70C) 5 to 90% (45 to 50% recommended) 5 to 95% 500 to 13,000 feet (152 to 4,000 meters) 1,000 to 30,000 feet (305 to 9,144 meters)

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-1

Chapter 3 Physical Specifications for the Cisco Nexus 7000 Series Chassis

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table 3-1 Environmental Specifications for the Cisco Nexus 7000 Series Switches (continued)

Description Noise Sound pressure levels Without air filter With air filter Sound power levels Without air filter With air filter

Cisco Nexus 7009 63.6 dBA 72.5 dBA

Cisco Nexus 7010 67.2 dBA 70.2 dBA 78.9 dBA 81.7 dBA

Cisco Nexus 7018 65.0 dBA 74.2 dBA

Physical Specifications for the Cisco Nexus 7000 Series Chassis


Table 3-2 lists the physical specifications for the Cisco Nexus 7000 Series chassis.
Table 3-2 Dimensions for the Cisco Nexus 7000 Series Chassis

Chassis

Width

Depth1

Height2

Cisco Nexus 7009 17.3 inches (43.9 cm) 24.0 inches (61.0 cm) 24.5 inches (62.2 cm) (14 RU) Cisco Nexus 7010 17.3 inches (43.9 cm) 32.0 inches (81.3 cm) 36.75 inches (93.3 cm) (21.0 RU) Cisco Nexus 7018 17.3 inches (43.9 cm) 32.0 inches (81.3 cm) 43.75 inches (111.1 cm) (25.0 RU)
1. This measurement is from the mounting bracket to the rear of the chassis (including the module handles at the rear). For the cable management system on either chassis, add 6.0 inches (15.4 cm) in front of the mounting brackets. The six inches in front of the mounting brackets includes the optional air filter and the optional front door and frame assemblies on the Cisco Nexus 7010 chassis and it includes the optional front door and air intake frame on the Cisco Nexus 7009 and 7018 chassis. 2. The height includes the bottom-support bracket for the Cisco Nexus 7010 and 7018. For the Cisco Nexus 7009, you

must add 0.75 inches (1.9 cm) for the bottom-support bracket, which can be removed after installation for front-mounted installations.

The weights, quantities, and mean time between failures (MTBF) hours are listed in Table 3-3 for the Cisco Nexus 7009 switch, Table 3-4 for the Cisco Nexus 7010 switch, and Table 3-5 for the Cisco Nexus 7018 switch. The weights in these tables do not include the rack or cabinet that holds the chassis or the interface and power cables. For those weights, see the documentation provided by the manufacturers of those components.
Table 3-3 Weights, Quantities, and MTBF for the Cisco Nexus 7009 Switch Components

Component Chassis Supervisor module (N7K-SUP1)

Weight per Unit 100 lb (45.0 kg) 10 lb (4.5 kg)

Quantity 1 2

MTBF1 (Hours) per Unit 260,000 99,491

Cisco Nexus 7000 Series Site Preparation Guide

3-2

OL-23070-05

Chapter 3

Technical Specifications Physical Specifications for the Cisco Nexus 7000 Series Chassis

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table 3-3 Weights, Quantities, and MTBF for the Cisco Nexus 7009 Switch Components (continued)

Component 48-port 10/100/1000 Ethernet I/O module (N7K-M148GT-11) 48-port 10/100/1000 Ethernet I/O module (N7K-M148GT-11L) 48-port 1-Gigabit Ethernet I/O module (N7K-M148GS-11) 48-port 1-Gigabit Ethernet I/O module with XL option (N7K-M148GS-11L) 48-port 1- and 10-Gigabit Ethernet I/O module (N7K-F248XP-25) 32-port 10-Gigabit Ethernet I/O module (N7K-M132XP-12) 32-port 10-Gigabit Ethernet I/O module with XL option (N7K-M132XP-12L) 32-port 1- and 10-Gigabit Ethernet I/O module (N7K-F132XP-15) 8-port 10-Gigabit Ethernet I/O module with XL option (N7K-M108X2-12L) Fabric-2 module (N7K-C7009-FAB-2) Fan tray (N7K-C7009-FAN) 6-kW AC power supply unit (N7K-AC-6.0KW) 6-kW DC power supply unit (N7K-DC-6.0KW) DC Power Interface Unit Door and air frame (optional)
1. The predicted mean time between failure (MTBF) is based on the Bellcore Methodology.

Weight per Unit 14 lb (6.4 kg) 14 lb (6.4 kg) 15.5 lb (7.0 kg) 15.5 lb (7.0 kg) 14.0 lb (6.4 kg) 17.0 lb (7.7 kg) 17.0 lb (7.7 kg) 14.0 lb (6.4 kg) 14.0 lb (6.4 kg) 5 lb (2.27 kg) 18 lb (8.2 kg) 21 lb (9.5 kg) 5 lb (2.3 kg)

Quantity

MTBF1 (Hours) per Unit

1 to 7 (can 75,116 mix I/O 73,974 module 75,064 types) 73,228 83,477 50,081 44,253 90,994 52,107 3 to 5 600,000 433,812

25.0 lb (11.3 kg) 1

7.5-kW AC power supply unit (N7K-AC-7.5KW-INT and N7K-AC-7.5KW-US) 26 lb (11.8 kg)

1 or 2 (can 341,536 mix power 204,053 supply 200,000 types) 0 to 2 0 or 1

Table 3-4

Weights, Quantities, and MTBF for the Cisco Nexus 7010 Switch Components

Component Chassis Supervisor module (N7K-SUP1) 48-port 10/100/1000 Ethernet I/O module (N7K-M148GT-11) 48-port 10/100/1000 Ethernet I/O module (N7K-M148GT-11L) 48-port 1-Gigabit Ethernet I/O module (N7K-M148GS-11) 48-port 1-Gigabit Ethernet I/O module with XL option (N7K-M148GS-11L) 48-port 1- and 10-Gigabit Ethernet I/O module (N7K-F248XP-25) 32-port 10-Gigabit Ethernet I/O module (N7K-M132XP-12) 32-port 10-Gigabit Ethernet I/O module with XL option (N7K-M132XP-12L) 32-port 1- and 10-Gigabit Ethernet I/O module (N7K-F132XP-15) 8-port 10-Gigabit Ethernet I/O module with XL option (N7K-M108X2-12L)

Weight per Unit 200 lb (90.9 kg) 10 lb (4.5 kg) 14 lb (6.4 kg) 14 lb (6.4 kg) 15.5 lb (7.0 kg) 15.5 lb (7.0 kg) 14.0 lb (6.4 kg) 17.0 lb (7.7 kg) 17.0 lb (7.7 kg) 14.0 lb (6.4 kg) 14.0 lb (6.4 kg)

Quantity 1 2

MTBF1 (Hours) per Unit 264,649 99,491

1 to 8 (can 75,116 mix I/O 73,974 module 75,064 types) 73,228 83,477 50,081 44,253 90,994 52,107

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-3

Chapter 3 Physical Specifications for the Cisco Nexus 7000 Series Chassis

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table 3-4 Weights, Quantities, and MTBF for the Cisco Nexus 7010 Switch Components (continued)

Component Fabric-1 module (N7K-C7010-FAB-1) Fabric-2 module (N7K-C7010-FAB-2) System fan tray (N7K-C7010-FAN-S) Fabric fan tray (N7K-C7010-FAN-F) 6-kW AC power supply unit (N7K-AC-6.0KW) 6-kW DC power supply unit (N7K-DC-6.0KW) DC Power Interface Unit Mid-frame doors and frame (optional)
1. The predicted mean time between failure (MTBF) is based on the Bellcore Methodology.

