Air System Sizing Summary for IPS/UPS

Project Name: J-NMC DAY CARE SURGERY Prepared by: OTC 03/25/2013 03:24PM

Air System Information


Air System Name Equipment Class Air System Type IPS/UPS CW AHU SZCAV Number of zones Floor Area Location 1 218.0 ft Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Central Cooling Coil Sizing Data


Total coil load Total coil load Sensible coil load Coil CFM at Jun 1600 Max block CFM Sum of peak zone CFM Sensible heat ratio ft/Ton BTU/(hr-ft) Water flow @ 16.0 F rise 4.3 51.4 51.0 3124 3124 3124 0.992 50.9 236.0 6.43 Tons MBH MBH CFM CFM CFM Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Jun 1600 113.3 / 84.8 69.7 / 59.5 54.5 / 53.5 52.8 0.100 53 55.0 1 of 1 0.0 F F F F % F OK F

gpm

Supply Fan Sizing Data


Actual max CFM Standard CFM Actual max CFM/ft 3124 CFM 3114 CFM 14.33 CFM/ft Fan motor BHP Fan motor kW Fan static 0.55 BHP 0.41 kW 0.60 in wg

Outdoor Ventilation Air Data


Design airflow CFM CFM/ft 0 CFM 0.00 CFM/ft CFM/person 0.00 CFM/person

Hourly Analysis Program v4.50

Page 1 of 1

Air System Design Load Summary for IPS/UPS


Project Name: J-NMC DAY CARE SURGERY Prepared by: OTC 03/25/2013 03:24PM

ZONE LOADS Window & Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions Ceiling Overhead Lighting Task Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads Zone Conditioning Plenum Wall Load Plenum Roof Load Plenum Lighting Load Return Fan Load Ventilation Load Supply Fan Load Space Fan Coil Fans Duct Heat Gain / Loss >> Total System Loads Central Cooling Coil >> Total Conditioning Key:

DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 113.3 F / 84.8 F HEATING OA DB / WB 52.0 F / 43.6 F Sensible Latent Sensible Latent Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) 41 ft 1232 41 ft 130 ft 368 130 ft 210 0 ft 0 0 ft 0 41 ft 935 41 ft 380 0 ft 0 0 ft 0 0 ft 0 0 ft 0 0 ft 0 0 ft 0 0 ft 0 0 ft 0 0 ft 0 0 ft 0 327 W 781 0 0 0W 0 0 0 0W 0 0 0 1 280 270 0 0 0 0 0 0 0 43236 0 0 0 0% / 0% 0 0 0% 0 0 46832 270 590 0 46851 270 583 0 20% 131 0 0 0% 0 0 0 30% 335 0 0 3124 CFM 0 3124 CFM 0 0 CFM 0 0 0 CFM 0 0 3124 CFM 1389 3124 CFM -1389 0 0 5% 2342 5% 30 51048 270 -777 0 51048 392 -777 0 51048 392 -777 0 Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads