Electrical Safety of PV installation

Standards Requirements Earth fault protection

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Basics

PV Systems from tens of W to multi MW Voltages from 12 V to 600 V and more Earthed and unearthed arrays Earthed and unearthed array frames Transformer and inverter isolation: 50 Hz Transformers Transformerless HF transformer Provide electrical safety for General public Informed workers (e.g. electricans) Emergeny workers

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Standards

International (IEC) for installations IEC 60364-7-712:2002-05 Electrical installations of buildings Part 7-712: Requirements for special installations or locations Solar photovoltaic (PV) power supply systems Technical specifications IEC TS 62257-7-1:2006-12 Recommendations for small renewable energy and hybrid systems for rural electrification Part 7-1: Generators Photovoltaic arrays Technical specifications IEC 62257-5:2005-07 Recommendations for small renewable energy and hybrid systems for rural electrification Part 5: Protection against electrical hazards International (IEC) for PV inverters IEC 62109-1 Ed.1: IEC 62109-1 Safety of power converters for use in photovoltaic power systems - Part 1: General requirements IEC 62109-2 Ed.1: Safety of power converters for use in photovoltaic power systems - Part 2: Particular requirements for inverters

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Standards

USA UL 1741:1999-05-07 Static inverters and charge controllers for use in photovoltaic power systems IEEE Std 929-2000 Recommended Practice for Utility-interface of Photovoltaic Systems NEC 690 Grid-connected Photovoltaic systems Other documentations IEA International energy agenca / www.iea.org Report IEA PVPS T05-04:2001 PV System Installation and Grid-Interconnection Guidlines in selected IEC countries Report IEC-PVPS T05-05:2002 Grid-connected photovoltaic power systems: Survey of inverter and related protection equipment

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Definitions according to IEC 60364-7-712 / DIN VDE 0100-712

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

PV system concept
String inverter Zentralised inverter

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

PV systems today

Small PV systems Transformerless inverter Application circuit earthed Insulation monitoring or residual current monitoring

Big PV systems Transformerless inverters Application circuit medium voltage via transformer Insulation monitoring

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Possible PV System Configurations

Array circuit (DC side) unearthed Inverter with transformer Application circuit earthed

Array circuit (DC side) unearthed Transformerless inverter Application circuit earthed

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Possible PV System Configurations

Array circuit (DC side) unearthed Inverter with transformer Application circuit unearthed

Array circuit (DC side) unearthed Inverter with transformer Application circuit unearthed

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Possible System Configurations

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

10

General philosophy

Safety

People

wire selection & installation class II earth fault protection earthing requirements equipment requirements

Equipment

disconnecting means emergency shutdown and alarm

Overcurrent Overvoltage

marking documentation

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

11

Earthing arrangement of PV arrays

Unearthed Isolated and Safe First fault no current but then earthed Earthed Shock risk First fault Fault current Shock risk same Class II insulation for larger system

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

12

Possible earthing arrangements

Non earthed

Negative earthed

Centre tap earthed

Capacitively Coupled centre tap earth


13

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

Possible protective measures (add. to IEC 60364-4-41)

IEC 60364-7-712 / DIN VDE 0100-712 712.312.2 Earthing of DC side is permitted if separation between AC and DC side 712.411.1 Protection by SELV / PELV max. DC 120 V 712.413.1 Protection by automatic disconnection On AC side, the PV supply cable shall be connected to the supply side of the protective device for automatic disconnection of circuits supplying current-using equipment PV system without separation between AC and the DC side an RCD installed to provide fault protection by automatic disconnection of supply shall be type B Protection by us of class II or equivalent insulation shoud preferable be adopted on the DC side 712.522.8.3 PV string cables, PV array cables and PV DC main cables shall be selected and erected so as to minimize the risk of earth faults and short circuits 712.536.2.1.1 To allow maintenance of the PV inverter, means of isolating PV inverter from the DC side and the AC side shall be provided.

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

14

Big PV system

Array circuit unearthed (IT system) with insulation monitoring

Sensivity (M) 36 / A where A is the PV array area in m2

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

15

A-ISOMETER IRDH275 with coupling unit AGH150W

Array circuit unearthed (IT system) with insulation monitoring

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

16

A-ISOMETER IRDH275 in String

Array circuit unearthed (IT system) with insulation monitoring

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

17

Earth fault protection for earthed PV array / earthed

Inverter with separating transformer, array and application circuit earthed

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

18

Earth fault protection for transformerless inverters (SMA)

Transformerless inverter, application circuit earthed

Dipl.-Ing. W. Bender GmbH&Co.KG 35305 Grnberg Germany www.bender-de.com Fxxx / 09.2005 nderungen vorbehalten

19

Thank you