Weight per Unit 4 lb (1.8 kg) 4 lb (1.8 kg) 20 lb (9.1 kg) 5 lb (2.3 kg) 18 lb (8.2 kg) 21 lb (9.5 kg) 5 lb (2.3 kg)

Quantity Up to 5 2 2

MTBF1 (Hours) per Unit 651,072 450,000 433,812 1,677,631

7.5-kW AC power supply unit (N7K-AC-7.5KW-INT and N7K-AC-7.5KW-US) 26 lb (11.8 kg)

2 to 3 (can 341,536 mix power 204,053 supply 200,000 types) 0 to 2 0 or 1

Table 3-5

Weights, Quantities, and MTBF for the Cisco Nexus 7018 Switch Components

Component Chassis Supervisor module (N7K-SUP1) 48-port 10/100/1000 Ethernet I/O module (N7K-M148GT-11) 48-port 10/100/1000 Ethernet I/O module (N7K-M148GT-11L) 48-port 1-Gigabit Ethernet I/O module (N7K-M148GS-11) 48-port 1-Gigabit Ethernet I/O module with XL option (N7K-M148GS-11L) 48-port 1- and 10-Gigabit Ethernet I/O module (N7K-F248XP-25) 32-port 10-Gigabit Ethernet I/O module (N7K-M132XP-12) 32-port 10-Gigabit Ethernet I/O module with XL option (N7K-M132XP-12L) 32-port 1- and 10-Gigabit Ethernet I/O module (N7K-F132XP-15) 8-port 10-Gigabit Ethernet I/O module with XL option (N7K-M108X2-12L) Fabric-1 module (N7K-C7018-FAB-1) Fabric-2 module (N7K-C7018-FAB-2) Fan tray (N7K-C7018-FAN) 6-kW AC power supply unit (N7K-AC-6.0KW) 6-kW DC power supply unit (N7K-DC-6.0KW) DC Power Interface Unit Front door (optional)

Weight per Unit 187 lb (85.0 kg) 10 lb (4.5 kg) 14 lb (6.4 kg) 14 lb (6.4 kg) 15.5 lb (7.0 kg) 15.5 lb (7.0 kg) 14.0 lb (6.4 kg) 17.0 lb (7.7 kg) 17.0 lb (7.7 kg) 14.0 lb (6.4 kg) 14 lb (6.4 kg) 7.5 lb (3.4 kg) 7.5 lb (3.4 kg)

Quantity 1 2 1 to 16 (can mix I/O module types)

MTBF1 (Hours) per Unit 206,038 99,491 75,116 73,974 75,064 73,228 83,477 50,081 44,253 90,994 52,107

Up to 5

423,846 450,000 276,352

25.8 lb (11.7 kg) 2 18 lb (8.2 kg) 21 lb (9.5 kg) 5 lb (2.3 kg) 25 lb (11.3 kg)

7.5-kW AC power supply unit (N7K-AC-7.5KW-INT and (N7K-AC-7.5KW-US) 26 lb (11.8 kg)

2 to 4 (can 341,536 mix power 204,053 supply 200,000 types) 0 to 2 0 or 1

Cisco Nexus 7000 Series Site Preparation Guide

3-4

OL-23070-05

Chapter 3

Technical Specifications Power Specifications for Cisco Nexus 7000 Series Switches

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
1. The predicted mean time between failure (MTBF) is based on the Bellcore Methodology.

Power Specifications for Cisco Nexus 7000 Series Switches


The number of power supplies that a Cisco Nexus 7000 Series switch requires depends on the quantities and types of modules that you include in the switch chassis, the type of power supply units that you are using, and the power redundancy mode that you are using. The following topics explain how to calculate the switch power requirements and the amount of power available for each type of power supply configuration mode:

Power Requirements for Switch Components, page 3-5 Power Supply Configuration Modes, page 3-6

Power Requirements for Switch Components


To determine the power requirements of the Cisco Nexus 7000 Series switches, add the power requirements of each of its components. For each component, multiply the number of its modules by its maximum or typical power requirement. To find the quantities and power requirements for each Cisco Nexus 7000 Series switch, see Table 3-6 for the Cisco Nexus 7009 switch, see Table 3-7 for the Cisco Nexus 7010 switch, and see Table 3-8 for the Cisco Nexus 7018 switch.
Table 3-6 Power Requirements for the Cisco Nexus 7009 Switch

Component Supervisor module 48-port 10/100/1000 Ethernet I/O module 48-port 10/100/1000 Ethernet I/O module with XL option 48-port 1-Gigabit Ethernet I/O module 48-port 1-Gigabit Ethernet I/O module with XL option 48-port 1- and 10-Gigabit Ethernet I/O module 32-port 10-Gigabit Ethernet I/O module 32-port 10-Gigabit Ethernet I/O module with XL option 32-port 1- and 10-Gigabit Ethernet I/O module 8-port 10-Gigabit Ethernet I/O module with XL option Fabric-2 module All fan trays (total)

Quantity 2 1 to 7

Maximum 210 W 400 W 400 W 400 W 400 W 450 W 750 W 750 W 385 W 650 W

Typical 190 W 358 W 358 W 358 W 358 W 400 W 611 W 611 W 283 W 520 W 55 W 190 W

3 to 5

70 W 650 W

Table 3-7

Power Requirements for the Cisco Nexus 7010 Switch

Component Supervisor module

Quantity 2

Maximum 210 W

Typical 190 W

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-5

Chapter 3 Power Specifications for Cisco Nexus 7000 Series Switches

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table 3-7 Power Requirements for the Cisco Nexus 7010 Switch (continued)

Component 48-port 10/100/1000 Ethernet I/O module 48-port 10/100/1000 Ethernet I/O module with XL option 48-port 1-Gigabit Ethernet I/O module 48-port 1-Gigabit Ethernet I/O module with XL option 48-port 1- and 10-Gigabit Ethernet I/O module 32-port 10-Gigabit Ethernet I/O module 32-port 10-Gigabit Ethernet I/O module with XL option 32-port 1- and 10-Gigabit Ethernet I/O module 8-port 10-Gigabit Ethernet I/O module with XL option Fabric-1 module Fabric-2 module All fan trays (total)

