MRA4 Modbus HighPROTEC Data point list

Manual DOK-TD-MRA4MDE

Table of Contents
MODBUS PARAMETERS.................................................................................................................................................................................................................3
Notes for the SCADA-System.......................................................................................................................................................................................................................4

SPECIFIC MODBUS FUNCTION CODES..............................................................................................................................................................................................5


Setting Date and Time...................................................................................................................................................................................................................................9 Supported MODBUS- Error Messages.......................................................................................................................................................................................................10

APPENDIX - DATA POINT LISTS....................................................................................................................................................................................................11


Signals........................................................................................................................................................................................................................................................11 Measuring values......................................................................................................................................................................................................................................101 Commands...............................................................................................................................................................................................................................................127 Settings.....................................................................................................................................................................................................................................................131

df79bde05d011db5d77e5c14aeae1dcd 5c39a8d1ecbf065b52d82dea56a335ef RMS_Handoff: ? Datei: ? This Manual is valid for version : Build: 10569 1.7.b

Page 2

EN MRA4 Modbus 05/10

Modbus Parameters

Modbus Parameters
For the Modbus Protocol several parameters have to be set which are relevant for the communication between the control system (SCADA) and the device. The parameters and their setting possibilities or value ranges are shown in the table below. ATTENTION! The Parameters are described within the appendix of the device manual (chapter Modbus).

EN MRA4 Modbus 05/10

Page 3

Modbus Parameters

Notes for the SCADA-System


When using Modbus RTU the following times have to be considered by the control system and are fixed within the device : The dwell times (tD ) before start of a telegram must at least be set to 3.5 characters. Examples: 3.5 characters 9600 Baud = 4 ms 3.5 characters 19200 Baud = 2 ms 3.6 3.5 characters 38400 Baud = 1 ms Start of a new telegram is expected when the dwell time (tD ) is > 3.5 characters. The fact that the probability of disruptions during transmission of a telegram increases with its length has to be taken into duly consideration and thus a query to the Slave should be possibly such that the response telegram is not much longer than 32 Byte.

Page 4

EN MRA4 Modbus 05/10

Specific Modbus Function Codes

Specific Modbus Function Codes


For reading out data from the device or to carry out commands, the services listed in the table, also called Function Codes, are supported. Functioncode 3 4 5 Designation Read Holding Registers Read Input Registers Write single Output (Bit) Description There are single or several data words read as from a specific data word address. Only status addresses and parameter addresses can be read. There are single or several data words read as from a specific data word address. Only measuring values can be read. All other values are illegal and will not affect the output. Via this function code acknowledgments can be executed as well as counters reseted or blockings set. Test function for the communication system There are single or several data words written as from a specific data word address.

8 Loopback Test 16 Load Multiple Registers Table 3.1: function codes

EN MRA4 Modbus 05/10

Page 5

Specific Modbus Function Codes On the following pages the Modbus functions are described in detail: Function-Code 3/4: Query Slave address Response Slave address

3/4

Register address HI

Register address LO

Register number HI

Register number LO

Check-sum HI

Check-sum LO

3/4

Byte number

Register 0 HI

Register 0 LO

...

Check-sum HI

Check-sum LO

Register address (HI*256 + LO) The data word address from where reading should start. Register number (HI*256 + LO) Number of data words to be read. Valid range: 1..125 Byte number Number of subsequent Bytes containing data words. Register Data words read out of the device (Highbyte and Lowbyte).

Page 6

EN MRA4 Modbus 05/10

Specific Modbus Function Codes Function Code 5: Query Slave address Response Slave address

Register address HI Register address HI

Register address LO Register address LO

Register data HI Register data HI

Register data LO Register data LO

Check-sum HI Check-sum HI

Check-sum LO Check-sum LO

Register address (HI*256 + LO) Data word address to be written Register data Value of the data word to be written (Highbyte and Lowbyte). Permitted value range : FF00 hex request for a single bit to be on: This often means to reset a counter, execute acknowledgments or set blockings signals. 0000 hex request for a single bit to be off: This often means to deactivate blocking signals or to reset single bits.

Function Code 8: Query Slave address Response Slave address 8 Data Diag Code HI 0x00 Data Diag Code HI Data Diag Code LO 0x00 Data Diag Code LO Test data Test data Check-sum HI Check-sum LO

Test data

Test data

Check-sum HI

Check-sum LO

Data Diag Code HI (high), Data Diag Code LO ( Low) Diagnostic Code (subfunction code of function code 8) for testing the communication system. The Diagnostic Code Return Query Data (0x00, 0x00) is being supported. Test Data By using the Diagnostic Code 0x00 0x00, the transmitted data is sent back to the Master unchanged.

EN MRA4 Modbus 05/10

Page 7

Specific Modbus Function Codes Function Code 16: Query Slave address Response Slave address 16 Register address HI 16 Register address LO Register number HI Register number LO Byte number Register 0 HI Register 0 LO ... Check-sum HI Check-sum LO

Register address HI

Register address LO

Register number HI

Register number LO

Check-sum HI

Check-sum LO

Register address (HI*256 + LO) Data word address as from where writing should start. Register number (HI*256 + LO) Query: Number of data words to be written. Valid range: 1..123 Response: Number of data words written. Byte number Number of subsequent Bytes to contain data words. Register Data words read out of the device (Highbyte und Lowbyte).

Page 8

EN MRA4 Modbus 05/10

Specific Modbus Function Codes

Setting Date and Time


Date and time can be set by means of function code 16 and read with function code 3. If the device address 0 (broadcast address) is selected, the times of all devices connected to this bus are simultaneously reset. The devices do not respond to a broadcast command.

EN MRA4 Modbus 05/10

Page 9

Specific Modbus Function Codes

Supported MODBUS- Error Messages


Exception Response Telegrams are described within the general Modbus Application Protocol Specification". An exception response table with examples is shown there. For the device we want to supply more information on these. The table below contains just the actually used codes. In case the device has recognized an error it will react in the following way: Exception Code 1 2 3 4 Designation Illegal Function Illegal Data Address Illegal Data Value Slave Device Failure Description The message received includes a function code which is not supported by the Slave. Access was sought on a data word address not included in the data module. The received message contains an invalid data structure (e.g. wrong number of data bytes). An unrecoverable error occurred while the server (or slave) was attempting to perform the requested action.

The response given by the device in a failure case has the following format: Slave Address 0x80 + Function Code Exception Code Checksum HI Checksum LO

In the second Byte of the response the Function Code is sent with the highest Bit set to 1. This is equivalent to an addition by 0x80. The third Byte holds the Exception Code of the error message.

Page 10

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Appendix - Data Point Lists


Signals
Module Subgroup Names Functions Prot ExBlo1-I ExBlo2-I active ExBlo Alarm L1 Alarm L2 Alarm L3 Alarm G Alarm 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Module input state: External blocking1 Module input state: External blocking2 Signal: active Signal: External Blocking Signal: GeneralAlarm L1 Signal: GeneralAlarm L2 Signal: GeneralAlarm L3 Signal: GeneralAlarm - Earth fault Signal: General Alarm

Page 11

Appendix - Data Point Lists Module Subgroup Names Functions Trip L1 (*) Trip L2 (*) Trip L3 (*) Trip G (*) Trip (*) TripCmd (*) Prot Blo TripCmd ExBlo TripCmd-I 1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Struct Bit Bit 0x1 (1) 0x2 (2) ExBlo TripCmd 2 1 3 Bit 0x4 (3) I dir fwd 2 1 3 Bit 0x80 (8) Signal: Trip Command blocked Module input state: External Blocking of the Trip Command Signal: External Blocking of the Trip Command Signal: Phase current failure forward direction 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) 0x2000 (14) 0x4000 (15) Signal: Trip Command Signal: General Trip L1 Signal: General Trip L2 Signal: General Trip L3 Signal: General Trip Ground fault Signal: General Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 12

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions I dir rev 2 1 3 Bit 0x100 (9) I dir n poss 2 1 3 Bit 0x200 (10) IG dir fwd IG rev dir IG dir n poss 2 2 2 1 1 1 3 3 3 Bit Bit Bit 0x400 (11) 0x800 (12) 0x1000 (13) I[1] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 3 3 3 3 1 1 1 1 3 3 3 3 Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 3 1 3 Bit 0x8 (4) active 3 1 3 Bit 0x10 (5) Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active Signal: Phase current failure reverse direction Signal: Phase fault missing reference voltage Signal: Earth fault forward Signal: Earth fault reverse direction Signal: Earth fault direction detection not possible Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 13

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo Ex rev Interl Blo TripCmd ExBlo TripCmd 3 3 3 3 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) IH2 Blo 3 1 3 Bit 0x200 (10) I[1] Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) 4 4 4 4 4 4 1 1 1 1 1 1 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) Signal: General Trip Phase L1 Signal: Alarm Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: External Blocking Signal: External reverse Interlocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Blocking the trip command by an inrush Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 14

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Trip L2 (*) Trip L3 (*) Trip (*) TripCmd (*) I[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 4 4 4 4 5 5 5 5 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 5 1 3 Bit 0x8 (4) active ExBlo 5 5 1 1 3 3 Bit Bit 0x10 (5) 0x20 (6) Signal: External Blocking Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: Trip Command Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 15

Appendix - Data Point Lists Module Subgroup Names Functions Ex rev Interl Blo TripCmd ExBlo TripCmd 5 5 5 1 1 1 3 3 3 Bit Bit Bit 0x40 (7) 0x80 (8) 0x100 (9) IH2 Blo 5 1 3 Bit 0x200 (10) I[2] Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) Trip L2 (*) 6 6 6 6 6 6 6 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: Alarm Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: External reverse Interlocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Blocking the trip command by an inrush Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 16

