Anda di halaman 1dari 75

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

GENERATOR
Generating units are the source of the power system and their security against any adverse conditions is most important in the system. The GENERATOR protection must ensure a fast and selective detection of any fault in order to minimize their dangerous effects.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

Generator is accompanied by excitation system, prime mover, voltage regulator, cooling system etc. Hence it is not a single equipment. The protection of generator should be co-ordinated with associated equipment. Protection of passive elements like transmission line and transformers is relatively simple which involves isolation of faulty element from the system , whereas protection of generators involves tripping of generator field breaker, generator breaker and turbine.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

GENERATOR PROTECTION SCHEME

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

GENERATOR AND GENERATOR TRANSFORMER AS A UNIT


Station Transformer: 11/6.6 kv transformer with LV grounded through high resistance, feeds the station auxiliary load. Unit auxiliary transformer: 11/6.6 kv transformer with LV grounded through high resistance feeds the unit auxiliary loads

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

Any earth fault on the 6.6 kv system cannot be seen by any E/L relay (since the 6.6 kv system is high resistance grounded ) However 3-O/L relays are provided on the 6.6kv side of the station transformers and unit auxiliary transformers. An open delta voltage of the 6.6 kv bus PT is connected to an over voltage relay with a very low setting. Any earth fault on the 6.6 kv system will cause the presence of the open-delta voltage and make the voltage relay operate which is connected to give alarm. The faulty 6.6kv feeder can be identified by tripping the 6.6kv outlets one after the other.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

GENERATOR HAS THREE PARTS


1. STATOR 2. ROTOR 3. EXCITATION SYSTEM

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

FAULTS IN GENERATOR
EXTERNAL FAULTS INTERNAL FAULTS FAULTS RELATED SYSTEM

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

4/11/2013

EXTERNAL FAULTS
OVER LOADING UNBALANCE LOADING SHORT CIRCUIT EARTH FAULT

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

10

4/11/2013

INTERNAL FAULTS
PHASE TO PHASE FAULTS IN WINDINGS PHASE TO EARTH FAULTS INTER TURN FAULTS

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

11

4/11/2013

FAULTS RELATED SYSTEM


UNDER VOLTAGE OVER VOLTAGE UNDER FREQUENCY OVER FREQUENCY REVERSE POWER LOSS OF EXCITATION LOW-FORWARD POWER

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

12

4/11/2013

GENERATOR PROTECTIONS ARE BROADLY CLASSIFIED INTO THREE TYPES


CLASS-A: (UNIT SHUT DOWN ) This covers all

electrical protections for faults within the generating unit in which GENERATOR FIELD BRK., GENERATOR BREAKER, UAT LV BRK. and TURBINE should be tripped

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

13

4/11/2013

CLASS-B: ( INTERLOCKED TRIPPING) This covers all MECHANICAL protections of the turbine in which TURBINE will be tripped first and following this generator will trip on REVERSE/LOW FORWARD POWER protection(GT/UAT/FIELD brks.)

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

14

4/11/2013

CLASS-C: This covers electrical protection for faults in the system in which generator will be unloaded by tripping of generator breaker only. The unit will come to house load operation and the UAT will be in service.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

15

4/11/2013

SOME OF CLASS-C PROTECTIONS ARE 1. Gen. T/F HV side breaker pole discrepancy 2. Gen. Neg. Ph. Sequence 3. Gen. T/F over current 4. Reverse power protection without turbine trip

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

16

4/11/2013

GENERATOR PROTECTIONS
1. Stator E/F (64)
95% stator E/F protection (64G1) 100% stator E/F protection (64G2)

2. Rotor E/F (64)


First rotor E/F protection (64R1) Second rotor E/F protection (64R2)

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

17

4/11/2013

3. Inter turn fault 4. Negative phase sequence (46G)


5. Loss of excitation protection(loss of field) (40G)

6. Minimum Impedance (Mho backup impedance) (21G) 7. Differential ( 87G) 8. Overall differential (87 O ) 9. Power protection
Low forward power (37G) Reverse power (32G)

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

18

4/11/2013

10.Frequency protection ( 8 1 )
Under frequency ( 8 1U) Over frequency ( 8 1O)

11.Thermal overload (51G) 12.Voltage protection


Over voltage (59) Under voltage (27)

