Anonymous Poster

How to Calculate CT Ratio and PT Ratio


10/16/2009 1:08 AM

Please tell me how to calculate the CT ratio and PT ratio for 11kV?
Interested in this topic? By joining CR4 you can "subscribe" to this discussion and receive notification when new comments are added. Join CR4, The Engineer's Place for News and Discussion!

Tornado
Guru

Re: How to Calculate CT Ratio and PT Ratio


10/16/2009 11:47 PM

#1

There may be variations, but usually the desired output from a CT is 05 amps. Determine the amps of the current passing through the center of the CT, and select the ratio accordongly. For PT, determine the voltage applied to the primary coil, and the output voltage you need. Select a ratio to match. __________________ In vino veritas; in cervisia carmen; in aqua E. coli.
Join Date: May 2009 Location: Ketchikan, AK, USA Posts: 12931 Good Answers: 463

jmueller
Guru Join Date: Jul 2006 Posts: 916 Good Answers: 74

Re: How to Calculate CT Ratio and PT Ratio


10/18/2009 12:14 AM

#3 In reply to #1

Friend, When you are connecting to a meter, you also would need the meter's faceplate to be printed with the proper scaled values. On our switchgear, the incoming voltage is nominally 12.5kV and the PT ratio is 12,000:120 or 100:1. This gives a secondary voltage that is wellwithin the normal insulation range of building wires. Before applying any PT's, it would be well to determine the actual type of connection for the incoming power--Wye (Star) or Delta, because this will also dictate the ratio and connections for the PT's. Similarly to this, for CT's the same scaling of the meter faceplate is

cr4.globalspec.com/thread/44881/How-to-Calculate-CT-Ratio-and-PT-Ratio

1/5

5/23/13

CR4 - Thread: How to Calculate CT Ratio and PT Ratio

needed. It may be ordered with a 0-5A movement, but scaled so the 5A corresponds to the full-scale primary current of the PT. --JMM

brich
Guru

Re: How to Calculate CT Ratio and PT Ratio


10/17/2009 5:16 AM

#2

Join Date: Oct 2009 Location: sometimes Wales,UK.. sometimes Libya! Posts: 1071 Good Answers: 76

CT output is 0 to 5 amps, if you are connecting to a map chart recorder such as a Bristol. The idea is to keep the output from CT to chart recorder at 2.5 amps, so with that in mind read the following...........................Current Transformers Electronic and mechanical measuring devices monitor the amperage in the switchboard. To monitor the motor current, it must be reduced to a level that is easier to measure. If the amperage drawn by the motor is not reduced, measuring devices have to be large and cumbersome in order to house components capable of withstanding high currents. Most submersible pump system measuring devices (motor controllers) are designed to operate from 0 A to 5 A. To reduce or scale-down the actual current in the switchboard to an acceptable level, current transformers are used. Current Transformer Ratios The current transformers should be sized so that under normal operating conditions, secondary control amperage levels are between 2.5 Aand 3.5 A. This is done to obtain the best motor controller performance and to have the pen track in the center of the recording ammeter char t. The current transformer size calculation is current transformer size = expected amperage through the switchboard x 1.6................next part............Example Motor and Switchboard Information 39 A, 990 V required motor surface voltage; MDFH size 3, 1,500 V switchboard. Using current transformer size = expected amperage through the switchboard x 1.6, current transformer size = 39 A x 1.6 = 62 A Choose a current transformer with a ratio as close to 62:5 as possible. (In this case, a 75:5 ratio.) (39/75) x 5 = 2.6 A hope this helps __________________ The square root of nothing is what you make it!

Anonymous Poster

Re: How to Calculate CT Ratio and PT Ratio


11/06/2009 7:55 AM

#4 In reply to #2

Hi, Could you please tell me where the 1.6 factor (which is applied to the load current in your calculation) comes from? is this just applied to allow for flexibility in full load current? or have i missed something?

brich
Guru

Re: How to Calculate CT Ratio and PT Ratio


11/06/2009 8:25 AM

#5 In reply to #4

it is the co-efficient used to calculate the correct answer. I asked that question years ago, that was the answer, so I used it. hope this helps __________________ The square root of nothing is what you make it!

Join Date: Oct 2009 Location: sometimes Wales,UK.. sometimes Libya! Posts: 1071 Good Answers: 76

Anonymous

Re: How to Calculate CT Ratio and PT

#6 In reply to #5
2/5

cr4.globalspec.com/thread/44881/How-to-Calculate-CT-Ratio-and-PT-Ratio

5/23/13

CR4 - Thread: How to Calculate CT Ratio and PT Ratio

Poster

Ratio
11/06/2009 9:21 AM

HAHA, thanks, about as much help as everyone else who i have asked. (None).

brich
Guru

Re: How to Calculate CT Ratio and PT Ratio


11/06/2009 9:30 AM

#7 In reply to #6

Join Date: Oct 2009 Location: sometimes Wales,UK.. sometimes Libya! Posts: 1071 Good Answers: 76

My friend, if you don't like the answer, there's not much I can do about it, your question "what is the 1.6 for?" was answered. It is part of the formula I have used for many years without fail. You have asked this forum to which many people reply free of charge to help other people, technical and non-technical to find answers to their technical problems. If you are not happy with the answer or ridicule the person suppling the answer, then don't use this forum, and remain ignorant. All you need to know is that without the "1.6" in the formula you will never get the correct answer you require. So unless you can prove to me you know more than I do on this matter, I have nothing more to say. I am always open to learn, but I suspect you are not, hence your comments. __________________ The square root of nothing is what you make it!

