The design of the ductworks in ventilation systems are often done by using the
Velocity Method Constant Pressure Loss Method (or Equal Friction Method) Static Pressure Recovery Method
Be aware that high velocities close to outlets and inlets may generate unacceptable noise.
The Constant Pressure Loss Method (or Equal Friction Loss Method)
A proper speed is selected in the main duct close to the fan. The pressure loss in the main duct are then used as a template for the rest of the system. The pressure (or friction) loss is kept at a constant level throughout the system. The method gives an automatic velocity reduction through the system. The method may add more duct cross sectional changes and can increase the number of components in the system compared to other methods.
comfort systems - air velocity 4 to 7 m/s (13 to 23 ft/s) industrial systems - air velocity 8 to 12 m/s (26 to 40 ft/s) high speed systems - air velocity 10 to 18 m/s (33 to 60 ft/s)
Use the maximum velocity limits when selecting the size of the main duct.
the actual length + additional lengths for bends, T's, inlets and outlets
The table is based on the diagram above. Air flow and friction loss from a diagram is added. Minor pressure loss coefficients must be summarized for for the actual applications. The pressure loss in each path is summarized on the right and pressure loss is added manually in the dampers to balance the system.
g = acceleration of gravity (m/s2, ft/s2) Minor loss can also be expressed as pressure loss instead of head loss. Minor loss coefficients for different components common in air duct distribution systems
Component or Fitting
90o bend, sharp 90o bend, with vanes 90o bend, rounded radius/diameter duct <1 90o bend, rounded radius/diameter duct >1 45o bend, sharp 45o bend, rounded radius/diameter duct <1 45o bend, rounded radius/diameter duct >1 T, flow to branch (applied to velocity in branch) Flow from duct to room Flow from room to duct Reduction, tapered Enlargement, abrupt (due to speed before reduction)
0.5
0.25
0.5
0.2
0.05
0.3
(v1= velocity before enlargement and v2 = velocity after enlargement) Enlargement, tapered angle < 8o (due to speed before reduction) 0.15 (1 - v2 / v1)2 (v1= velocity before enlargement and v2 = velocity after enlargement) Enlargement, tapered angle > 8o (due to speed before reduction) (v1= velocity before enlargement and v2 = velocity after enlargement) Grilles, 0.7 ratio free area to total surface Grilles, 0.6 ratio free area to total surface Grilles, 0.5 ratio free area to total surface Grilles, 0.4 ratio free area to total surface Grilles, 0.3 ratio free area to total surface Grilles, 0.2 ratio free area to total surface
(1 - v2 / v1)2
10
20
50
Friction loss (head loss) in standard air ducts are indicated in the diagram below:
The diagram is based on standard air 0.075 lb/ft3 in clean round galvanized metal ducts.
1 inch water = 248.8 N/m2 (Pa)= 0.0361 lb/in2 (psi) = 25.4 kg/m2 = 0.0739 in mercury 1 ft3/min (cfm) = 1.7 m3/h = 0.47 l/s 1 ft/min = 5.08x10-3 m/s 1 inch = 25.4 mm = 2.54 cm = 0.0254 m = 0.08333 ft
The friction loss in a 20 inches duct with air flow 4000 cfm can be estimated to approximately 0.23 inches water per 100 feet duct as shown in the diagram below. The air velocity can be estimated to approximately 1850 feet per minute.
Calculating indoor heat or cooling loads Calculating surrounding heat or cooling loads
Calculate the pollution created by persons and their activity and processes.
For heating, 38 - 50oC (100-120oF) may be suitable For cooling where the inlets are near occupied zones - 6 - 8oC (10-15oF) below room temperature For cooling where high velocity diffusing jets are used - 17oC (30oF) below room temperature
Air Cooling
If air is used for cooling, the needed air flow rate may be expressed as qc = Hc / cp (to - tr) where qc = volume of airfor cooling (m3/s) Hc =cooling load (W) to = outlet temperature (oC) where to = tr if the air in the room is mixed (2)
qh = (400 W) / (1.2 kg/m3) (1005 J/kg K) ((30 oC) - (22 oC)) = 0.041 m3/s = 149 m3/h
Moisture
If it is necessary to humidify the indoor air, the amount of supply air needed may be calculated as: qmh = Qh / (x2 - x1) where qm = volume of air for humidifying (m3/s) Qh = moisture to be supplied (kg/s) = density of air (kg/m3) x2 = humidity of room air (kg/kg) x1 = humidity of supply air (kg/kg) (3)
Dehumidifying
If it is necessary to dehumidify the indoor air, the amount of supply air needed may be calculated as: qmd = Qd / (x1 - x2) where qmd = volume of air for dehumidifying (m3/s) Qd = moisture to be dehumified (kg/s) (4)
Example - humidifying
If added moisture Qh = 0.003 kg/s, room humidity x1 = 0.001 kg/kg and supply air humidity x2 = 0.008 kg/kg, the amount of air can expressed as: qmh = (0.003 kg/s) / (1.2 kg/m3) ((0.008 kg/kg)- (0.001 kg/kg)) = 0.36 m3/s Alternatively the air quantity is determined by the requirements of occupants or processes.