Quantity 1 to 8

Maximum 400 W 400 W 400 W 400 W 450 W 750 W 750 W 385 W 650 W

Typical 358 W 358 W 358 W 358 W 400 W 611 W 611 W 283 W 520 W 55 W 60W 300 W

3 to 5

60 W 80 W 2184 W

Table 3-8

Power Requirements for the Cisco Nexus 7018 Switch

Component Supervisor module 48-port 10/100/1000 Ethernet I/O module 48-port 10/100/1000 Ethernet I/O module with XL option 48-port 1-Gigabit Ethernet I/O module 48-port 1-Gigabit Ethernet I/O module with XL option 48-port 1- and 10-Gigabit Ethernet I/O module 32-port 10-Gigabit Ethernet I/O module 32-port 10-Gigabit Ethernet I/O module with XL option 32-port 1- and 10-Gigabit Ethernet I/O module 8-port 10-Gigabit Ethernet I/O module with XL option Fabric-1 module Fabric-2 module All fan trays (total)

Quantity 2 1 to 16

Maximum 210 W 400 W 400 W 400 W 400 W 450 W 750 W 750 W 385 W 650 W

Typical 190 W 358 W 358 W 358 W 358 W 400 W 611 W 611 W 283 W 520 W 90 W 110 W 569 W

3 to 5

100 W 150 W 1433 W

Power Supply Configuration Modes


You can configure one of the following power modes to either use the combined power provided by the installed power supply units or to provide power redundancy when there is a power loss: Combined modeProvides the maximum amount of available power by utilizing the combined power output from all installed power supply units for switch operations. This mode does not provide redundancy.

Cisco Nexus 7000 Series Site Preparation Guide

3-6

OL-23070-05

Chapter 3

Technical Specifications Power Specifications for Cisco Nexus 7000 Series Switches

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Power-supply redundancy modeAllows you to replace a power supply during switch operations. All power supplies are active. The available power is calculated as the least amount of power available from all but one of the power supply units (N+1). The reserve power is the amount of power output by the power supply unit that can output the most power. For example, if three power supply units output 3 kW, 6 kW, and 6 kW, the available power is 9 kW (3 kW + 6 kW) and the reserve power is 6 kW. Input source redundancy modeTakes power from two electrical grids so that if one grid goes down, the other grid can provide the power needed by the switch. Each grid powers half of each power supply unit (grid A is connected to the Input 1 receptacle on each power supply unit and grid B is connected to the Input 2 receptacle on each power supply unit). The available power is the amount of power output by the portions of the power supply units that are connected to the same grid. For example, if three power supply units are connected to a 110-V grid and a 220-V grid, each power supply outputs 1.2 kW for the 110-V grid and 3.0 kW for the 220-V grid. The available power would be 3.6 kW (1.2 kW + 1.2 kW + 1.2 kW) and the reserve power would be 9.0 kW (3.0 kW + 3.0 kW + 3.0 kW). Full redundancy modeProvides both power-supply redundancy and input-source redundancy. This mode allows you to replace a power supply unit without interrupting switch operations or continue powering the switch if one of two grids goes down. The available power is the lesser amount of output power for power supply redundancy or input source redundancy.

The amount of power available for use with your Cisco Nexus 7000 Series switch depends on the number of power supply units, input voltage used, and the power mode used. To determine the amount of available power for 6-kW AC power supply units, see Table 3-9. To determine the amount of power available for 7.5-kW AC power supply units, see Table 3-10. To determine the amount of power available for the 6-kW DC power supply units, see Table 3-11.

Table 3-9

Power Availability for 6-kW AC Power Supply Units

Power Inputs Dual inputs per power supply unit 220-V and 220-V inputs 1 power supply unit 2 power supply units 3 power supply units 4 power supply units 220-V and 110-V inputs 1 power supply unit 2 power supply units 3 power supply units 4 power supply units 110-V and 110-V inputs 1 power supply unit 2 power supply units 3 power supply units
1 1

Combined Mode

Power Supply Redundancy Mode

Input Source Full Redundancy Redundancy Mode Mode

6000 W 12,000 W 18,000 W 24,000 W 4200 W 8400 W 12,600 W 16,800 W 2400 W 4800 W 7200 W

6000 W 12,000 W 18,000 W 4200 W 8400 W 12,600 W 2400 W 4800 W

3000 W 6000 W 9000 W 12,000 W 1200 W 2400 W 3600 W 4800 S 1200 W 2400 W 3600 W

6000 W 9000 W 12,000 W 2400 W 3600 W 4800 W 2400 W 3600 W

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-7

Chapter 3 Power Specifications for Cisco Nexus 7000 Series Switches

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table 3-9 Power Availability for 6-kW AC Power Supply Units (continued)

Power Inputs 4 power supply units1 Single input per power supply unit 220-V input 1 power supply unit 2 power supply units 3 power supply units 4 power supply units 110-V input 1 power supply unit 2 power supply units 3 power supply units 4 power supply units
1 1

Combined Mode 9600 W

Power Supply Redundancy Mode 7200 W

Input Source Full Redundancy Redundancy Mode Mode 4800 W 4800 W

3000 W 6000 W 9000 W 12,000 W 1200 W 2400 W 3600 W 4800 W

3000 W 6000 W 9000 W 1200 W 2400 W 3600 W

1. A fourth power supply unit can be added to only the Cisco Nexus 7018 switch. The Cisco Nexus 7010 holds up to three power supply units.

Table 3-10

Power Availability for 7.5-kW AC Power Supply Units

Power Inputs Dual inputs per power supply unit 220-V and 220-V inputs 1 power supply unit 2 power supply units 3 power supply units 4 power supply units 220-V input 1 power supply unit 2 power supply units 3 power supply units 4 power supply units
1 1

Power Supply Input Source Full Combined Redundancy Redundancy Redundancy Mode Mode Mode Mode

7500 W

3750 W 7500 W 11,250 W 15,000 W

7500 W 11,250 W 15,000 W

15,000 W 7500 W 22,500 W 15,000 W 30,000 W 22,500 W

Single input per power supply unit 3750 W 7500 W 3750 W

11,250 W 7500 W 15,000 W 11,250 W

1. A fourth power supply unit can be added to only the Cisco Nexus 7018 switch. The Cisco Nexus 7010 holds up to three power supply units.