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Trip L3 (*) Trip (*) TripCmd (*) I[3] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 6 6 6 7 7 7 7 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 7 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl 7 7 7 1 1 1 3 3 3 Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: External reverse Interlocking Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active 0x40 (7) 0x80 (8) 0x100 (9) Signal: Trip Command Signal: General Trip Phase L3 Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 17

Appendix - Data Point Lists Module Subgroup Names Functions Blo TripCmd ExBlo TripCmd 7 7 1 1 3 3 Bit Bit 0x80 (8) 0x100 (9) IH2 Blo 7 1 3 Bit 0x200 (10) I[3] Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) Trip L2 (*) Trip L3 (*) 8 8 8 8 8 8 8 8 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Alarm Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Blocking the trip command by an inrush Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 18

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Trip (*) TripCmd (*) I[4] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 8 8 9 9 9 9 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 9 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl Blo TripCmd 9 9 9 9 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) Signal: External Blocking Signal: External reverse Interlocking Signal: Trip Command blocked Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active 0x80 (8) 0x100 (9) Signal: Trip Command Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 19

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo TripCmd 9 1 3 Bit 0x100 (9) IH2 Blo 9 1 3 Bit 0x200 (10) I[4] Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) Trip L2 (*) Trip L3 (*) Trip (*) 10 10 10 10 10 10 10 10 10 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Signal: Alarm Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: External Blocking of the Trip Command Signal: Blocking the trip command by an inrush Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 20

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions TripCmd (*) I[5] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 10 11 11 11 11 1 1 1 1 1 3 3 3 3 3 Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 11 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl Blo TripCmd ExBlo TripCmd 11 11 11 11 11 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: External Blocking Signal: External reverse Interlocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active 0x100 (9) Signal: Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 21

Appendix - Data Point Lists Module Subgroup Names Functions IH2 Blo 11 1 3 Bit 0x200 (10) I[5] Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) Trip L2 (*) Trip L3 (*) Trip (*) TripCmd (*) I[6] 12 12 12 12 12 12 12 12 12 12 13 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit Bit Bit Bit Struct 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: Trip Command Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Signal: Alarm Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: Blocking the trip command by an inrush Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 22

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 13 13 13 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 13 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl Blo TripCmd ExBlo TripCmd 13 13 13 13 13 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) IH2 Blo 13 1 3 Bit 0x200 (10) I[6] 14 1 3 Struct Signal: External Blocking Signal: External reverse Interlocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Blocking the trip command by an inrush Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 23

Appendix - Data Point Lists Module Subgroup Names Functions Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) Trip L2 (*) Trip L3 (*) Trip (*) TripCmd (*) IG[1] ExBlo1-I ExBlo2-I 14 14 14 14 14 14 14 14 14 15 15 15 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit Bit Struct Bit Bit 0x1 (1) 0x2 (2)
Page 24

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position) 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9)

Unit

Description

Signal: Alarm L1 Signal: Alarm L2 Signal: Alarm L3 Signal: Alarm Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Signal: Trip Command

Module input state: External blocking1 Module input state: External blocking2

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo TripCmd-I 15 1 3 Bit 0x4 (3) Ex rev Interl-I 15 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl Blo TripCmd ExBlo TripCmd 15 15 15 15 15 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) IGH2 Blo Alarm Trip (*) TripCmd (*) 15 15 15 15 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active Signal: External Blocking Signal: External reverse Interlocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: blocked by an inrush Signal: Alarm IG Signal: Trip Signal: Trip Command

Page 25

Appendix - Data Point Lists Module Subgroup Names Functions IG[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 16 16 16 16 1 1 1 1 3 3 3 3 Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 16 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl Blo TripCmd ExBlo TripCmd 16 16 16 16 16 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) IGH2 Blo 16 1 3 Bit 0x200 (10) Signal: External Blocking Signal: External reverse Interlocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: blocked by an inrush Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 26

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) IG[3] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 16 16 16 17 17 17 17 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 17 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl 17 17 17 1 1 1 3 3 3 Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: External reverse Interlocking Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking Signal: active 0x400 (11) 0x800 (12) 0x1000 (13) Signal: Trip Command Signal: Trip Signal: Alarm IG Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 27

Appendix - Data Point Lists Module Subgroup Names Functions Blo TripCmd ExBlo TripCmd 17 17 1 1 3 3 Bit Bit 0x80 (8) 0x100 (9) IGH2 Blo Alarm Trip (*) TripCmd (*) IG[4] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 17 17 17 17 18 18 18 18 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 18 1 3 Bit 0x8 (4) Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: External reverse interlocking 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) Signal: Trip Command Signal: Trip Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: blocked by an inrush Signal: Alarm IG Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 28

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions active ExBlo Ex rev Interl Blo TripCmd ExBlo TripCmd 18 18 18 18 18 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) IGH2 Blo Alarm Trip (*) TripCmd (*) ThR ExBlo1-I 18 18 18 18 19 19 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Bit Bit Struct Bit 0x1 (1) Module input state: External blocking1 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) Signal: Trip Command Signal: Trip Signal: External Blocking Signal: External reverse Interlocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: blocked by an inrush Signal: Alarm IG Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 29

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo2-I ExBlo TripCmd-I 19 19 1 1 3 3 Bit Bit 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 19 19 19 19 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) IH2 ExBlo1-I 19 19 19 22 22 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Struct Bit 0x1 (1) Module input state: External blocking1 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Thermal Overload Signal: Trip Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 30

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo2-I active ExBlo Blo L1 Blo L2 Blo L3 Blo IG meas 22 22 22 22 22 22 22 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) Signal: Blocking of the ground (earth) protection module (measured ground current) Signal: Inrush was detected in at least one phase - trip command blocked. Signal: Blocking of the ground (earth) protection module (calculated ground current) Signal: Blocked L3 Signal: Blocked L2 Signal: External Blocking Signal: Blocked L1 Module input state: External blocking2 Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

3-ph Blo

22

Bit

0x100 (9)

Blo IG calc

22

Bit

0x200 (10)

EN MRA4 Modbus 05/10

Page 31

Appendix - Data Point Lists Module Subgroup Names Functions V[1] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 24 24 24 24 1 1 1 1 3 3 3 3 Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 24 24 24 24 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) V[1] Alarm L1 Alarm L2 Alarm L3 25 25 25 25 1 1 1 1 3 3 3 3 Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 32

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip L1 (*) Trip L2 (*) Trip L3 (*) Trip (*) TripCmd (*) V[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 25 25 25 25 25 25 26 26 26 26 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active 26 1 3 Bit 0x8 (4) Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: Trip Command Signal: Alarm voltage stage Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 33

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo Blo TripCmd ExBlo TripCmd 26 26 26 1 1 1 3 3 3 Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) V[2] Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) Trip L2 (*) Trip L3 (*) 27 27 27 27 27 27 27 27 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: Alarm voltage stage Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 34

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Trip (*) TripCmd (*) V[3] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 27 27 28 28 28 28 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 28 28 28 28 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) V[3] Alarm L1 29 29 1 1 3 3 Struct Bit 0x1 (1) Signal: Alarm L1 Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) Signal: Trip Command Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 35

Appendix - Data Point Lists Module Subgroup Names Functions Alarm L2 Alarm L3 Alarm Trip L1 (*) Trip L2 (*) Trip L3 (*) Trip (*) TripCmd (*) V[4] ExBlo1-I ExBlo2-I 29 29 29 29 29 29 29 29 30 30 30 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit Struct Bit Bit 0x1 (1) 0x2 (2) Module input state: External blocking1 Module input state: External blocking2 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: Trip Command Signal: Alarm voltage stage Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Signal: Alarm L3 Signal: Alarm L2 Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 36

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo TripCmd-I 30 1 3 Bit 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 30 30 30 30 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) V[4] Alarm L1 Alarm L2 Alarm L3 Alarm Trip L1 (*) 31 31 31 31 31 31 1 1 1 1 1 1 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) Signal: Alarm voltage stage Signal: General Trip Phase L1 Signal: Alarm L3 Signal: Alarm L2 Signal: Alarm L1 Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 37

Appendix - Data Point Lists Module Subgroup Names Functions Trip L2 (*) Trip L3 (*) Trip (*) TripCmd (*) VG[1] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 31 31 31 31 32 32 32 32 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd 32 32 32 1 1 1 3 3 3 Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) Signal: External Blocking Signal: Trip Command blocked Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: Trip Command Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 38

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo TripCmd 32 1 3 Bit 0x40 (7) Alarm 32 1 3 Bit 0x80 (8) Trip (*) TripCmd (*) VG[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 32 32 33 33 33 33 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd 33 33 33 1 1 1 3 3 3 Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) Signal: External Blocking Signal: Trip Command blocked Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x100 (9) 0x200 (10) Signal: Trip Command Signal: External Blocking of the Trip Command Signal: Alarm Residual Voltage Supervision-stage Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 39

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo TripCmd 33 1 3 Bit 0x40 (7) Alarm 33 1 3 Bit 0x80 (8) Trip (*) TripCmd (*) f[1] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 33 33 34 34 34 34 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo by V< 34 34 34 1 1 1 3 3 3 Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) Signal: External Blocking Signal: Module is blocked by undervoltage. Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x100 (9) 0x200 (10) Signal: Trip Command Signal: External Blocking of the Trip Command Signal: Alarm Residual Voltage Supervision-stage Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 40

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Blo TripCmd ExBlo TripCmd 34 34 1 1 3 3 Bit Bit 0x40 (7) 0x80 (8) f[1] Alarm f Alarm df/dt | DF/DT 35 35 35 1 1 1 3 3 3 Struct Bit Bit 0x1 (1) 0x2 (2) Trip f (*) 35 1 3 Bit 0x4 (3) Trip df/dt | DF/DT (*) 35 Alarm 35 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) Alarm delta phi Trip (*) 35 35 1 1 3 3 Bit Bit 0x20 (6) 0x40 (7) Signal: Alarm Frequency Protection Alarm instantaneous or average value of the rate-offrequency-change Signal: Frequency has exceeded the limit. Signal: Trip df/dt or DF/DT Signal: Alarm Frequency Protection (collective signal) Signal: Alarm Vector Surge Signal: Trip Frequency Protection (collective signal) Signal: Trip Command blocked Signal: External Blocking of the Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 41