where H = heat loss (W) A = area of duct walls(m2) t1 = initial temperature in duct (oC) t2 = final temperature in duct (oC) k = heat loss coefficient of duct walls (W/m2 K) (5.68 W/m2 K for sheet metal ducts, 2.3 W/m2 K for insulated ducts) tr = surrounding room temperature (oC) The heat loss in the air flow can be expressed as: H = q cp (t1 - t2) where q = mass of air flowing (kg/s) cp = specific heat capacity of air (kJ/kg K) (5) and (5b) can be combined to H = A k ((t1 + t2) / 2 - tr)) = q cp (t1 - t2) (5c) (5b)
7. Boiler
The boiler rating can be expressed as: B = H (1 + x) where B = boiler rating (kW) H = total heat load of all heater units in system (kW) x = margin for heating up the system, it is common to use values 0.1 to 0.2 Boiler with correct rating must be selected from manufacturer catalogues. (6)
8. Sizing Ducts
Air speed in a duct can be expressed as: v=Q/A where v = air velocity (m/s) Q = air volume (m3/s) A = cross section of duct (m2) Overall pressure loss in ducts can be expressed as: dpt = dpf + dps + dpc where dpt = total pressure loss in system (Pa, N/m 2) dpf = major pressure loss in ducts due to friction (Pa, N/m 2) dps = minor pressure loss in fittings, bends etc. (Pa, N/m2) dpc = minor pressure loss in components as filters, heaters etc. (Pa, N/m 2) Major pressure loss in ducts due to friction can be expressed as dpf = R l where R = duct friction resistance per unit length (Pa, N/m2 per m duct) l = length of duct (m) Duct friction resistance per unit length can be expressed as R = / dh ( v2 / 2) where R = pressure loss (Pa, N/m2) = friction coefficient dh = hydraulic diameter (m) (10) (9) (8) (7)
6 A rough guide to maximum air volume capacity of circular ducts in comfort, industrial and high speed ventilation systems
Maximum air velocity in the ducts should be kept below certain limits to avoid unacceptable generation of noise.
The values from the table below can be used to rough sizing of ducts in comfort, industrial and high speed ventilation systems. Maximum Air Volume Flow (m3/h) Comfort systems Industrial systems High speed systems
Main Secondary Connecting Main Secondary Connecting Main Secondary Connecting ducts ducts ducts ducts ducts ducts ducts ducts ducts Speed (m/s) 5.5 4 45 72 2 22 36 10 112 181 6.5 73 118 4 45 72 14 157 253 9 101 163 6.5 73 118
63 80
0.003 0.005
62 99
100 125 160 200 250 315 400 500 630 800 1000 1250
0.008 155 0.012 243 0.020 398 0.031 622 0.049 971 0.078 1542 0.126 2487 0.196 3886 0.312 6169 0.502 9948 0.785 15543 1.227 24286
113 177 289 452 707 1122 1809 2826 4487 7235 11304 17663
57 88 145 226 353 561 904 1413 2243 3617 5652 8831
283 442 723 1130 1766 2804 4522 7065 11216 18086 28260 44156
184 287 470 735 1148 1823 2939 4592 7291 11756 18369 28702
113 177 289 452 707 1122 1809 2826 4487 7235 11304 17663
396 618 1013 1583 2473 3926 6330 9891 15703 25321 39564 61819
254 397 651 1017 1590 2524 4069 6359 10095 16278 25434 39741
184 287 470 735 1148 1823 2939 4592 7291 11756 18369 28702
7 Equivalent diameters for rectangular and circular ducts - air flows between 100 - 50,000 cfm
The table below can be used to compare equivalent diameters for rectangular and round circular ducts. The table is based on the ducts friction loss formula.
The rectangular dimensions and the air flow volume are adapted to the equal friction loss method of sizing ventilation duct systems. An approximate friction loss of 0.8 inches water gauge per 100 ft duct (6.6 Pa/m) is used.