Cisco Nexus 7000 Series Site Preparation Guide

3-8

OL-23070-05

Chapter 3

Technical Specifications Power Supply Cable Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Table 3-11

Power Availability for 6.0-kW DC Power Supply Units

Power Inputs Dual inputs per power supply unit 1 power supply unit 2 power supply unit 3 power supply unit 4 power supply unit 1 Single input per power supply unit 1 power supply unit 2 power supply unit 3 power supply unit 4 power supply unit 1

Combined Mode 6,000 W 12,000 W 18,000 W 24,000 W

Power Supply Input Source Redundancy Redundancy Mode Mode 6,000 W 12,000 W 18,000 W 3,000 W 6,000 W 9,000 W 12,000 W

Full Redundancy Mode 6,000 W 9,000 W 12,000 W

3,000 W 6,000 W 9,000 W 12,000 W

3,000 W 6,000 W 9,000 W

9,000 W 12,000 W

6,000 W 9,000 W

1. A fourth power supply unit can be added to only the Cisco Nexus 7018 switch. The Cisco Nexus 7010 holds up to three power supply units.

Power Supply Cable Specifications


For specifications of the AC power cables that you can connect to a 6-kW AC power supply unit, see Table 3-12. For specifications of the AC power cord connectors attached to the 7.5-kW AC power supply units, see Table 3-13. For specifications of the DC power cord used with the 6-kW DC power supply units, see Table 3-14.
Table 3-12 6-kW AC Power Supply Power Cords

Locale Australia and New Zealand Peoples Republic of China Continental Europe International Israel

Power Cord Part Number CAB-AC-16A-AUS CAB-AC-16A-CH CAB-AC-2500W-EU CAB-AC-2500W-INT CAB-AC-2500W-ISRL

Power Cord Reference Cord Set Rating Illustration 16A, 250 VAC 16A, 250 VAC 16A, 250 VAC 16A, 250 VAC 16A, 250 VAC 16A, 250 VAC 16A, 250 VAC 16A, 250 VAC Figure 3-1 Figure 3-2 Figure 3-3 Figure 3-4 Figure 3-5 Figure 3-6 Figure 3-7 Figure 3-8

Japan and North America (nonlocking) 200 CAB-AC-2500W-US1 to 240 VAC operation Japan and North America (locking) 200 to 240 VAC operation Japan and North America 100 to 120 VAC operation CAB-AC-C6K-TWLK CAB-7513AC

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-9

Chapter 3 Power Supply Cable Specifications

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table 3-12 6-kW AC Power Supply Power Cords (continued)

Locale North America 125 VAC operation Power distribution unit (PDU) Switzerland
Figure 3-1

Power Cord Part Number CAB-L520P CAB-C19-CBN CAB-ACS-16

Power Cord Reference Cord Set Rating Illustration 16A, 250 VAC 16A, 250 VAC 16A, 250 VAC Figure 3-9 Figure 3-10 Figure 3-11

CAB-AC-16A-AUS Power Cord and Connectors for the 6-kW Power Supply

Plug: AU20S3

Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Connector: IEC 60320 C19
140586

Figure 3-2

CAB-AC-16A-CH Power Cord and Connectors for the 6-kW Power Supply

Plug: GB16C

Cordset rating: 16A, 250V Length: 14 ft 0 in. (4.26 m) Connector: IEC 60320-1 C19

Cisco Nexus 7000 Series Site Preparation Guide

3-10

126792

OL-23070-05

Chapter 3

Technical Specifications Power Supply Cable Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-3 CAB-AC-2500W-EU Power Cord and Connectors for the 6-kW Power Supply

Plug: CEE 7/7

Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Connector: IEC 60320 C19
113360

Figure 3-4

CAB-AC-2500W-INT Power Cord and Connectors for the 6-kW Power Supply

Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Plug: IEC 309 Connector: IEC 60320 C19

Figure 3-5

CAB-AC-2500W-ISRL Power Cord and Connectors for the 6-kW Power Supply

Plug: SI16S3

Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Connector: IEC 60320 C19

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

130113

113361

3-11

Chapter 3 Power Supply Cable Specifications

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-6 CAB-AC-2500W-US1 Power Cord and Connectors for the 6-kW Power Supply

Plug: NEMA 6-20

Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Connector: IEC 60320 C19

Figure 3-7

CAB-AC-C6K-TWLK Power Cord and Connectors for the 6-kW Power Supply

Plug: NEMA L6-20

Cordset rating: 16 A, 250 V Length: 14 ft 0 in. (4.26 m) Connector: IEC 60320 C19
113363

Figure 3-8

CAB-7513AC Power Cord and Connectors for the 6-kW Power Supply

Cisco Nexus 7000 Series Site Preparation Guide

3-12

113362

OL-23070-05

Chapter 3

Technical Specifications Power Supply Cable Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-9 CAB-L520P-C19-US Power Cord and Connectors for the 6-kW Power Supply

Figure 3-10

CAB-C19-CBN Power Cord and Connectors for the 6-kW Power Supply

Figure 3-11

CAB-ACS-16 Power Cord and Connectors for the 6-kW Power Supply

Cordset rating: 16 A, 250 V Length: 8 ft 2 in. (2.5 m) Plug: SEV 5934-2 Type 23 Connector: IEC 60320 C19
192844

Table 3-13

7.5-kW AC Power Supply Power Cords

Locale Japan and North America International

Cord rating 30 A, 250 VAC 32 A, 250 VAC

Power cord reference illustration Figure 3-12 Figure 3-13

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

140587

Connector: IEC 60320 C20

Cordset rating: 16 A, 250 V Length: 9 ft 0 in. (2.7 m)

Connector: IEC 60320 C19

3-13

Chapter 3 Power Supply Cable Specifications

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-12 NEMA L6-30 Power Connector for the 7.5-kW Power Supply

Cordset rating: 30 A, 250 V Length: 12 ft 0 in. (3.65 m) Plug: NEMA L6-30

Figure 3-13

IEC 603090 Power Connector for the 7.5-kW Power Supply

113366

Hardwired to power supply

Cordset rating: 32 A, 250 V Length: 12 ft 0 in. (3.65 m)

Hardwired to power supply

Plug: IEC 60309

Table 3-14

6-kW DC Power Supply Power Cord

Locale All

Power Cord Part Number N7K-DC-CAB

Cord Rating 40 A, 48V-48V

Cisco Nexus 7000 Series Site Preparation Guide

3-14

113365

OL-23070-05

Chapter 3

Technical Specifications Chassis Clearances

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-14 Power Connector for the 6.0-kW DC Power Supply Unit

Chassis Clearances
You must provide adequate clearance for installing the switch, replacing switch modules, routing cables, and allowing airflow to and from the switch. This section includes the following topics:

Cisco Nexus 7009 Chassis Clearances, page 3-15 Cisco Nexus 7010 Chassis Clearances, page 3-16 Cisco Nexus 7018 Chassis Clearances, page 3-16

Cisco Nexus 7009 Chassis Clearances


The Cisco Nexus 7009 chassis requires the following clearances:

If you are using a four-post rack or cabinet, you must have 7 inches (17.8 cm) between the chassis and the front and back of a four-post rack or interior of the cabinet (required for cabling). This requirement does not apply to a two-post rack.