Appendix - Data Point Lists Module Subgroup Names Functions Trip delta phi (*) TripCmd (*) f[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 35 35 36 36 36 36 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo by V< 36 36 36 1 1 1 3 3 3 Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) Blo TripCmd ExBlo TripCmd 36 36 1 1 3 3 Bit Bit 0x40 (7) 0x80 (8) f[2]
Page 42

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position) 0x80 (8) 0x100 (9)

Unit

Description

Signal: Trip Vector Surge Signal: Trip Command

Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active Signal: External Blocking Signal: Module is blocked by undervoltage. Signal: Trip Command blocked Signal: External Blocking of the Trip Command

37

Struct
EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm f Alarm df/dt | DF/DT 37 37 1 1 3 3 Bit Bit 0x1 (1) 0x2 (2) Trip f (*) 37 1 3 Bit 0x4 (3) Trip df/dt | DF/DT (*) 37 Alarm 37 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) Alarm delta phi Trip (*) 37 37 1 1 3 3 Bit Bit 0x20 (6) 0x40 (7) Trip delta phi (*) TripCmd (*) f[3] ExBlo1-I 37 37 38 38 1 1 1 1 3 3 3 3 Bit Bit Struct Bit 0x1 (1)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Signal: Alarm Frequency Protection Alarm instantaneous or average value of the rate-offrequency-change Signal: Frequency has exceeded the limit. Signal: Trip df/dt or DF/DT Signal: Alarm Frequency Protection (collective signal) Signal: Alarm Vector Surge Signal: Trip Frequency Protection (collective signal) Signal: Trip Vector Surge Signal: Trip Command

0x80 (8) 0x100 (9)

Module input state: External blocking1

Page 43

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo2-I ExBlo TripCmd-I 38 38 1 1 3 3 Bit Bit 0x2 (2) 0x4 (3) active ExBlo Blo by V< 38 38 38 1 1 1 3 3 3 Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) Blo TripCmd ExBlo TripCmd 38 38 1 1 3 3 Bit Bit 0x40 (7) 0x80 (8) f[3] Alarm f Alarm df/dt | DF/DT 39 39 39 1 1 1 3 3 3 Struct Bit Bit 0x1 (1) 0x2 (2) Signal: Alarm Frequency Protection Alarm instantaneous or average value of the rate-offrequency-change Signal: External Blocking Signal: Module is blocked by undervoltage. Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 44

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Trip f (*) 39 1 3 Bit 0x4 (3) Trip df/dt | DF/DT (*) 39 Alarm 39 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) Alarm delta phi Trip (*) 39 39 1 1 3 3 Bit Bit 0x20 (6) 0x40 (7) Trip delta phi (*) TripCmd (*) f[4] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 39 39 40 40 40 40 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command 0x80 (8) 0x100 (9) Signal: Frequency has exceeded the limit. Signal: Trip df/dt or DF/DT Signal: Alarm Frequency Protection (collective signal) Signal: Alarm Vector Surge Signal: Trip Frequency Protection (collective signal) Signal: Trip Vector Surge Signal: Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 45

Appendix - Data Point Lists Module Subgroup Names Functions active ExBlo Blo by V< 40 40 40 1 1 1 3 3 3 Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) Blo TripCmd ExBlo TripCmd 40 40 1 1 3 3 Bit Bit 0x40 (7) 0x80 (8) f[4] Alarm f Alarm df/dt | DF/DT 41 41 41 1 1 1 3 3 3 Struct Bit Bit 0x1 (1) 0x2 (2) Trip f (*) 41 1 3 Bit 0x4 (3) Trip df/dt | DF/DT (*) 41 1 3 Bit 0x8 (4) Signal: Alarm Frequency Protection Alarm instantaneous or average value of the rate-offrequency-change Signal: Frequency has exceeded the limit. Signal: Trip df/dt or DF/DT Signal: External Blocking Signal: Module is blocked by undervoltage. Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 46

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm 41 1 3 Bit 0x10 (5) Alarm delta phi Trip (*) 41 41 1 1 3 3 Bit Bit 0x20 (6) 0x40 (7) Trip delta phi (*) TripCmd (*) f[5] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 41 41 42 42 42 42 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo 42 42 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) Signal: External Blocking Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) Signal: Alarm Frequency Protection (collective signal) Signal: Alarm Vector Surge Signal: Trip Frequency Protection (collective signal) Signal: Trip Vector Surge Signal: Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 47

Appendix - Data Point Lists Module Subgroup Names Functions Blo by V< 42 1 3 Bit 0x20 (6) Blo TripCmd ExBlo TripCmd 42 42 1 1 3 3 Bit Bit 0x40 (7) 0x80 (8) f[5] Alarm f Alarm df/dt | DF/DT 43 43 43 1 1 1 3 3 3 Struct Bit Bit 0x1 (1) 0x2 (2) Trip f (*) 43 1 3 Bit 0x4 (3) Trip df/dt | DF/DT (*) 43 Alarm 43 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) Alarm delta phi 43 1 3 Bit 0x20 (6) Signal: Alarm Frequency Protection Alarm instantaneous or average value of the rate-offrequency-change Signal: Frequency has exceeded the limit. Signal: Trip df/dt or DF/DT Signal: Alarm Frequency Protection (collective signal) Signal: Alarm Vector Surge Signal: Module is blocked by undervoltage. Signal: Trip Command blocked Signal: External Blocking of the Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 48

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Trip (*) 43 1 3 Bit 0x40 (7) Trip delta phi (*) TripCmd (*) f[6] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 43 43 44 44 44 44 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo by V< 44 44 44 1 1 1 3 3 3 Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) Blo TripCmd 44 1 3 Bit 0x40 (7) Signal: External Blocking Signal: Module is blocked by undervoltage. Signal: Trip Command blocked Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) Signal: Trip Frequency Protection (collective signal) Signal: Trip Vector Surge Signal: Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 49

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo TripCmd 44 1 3 Bit 0x80 (8) f[6] Alarm f Alarm df/dt | DF/DT 45 45 45 1 1 1 3 3 3 Struct Bit Bit 0x1 (1) 0x2 (2) Trip f (*) 45 1 3 Bit 0x4 (3) Trip df/dt | DF/DT (*) 45 Alarm 45 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) Alarm delta phi Trip (*) 45 45 1 1 3 3 Bit Bit 0x20 (6) 0x40 (7) Trip delta phi (*) 45 1 3 Bit 0x80 (8) Signal: Alarm Frequency Protection Alarm instantaneous or average value of the rate-offrequency-change Signal: Frequency has exceeded the limit. Signal: Trip df/dt or DF/DT Signal: Alarm Frequency Protection (collective signal) Signal: Alarm Vector Surge Signal: Trip Frequency Protection (collective signal) Signal: Trip Vector Surge Signal: External Blocking of the Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 50

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions TripCmd (*) AR active ExBlo running t-dead 45 46 46 46 46 46 1 1 1 1 1 1 3 3 3 3 3 3 Bit Struct Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x8 (4) 0x10 (5) successful (*) failed (*) CB Pos Detect-I 46 46 46 1 1 1 3 3 3 Bit Bit Bit 0x100 (9) 0x200 (10) 0xc00 (11) Signal: External Blocking Signal: Auto Reclosing running Signal: Dead time between trip and reclosure attempt Signal: Auto Reclosing successful Signal: Auto Reclosing failure Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected. Signal: AR Supervision Signal: active 0x100 (9) Signal: Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

t-AR Supervision AR

46 47

1 1

3 3

Bit Struct

0x1000 (13)

EN MRA4 Modbus 05/10

Page 51

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I Ex Sync running-I 47 47 47 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ready-I CB ON Cmd Pre Shot (*) Shot 1 (*) Shot 2 (*) Shot 3 (*) Shot 4 (*) Shot 5 (*) 47 47 47 47 47 47 47 47 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) 0x200 (10) 0x400 (11) Shot Control Shot Control Shot Control Shot Control Shot Control Module input state: External blocking1 Module input state: External blocking2 Module input state: External synchronism signal Module input state: CB ready Signal: CB switch ON Command Pre Shot Control Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 52

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Shot 6 (*) ExP[1] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 47 49 49 49 49 1 1 1 1 1 3 3 3 3 3 Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Alarm-I Trip-I active ExBlo Blo TripCmd ExBlo TripCmd 49 49 49 49 49 49 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: Alarm Module input state: Trip Signal: active 0x800 (12) Shot Control Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 53

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) ExP[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 49 49 49 50 50 50 50 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Alarm-I Trip-I active ExBlo 50 50 50 50 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: Alarm Module input state: Trip Signal: active 0x200 (10) 0x400 (11) 0x800 (12) Signal: Trip Command Signal: Trip Signal: Alarm Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 54

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Blo TripCmd ExBlo TripCmd 50 50 1 1 3 3 Bit Bit 0x80 (8) 0x100 (9) Alarm Trip (*) TripCmd (*) ExP[3] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 50 50 50 51 51 51 51 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Alarm-I Trip-I 51 51 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Module input state: Alarm Module input state: Trip 0x200 (10) 0x400 (11) 0x800 (12) Signal: Trip Command Signal: Trip Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 55

Appendix - Data Point Lists Module Subgroup Names Functions active ExBlo Blo TripCmd ExBlo TripCmd 51 51 51 51 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Alarm Trip (*) TripCmd (*) ExP[4] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 51 51 51 52 52 52 52 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command 0x200 (10) 0x400 (11) 0x800 (12) Signal: Trip Command Signal: Trip Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 56