13.Out of step (pole slipping ) (78G) 14.Voltage restrained over current (51/27G) 15.Standby earth fault (51N) 16.Inadvertent Energization

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

19

4/11/2013

1. STATO E/F PROTECTION The most common practice is the neutral point of the generator is usually earthed to enable detection of earth faults associated with the stator winding and associated systems and also to limit the transient over voltages during faults or switching. The commonly adopted earthing methods for industrial generators. High impedance Earthing: In this method the neutral of the generator is earthed through the primary winding of a grounding transformer having a loading resistor across its secondary. This method of earthing of is called high impedance earthing. In this arrangement , the primary earth fault current will be limited to between 3 to 25 amps depending upon the size of the machine and phase to ground capacitance of the Stator.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

20

4/11/2013

High impedance grounding is generally used in case of unit connected Generators where the generators is connected to the system through a delta/star step up transformer with control breaker on the HV (star) side. The neutral of the HV star winding is solidly grounded. A neutral displacement relay ( voltage operated) connected across secondary of the distribution transformer. The relay is IDMT type with typical setting range of 5-20 volts and is tuned to supply frequency.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

21

4/11/2013

Short circuits between the stator winding in the slots and the stator core are the most common electrical fault in Generators. Inter turn faults, which normally are difficult to detect, will quickly develop into a ground fault and will be tripped by the stator ground fault protection.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

22

4/11/2013

95% STATOR E/F PROTECTION


The relay is normally set to operate at 5% of maximum neutral voltage with a time delay of 0.3 0.5 seconds. With this voltage setting , it protects approximately 95% of the stator winding. RESULTS IN VOLTAGE SHIFT OF GEN NEUTRAL W.R.T GROUND DETECTED BY OVER VOLTAGE RELAY CONNECTED ACROSS GROUNDING RESISTOR PROTECT APPROX 95% OF STATOR WDG It also covers the generator bus, the low voltage winding of the unit transformer and the high voltage winding of the unit auxiliary transformer.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

23

4/11/2013

100% STATOR E/F PROTECTION THIRD HARMONIC PRINCIPLE


For Single line to Ground fault near the neutral end of winding , there will be proportionately less voltage available to drive the current through the ground, resulting in a lower fault current and lower neutral bus voltage. If an earth fault occurs and remains undetected because of its location (near the neutral end). A 100 % Stator earth fault protection is designed to detect earth faults occurring in the regions of Machine winding close to the neutral end.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

24

4/11/2013

Principle: This works on the principle involving monitoring neutral side and line side

of the

components of the third harmonic

voltages produced by the AC generators. AC Generators in service produce a certain magnitude of third harmonic voltages in their windings. Under the healthy conditions of working the third harmonic voltage developed by the machine is shared between the phase to ground capacitive impedance at the machine terminal and the neutral to ground impedance at the machine neutral.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

25

4/11/2013

The 100% stator E/F relay includes 95% unit which covers the stator winding from 5% of the neutral and a 3rd harmonic voltage measuring unit -2 which protects the rest of the stator winding. The voltage check unit is included to prevent faulty operation of the relay at generator standstill or during the machine running up or running down period.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

26

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

27

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

28

4/11/2013

ROTOR E/F PROTECTION


The field circuit of a generator has no intentional earthing and hence a single earth fault occurring in the field system poses no immediate threat. However, the presence of the first ground increases the risk of a second earth fault developing due to increased insulation stresses between the field system and earth. The resulting double earth fault will cause part of the filed winding short circuited there by producing an unbalance in the magnetic field and consequent vibrations and mechanical damage.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

29

4/11/2013

METHODS OF DETECTION
Potentiometer method A.C injection method D.C injection method

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

30

4/11/2013

MODERN ROTOR EARTH FAULT PROTECTION RELAY OPERATES ON THE PRINCIPLE OF LOW FREQUENCY INJECTION INTO THE FIELD WINDING VIA CAPACITORS. IF AN EARTH FAULT OCCURS, THE CORRESPONDING CURRENT OR RESISTANCE IS DETECTED In general ALARM 25 K OHM TIME = 1.0 SEC TRIP 5 K OHM TIME = 0.5 SEC