Note

If the chassis is installed with the alternative center-mount bottom-support brackets, the chassis will protrude 6 inches (15.25 cm) beyond the mounting rails, so you must plan for 13 inches (33.0 cm) clearance in front of the mounting rails to get the required 7 inches (17.8 cm) clearance in front of the chassis.

37 inches (94.0 cm) between the front of the chassis and the next rack, cabinet, or wall in the cold aisle (required for installing or replacing the chassis or its modules)

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-15

Chapter 3 Facility Cooling Requirements

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

26 inches (66.0 cm) between the rear of the chassis and the next rack, cabinet, or wall in the hot aisle (required for replacing the fan tray) 11 inches (27.9 cm) between the side of the chassis and the interior of the cabinet, or the clearance area for the next rack or cabinet (required for side-to-side airflow)

Cisco Nexus 7010 Chassis Clearances


The Cisco Nexus 7010 chassis requires the following clearances:

7 inches (17.8 cm) between the chassis and the front and back of the rack or interior of the cabinet (required for cabling) 38 inches (96.5 cm) open passageway between the front of the rack or cabinet and the next rack, cabinet, or wall in the cold aisle (required for installing or replacing the chassis or its modules) 30 inches (76.2 cm) between the rear of the rack or cabinet and the next rack, cabinet, or wall in the hot aisle (required for replacing the fan tray)

Cisco Nexus 7018 Chassis Clearances


The Cisco Nexus 7018 chassis requires the following clearances:

7 inches (17.8 cm) between the chassis and the front and back of the rack or interior of the cabinet (required for cabling) 38 inches (96.5 cm) open passageway between the front of the rack or cabinet and the next rack, cabinet, or wall in the cold aisle (required for installing or replacing the chassis or its modules) 30 inches (76.2 cm) between the rear of the rack or cabinet and the next rack, cabinet, or wall in the hot aisle (required for replacing the fan tray) 11 inches (27.9 cm) between the side of the chassis and the interior of the cabinet, or the clearance area for the next rack or cabinet (required for side-to-side airflow)

Facility Cooling Requirements


The Cisco Nexus 7000 Series switches dissipate considerable power that generates much heat. The following is the heat dissipation requirement for these switches:

Cisco Nexus 7009 dissipates up to 28,101 BTUs per hour Cisco Nexus 7010 dissipates up to 35,162 BTUs per hour Cisco Nexus 7018 dissipates up to 51,195 BTUs per hour

Chassis Airflow
To see how the cooling air flows through the Cisco Nexus 7000 Series switches, see Figure 3-15 for the Cisco Nexus 7009 switch, Figure 3-16 for the Cisco Nexus 7010 switch, and Figure 3-17 for the Cisco Nexus 7018 switch. All of the Cisco Nexus 7000 Series switches are designed to work in a hot-aisle/cold-aisle environment, but the Cisco Nexus 7009 and 7018 switches also require side clearances to allow airflow in and out the sides.

Cisco Nexus 7000 Series Site Preparation Guide

3-16

OL-23070-05

Chapter 3

Technical Specifications Chassis Airflow

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-15 Airflow for the Cisco Nexus 7009 Chassis

Airflow for cooling the supervisor, I/O modules, and fabric modules

Airflow for cooling the power supply units

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-17

Chapter 3 Chassis Airflow

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-16 Airflow for the Cisco Nexus 7010 Chassis

1 2

Airflow for cooling the supervisor and I/O modules Airflow for cooling the fabric modules

Airflow for cooling the power supply units

Cisco Nexus 7000 Series Site Preparation Guide

3-18

270544

OL-23070-05

Chapter 3

Technical Specifications Chassis Airflow

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Figure 3-17 Airflow for the Cisco Nexus 7018 Chassis

3 3
189973

1 2

Airflow for cooling the supervisor and I/O modules Airflow for cooling the fabric modules

Airflow for cooling the power supply units

To allow for the Cisco Nexus 7009 and 7018 switches to take in air from the cold aisle and floor on the right side, you should route cables on the left front side of the switch. If necessary, you can route cables on the upper right front side of the chassis, which leaves the lower right side open to cooling air from the cold aisle in front of the chassis. By having the cables on the left side and leaving the left rear side unobstructed, the exhaust is directed to the hot aisle in back. For the clearances required on each side of the switch, see the Chassis Clearances section on page 3-15. To determine the clearances required on each side of the switch, see the Chassis Clearances section on page 3-15. To determine the maximum amount of airflow for a fully configured switch, see Table 3-16 for the Cisco Nexus 7010 switch or see Table 3-17 for the Cisco Nexus 7018 switch.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-19

Chapter 3 Chassis Airflow

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Note

Systems with fewer than the maximum number of supervisor, I/O, or fabric modules will have less airflow.

Table 3-15

Airflow for a Fully Configured Cisco Nexus 7009 Switch

Temperature <55F (13C) 55 to 62F (13 to 17C) 64 to 71F (18 to 22C) 73 to 80F (23 to 27C) 82 to 89F (28 to 32C) 91 to 98F (33 to 37C)

System Airflow (cfm) 686 686 686 686 686 768

Fabric Airflow (cfm) 76 92 107 123 143 153 173 189 203 221 250

Total Airflow (cfm) 762 778 793 809 829 921 1015 1233 1406 1547 1576

100 to 107F (38 to 42C) 842 109 to 116F (43 to 47C) 1044 118 to 125F (48 to 52C) 1203 127 to 136F (53 to 58C) 1326 >136F (>58C) 1203

Table 3-16

Airflow for a Fully Configured Cisco Nexus 7010 Switch

Temperature <55F (13C) 55 to 62F (13 to 17C) 64 to 71F (18 to 22C) 73 to 80F (23 to 27C) 82 to 89F (28 to 32C) 91 to 98F (33 to 37C)

System Airflow (cfm) 406 493 534 576 659 744

Fabric Airflow (cfm) 37 44 50 56 63 70 75 100 154 162 162

Total Airflow (cfm) 443 537 584 632 722 814 928 1144 1396 1609 1609

100 to 107F (38 to 42C) 853 109 to 116F (43 to 47C) 1044 118 to 125F (48 to 52C) 1242 127 to 136F (53 to 58C) 1447 >136F (>58C) 1447

Cisco Nexus 7000 Series Site Preparation Guide

3-20

OL-23070-05

Chapter 3

Technical Specifications Chassis Airflow

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Table 3-17

Airflow for a Fully Configured Cisco Nexus 7018 Switch

Temperature <55F (13C) 55 to 62F (13 to 17C) 64 to 71F (18 to 22C) 73 to 80F (23 to 27C) 82 to 89F (28 to 32C) 91 to 98F (33 to 37C)