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm-I Trip-I active ExBlo Blo TripCmd ExBlo TripCmd 52 52 52 52 52 52 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Alarm Trip (*) TripCmd (*) CBF ExBlo1-I 52 52 52 53 53 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Struct Bit 0x1 (1) Module input state: External blocking1 0x200 (10) 0x400 (11) 0x800 (12) Signal: Trip Command Signal: Trip Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Module input state: Alarm Module input state: Trip Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 57

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo2-I active ExBlo Trigger1 Trigger2 Trigger3 running Alarm (*) VTS Ex Fuse Fail VT-I 53 53 53 53 53 53 53 53 56 56 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit Struct Bit 0x1 (1) Ex Fuse Fail EVT-I 56 1 3 Bit 0x2 (2) Module input state: External fuse failure voltage transformers Module input state: External fuse failure earth voltage transformer 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) 0x100 (9) Signal: External Blocking Module Input: Trigger that will start the CBF Module Input: Trigger that will start the CBF Module Input: Trigger that will start the CBF Signal: CBF-Module started Signal: Circuit Breaker Failure Module input state: External blocking2 Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 58

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I active ExBlo Alarm V 56 56 56 56 56 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Bit Bit 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm 56 1 3 Bit 0x80 (8) Ex FF VT 56 1 3 Bit 0x100 (9) Ex FF EVT 56 1 3 Bit 0x200 (10) Prot FaultNo Prot 57 57 58 1 1 1 3 3 3 Struct Bit Struct 0xffff (1) Disturbance No Signal: External Blocking Signal: Alarm V Voltage Transformer Measuring Circuit Supervision Signal: Alarm Voltage Transformer Measuring Circuit Supervision Signal: Alarm Fuse Failure Voltage Transformers Signal: Alarm Fuse Failure Earth Voltage Transformers Module input state: External blocking1 Module input state: External blocking2 Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 59

Appendix - Data Point Lists Module Subgroup Names Functions No of grid faults 58 1 3 Bit 0xffff (1) Number of grid faults: A grid fault, e.g. a short circuit, might cause several faults with trip and autoreclosing, each fault being identified by an increased fault number. In this case, the grid fault number remains the same. Signal: Parameter Set 1 Signal: Parameter Set 2 Signal: Parameter Set 3 Signal: Parameter Set 4 Signal: Manual Switch over of a Parameter Set Signal: Parameter Set Switch via Scada Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

PSet-Switch PS 1 PS 2 PS 3 PS 4 PSS manual

59 59 59 59 59 59

1 1 1 1 1 1

3 3 3 3 3 3

Struct Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) -

PSS via Scada

59

Bit

0x20 (6)

Page 60

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions PSS via Inp fct 59 1 3 Bit 0x40 (7) PS1-I 59 1 3 Bit 0x80 (8) Signal: Parameter Set Switch via input function State of the module input respectively of the signal, that should activate this Parameter Setting Group. State of the module input respectively of the signal, that should activate this Parameter Setting Group. State of the module input respectively of the signal, that should activate this Parameter Setting Group. State of the module input respectively of the signal, that should activate this Parameter Setting Group. Signal: At least one parameter has been changed Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

PS2-I

59

Bit

0x100 (9)

PS3-I

59

Bit

0x200 (10)

PS4-I

59

Bit

0x400 (11)

min 1 param changed (*) EnergyCr


EN MRA4 Modbus 05/10

59

Bit

0x800 (12)

60

Struct
Page 61

Appendix - Data Point Lists Module Subgroup Names Functions Cr Overflow Wp+ Cr Overflow WpCr Overflow Wq+ Cr Overflow WqCr Overflow Wp Net Cr Overflow Wq Net Cr Overflow Ws Net 60 60 60 60 60 60 60 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Cr OverflwWarn Wp+ 60 Cr OverflwWarn Wp- 60 Cr OverflwWarn Wq+ 60 Cr OverflwWarn Wq- 60 0x80 (8) 0x100 (9) 0x200 (10) 0x400 (11) Signal: Counter Overflow Wp+ Signal: Counter Overflow WpSignal: Counter Overflow Wq+ Signal: Counter Overflow WqSignal: Counter Overflow Wp Net Signal: Counter Overflow Wq Net Signal: Counter Overflow Ws Net Signal: Counter Wp+ will overflow soon Signal: Counter Wpwill overflow soon Signal: Counter Wq+ will overflow soon Signal: Counter Wqwill overflow soon Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 62

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Cr OverflwWarn Wp Net Cr OverflwWarn Wq Net Cr OverflwWarn Ws Net SOTF ExBlo1-I ExBlo2-I Ext SOTF-I 60 1 3 Bit 0x800 (12) 60 1 3 Bit 0x1000 (13) 60 1 3 Bit 0x2000 (14) 65 65 65 65 1 1 1 1 3 3 3 3 Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) Ex rev Interl-I 65 1 3 Bit 0x8 (4) active ExBlo Ex rev Interl 65 65 65 1 1 1 3 3 3 Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: External reverse Interlocking Module input state: External blocking Module input state: External blocking Module input state: External Switch Onto Fault Alarm Module input state: External reverse interlocking Signal: active Signal: Counter Wp Net will overflow soon Signal: Counter Wq Net will overflow soon Signal: Counter Ws Net will overflow soon Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 63

Appendix - Data Point Lists Module Subgroup Names Functions CB Pos Detect-I 65 1 3 Bit 0x300 (9) Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected. Signal: Blocked by AR Signal: Switch Onto Fault enabled. This Signal can be used to modify Overcurrent Protection Settings. Module input state: Circuit breaker was switched on manually Signal: No Load Current. Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

AR Blo enabled

65 65

1 1

3 3

Bit Bit

0x400 (11) 0x800 (12)

Manual ON-I (*)

65

Bit

0x1000 (13)

I< CLPU ExBlo1-I ExBlo2-I Ex rev Interl-I

65 66 66 66 66

1 1 1 1 1

3 3 3 3 3

Bit Struct Bit Bit Bit

0x2000 (14) 0x1 (1) 0x2 (2) 0x4 (3)

Module input state: External blocking Module input state: External blocking Module input state: External reverse interlocking

Page 64

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions active ExBlo Ex rev Interl CB Pos Detect-I 66 66 66 66 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x180 (8) Signal: External Blocking Signal: External reverse Interlocking Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected. Signal: Cold Load enabled Signal: Cold Load detected Signal: No Load Current. Module input state: AR Blo Signal: Load Inrush Signal: Settle Time Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

enabled detected (*) I< AR Blo Load Inrush Settle Time PQS [1]

66 66 66 66 66 66 67

1 1 1 1 1 1 1

3 3 3 3 3 3 3

Bit Bit Bit Bit Bit Bit Struct

0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) 0x2000 (14) 0x4000 (15)

EN MRA4 Modbus 05/10

Page 65

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 67 67 67 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 67 67 67 67 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) PQS [2] 67 67 67 68 1 1 1 1 3 3 3 3 Bit Bit Bit Struct 0x80 (8) 0x100 (9) 0x200 (10) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Protection Signal: Trip Power Protection Signal: Trip Command Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 66

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 68 68 68 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 68 68 68 68 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) PQS [3] 68 68 68 69 1 1 1 1 3 3 3 3 Bit Bit Bit Struct 0x80 (8) 0x100 (9) 0x200 (10) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Protection Signal: Trip Power Protection Signal: Trip Command Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 67

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 69 69 69 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 69 69 69 69 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) PQS [4] 69 69 69 70 1 1 1 1 3 3 3 3 Bit Bit Bit Struct 0x80 (8) 0x100 (9) 0x200 (10) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Protection Signal: Trip Power Protection Signal: Trip Command Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 68

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 70 70 70 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 70 70 70 70 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) PQS [5] 70 70 70 71 1 1 1 1 3 3 3 3 Bit Bit Bit Struct 0x80 (8) 0x100 (9) 0x200 (10) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Protection Signal: Trip Power Protection Signal: Trip Command Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 69

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 71 71 71 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 71 71 71 71 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) PQS [6] 71 71 71 72 1 1 1 1 3 3 3 3 Bit Bit Bit Struct 0x80 (8) 0x100 (9) 0x200 (10) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Protection Signal: Trip Power Protection Signal: Trip Command Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 70

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 72 72 72 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 72 72 72 72 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) PF[1] 72 72 72 73 1 1 1 1 3 3 3 3 Bit Bit Bit Struct 0x80 (8) 0x100 (9) 0x200 (10) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Protection Signal: Trip Power Protection Signal: Trip Command Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 71

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo1-I ExBlo2-I ExBlo TripCmd-I 73 73 73 1 1 1 3 3 3 Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 73 73 73 73 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) TripCmd (*) Compensator 73 73 73 73 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x80 (8) 0x100 (9) 0x200 (10) 0x400 (11) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Factor Signal: Trip Power Factor Signal: Trip Command Signal: Compensation Signal Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 72

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Impossible PF[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 73 74 74 74 74 1 1 1 1 1 3 3 3 3 3 Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 74 74 74 74 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Trip (*) 74 74 1 1 3 3 Bit Bit 0x80 (8) 0x100 (9) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm Power Factor Signal: Trip Power Factor Module input state: External blocking Module input state: External blocking Module input state: External Blocking of the Trip Command Signal: active 0x800 (12) Signal: Alarm Power Factor Impossible Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 73

Appendix - Data Point Lists Module Subgroup Names Functions TripCmd (*) Compensator Impossible I2>[1] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 74 74 74 82 82 82 82 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 82 82 82 82 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x200 (10) 0x400 (11) 0x800 (12) Signal: Trip Command Signal: Compensation Signal Signal: Alarm Power Factor Impossible Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 74

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) I2>[2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 82 82 82 83 83 83 83 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 83 83 83 83 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm Negative Sequence Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 75

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) V[5] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 83 83 83 92 92 92 92 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 92 92 92 92 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm Negative Sequence Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 76