Anonymous Poster

Re: How to Calculate CT Ratio and PT Ratio


11/06/2009 9:45 AM

#8 In reply to #7

Dont get me wrong, i appreciate the reply, but as an engineering student, submitting technical information to professional institutes to demonstrate an understanding of basic engineering theory, i am trying to gain an understanding of WHY a factor of 1.6 is applied to a current, not simply "that it must be done". Where this information is sourced is not important, but understanding it is key.

brich
Guru

Re: How to Calculate CT Ratio and PT Ratio


11/06/2009 9:51 AM

#9 In reply to #8

Join Date: Oct 2009 Location: sometimes Wales,UK.. sometimes Libya! Posts: 1071 Good Answers: 76

that my friend is a FAR FAR better reply, rather than the previous answer. I thought you might be in college/university, so give me time and will TRY and get a FULLER answer for you. However I would ask this.... why do you apply 3.14 to every equation when calculating the circumference of a circle? Because it's "Pie" and we know it works, same theory, but I will look for answer for you OK? __________________ The square root of nothing is what you make it!

jmueller
Guru Join Date: Jul 2006 Posts: 916 Good Answers: 74

Re: How to Calculate CT Ratio and PT Ratio


11/08/2009 2:02 AM

#12 In reply to #8

Guest,

cr4.globalspec.com/thread/44881/How-to-Calculate-CT-Ratio-and-PT-Ratio

3/5

5/23/13

CR4 - Thread: How to Calculate CT Ratio and PT Ratio

In reading the exchange you are part of, I believe the answer of the 1.6 factor is embedded in the original answer. IF you are wanting to get the current reading marginally above the midpoint of the meter range (as suggested for keeping a chart recording pen near the middle of its full scale), then the 1.6 is simply a scaling factor for shortening the range of the fullscale reading. That may be a valid approach, depending on the nature of your data needs. Problems with this approach include an increased % reading error and decreased ability to read very low loads. All-in-all, your approach needs to be determined problem being solved. If accuracy is important, scaling the reading near fullscale is better. If ability to read overloads is important, scaling for the normal load at (say) 60% of full-scale is more reasonable. Whatever you do, make sure that any assumptions and limits to the validity of the readings are included in your documentation. That also is good basic engineering practice. --JMM

brich
Guru

Re: How to Calculate CT Ratio and PT Ratio


11/06/2009 10:31 AM

#10

would you like to give me your email address? mine is contact@submersiblepumpstandards.com __________________ The square root of nothing is what you make it!
Join Date: Oct 2009 Location: sometimes Wales,UK.. sometimes Libya! Posts: 1071 Good Answers: 76

Anonymous Poster
Reply to Forum Thread

Re: How to Calculate CT Ratio and PT Ratio


11/06/2009 11:46 AM

#11 In reply to #10

my email address is rgold@acdp.co.uk


12 comments

Back to top

Interested in this topic? By joining CR4 you can "subscribe" to this discussion and receive notification when new comments are added. Join CR4, The Engineer's Place for News and Discussion!

Users who posted comments: Anonymous Poster (4); brich (5); jmueller (2); Tornado (1)

C opy to C lipboard

Previous in Forum: Signal Cables Next in Forum: Dynamo Regenerative Braking? You might be interested in: Refrigeration Compressors and Air Conditioning Compressors, IC Analog Multiplexers, GPIB Converters

cr4.globalspec.com/thread/44881/How-to-Calculate-CT-Ratio-and-PT-Ratio

4/5

5/23/13

CR4 - Thread: How to Calculate CT Ratio and PT Ratio

"Knowledge is power." -- Francis Bacon


All times are displayed in US/Eastern (EDT) (Register to change time zone) 2013 IHS. GlobalSpec, the GlobalSpec logo, SpecSearch, the Engineering Web, the Engineering Search Engine, C R4 and C onference Room 4 are registered trademarks of IHS. All other company and product names may be trademarks of their respective owners. No portion of this site may be copied, retransmitted, reposted, duplicated or otherwise used without the express written permission of IHS GlobalSpec, 30 Tech Valley Dr. Suite 102, East Greenbush, NY, 12061

cr4.globalspec.com/thread/44881/How-to-Calculate-CT-Ratio-and-PT-Ratio

5/5

Anda mungkin juga menyukai