System Airflow (cfm) 1459 1459 1459 1459 1459 1583

Fabric Airflow (cfm) 71 83 89 95 124 153 180 195 207 207 207

Total Airflow (cfm) 1530 1542 1548 1554 1583 1736 1893 2353 2668 2977 2977

100 to 107F (38 to 42C) 1713 109 to 116F (43 to 47C) 2158 118 to 125F (48 to 52C) 2461 127 to 136F (53 to 58C) 2770 >136F (58C) 2770

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

3-21

Chapter 3 Chassis Airflow

Technical Specifications

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Cisco Nexus 7000 Series Site Preparation Guide

3-22

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

A P P E N D I X

Site Preparation and Maintenance Records


This appendix provides a site planning list that you can use when preparing your site for the Cisco Nexus 7000 Series switches and includes these sections:

Site Preparation Checklist, page A-1 Contact and Site Information, page A-3 Chassis and Module Information, page A-3

Site Preparation Checklist


Planning the location and layout of your equipment rack or cabinet is essential for successful switch operation, ventilation, and accessibility. Table A-1 lists the site planning tasks that we recommend that you complete before you install the Cisco Nexus 7000 Series switches. Your completion of each task ensures a successful switch installation.
Table A-1 Site Preparation Checklist

Planning Activity
Space evaluation:

Verification Time and Date

Space and layout Floor covering Impact and vibration Lighting Physical access Maintenance access Ambient temperature Humidity Altitude Atmospheric contamination Airflow

Environmental evaluation:

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

A-1

Appendix A Site Preparation Checklist

Site Preparation and Maintenance Records

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table A-1 Site Preparation Checklist (continued)

Planning Activity
Power evaluation:

Verification Time and Date

Input power type Power receptacles Receptacle proximity to the equipment Dedicated (separate) circuits for power redundancy UPS for power failures Grounding: proper gauge wire and lugs Circuit breaker size Data center ground Cable type Connector type Cable distance limitations Interface equipment (transceivers) Distance limitations for signaling Site wiring RFI levels

Grounding evaluation:

Cable and interface equipment evaluation:

EMI evaluation:

Cisco Nexus 7000 Series Site Preparation Guide

A-2

OL-23070-05

Appendix A

Site Preparation and Maintenance Records Contact and Site Information

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Contact and Site Information


Use the following worksheet (Table A-2) to record contact and site information.
Table A-2 Contact person Contact phone Contact e-mail Building/site name Data center location Floor location Address (line 1) Address (line 2) City State ZIP code Country Contact and Site Information

Chassis and Module Information


Use the following worksheets (Table A-3, Table A-4, Table A-5, and Table A-6) to record information about the chassis and modules. Contract Number Chassis serial number Product number
Table A-3 Network-Related Information

Switch IP address Switch IP netmask Hostname Domain name IP broadcast address Gateway/router address DNS address

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

A-3

Appendix A Chassis and Module Information

Site Preparation and Maintenance Records

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Table A-4

Cisco Nexus 7009 Module Information

Slot
1 2 3 4 5 6 7 8 9

Module Type
Supervisor Supervisor

Module Serial Number

Notes

Table A-5

Cisco Nexus 7010 Module Information

Slot
1 2 3 4 5 6 7 8 9 10

Module Type

Module Serial Number

Notes

Supervisor Supervisor

Table A-6

Cisco Nexus 7018 Module Information

Slot
1 2 3 4 5 6 7 8

Module Type

Module Serial Number

Notes

Cisco Nexus 7000 Series Site Preparation Guide

A-4

OL-23070-05

Appendix A

Site Preparation and Maintenance Records Chassis and Module Information

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Table A-6 Cisco Nexus 7018 Module Information

Slot
9 10 11 12 13 14 15 16 17 18

Module Type
Supervisor Supervisor

Module Serial Number

Notes

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

A-5

Appendix A Chassis and Module Information

Site Preparation and Maintenance Records

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Cisco Nexus 7000 Series Site Preparation Guide

A-6

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

A P P E N D I X

Cabinet and Rack Requirements


This appendix describes the cabinet and rack requirements for the Cisco Nexus 7000 Series switches and includes these sections:

General Requirements for Cabinets and Racks, page B-1 Cabinet and Rack Vendors, page B-3

General Requirements for Cabinets and Racks


This section provides the Cisco Nexus 7000 Series switch requirements for the following types of racks and cabinets, assuming an external ambient air temperature range of 32 to 104F (0 to 40C):

Standard perforated cabinets Solid-walled cabinets with a roof fan tray (bottom to top cooling) Standard open racks Four-post Telco racks (required by the Cisco Nexus 7010 and 7018 switches and can be used for the Cisco Nexus 7009 switches) Two-post Telco racks (used with only the Cisco Nexus 7009 switches)

Note

If you select an enclosed cabinet, we recommend that you use one of the following thermally validated types: standard perforated or solid-walled with a fan tray. To correctly install the Cisco Nexus 7000 Series switch in a cabinet that is located in a hot-aisle/cold-aisle environment, you should fit a cabinet with baffles to prevent exhaust air from recirculating into the chassis air intake. The rack or cabinet used to hold a Cisco Nexus 7000 Series chassis should meet the following physical requirements:

Use a standard 19-inch, four-post Electronic Industries Alliance (EIA) cabinet or rack with mounting rails that conform to English universal hole spacing per section 1 of the ANSI/EIA-310-D-1992 standard. The height of the rack or cabinet must accommodate the Cisco Nexus 7000 Series switches as follows:
For the Cisco Nexus 7009 switch, the rack height must be at least 15 RU for one chassis and at

least 30 RU for two chassis.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

B-1

Appendix B General Requirements for Cabinets and Racks

Cabinet and Rack Requirements

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Note

Alternatively, if you need to install three 14 RU Cisco Nexus 7009 chassis in a 42 RU rack, you can perform a front-mount installation for all three chassis without using the bottom-support rails. For front-mount installations, you must use a mechanical lift to first position the lowest chassis at the lowest RU in the rack before attaching it. After that, you raise a second chassis to the top of the lowest chassis and slide the second chassis on top before attaching it to the rack. Finally, you raise a third chassis to the top of the second installed chassis, slide the third one on top of the second installed chassis before attaching it to the rack.

Caution

If you are doing center-mount installations, you must use a bottom-support rail for each chassis, which requires 15 RU for each installed chassis.
For the Cisco Nexus 7010 switch, the rack height must be at least 21 RU for one chassis and 42

RU for two chassis (45 RU is recommended).


For the Cisco Nexus 7018 switch, the rack height must be at least 25 RU for one chassis.

The depth of a four-post rack must be 24 to 32 inches (61.0 to 81.3 cm) between the front and rear mounting brackets. Required clearances between the Cisco Nexus 7009 chassis and the edge of its rack or interior of its cabinet are as follows:
If you are using a four-post rack or cabinet, you must have 7 inches (17.8 cm) between the

chassis and the front and back of a four-post rack or interior of the cabinet (required for cabling). This requirement does not apply to a two-post rack.