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Alarm L1 Alarm L2 Alarm L3 Trip (*) Trip L1 (*) Trip L2 (*) Trip L3 (*) TripCmd (*) V[6] ExBlo1-I ExBlo2-I 92 92 92 92 92 92 92 92 92 93 93 93 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit Bit Struct Bit Bit 0x1 (1) 0x2 (2)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position) 0x80 (8) 0x100 (9) 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) 0x2000 (14) 0x4000 (15) 0x8000 (16)

Unit

Description

Signal: Alarm voltage stage Signal: Alarm L1 Signal: Alarm L2 Signal: Alarm L3 Signal: Trip Signal: General Trip Phase L1 Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Command

Module input state: External blocking1 Module input state: External blocking2

Page 77

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo TripCmd-I 93 1 3 Bit 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 93 93 93 93 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Alarm Alarm L1 Alarm L2 Alarm L3 Trip (*) Trip L1 (*) 93 93 93 93 93 93 1 1 1 1 1 1 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit 0x80 (8) 0x100 (9) 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) Signal: General Trip Phase L1 Signal: Trip Signal: Alarm L3 Signal: Alarm L2 Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Signal: Alarm voltage stage Signal: Alarm L1 Module input state: External Blocking of the Trip Command Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 78

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Trip L2 (*) Trip L3 (*) TripCmd (*) V 012 [1] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 93 93 93 100 100 100 100 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 100 100 100 100 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x2000 (14) 0x4000 (15) 0x8000 (16) Signal: General Trip Phase L2 Signal: General Trip Phase L3 Signal: Trip Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 79

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) V 012 [2] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 100 100 100 101 101 101 101 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 101 101 101 101 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm voltage asymmetry Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 80

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) V 012 [3] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 101 101 101 102 102 102 102 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 102 102 102 102 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm voltage asymmetry Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 81

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) V 012 [4] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 102 102 102 103 103 103 103 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 103 103 103 103 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm voltage asymmetry Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 82

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) V 012 [5] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 103 103 103 104 104 104 104 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 104 104 104 104 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm voltage asymmetry Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 83

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) V 012 [6] ExBlo1-I ExBlo2-I ExBlo TripCmd-I 104 104 104 105 105 105 105 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) active ExBlo Blo TripCmd ExBlo TripCmd 105 105 105 105 1 1 1 1 3 3 3 3 Bit Bit Bit Bit 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: External Blocking Signal: Trip Command blocked Signal: External Blocking of the Trip Command Module input state: External blocking1 Module input state: External blocking2 Module input state: External Blocking of the Trip Command Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm voltage asymmetry Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 84

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Alarm Trip (*) TripCmd (*) BW ExBlo1-I ExBlo2-I active ExBlo Isum Intr trip 105 105 105 123 123 123 123 123 123 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 Bit Bit Bit Struct Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) Signal: External Blocking Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded in at least one phase. Module input state: External blocking1 Module input state: External blocking2 Signal: active 0x80 (8) 0x100 (9) 0x200 (10) Signal: Trip Command Signal: Alarm voltage asymmetry Signal: Trip Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 85

Appendix - Data Point Lists Module Subgroup Names Functions Isum Intr trip: IL1 123 1 3 Bit 0x20 (6) Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded: IL1 Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded: IL2 Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded: IL3 Signal: Service Alarm, too many Operations Module input state: External blocking1 Module input state: External blocking2 Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Isum Intr trip: IL2

123

Bit

0x40 (7)

Isum Intr trip: IL3

123

Bit

0x80 (8)

Operations Alarm

123

Bit

0x100 (9)

CTS ExBlo1-I ExBlo2-I active

137 137 137 137

1 1 1 1

3 3 3 3

Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) -

Page 86

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo Alarm 137 137 1 1 3 3 Bit Bit 0x8 (4) 0x10 (5) IRIG-B active inverted Control Signal1 Control Signal2 Control Signal4 Control Signal5 Control Signal6 Control Signal7 148 148 148 148 148 148 148 148 148 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) Signal: IRIG-B inverted Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: active Signal: External Blocking Signal: Alarm Current Transformer Measuring Circuit Supervision Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 87

Appendix - Data Point Lists Module Subgroup Names Functions Control Signal8 Control Signal9 Control Signal10 Control Signal11 Control Signal12 Control Signal13 Control Signal14 Control Signal15 IRIG-B Control Signal16 Control Signal17 Control Signal18 148 148 148 148 148 148 148 148 149 149 149 149 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit Struct Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3)
Page 88

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position) 0x100 (9) 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) 0x2000 (14) 0x4000 (15) 0x8000 (16)

Unit

Description

Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal

Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal Signal: IRIG-B Control Signal

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions TCS ExBlo1-I ExBlo2-I active ExBlo Alarm Not Possible 150 150 150 150 150 150 150 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) CB Pos Detect-I 150 1 3 Bit 0xc0 (7) Signal: External Blocking Signal: Alarm Trip Circuit Supervision Not possible because no state indicator assigned to the breaker. Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected. Position indicator/check-back signal of the CB (52a) Module input state: External blocking1 Module input state: External blocking2 Signal: active Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Aux ON

150

Bit

0x100 (9)

EN MRA4 Modbus 05/10

Page 89

Appendix - Data Point Lists Module Subgroup Names Functions Aux OFF 150 1 3 Bit 0x200 (10) Module input state: Position indicator/check-back signal of the CB (52b) Module input state: External AR lockout. Module input state: The AR Shot counter will be incremented by this external Signal. This can be used for Zone Coordination (of upstream Auto Reclosure devices). Note: This parameter enables the functionallity only. The assignment has to be set within the global parameters. Signal: Auto Reclosure is blocked Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

AR Ex Lock-I Ex Shot Inc-I

156 156 156

1 1 1

3 3 3

Struct Bit Bit 0x1 (1) 0x2 (2) -

Blo

156

Bit

0x4 (3)

Page 90

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions t-Blo after CB man ON 156 1 3 Bit 0x8 (4) Signal: AR blocked after circuit breaker was switched on manually. This timer will be started if the circuit breaker was switched on manually. While this timer is running, AR cannot be started. Signal: Auto Reclosure is locked out Signal: Delay Timer for resetting the AR lockout. The reset of the AR lockout state will be delayed for this time, after the reset signal (e.g digital input or Scada) has been detected . Signal: Ready to shoot Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Lock

156

Bit

0x10 (5)

t-Reset Lockout

156

Bit

0x20 (6)

Ready

156

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 91

Appendix - Data Point Lists Module Subgroup Names Functions t-Run2Ready 156 1 3 Bit 0x80 (8) Signal: Examination Time: If the Circuit Breaker remains after an reclosure attempt for the duration of this timer in the Closed position, the AR has been successful and the AR module returns into the ready state. Signal: Standby Signal: AR - Service Alarm 1, too many switching operations Signal: AR - Service Alarm 2 - too many switching operations Signal: The maximum allowed number of shots per hour has been exceeded. Module input state: External blocking1 Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Standby Service Alarm 1

156 156

1 1

3 3

Bit Bit

0x100 (9) 0x200 (10)

Service Alarm 2

156

Bit

0x400 (11)

Max Shots / h exceeded

156

Bit

0x800 (12)

Q->&V< ExBlo1-I

157 157

1 1

3 3

Struct Bit 0x1 (1) -

Page 92

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions ExBlo2-I active ExBlo Fuse Fail VT Blo Alarm 157 157 157 157 157 1 1 1 1 1 3 3 3 3 3 Bit Bit Bit Bit Bit 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) V Ext Release PCC 157 1 3 Bit 0x40 (7) Signal: External Blocking Signal: Blocked by Fuse Failure (VT) Signal: Alarm Reactive Power Undervoltage Protection Module input state: Release signal is beeing generated by the PCC (External Release) Signal: Voltage Release from the Point of Common Coupling Signal: Release Energy Resource. Internal (local) voltage release Signal: Decoupling at the Point of Common Coupling
Page 93

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Module input state: External blocking2 Signal: active

PCC (External Release)

157

Bit

0x80 (8)

Release Energy Resource

157

Bit

0x100 (9)

Decoupling PCC

157

Bit

0x200 (10)

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Decoupling Energy Resource DI Slot X1 DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 DI Slot X6 DI 1 157 1 3 Bit 0x400 (11) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1001 1001 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 Struct Bit Bit Bit Bit Bit Bit Bit Bit Struct Bit 0x1 (1) Signal: Digital Input 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8) Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Decoupling of the (local) Energy Resource Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 94

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 BO Slot X2 BO 1 BO 2 BO 3 BO 4 1001 1001 1001 1001 1001 1001 1001 1003 1003 1003 1003 1003 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Struct Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) 0x80 (8)

Unit

Description

Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input Signal: Digital Input

Signal: Binary Output Relay Signal: Binary Output Relay Signal: Binary Output Relay Signal: Binary Output Relay

Page 95

Appendix - Data Point Lists Module Subgroup Names Functions BO 5 BO 6 DISARMED! 1003 1003 1003 1 1 1 3 3 3 Bit Bit Bit 0x10 (5) 0x20 (6) 0x40 (7) Signal: Binary Output Relay Signal: Binary Output Relay Signal: CAUTION! RELAYS DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process offline. (Note: The Self Supervision Contact cannot be disarmed). YOU MUST ENSURE that the relays are ARMED AGAIN after maintenance Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals. Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Outs forced

1003

Bit

0x80 (8)

BO Slot X5

1004

Struct

Page 96

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions BO 1 BO 2 BO 3 BO 4 BO 5 BO 6 DISARMED! 1004 1004 1004 1004 1004 1004 1004 1 1 1 1 1 1 1 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) Signal: Binary Output Relay Signal: Binary Output Relay Signal: Binary Output Relay Signal: Binary Output Relay Signal: Binary Output Relay Signal: Binary Output Relay Signal: CAUTION! RELAYS DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process offline. (Note: The Self Supervision Contact cannot be disarmed). YOU MUST ENSURE that the relays are ARMED AGAIN after maintenance Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 97

