1.
MEASUREMENTS RELATED TO AC GENERATOR ....................................................................................... 4 1.1. 1.2. 1.3. 1.4. 1.5. 1.6. 1.7. 1.8. MEASURING EQUIPMENT ...................................................................................................................... 4 AC GENERATOR PARAMETERS ................................................................................................................ 4 HARMONIC CURRENT FACTOR (HCF) ........................................................................................................ 8 SYMMETRICAL COMPONENTS OF CURRENTS ............................................................................................... 9 RATIO OF THE NEGATIVE-SEQUENCE COMPONENT OF CURRENT TO THE RATED CURRENT (I2/IN) ............................. 11 VOLTAGE AND FREQUENCY VARIATIONS DURING OPERATION......................................................................... 12 VOLTAGE DEPENDENCE OF THE GENERATOR FREQUENCY .............................................................................. 15 SUMMARY OF THE REPORT ................................................................................................................... 15
2.
MEASUREMENTS RELATED TO 110 KV DISTRIBUTION NETWORK .......................................................... 17 2.1. 2.2. 2.3. 2.4. 2.5. 2.6. 2.7. 2.8. MEASURING EQUIPMENT .................................................................................................................... 17 POWER FREQUENCY ASSESSMENT .......................................................................................................... 17 LONG TERM FLICKER SEVERITY ............................................................................................................... 19 VOLTAGE UNBALANCE ASSESSMENT ....................................................................................................... 20 HARMONICS ASSESSMENT ................................................................................................................... 21 SUPPLY VOLTAGE VARIATION ................................................................................................................ 24 EVENTS ........................................................................................................................................... 25 SUMMARY OF THE REPORT ................................................................................................................... 26
3.
LITERATURE........................................................................................................................................... 26
Measurements were done on the voltage and current transformers terminals in the XXX Localization of the power quality recorder in the generator circuitry presents XX
The generator parameters during 1 week assessment time are shown in Table 1-1:
Values Parameter min Active power P [MW] Reactive power Q [MVAr] Apparent Power S [MVA] cos tan Power factor PF 24,515 2,604 24,752 0,934 0,045 0,964 Percentile 95% 62,975 18,361 64,802 0,994 0,110 0,993 max 64,291 22,961 66,782 0,999 0,382 0,998
Fig. 1.1. Visualization of the generators active power in 1 week. (yellow line sum of three phase quantities)
Fig. 1.6. Localization of the power quality measurements in the generator circuitry.
where in is the ratio of the harmonic current In to the rated current IN; n is the order of harmonic; k = 13. Harmonic components are shown in Fig. 1.7.
Table 1-2. Assessment of the HCF HCF assessment min Percentile 95% max HCF [%] 1,01 1,69 1,83
During 100% of the assessment period the maximum HCF values are within the range of 1,01% 1,83%, all below the limit of 5%.
Fig. 1.7. Visualization of the currents harmonics averaged over 1 week. (in all figures the plots of L1 are blue, L2-red, L3-green)
Table 1-3. Assessment of the negative and zero-sequence components Components ratio Components ratio assessment min Zero/Pos Neg/Pos 0,43 0,55 [%] Percentile 95% 0,50 1,11 max 0,50 2,35
During 100% of the assessment period measured values hold in range from 0,43% to 0,50% for zero sequence component and from 0,55% to 2,35% for negative sequence component, all below the limit of 5%.
Table 1-4. Assessment of the I2/IN I2/IN assessment I2/IN I2/IN I2/IN min Percentile 95% max I2/IN [%] 0,008 0,152 0,356
Figure 1.10 and Table 1-4 contains statistical parameters which confirmed that in the investigated case requirements for I2/IN are fulfilled. The recorded r.m.s. values hold in range from 0,008% to 0,356%.
Fig. 1.11. Voltage and frequency limits for generators with plotted limit range of recorded values (red rectangle).
Table 1-5. Assessment of voltage and frequency limits Voltage and frequency limits min
U,
Visualization of the recorded data in Figures 1.12 and 1.1.3 and Table 1-5 contain statistical parameters which confirmed that in the investigated case requirements for voltage and frequency limits are fulfilled.
Ug/f
[p.u.]
Ug Ug/f10min f
max
For measured data, the maximum of numerical approximate gradient showed the point where the change of frequency was the highest (22.11.2010 06:00:00), see Table 1-6. Corresponding change of voltage was determined and the ratio Ug/f computed at this time point [2]. The requirements are fulfilled.