Note

If the chassis is installed with the alternative center-mount bottom-support brackets, the chassis will protrude 6 inches (15.25 cm) beyond the mounting rails, so you must plan for 13 inches (33.0 cm) clearance in front of the mounting rails to get the required 7 inches (17.8 cm) clearance in front of the chassis.

11 inches (27.9 cm) between the side of the chassis and the interior of the cabinet or the

clearance area for the next rack or cabinet (required for side-to-side airflow with all types of racks or cabinets)

Required clearances between the Cisco Nexus 7010 chassis and the edges of its rack or the interior of its cabinet are as follows:
7 inches (17.8 cm) between the chassis and the front and back of the rack or interior of the

cabinet (required for cabling)


No clearance is required to the sides of the rack or cabinet with front-to-back airflow.

Required clearances between the Cisco Nexus 7018 chassis and the edges of its rack or the interior of its cabinet are as follows:
7 inches (17.8 cm) between the chassis and the front and back of the rack or interior of the

cabinet (required for cabling)


11 inches (27.9 cm) between the side of the chassis and the interior of the cabinet or the

clearance area for the next rack or cabinet (required for side-to-side airflow) Additionally, you must consider the following site requirements for the rack:

AC power receptacles must be located within 12 feet (3.6 m) of each power supply unit in each chassis.

Cisco Nexus 7000 Series Site Preparation Guide

B-2

OL-23070-05

Appendix B

Cabinet and Rack Requirements Cabinet and Rack Vendors

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Cable management for one or two switches in the same rack are as follows:
For the Cisco Nexus 7009 switch, provide cable management for up to 336 ports for each

chassis.
For the Cisco Nexus 7010 switch, provide cable management for up to 384 ports for each

chassis.
For the Cisco Nexus 7018 switch, provide cable management for up to 768 ports for each

chassis.

Cable routing within the cabinet or beside the rack must not block access to any of the removable modules installed in a chassis or block any airflow on the inlet and exhaust vents of the chassis. With cabinets, route the cables out the top or bottom as follows:
For the Cisco Nexus 7009 switch, route the cables along the left side of the front of the chassis

so that cooling air can flow to the chassis from the right front side and heated exhaust air is vented to the left and directed to the hot aisle in the rear. If necessary, you can also route cables to the upper half of the right side of the chassis if the lower right side of the front is open for airflow from the cold-aisle and floor to the air intake.
For the Cisco Nexus 7010 switch, route the cables through the cable management area on the

top front of the switch.


For the Cisco Nexus 7018 switch, route the cables along the left side of the front of the chassis

so that cooling air can flow to the chassis from the right front side and heated exhaust air is vented to the left and directed to the hot aisle in the rear. If necessary, you can also route cables to the upper half of the right side of the chassis if the lower right side of the front is open for airflow from the cold-aisle and floor to the air intake.

Where necessary, have a seismic rating of Network Equipment Building Standards (NEBS) Zone 3 or Zone 4, per GR-63-CORE if required. Minimum gross load rating of 2000 lb (907.2 kg) (static load rating) if supporting two switches.

Cabinet and Rack Vendors


You can install a Cisco Nexus 7000 Series switch in any cabinet or rack that meets the specifications listed in the General Requirements for Cabinets and Racks section on page B-1. Work with your cabinet vendors to determine which of their cabinets meet these requirements or see the Cisco Technical Assistance Center (TAC) for recommendations.

Cisco Nexus 7000 Series Site Preparation Guide OL-23070-05

B-3

Appendix B Cabinet and Rack Vendors

Cabinet and Rack Requirements

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

Cisco Nexus 7000 Series Site Preparation Guide

B-4

OL-23070-05

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

INDEX

Numerics
32-port 10-Gigabit Ethernet I/O module MTBF weight MTBF weight MTBF weight MTBF weight MTBF weight MTBF weight
3-3, 3-4 3-5, 3-6

power requirements weight


3-3, 3-4

3-5, 3-6

6-kW AC power supply unit cable specifications MTBF weight


3-4 3-3, 3-4 3-9

power requirements
3-3, 3-4

32-port 10-Gigabit Ethernet I/O module with XL


3-3, 3-4 3-5, 3-6

6-kW DC power supply unit cable specifications MTBF weight


3-4 3-3, 3-4 3-14

power requirements
3-3, 3-4

32-port 1- and 10-Gigabit Ethernet I/O module


3-3, 3-4 3-5, 3-6

7.5-kW AC power supply unit cable specifications MTBF weight MTBF


3-4 3-3, 3-4 3-9

power requirements
3-3, 3-4

48-port 10/100/1000 Ethernet I/O module


3-3, 3-4 3-5, 3-6

8-port 10-Gigabit Ethernet I/O module with XL


3-3, 3-4 3-5, 3-6

power requirements
3-3, 3-4

power requirements weight


3-3, 3-4

48-port 10/100/1000 Ethernet I/O module with XL


3-3, 3-4 3-5, 3-6

power requirements
3-3, 3-4

A
airflow Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018 altitude preparing for specifications
2-3 3-1 3-17 3-18 3-19

48-port 1- and 10-gigabit Ethernet I/O module


3-3, 3-4 3-3, 3-4

48-port 1- and 10-Gigabit Ethernet I/O module with XL power requirements MTBF weight MTBF
3-3, 3-4 3-5, 3-6 3-5, 3-6

48-port 1-Gigabit Ethernet I/O module power requirements


3-3, 3-4

C
cabinets requirements
B-1

48-port 1-Gigabit Ethernet I/O module with XL


3-3, 3-4

Nexus 7000 Series Site Preparation Guide OL-23070-05

IN-1

Index

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
vendors cable routing Cisco Nexus 7009 chassis Cisco Nexus 7010 chassis Cisco Nexus 7018 chassis chassis airflow
3-16 B-3 B-3 B-3 B-3 B-3

MTBF

3-3 3-5

cable management

power requirements Cisco Nexus 7018 airflow


3-19 B-3

cable routing clearances components

chassis dimensions
3-16

3-2

component power requirements


1-1 3-4 3-15 3-16, B-2 3-16, B-2

3-6

clearance inside rack Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018 clearance outside rack Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018 records weight Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018 checklist, site preparation Cisco Nexus 7009 airflow
3-17 B-3 3-2 3-2 3-3 3-4 A-1 A-3 3-15 3-16 3-16

component weights MTBF clearances Cisco Nexus 7009 inside the rack outside the rack Cisco Nexus 7010 inside the rack outside the rack Cisco Nexus 7018 inside the rack outside the rack planning contact list
3-15 3-4

power requirements

3-6

3-15 3-15

3-16, B-2 3-16

3-16, B-2 3-16

combined power mode


A-3

3-6

cable routing clearances components MTBF


3-2

chassis dimensions
3-15 1-1

cooling requirements corrosion, preventing

3-16 2-3

component weights power requirements Cisco Nexus 7010 airflow


3-18 B-3

3-2

D
DC Power Interface Unit quantity weight
1-2, 3-4 3-4 2-3

3-5

cable routing clearances components

dust, minimizing
3-2

chassis dimensions
3-16

component power requirements


1-1 3-3

3-5, 3-6

E
electromagnetic interference (EMI), preparing for
2-3

component weights

Nexus 7000 Series Site Preparation Guide

IN-2

OL-23070-05

Index

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
environmental specifications
3-1