Appendix - Data Point Lists Module Subgroup Names Functions Outs forced 1004 1 3 Bit 0x80 (8) Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals. Scada Command Scada Command Scada Command Scada Command Scada Command Scada Command Scada Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Modbus Scada Cmd 1 Scada Cmd 2 Scada Cmd 3 Scada Cmd 4 Scada Cmd 5 Scada Cmd 6 Scada Cmd 7

1005 1005 1005 1005 1005 1005 1005 1005

1 1 1 1 1 1 1 1

3 3 3 3 3 3 3 3

Struct Bit Bit Bit Bit Bit Bit Bit 0x1 (1) 0x2 (2) 0x4 (3) 0x8 (4) 0x10 (5) 0x20 (6) 0x40 (7) -

Page 98

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Scada Cmd 8 Scada Cmd 9 Scada Cmd 10 Scada Cmd 11 Scada Cmd 12 Scada Cmd 13 Scada Cmd 14 Scada Cmd 15 Scada Cmd 16 Modbus Transmission CB 1005 1005 1005 1005 1005 1005 1005 1005 1005 1006 1006 1010 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 Bit Bit Bit Bit Bit Bit Bit Bit Bit Struct Bit Struct 0x1 (1) Signal: SCADA active 0x80 (8) 0x100 (9) 0x200 (10) 0x400 (11) 0x800 (12) 0x1000 (13) 0x2000 (14) 0x4000 (15) 0x8000 (16) Scada Command Scada Command Scada Command Scada Command Scada Command Scada Command Scada Command Scada Command Scada Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 99

Appendix - Data Point Lists Module Subgroup Names Functions Ready 1010 1 3 Bit 0x1 (1) Pos 1010 1 3 Bit 0x6 (2) Signal: Circuit breaker is ready for operation. Signal: Circuit Breaker Position (0 = Indeterminate, 1 = OFF, 2 = ON, 3 = Disturbed) Signal: Circuit Breaker is in Indeterminate Position Signal: Circuit Breaker is in OFFPosition Signal: Circuit Breaker is in ONPosition Signal: Circuit Breaker Disturbed Undefined Breaker Position. The Position Indicators contradict themselves. After expiring of a supervision timer this signal becomes true. Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Pos Indeterm

1010

Bit

0x8 (4)

Pos OFF

1010

Bit

0x10 (5)

Pos ON

1010

Bit

0x20 (6)

Pos Disturb

1010

Bit

0x40 (7)

Legend * = These Signals have to be acknowledged by the Scada System.

Page 100

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Measuring values
Module Subgroup Names Functions Date and Time y m d h min ms BW TripCmd Cr 20000 20000 20000 20000 20000 20000 20000 20006 6 6 6 6 6 6 6 2 4 4 4 4 4 4 4 4 Struct Short Short Short Short Short Short Float IEE754 Word 0 (1) Word 1 (17) Word 2 (33) Word 3 (49) Word 4 (65) Word 5 (81) Counter: Total number of trips of the switchgear (circuit breaker, load break switch). Build Operating hours counter milliseconds minute hours days month year Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Values Values

Build Operating hours Cr

20008 20010

2 2

4 4

Float IEE754 Float IEE754

EN MRA4 Modbus 05/10

Page 101

Appendix - Data Point Lists Module Subgroup Names Functions Current IL1 20100 2 4 Float IEE754 A Measured value: Phase current (fundamental) Measured value: Phase current (fundamental) Measured value: Phase current (fundamental) Measured value (measured): IG (fundamental) Measured value: Thermal Capacity Used Measured value (calculated/measured ): Remaining time until the thermal overload module will trip Measured value (calculated): Zero current (fundamental) Measured value (calculated): Positive phase sequence current (fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current

IL2

20102

Float IEE754

Current

IL3

20104

Float IEE754

Current

IG meas

20106

Float IEE754

ThR

Thermal Cap Used

20110

Float IEE754

ThR

Time To Trip

20112

Float IEE754

Current

I0

20114

Float IEE754

Current

I1

20116

Float IEE754

Page 102

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Current I2 20118 2 4 Float IEE754 A Measured value (calculated): Unbalanced load current (fundamental) Measured value: 2nd harmonic/1st harmonic of IL1 Measured value: 2nd harmonic/1st harmonic of IL2 Measured value: 2nd harmonic/1st harmonic of IL3 Measured value: 2nd harmonic/1st harmonic of IG (measured) Measured value: Frequency Measured value: Phase-to-phase voltage (fundamental) Measured value: Phase-to-phase voltage (fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current

IL1 H2

20120

Float IEE754

Current

IL2 H2

20122

Float IEE754

Current

IL3 H2

20124

Float IEE754

Current

IG H2 meas

20126

Float IEE754

Voltage Voltage

f VL12

20128 20130

2 2

4 4

Float IEE754 Float IEE754

Hz V

Voltage

VL23

20132

Float IEE754

EN MRA4 Modbus 05/10

Page 103

Appendix - Data Point Lists Module Subgroup Names Functions Voltage VL31 20134 2 4 Float IEE754 V Measured value: Phase-to-phase voltage (fundamental) Measured value: Phase-to-neutral voltage (fundamental) Measured value: Phase-to-neutral voltage (fundamental) Measured value: Phase-to-neutral voltage (fundamental) Measured value (measured): VG measured (fundamental) Measured value (calculated): Symmetrical components Zero voltage(fundamental) Measured value (calculated): Symmetrical components positive phase sequence voltage(fundamental)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Voltage

VL1

20136

Float IEE754

Voltage

VL2

20138

Float IEE754

Voltage

VL3

20140

Float IEE754

Voltage

VG meas

20142

Float IEE754

Voltage

V0

20146

Float IEE754

Voltage

V1

20148

Float IEE754

Page 104

Appendix - Data Point Lists Module Subgroup Names Functions Voltage V2 20150 2 4 Float IEE754 V Measured value (calculated): Symmetrical components negative phase sequence voltage(fundamental) Measured value (calculated): Power factor Measured value (calculated): Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (fundamental) Measured value (calculated): Reactive power (Q- = Fed Reactive Power, Q+ = Consumpted Reactive Power) (fundamental) Measured Value (Calculated): Apparent power (fundamental) Measured value (calculated): IG (fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EnergyCr

cos phi

20152

Float IEE754

EnergyCr

20154

Float IEE754

EnergyCr

20156

Float IEE754

VAr

EnergyCr

20158

Float IEE754

VA

Current

IG calc

20160

Float IEE754

EN MRA4 Modbus 05/10

Page 105

Appendix - Data Point Lists Module Subgroup Names Functions Voltage VG calc 20162 2 4 Float IEE754 V Measured value (calculated): VG (fundamental) Total number of all executed Automatic Reclosures Attempts Total number of unsuccessfully executed automatic reclosure attempts Total number of successfully executed Automatic Reclosures Remaining numbers of ARs until Service Alarm 1 Remaining numbers of ARs until Service Alarm 2 Positive Active Power is consumed active energy Negative Active Power (Fed Energy) Positive Reactive Power is consumed Reactive Energy Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

AR

Total number Cr

20164

Float IEE754

AR

Cr failed

20166

Float IEE754

AR

Cr successfl

20168

Float IEE754

AR

Cr Service Alarm1

20170

Float IEE754

AR

Cr Service Alarm2

20172

Float IEE754

EnergyCr

Wp+

20174

Float IEE754

kWh

EnergyCr EnergyCr

WpWq+

20176 20178

2 2

4 4

Float IEE754 Float IEE754

kWh kVArh

Page 106

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions EnergyCr BW WqSum trip IL1 20180 20182 2 2 4 4 Float IEE754 Float IEE754 kVArh A Negative Reactive Power (Fed Energy) Summation of the tripping currents phase1 Summation of the tripping currents phase2 Summation of the tripping currents phase3 Counter - Auto Reclosure Attempts Measured value (calculated): Angle of Phasor IG calc Measured value: Angle of Phasor IG meas Measured value (calculated): Angle of Phasor IL1 Measured value (calculated): Angle of Phasor IL2 Measured value (calculated): Angle of Phasor IL3 Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

BW

Sum trip IL2

20184

Float IEE754

BW

Sum trip IL3

20186

Float IEE754

AR Current

AR Shot No. phi IG calc

20188 20200

2 2

4 4

Float IEE754 Float IEE754

Current

phi IG meas

20202

Float IEE754

Current

phi IL1

20204

Float IEE754

Current

phi IL2

20206

Float IEE754

Current

phi IL3

20208

Float IEE754

EN MRA4 Modbus 05/10

Page 107

Appendix - Data Point Lists Module Subgroup Names Functions IRIG-B IRIG-B Edges NoOfFrameErrors 20298 20300 2 2 4 4 Float IEE754 Float IEE754 Edges Total Number of Frame Errors. Physically corrupted Frame. Total Number valid Frames. Measured value: Phase current (RMS) Measured value: Phase current (RMS) Measured value: Phase current (RMS) Measured value (measured): IG (RMS) Measured value (calculated): IG (RMS) Counter for the maximum allowed shots per hour. Measured value (calculated): I2/I1 if ABC, I1/I2 if CBA Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

IRIG-B Current Current Current Current

NoOfFramesOK IL1 RMS IL2 RMS IL3 RMS IG meas RMS

20302 20316 20318 20320 20322

2 2 2 2 2

4 4 4 4 4

Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754

A A A A

Current

IG calc RMS

20324

Float IEE754

AR

Max Shots / h Cr

20374

Float IEE754

Current

%(I2/I1)