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

31

4/11/2013

POTENTION METHER METHOD


In this scheme, a centre tapped resistor is connected in parallel with the main field winding. The centre point of the resistor is connected to earth through a voltage relay. An earth fault on the field winding will produce a voltage across the relay. The maximum voltage occurring for faults at the ends of the winding.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

32

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

33

4/11/2013

AC INJECTION METHOD
It comprises of an auxiliary supply transformer, the secondary of which is connected between earth and one side of the field circuit through an interposed capacitor and a relay coil. The field circuit is subjected to an alternating potential at the same level through out, so that an earth fault anywhere in the field system will give rise to a current which is detected by the relay. The capacitor limits the magnitude of the current and blocks the normal field voltage, preventing the discharge of a large direct current through the transformer.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

34

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

35

4/11/2013

D.C Injection Method


The capacitance current objection to the a.c injection scheme is overcome by rectifying the injection voltage. The d.c out put of a transformer rectifier power unit is arranged to bias the positive side of the field circuit to a negative voltage relative to earth. The current is limited by including a high resistance in the circuit and a sensitive relay is used to detect the current.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

36

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

37

4/11/2013

INTER TURN FAULT PROTECTION


Inter turn faults have commonly been disregarded on the basis that if they occur they will quickly develop into earth faults. This is probably true if the fault is in the slot portion is never attractive and may be entirely unjustified. There is a possibility of the machine being very seriously damaged before the fault evolves to a condition that can be detected by the longitudinal system.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

38

4/11/2013

It is generally considered difficult to obtain a reliable protection against short-circuiting of one turn if the stator winding has a large number of turn per phase. For generators with split neutrals, the conventional inter turn fault protective scheme comprises a time delayed low set over current relay which senses the current flowing in the connection between the neutrals of the stator winding.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

39

4/11/2013

zero sequence voltage measurement Short circuit of one or more turns will cause the Generated E M F to contain zero Sequence component Earth faults will also produce a zero sequence voltage. Most of the voltage will be expended on Earthing Resistor Hence, drop across the winding should be measured

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

40

4/11/2013

NEG.PH.SEQUENCE PORTECTION
When the generator is connected to a balanced load, the phase currents are equal in magnitude and displaced electrically by 120 deg. The ampere turn wave produced by the stator currents rotate synchronously with the rotor and no eddy currents are induced in the rotor parts. Unbalance loading gives rise to a negative sequence component in the stator current. The negative sequence current produces an additional ampere turn wave which rotates backwards, hence it moves relatively to the rotor at twice the synchronous speed. The double frequency eddy currents induced in the rotor may cause excessive heating, primarily in the surface of cylindrical rotors and in the damper winding of rotors with salient poles.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

41

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

42

4/11/2013

LOSS OF EXCITATION
Loss of excitation may occur under normal running conditions due to following reasons: 1. Failure of Brush gear of the pilot or shunt exciter 2. Accidental opening of the field breaker 3. Failure of the regulation system 4. An open circuit or a short circuit of the main field

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

43

4/11/2013

The condition is particularly detrimental when the generator is operating in paralleled with other generators or with the utility system. When the generator looses its field on load , it runs as an induction generator, operating at super synchronous speed. The defaulting machine absorbs VARs from the system to support excitation and continues generating action. Slip frequency currents are induced in the field system which, it allowed to persist for long, cause over heating of the field winding /rotor iron.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

44

4/11/2013

The maximum active power that can be generated without loss of synchronism when the generator losses its excitation depends on the difference between the direct axis and quadrature axis synchronous reactance. For generators with salient poles, the difference is normally sufficiently large to keep the machine running synchronously, even with an active load of 15-25% or rated load.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

45

4/11/2013

For cylindrical turbo generators, the direct and quardrature axis reactance are practically equal, and the machine fails out of synchronism even with a very small active lode, The slip speed increases with the active load. The stator end regions and parts of the rotor will be overheated, it the machine is permitted to run for a long time at higher slip speeds.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

46

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

47

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

48

4/11/2013

BACKUP IMPEDANCE
The generator minimum impedance protection(impedance backup protection) is primarily provided to protect the generator against uncleared external short circuits on the lines emanating from the station bus bars. The relay has an impedance or offset MHO characteristic and is set to cover the impedance of the longest line.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