Air flow -qRectangular Duct (Cubic Feet per Sizes Minute, cfm) (Inches) (m3/s)
Equivalent Diameter Round Duct Sizes - de (Inches) 4.9 4.9 5.7 6.0 6.4 6.4 6.6
0.88
0.82
400 (0.19)
1736 (8.8)
0.80
500 (0.24)
6x7
7.1
1819 (9.2)
0.78
750 (0.35)
8.3 8.4 8.2 9.1 9.3 9.8 9.8 10.7 10.9 11.5 11.3 11.5 11.8 12.0
1996 (10.1)
0.77
0.79
0.88
0.77
1750 (0.83)
2469 (12.5)
0.78
2000 (0.94)
2589 (13.2)
0.81
2500 (1.2) 3000 (1.4) 3500 (1.7) 4000 (1.9) 4500 (2.1)
10 x 14 12 x 12
12.9 13.1
2712 (13.8) 2767 (14.1) 3010 (15.3) 2938 (14.9) 3068 (15.6)
0.8
12 x 14
14.1
0.75
12 x 15
14.6
0.84
10 x 22 14 x 15 12 x 19 14 x 16 10 x 25 12 x 20 15 x 16 14 x 20 15 x 18 12 x 26 16 x 20 12 x 30 14 x 25 12 x 34 15 x 25 12 x 36 16 x 25 20 x 20 12 x 45 16 x 30 20 x 24 16 x 36 18 x 30 23 x 25 16 x 40
15.9 15.8 16.4 16.4 16.9 16.8 16.9 18.2 17.9 19.0 19.5 20.2 20.2 21.4 21.0 21.9 21.7 21.9 24.1 23.7 23.9 24.7 25.2 26.2 27.0
0.73
0.76
5000 (2.4)
3248 (16.5)
0.82
0.8
0.8
0.8
0.78
10000 (4.7)
3858 (19.6)
0.83
12500 (5.9)
4012 (20.4)
0.8
15000 (7.1)
4331 (22)
0.87
17500
4337
0.79
(8.3)
20 x 32 25 x 25 20 x 35 25 x 28 16 x 55 20 x 43 25 x 38 20 x 50 30 x 32 20 x 55 30 x 35 25 x 48 30 x 40
27.5 27.3 28.6 28.9 31.0 31.5 33.5 33.7 33.9 35.2 35.4 37.4 37.8
(22)
20000 (9.4)
4483 (22.8)
0.79
25000 (11.8)
4709 (23.9)
0.78
30000 (14.2) 35000 (16.5) 40000 (18.9) 45000 (21.2) 50000 (23.6)
4815 (24.5) 5179 (26.3) 5243 (26.6) 5397 (27.4) 5222 (26.5)
0.74
0.81
0.77
32 x 40
39.1
0.77
32 x 45 35 x 40
41.3 40.9
0.66
8 Friction loss or major loss in ducts - equations and online calculator for rectangular and circular ducts - imperial units
The major loss, or friction loss, in a circular duct in galvanized steel with turbulent flow can for imperial units be expressed p = (0.109136 q1.9) / de5.02 where p = friction (head or pressure loss) (inches water gauge/100 ft of duct) (1)
de = equivalent duct diameter (inches) q = air volume flow - (cfm - cubic feet per minute) For rectangular ducts the equivalent diameter must be calculated.
10
Pressure loss and air flow velocity for some common duct sizes and air flow volumes can be taken from the table below: Pressure Loss (inches water gauge per 100 feet duct) Air velocity (ft/min) Duct Size (inches) Air Volume (cfm) 4 0.65 100 1146 733 0.8 200 1467 1019 1.19 400 2037 1146 733 0.34 800 1467 1019 573 509 0.14 286 0.03 573 0.28 367 0.09 255 0.04 0.01 509 0.32 286 0.08 183 0.02 0.01 5 0.21 6 0.09 8 0.02 10 0.01 12 16
The air velocity should not exceed certain limits to avoid unacceptable noise generation.
laminar if Re < 2300 transient for 2300 < Re < 4000 turbulent if Re > 4000
The hydraulic diameter is also used to calculate the pressure loss in a ducts or pipe. The hydraulic diameter is not the same as the geometrical diameter in a non-circular duct or pipe and can be calculated with the generic equation dh = 4 A / p where dh = hydraulic diameter (m, ft) A = area section of the duct (m2, ft2) p = wetted perimeter of the duct (m, ft) Note! Inches are commonly used in the Imperial unit system. (1)
Based on equation (1) the hydraulic diameter of a circular duct can be expressed as:
dh = 4 r 2 / 2 r =2r where r = pipe or duct radius (m, ft) As we could expect the hydraulic diameter of a standard circular tube or duct is two times the radius. (2)
Based on equation (1) the hydraulic diameter of a circular duct or tube with an inside duct or tube can be expressed as dh = 4 ( ro2 - ri2) / (2 ro + 2 ri) = 2 (ro - ri) where ro = inside radius of the outside tube (m, ft) ri = outside radius of the inside tube (m, ft) (3)
Based on equation (1) the hydraulic diameter of a rectangular duct or pipe can be calculated as dh = 4 a b / (2 (a + b))
= 2 a b / (a + b) where
(4)
a = width/height of the duct (m, ft) b = height/width of the duct (m, ft)