20376

Float IEE754

Page 108

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Current phi I0 20378 2 4 Float IEE754 Measured value (calculated): Angle Zero Sequence System Measured value (calculated): Angle of Positive Sequence System Measured Value (calculated): Angle of Negative Sequence System Measured value (calculated): Angle of Phasor VG calc Measured value: Angle of Phasor VG meas Measured value (calculated): Angle of Phasor VL12 Measured value (calculated): Angle of Phasor VL1 Measured value (calculated): Angle of Phasor VL23 Measured value (calculated): Angle of Phasor VL2
Page 109

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Current

phi I1

20380

Float IEE754

Current

phi I2

20382

Float IEE754

Voltage

phi VG calc

20386

Float IEE754

Voltage

phi VG meas

20388

Float IEE754

Voltage

phi VL12

20390

Float IEE754

Voltage

phi VL1

20392

Float IEE754

Voltage

phi VL23

20394

Float IEE754

Voltage

phi VL2

20396

Float IEE754

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Voltage phi VL31 20398 2 4 Float IEE754 Measured value (calculated): Angle of Phasor VL31 Measured value (calculated): Angle of Phasor VL3 Measured value (calculated): Angle Zero Sequence System Measured value (calculated): Angle of Positive Sequence System Measured Value (calculated): Angle of Negative Sequence System Measured value (calculated): VG (RMS) Measured value (measured): VG measured (RMS) Measured value: Phase-to-neutral voltage (RMS) Measured value: Phase-to-phase voltage (RMS)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Voltage

phi VL3

20400

Float IEE754

Voltage

phi V0

20402

Float IEE754

Voltage

phi V1

20404

Float IEE754

Voltage

phi V2

20406

Float IEE754

Voltage

VG calc RMS

20432

Float IEE754

Voltage

VG meas RMS

20434

Float IEE754

Voltage

VL1 RMS

20436

Float IEE754

Voltage

VL12 RMS

20438

Float IEE754

Page 110

Appendix - Data Point Lists Module Subgroup Names Functions Voltage VL2 RMS 20440 2 4 Float IEE754 V Measured value: Phase-to-neutral voltage (RMS) Measured value: Phase-to-phase voltage (RMS) Measured value: Phase-to-neutral voltage (RMS) Measured value: Phase-to-phase voltage (RMS) Measured value (calculated): %V2/V1 if ABC, %V1/V2 if CBA Measured value (calculated): Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (RMS) Measured Value (Calculated): Apparent power (RMS) Measured value (calculated): Power factor Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Voltage

VL23 RMS

20442

Float IEE754

Voltage

VL3 RMS

20444

Float IEE754

Voltage

VL31 RMS

20446

Float IEE754

Voltage

%(V2/V1)

20450

Float IEE754

EnergyCr

P RMS

20452

Float IEE754

EnergyCr

S RMS

20454

Float IEE754

VA

EnergyCr

cos phi RMS

20456

Float IEE754

EN MRA4 Modbus 05/10

Page 111

Appendix - Data Point Lists Module Subgroup Names Functions EnergyCr EnergyCr EnergyCr EnergyCr Wp Net Wq Net Ws Net P1 20460 20462 20464 20496 2 2 2 2 4 4 4 4 Float IEE754 Float IEE754 Float IEE754 Float IEE754 kWh kVArh kVAh W Absolute Active Power Hours Absolute Reactive Power Hours Absolute Apparent Power Hours Measured value (calculated): Active power in positive sequence system (P= Fed Active Power, P+ = Consumpted Active Power) Measured value (calculated): Reactive power in positive sequence system (Q- = Fed Reactive Power, Q+ = Consumpted Reactive Power) Measured value (calculated): 2nd harmonic/1st harmonic of IG (calculated) Average frequency value Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EnergyCr

Q1

20498

Float IEE754

VAr

Current

IG H2 calc

20500

Float IEE754

Voltage

f avg

21000

Float IEE754

Hz

Page 112

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage f max f min VL12 avg VL12 max VL12 min VL23 avg VL23 max VL23 min VL31 avg VL31 max VL31 min 21002 21004 21006 21008 21010 21012 21014 21016 21018 21020 21022 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Hz Hz V V V V V V V V V Max. frequency value Min. frequency value VL12 average value (fundamental) VL12 maximum value (fundamental) VL12 minimum value (fundamental) VL23 average value (fundamental) VL23 maximum value (fundamental) VL23 minimum value (fundamental) VL31 average value (fundamental) VL31 maximum value (fundamental) VL31 minimum value (fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 113

Appendix - Data Point Lists Module Subgroup Names Functions Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage VL1 avg VL1 max VL1 min VL2 avg VL2 max VL2 min VL3 avg VL3 max VL3 min V1 avg 21024 21026 21028 21030 21032 21034 21036 21038 21040 21042 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 V V V V V V V V V V VL1 average value (fundamental) VL1 maximum value (fundamental) VL1 minimum value (fundamental) VL2 average value (fundamental) VL2 maximum value (fundamental) VL2 minimum value (fundamental) VL3 average value (fundamental) VL3 maximum value (fundamental) VL3 minimum value (fundamental) Average value: Symmetrical components positive phase sequence voltage(fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 114

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Voltage V1 max 21044 2 4 Float IEE754 V Maximum value: Symmetrical components positive phase sequence voltage(fundamental) Minimum value: Symmetrical components positive phase sequence voltage(fundamental) Average value: Symmetrical components negative phase sequence voltage(fundamental) Maximum value: Symmetrical components negative phase sequence voltage(fundamental) Minimum value: Symmetrical components negative phase sequence voltage(fundamental) IL1 average value (fundamental) IL1 maximum value (fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Voltage

V1 min

21046

Float IEE754

Voltage

V2 avg

21048

Float IEE754

Voltage

V2 max

21050

Float IEE754

Voltage

V2 min

21052

Float IEE754

Current Current

IL1 avg IL1 max

21054 21056

2 2

4 4

Float IEE754 Float IEE754

A A

EN MRA4 Modbus 05/10

Page 115

Appendix - Data Point Lists Module Subgroup Names Functions Current Current Current Current Current Current Current Current IL1 min IL2 avg IL2 max IL2 min IL3 avg IL3 max IL3 min I1 avg 21058 21060 21062 21064 21066 21068 21070 21072 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 A A A A A A A A IL1 minimum value (fundamental) IL2 average value (fundamental) IL2 maximum value (fundamental) IL2 minimum value (fundamental) IL3 average value (fundamental) IL3 maximum value (fundamental) IL3 minimum value (fundamental) Average value positive phase sequence current (fundamental) Maximum value positive phase sequence current (fundamental) Minimum value positive phase sequence current (fundamental)
EN MRA4 Modbus 05/10

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask / (Bit Position)

Unit

Description

Current

I1 max

21074

Float IEE754

Current

I1 min

21076

Float IEE754

Page 116

Appendix - Data Point Lists Module Subgroup Names Functions Current I2 avg 21078 2 4 Float IEE754 A Average value unbalanced load current (fundamental) Maximum value unbalanced load (fundamental) Minimum value unbalanced load current (fundamental) Thermal Capacity average value Thermal Capacity maximum value Thermal Capacity minimum value Average of the power factor Maximum value of the power factor Minimum value of the power factor Average of the active power (fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current

I2 max

21080

Float IEE754

Current

I2 min

21082

Float IEE754

ThR ThR ThR EnergyCr EnergyCr EnergyCr EnergyCr

Thermal Cap avg Thermal Cap max Thermal Cap min cos phi avg cos phi max cos phi min P avg

21084 21086 21088 21090 21092 21094 21096

2 2 2 2 2 2 2

4 4 4 4 4 4 4

Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754

% % % W

EN MRA4 Modbus 05/10

Page 117

Appendix - Data Point Lists Module Subgroup Names Functions EnergyCr P max 21098 2 4 Float IEE754 W Maximum value of the active power (fundamental) Minimum value of the active power (fundamental) Average of the reactive power (fundamental) Maximum value of the reactive power (fundamental) Minimum value of the reactive power (fundamental) Average of the apparent power (fundamental) Maximum value of the apparent power (fundamental) Minimum value of the apparent power (fundamental) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EnergyCr

P min

21100

Float IEE754

EnergyCr

Q avg

21102

Float IEE754

VAr

EnergyCr

Q max

21104

Float IEE754

VAr

EnergyCr

Q min

21106

Float IEE754

VAr

EnergyCr

S avg

21108

Float IEE754

VA

EnergyCr

S max

21110

Float IEE754

VA

EnergyCr

S min

21112

Float IEE754

VA

Page 118

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Statistics MeasPointNo 21114 2 4 Float IEE754 Each measuring point that is taken over by the statistics increments this counter. By means of this counter, the User can check whether the statistics are alive and if data are being acquired. IL1 average value (RMS) IL2 average value (RMS) IL3 average value (RMS) IL1 maximum value (RMS) IL2 maximum value (RMS) IL3 maximum value (RMS) IL1 minimum value (RMS) IL2 minimum value (RMS) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current Current Current Current Current Current Current Current

IL1 avg RMS IL2 avg RMS IL3 avg RMS IL1 max RMS IL2 max RMS IL3 max RMS IL1 min RMS IL2 min RMS

21130 21132 21134 21136 21138 21140 21142 21144

2 2 2 2 2 2 2 2

4 4 4 4 4 4 4 4

Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754

A A A A A A A A

EN MRA4 Modbus 05/10

Page 119

Appendix - Data Point Lists Module Subgroup Names Functions Current Current IL3 min RMS IG H2 meas avg 21146 21220 2 2 4 4 Float IEE754 Float IEE754 A % IL3 minimum value (RMS) Measured value: Average ratio of 2nd harmonic over fundamental of IG (measured) Measured value: Maximum ratio of 2nd harmonic over fundamental of IG (measured) Measured value: Minimum ratio of 2nd harmonic over fundamental of IG (measured) Average ratio of 2nd harmonic over fundamental of IL1 Maximum ratio of 2nd harmonic over fundamental of IL1 Minimum ratio of 2nd harmonic over fundamental of IL1 Average ratio of 2nd harmonic over fundamental of IL2 Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current