49

4/11/2013

In case of generator, though the initial short circuit current may be high during the sub transient/transient periods, the steady state short circuit current may be less than the full load current, due to the effect of armature reaction. Since the initial short circuit current is high and almost wholly reactive the armature reaction flux is in direct opposition to the field flux. This would reduce the field flux, which in turn reduces the induced EMF and hence the short circuit current. The AVR tends to compensate the reduction by forcing the field in case of system faults.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

50

4/11/2013

However, for close up faults, the AVR compensation may not be enough to boost the voltage and hence the fault current. Conventional over current relays may not, therefore, be suitable for generator application. Voltage controlled or voltage restrained over current relays are commonly adopted in such situations. These relays are designed to become more sensitive with generator voltage reduction and hence operate positively, even if the sustained short circuit current fails below the full load current.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

51

4/11/2013

DIFFERENTIAL PROTECTION
Differential protection is commonly applied to generators above 1 MVA rating. This is a unit protection, which covers both phase, and earth faults within the machine. The zone of protection is defined by current transformers at neutral side and line side of the stator winding.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

52

4/11/2013

Current transformer at each end of the protected zone are interconnected by an auxiliary pilot circuit. Current transmitted through the zone causes secondary current to circulate round the pilot circuit without producing any current in the relay. A fault within the protected zone will cause secondary currents of opposite relative phase as compared with the through fault condition. The summated value of these currents will flow in the relay, thus energizes the relay. The voltage setting is decided from the secondary load drop by the following formula.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

53

4/11/2013

The differential relay is usually high impedance relay. The current transformers on the generator neutral and the line side shall have identical turns ration and similar magnetizing characteristics. Hence under normal service conditions and external faults, with unsaturated current transformers, the voltage across the relay is negligible.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

54

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

55

4/11/2013

GEN.OVERALL DIFFERENTIAL PROTECTION


This protection is used to protect the complete bus of generator, generator transformer and high voltage bus side of unit auxiliary transformer. The special features of the relay are: 1. Through current restraint for external faults 2. Magnetizing inrush restraint 3. Over excitation restraint to counteract operation at abnormal magnetizing currents caused by high voltage/low frequency

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

56

4/11/2013

The magnetizing restraint is required to keep the relay stable when a nearby fault on an adjacent feeder is cleared. During the time of fault, the terminal voltage of the main transformer is practically zero and after fault clearance i.e when the circuit breaker of the faulty feeder opens, the transformer terminal voltage quickly rises. This may cause severe recovery inrush currents. The inrush restraint is also required when the unit transformer is energized for the H.V bus.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

57

4/11/2013

The over excitation restraint is important since there is a possibility of over voltage when load is suddenly disconnected in which the differential relay may trip the generator and the voltage remains high until the automatic voltage regulator (AVR) brought it back to the normal valve.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

58

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

59

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

60

4/11/2013

POWER PROTECTION
1. LOW FORWARD POWER: In thermal machines, when the steam flow through turbine is interrupted by closing the ESVs or the governor valves, the remaining steam in the turbine generates (low) power and the machine enters to motoring conditions drawing power from the system. This protection detects low forward power conditions of the generator and trips generator breaker after a time delay, avoiding motoring of generator.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

61

4/11/2013

The low forward power relay will be provided with TURBINE TRIP interlock in thermal machines. A setting of 0.5% of rated active power of generator with a time delay of 2.0 sec. Shall be adopted. 2. REVERSE POWER: Reverse power protection shall be used for all types of generators. When the input to the turbine is interrupted the machine enters into motoring condition drawing power from the system. Reverse power relay protects the generators from motoring condition. In thermal machines, reverse power condition appears subsequent to low forward power condition.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

62

4/11/2013

For reverse power relay, a setting of 0.5% of rated active power of generator with 2 stage timer as 1. Stage-1: with turbine trip interlock, a time delay of 2 sec. shall be adopted. 2. Stage-2: Without turbine trip interlock a time delay of about 20 sec. can be adopted to avoid unnecessary tripping of unit during system disturbance causing sudden rise in frequency or power swing conditions.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

63

4/11/2013

FREQUENCY PROTECTION
1. UNDER FREQUENCY 2. OVER FREQUENCY The generators are designed to give rated output at rated terminal voltage and rated frequency. Hence an operation above certain limit i.e. +5% and -5% of rated frequency is avoided to protect various apparatus in a network and also the generator and turbine.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