G
grounding
2-4

F
fabric fan trays, Cisco Nexus 7010 MTBF weight
3-4 3-4

H
hot-aisle/cold-aisle, cable routing humidity preparing for specifications
2-2 3-1 B-3

fabric modules Cisco Nexus 7009 MTBF weight MTBF weight MTBF
3-3 3-3

Cisco Nexus 7010


3-4 1-2

I
I/O modules power requirements quantities weights
3-6 1-2 3-3, 3-4, 3-5, 3-6 3-7 3-6

quantities
3-4

Cisco Nexus 7018


3-4

power requirements quantities weight


3-4 1-2

input-source power redundancy

fabric modules, Cisco Nexus 7010 power requirements fan trays Cisco Nexus 7009 MTBF weight
3-3 3-3 3-5, 3-6

M
mean time between failures. See MTBF module records MTBF 32-port 10-Gigabit Ethernet I/O module
3-4 3-5, 3-6 3-3, 3-4 3-3, 3-3, A-3

32-port 10-Gigabit Ethernet I/O module with XL 32-port 1- and 10-Gigabit Ethernet I/O module
3-4

Cisco Nexus 7010 total power requirements Cisco Nexus 7018 MTBF
3-4 3-6

48-port 10/100/1000 Ethernet I/O module

3-3

power requirements quantities weight FCC compliance


3-4 2-4 1-2

48-port 10/100/1000 Ethernet I/O module with XL 3-3, 3-4 48-port 1-Gigabit Ethernet I/O module
3-4 3-3, 3-4 3-3,

48-port 1-Gigabit Ethernet I/O module with XL 6-kW AC power supply unit 6-kW DC power supply unit 7.5-kW AC power supply unit
3-4 3-4 3-4 3-4

Federal Communications Commission. See FCC

8-port 10-Gigabit Ethernet I/O module with XL

3-3,

Nexus 7000 Series Site Preparation Guide OL-23070-05

IN-3

Index

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
chassis Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018 fabric modules Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018
3-3 3-4 3-4 3-3 3-4 3-2 3-3 3-4 3-4

power requirements 32-port 10-Gigabit Ethernet I/O module


3-6 3-5, 3-6 3-5, 3-5,

32-port 10-Gigabit Ethernet I/O module with XL 32-port 1- and 10-Gigabit Ethernet I/O module
3-6

fabric fan trays, Cisco Nexus 7010

48-port 10/100/1000 Ethernet I/O module

3-5, 3-6

48-port 10/100/1000 Ethernet I/O module with XL 3-5, 3-6 48-port 1- and 10-Gigabit Ethernet I/O module
3-6

fan trays, Cisco Nexus 7009 fan trays, Cisco Nexus 7018 supervisor module
3-2, 3-3

48-port 1- and 10-Gigabit Ethernet I/O module with XL 3-5 48-port 1-Gigabit Ethernet I/O module
3-6 3-5, 3-6 3-5, 3-5,

48-port 1-Gigabit Ethernet I/O module with XL

N
NEBS, seismic rating noise specifications
B-3

8-port 10-Gigabit Ethernet I/O module with XL


3-6

Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018

3-5 3-5 3-6

Network Equipment Building Standards. See NEBS


3-2

Cisco Nexus 7010 chassis


3-6

O
overvoltage, preparing for
2-4

fabric module Cisco Nexus 7018 fabric modules Cisco Nexus 7010
3-5, 3-6 3-5, 3-6 3-6

P
particles in air, minimizing physical specifications power availability
3-7 3-2 2-3

fan trays, Cisco Nexus 7018 supervisor module


3-5 3-6 2-4 3-7

Cisco Nexus 7018 power source requirements power-supply redundancy power supply units
3-9 3-14 3-9

power cable specifications 6-kW AC power supply unit 6-kW DC power supply unit 7.5-kW AC power supply unit power modes combined
3-6 3-7 3-7 3-7

power source requirements quantities receptacles weights


1-2 2-4

2-4

3-3, 3-4

full redundancy

input-source redundancy power-supply redundancy power receptacles


B-2

R
racks clearances

Nexus 7000 Series Site Preparation Guide

IN-4

OL-23070-05

Index

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m
Cisco Nexus 7010 Cisco Nexus 7018 requirements vendors
B-3 2-3 B-1 B-2 B-2

32-port 1- and 10-Gigabit Ethernet I/O module


3-4

3-3,

48-port 10/100/1000 Ethernet I/O module

3-3

48-port 10/100/1000 Ethernet I/O module with XL 3-3, 3-4 48-port 1-Gigabit Ethernet I/O module
3-4 B-1 3-3, 3-4 3-3, 2-4, B-2

radio frequency interference (RFI), preparing for receptacles for power relative humidity. See humidity requirements, cabinets and racks

48-port 1-Gigabit Ethernet I/O module with XL 6-KW AC power supply unit 6-KW DC power supply unit 7.5-KW AC power supply unit
3-3, 3-4 3-3, 3-4 3-3, 3-4

S
seismic requirements shock resistance supervisor module MTBF quantity weight
3-2, 3-3 3-5 2-4 A-1 B-3

8-port 10-Gigabit Ethernet I/O module with XL


3-4

3-3,

chassis Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018 DC Power Interface Unit fabric modules Cisco Nexus 7009 Cisco Nexus 7010 Cisco Nexus 7018 fan trays Cisco Nexus 7009
3-3 3-4 3-4 3-3 3-4 3-4 3-2 3-3 3-4 3-4 3-4

site preparation checklist

power requirements
1-1 3-2, 3-3

fabric fan trays, Cisco Nexus 7010

supervisor module, Cisco Nexus 7018 power requirements switch clearances


3-15 3-6

T
temperature preparing for specifications
2-2 3-1

Cisco Nexus 7010 Cisco Nexus 7018 supervisor module

3-2, 3-3 3-3 3-4

system fan trays, Cisco Nexus 7009 system fan trays, Cisco Nexus 7010 wiring recommendations
2-4

V
vibration resistance
2-4

W
weight 32-port 10-Gigabit Ethernet I/O module
3-4
Nexus 7000 Series Site Preparation Guide OL-23070-05

3-3, 3-4 3-3,

32-port 10-Gigabit Ethernet I/O module with XL

IN-5

Index