IG H2 meas max

21222

Float IEE754

Current

IG H2 meas min

21224

Float IEE754

Current

IL1 H2 avg

21226

Float IEE754

Current

IL1 H2 max

21228

Float IEE754

Current

IL1 H2 min

21230

Float IEE754

Current

IL2 H2 avg

21232

Float IEE754

Page 120

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Current IL2 H2 max 21234 2 4 Float IEE754 % Maximum ratio of 2nd harmonic over fundamental of IL2 Minimum ratio of 2nd harmonic over fundamental of IL2 Average ratio of 2nd harmonic over fundamental of IL3 Maximum ratio of 2nd harmonic over fundamental of IL3 Minimum ratio of 2nd harmonic/1st harmonic minimum value of IL3 Measured value (calculated):IG average value (RMS) Measured value (calculated):IG maximum value (RMS) Measured value (calculated):IG minimum value (RMS) Measured value: IG average value (RMS) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current

IL2 H2 min

21236

Float IEE754

Current

IL3 H2 avg

21238

Float IEE754

Current

IL3 H2 max

21240

Float IEE754

Current

IL3 H2 min

21242

Float IEE754

Current

IG calc avg RMS

21454

Float IEE754

Current

IG calc max RMS

21456

Float IEE754

Current

IG calc min RMS

21458

Float IEE754

Current

IG meas avg RMS

21460

Float IEE754

EN MRA4 Modbus 05/10

Page 121

Appendix - Data Point Lists Module Subgroup Names Functions Current IG meas max RMS 21462 2 4 Float IEE754 A Measured value: IG maximum value (RMS) Measured value: IG minimum value (RMS) Measured value (calculated): I2/I1 maximum value if ABC, I1/I2 if CBA Measured value (calculated): I2/I1 maximum value if ABC, I1/I2 if CBA %(I2/I1) min Measured value (calculated):VG average value (RMS) Measured value (calculated):VG maximum value (RMS) Measured value (calculated):VG minimum value (RMS) Measured value: VG average value (RMS) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current

IG meas min RMS

21464

Float IEE754

Current

%(I2/I1) avg

21466

Float IEE754

Current

%(I2/I1) max

21468

Float IEE754

Current Voltage

%(I2/I1) min VG calc avg RMS

21470 21496

2 2

4 4

Float IEE754 Float IEE754

% V

Voltage

VG calc max RMS

21498

Float IEE754

Voltage

VG calc min RMS

21500

Float IEE754

Voltage

VG meas avg RMS

21502

Float IEE754

Page 122

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Voltage VG meas max RMS 21504 2 4 Float IEE754 V Measured value: VG maximum value (RMS) Measured value: VG minimum value (RMS) VL12 average value (RMS) VL12 maximum value (RMS) VL12 average value (RMS) VL1 average value (RMS) VL1 maximum value (RMS) VL1 minimum value (RMS) VL23 average value (RMS) VL23 maximum value (RMS) VL23 average value (RMS) Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Voltage

VG meas min RMS

21506

Float IEE754

Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage

VL12 avg RMS VL12 max RMS VL12 min RMS VL1 avg RMS VL1 max RMS VL1 min RMS VL23 avg RMS VL23 max RMS VL23 min RMS

21508 21510 21512 21514 21516 21518 21520 21522 21524

2 2 2 2 2 2 2 2 2

4 4 4 4 4 4 4 4 4

Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754

V V V V V V V V V

EN MRA4 Modbus 05/10

Page 123

Appendix - Data Point Lists Module Subgroup Names Functions Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage Voltage VL2 avg RMS VL2 max RMS VL2 min RMS VL31 avg RMS VL31 max RMS VL31 min RMS VL3 avg RMS VL3 max RMS VL3 min RMS %(V2/V1) mit 21526 21528 21530 21532 21534 21536 21538 21540 21542 21550 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 V V V V V V V V V % VL2 average value (RMS) VL2 maximum value (RMS) VL2 minimum value (RMS) VL31 average value (RMS) VL31 maximum value (RMS) VL31 average value (RMS) VL3 average value (RMS) VL3 maximum value (RMS) VL3 minimum value (RMS) Measured value (calculated):%V2/V1 average value Measured value (calculated):%V2/V1 maximum value Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Voltage

%(V2/V1) max

21552

Float IEE754

Page 124

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Voltage %(V2/V1) min 21554 2 4 Float IEE754 % Measured value (calculated):%V2/V1 minimum value Average of the active power Maximum value of the active power Minimum value of the active power Average of the apparent power Maximum value of the apparent power Minimum value of the apparent power Average of the power factor Maximum value of the power factor Minimum value of the power factor Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EnergyCr EnergyCr EnergyCr EnergyCr EnergyCr EnergyCr EnergyCr EnergyCr EnergyCr

P avg P max P min S avg S max S min cos phi avg RMS cos phi max RMS cos phi min RMS

21556 21558 21560 21562 21564 21566 21568 21570 21572

2 2 2 2 2 2 2 2 2

4 4 4 4 4 4 4 4 4

Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754 Float IEE754

W W W VA VA VA -

EN MRA4 Modbus 05/10

Page 125

Appendix - Data Point Lists Module Subgroup Names Functions Current IG H2 calc avg 21772 2 4 Float IEE754 % Measured value (calculated): Average ratio of 2nd harmonic over fundamental of IG (calculated) Measured value (calculated): Maximum ratio of 2nd harmonic over fundamental of IG (calculated) IG H2 calc min Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Current

IG H2 calc max

21774

Float IEE754

Current

IG H2 calc min

21776

Float IEE754

Page 126

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Commands
Module Subgroup Names Functions Acknowledge Acknowledge Acknowledge Acknowledge Acknowledge Reset Reset Reset Reset Reset LEDs Binary Outputs Scada Device Ack TripCmd Modbus diagnosis counter Wp+ Reset Cr Wp- Reset Cr Wq+ Reset Cr Wq- Reset Cr 22000 22001 22002 22003 22005 22006 22007 22008 22009 22010 1 1 1 1 1 1 1 1 1 1 5 5 5 5 5 5 5 5 5 5 0xFF00 0xFF00 0xFF00 0xFF00 0xFF00 0xFF00 Short Short Short Short LEDs Binary Outputs Scada Device Signal: Acknowledge Trip Command Modbus diagnosis counter Wp+ Reset Counter Wp- Reset Counter Wq+ Reset Counter Wq- Reset Counter Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 127

Appendix - Data Point Lists Module Subgroup Names Functions Reset Reset Scada Cmd Res all Energy Cr Res Sum trip Assbl Scada Cmd 1 22011 22012 22020 1 1 1 5 5 5 Short Short 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 2 22021 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 3 22022 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 4 22023 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 5 22024 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 6 22025 1 5 0xFF00=On 0x0000=Off Assignable Scada Command Assignable Scada Command Assignable Scada Command Assignable Scada Command Assignable Scada Command Reset of all Energy Counters Reset summation of the tripping currents Assignable Scada Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 128

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module Subgroup Names Functions Scada Cmd Assbl Scada Cmd 7 22026 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 8 22027 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 9 22028 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 10 22029 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 11 22030 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 12 22031 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 13 22032 1 5 0xFF00=On 0x0000=Off Assignable Scada Command Assignable Scada Command Assignable Scada Command Assignable Scada Command Assignable Scada Command Assignable Scada Command Assignable Scada Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 129

Appendix - Data Point Lists Module Subgroup Names Functions Scada Cmd Assbl Scada Cmd 14 22033 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 15 22034 1 5 0xFF00=On 0x0000=Off Scada Cmd Assbl Scada Cmd 16 22035 1 5 0xFF00=On 0x0000=Off PSet-Switch PSet-Switch PSet-Switch PSet-Switch AFRMS Mode Scada PS1 Scada PS2 Scada PS3 Scada PS4 AFRMS SCADA 22050 22051 22052 22053 22054 1 1 1 1 1 5 5 5 5 5 0xFF00 0xFF00 0xFF00 0xFF00 0xFF00 Scada Setting Group1 Scada Setting Group2 Scada Setting Group3 Scada Setting Group4 Signal: Arcflash Reduction Maintenance SCADA Mode Assignable Scada Command Assignable Scada Command Assignable Scada Command Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

Page 130

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Settings
Module Subgroup Names Functions Date and Time y m d h min ms 32500 32500 32500 32500 32500 32500 32500 6 6 6 6 6 6 6 3 16 3 16 3 16 3 16 3 16 3 16 3 16 Struct Short Short Short Short Short Short Word 0 (1) Word 1 (17) Word 2 (33) Word 3 (49) Word 4 (65) Word 5 (81) milliseconds minute hours days month year Start Register Address No. of Modbus Registers Function Code Format Bit Mask / (Bit Position) Unit Description

EN MRA4 Modbus 05/10

Page 131

Appendix - Data Point Lists We appreciate your comments about the content of our publications. Please send comments to: kemp.doc@woodward.com Please include the manual number from the front cover of this publication. Woodward SEG reserves the right to update any portion of this publication at any time. Information provided by Woodward SEG is believed to be correct and reliable. However, Woodward SEG assumes no responsibility unless otherwise expressly undertaken. Woodward SEG, all rights reserved

Woodward SEG GmbH & Co. KG Krefelder Weg 47 D 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet Homepage http://www.woodward-seg.com Documentation http://doc.seg-pp.com Sales Phone: +49 (0) 21 52 145 635 Telefax: +49 (0) 21 52 145 354 e-mail: kemp.electronics@woodward.com Service Phone: +49 (0) 21 52 145 614 Fax: +49 (0) 21 52 145 455 e-mail: kemp.pd@woodward.com

Page 132

EN MRA4 Modbus 05/10