64

4/11/2013

OVER LAOD PROTECTION


A generator operating on a large system under continuous supervision is not in much danger of accidental overloading. The power r that can be generated is limited by the steam production and hence can not rise un noticed or maintained for any appreciable period above the programmed level. Overloads in terms of current or MVA as distinct from megawatts are possible. Depending on the voltage regulator setting and type of control relative to the rest of the system, a given generator may take a disproportionate share of the MVAR load on the system. Overloads up to 1.4 times the rated current are not normally detected by the impedance or over current protection. Sustained loads within this range are usually supervised by temperature monitors (RTD/or thermocouples)

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

65

4/11/2013

OVER VOLTAGE PROTECTION


During the starting up of a generator, prior to synchronization, the generator terminal voltage is obtained by the proper operation of the automatic voltage regulator (AVR). After synchronization, the terminal voltage of the machine will be dictated by its own AVR and also by the voltage level of the system and the AVRs of nearby machines. It is not possible for one machine to cause any appreciable rise in the terminal voltage as long as it is connected to the system.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

66

4/11/2013

Increasing the field excitation, owing to a fault in the AVR, merely increases the reactive MVAR output, which may ultimately lead to tripping of the impedance relay or the V/Hz relay. Maximum excitation limit prevents the rotor field current and the reactive output power from exceeding the design limits. This protection is used for the insulation level of the generator stator windings. Severe overvoltage will occur, if the generator circuit breaker is tripped while the machine is running at full load and rated power factor, the subsequent increase in terminal voltage will normally be limited by a quick acting AVR

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

67

4/11/2013

However, if the AVR faulty or at this particular time switched over to manual control, over voltage will occur. This voltage rise will be further increased if simultaneous over speeding should occur, owing to a slow acting turbine governor. Modern unit transformers with high magnetic qualities have a relatively sharp and well defined saturation level, with a knee point voltage between 1.2 and 1.25 times the rated voltage (Un). A suitable setting of the over voltage relay is, therefore, between 1.15 and 1.2 times Un and with a definite delay of 1 to 3 sec. An instantaneous high set voltage rely can be included to trip the generator quickly in case of excessive over voltage following a sudden loss of load and generator over speeding.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

68

4/11/2013

OUT OF STEP (POLE SLIPPING)


An generator may lose synchronism with the power system, without failure of the excitation system, because of severe system fault disturbance operation at a high load with a leading power factor and hence a relatively weak field, In this condition, which is quite different from the failure of field system, the machine is subject to violent oscillations of torque, with wide various in current, power and power factor. Synchronism can be regained if the load is sufficiently reduced but if this does not occur within a few seconds it is necessary to isolate the generator and then resynchronize.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

69

4/11/2013

The impedance of the generator measure at the stator terminals changes mostly when synchronism is lost by the machine. The terminal voltage will begin to decrease and the current to increase, resulting in a decrease of impedance and also a change in power factor. A pole slipping protection comprising of two ohm relays is used to detect out of step operation. The relay monitors the load impedance at the machine terminals and operates when the terminal impedance locus sequentially crosses both ohm relay characteristics which corresponds to one pole slip between the defaulting machine and the system

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

70

4/11/2013

VOLTAGE RESTRAINED OVER CURRENT This will operate when the fault current from the generator terminal becomes low due to excitation system characteristic with under voltage criteria. It operates as a backup protection for system faults with suitable time delay.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

71

4/11/2013

STANDBY EARTH FAULT


This relay monitors the current in the generator transformer neutral. It can detect earth faults in the transformer HV side or in the adjacent network.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

72

4/11/2013

INADVERTENT ENERGIZATION
Many instances of inadvertent energization 1. Closing the generator breaker with the machine at standstill 2. Closing a unit service breaker with the machine at standstill 3. High voltage breaker flashover near synchronism 4. Closing of generator disconnect with unit breaker closed

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

73

4/11/2013

Full voltage energization of a machine at standstill does not produce an enormous magnitude of current, but it does supply an extreme impact of torque and mechanical damage to the shaft or bearings may occur. The resulting current is of sufficient magnitude that fast removal is necessary if thermal damage to the generator is to be avoided.

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

74

4/11/2013

PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

75

Anda mungkin juga menyukai