During the assessment period no events were detected (with exception to one generator disconnection from the grid due to causes not relevant to power quality assessment).
2.1.Measuring equipment
Fluke 1760, Three-Phase Power Quality Recorder Topas, Serial No. UO13379, GPS time synchronization, Class-A compliance. Measurements were done on the voltage and current transformers terminals of transmission line 1 in XXX.
Localization of the power quality recorder in the distribution network of the 110 kV line No. 1 presents XX
Fig. 2.1. Localization of the power quality measurements in 110 kV distribution network.
50 Hz 1 % (i.e. 49,5 Hz... 50,5 Hz) during 99 ,5 % of a week; 50 Hz + 4 % / - 6 % (i.e. 47 Hz... 52 Hz) during 100 % of the week;
Table 2-1. Assessment of power frequency variation Frequency assessment f10s f10s f10s min Percentile 99,5% max f [Hz] 49,905 50,009 50,109
Visualization of the recorded set of frequency values is shown in Fig. 2.2. Figure 2.2 and Table 1-2 contains the statistical parameters which confirmed that in the investigated case requirements for frequency standards are fulfilled. During 100% of the assessment period frequency values hold in range from 49,905 to 50,109 Hz.
Fig. 2.3. Visualization of long-term flicker severity Table 2-2. Assessment of long-term flicker severity Flicker assessment min Plt2h Percentile 95% max L1 [-] 0,15 0,73 0,75 L2 [-] 0,16 0,65 0,66 L3 [-] 0,15 0,63 0,64
Visualization of the recorded set of long-term flicker coefficient values is shown in Fig 2.3. The standards indicate that under normal operating conditions, in any period of one week the long term flicker severity caused by voltage fluctuation should be Plt 0,8 for 95 % of the time [5]. Table 2-2 contains the statistical parameters which confirmed that in the investigated case requirements for flicker severity are fulfilled. 95% of the recorded long-term flicker values hold in range from 0,15 to 0,75. Moreover 100% of the recorded values follows by the standard expectation.
Fig. 2.4. Visualization of the voltage unbalance variation Table 2-3. Assessment of unbalance variation Unbalance assessment min Neg/Pos10min Percentile 95% max Neg/Pos [%] 0,15 0,26 0,29
Visualization of the recorded set of unbalance values is shown in Fig. 2.4. The standard [4] indicates that under normal operating conditions, during each period of one week, 95 % of the 10 min mean r.m.s. values of the negative phase sequence component (fundamental) of the supply voltage shall be within the range 0 % to 1 % of the positive phase sequence component (fundamental). Table 2-3 contains statistical parameters which confirm that in the investigated case requirements for unbalance standards are fulfilled. The recorded unbalance coefficient hold in range from 0,15% to 0,29%.(with 95% values not greater than 0,26%).
2.5.Harmonics assessment
Table 2-4. Assessment of harmonic variations
Max L3 [%]
0,06 0,15 0,02 0,71 0,02 0,39 0,03 0,04 0,03 0,15 0,02 0,19 0,02 0,02 0,01 0,12 0,02 0,06 0,01 0,01 0,01 0,08 0,01 0,07 0,01 0,01 0,01 0,02 0,01 0,02 L1 L2
Limits [%]
1,50 2,00 1,00 2,00 0,50 2,00 0,50 1,00 0,50 1,50 0,50 1,50 0,50 0,50 0,50 0,00 0,50 1,00 0,50 0,50 0,50 0,70 0,50 0,70 0,68 0,66 0,65 0,63 0,62 0,60
L1
L2
L3 [%]
0,08 0,19 0,04 0,95 0,03 0,50 0,05 0,07 0,07 0,19 0,02 0,28 0,03 0,03 0,02 0,15 0,03 0,08 0,03 0,03 0,02 0,11 0,02 0,13 0,01 0,01 0,01 0,02 0,01 0,02
[%]
0,06 0,26 0,03 0,74 0,02 0,41 0,03 0,04 0,03 0,14 0,02 0,19 0,02 0,02 0,01 0,10 0,01 0,07 0,01 0,01 0,01 0,07 0,01 0,07 0,01 0,01 0,01 0,02 0,01 0,02
[%]
0,06 0,30 0,02 0,66 0,02 0,39 0,02 0,04 0,03 0,16 0,02 0,19 0,02 0,02 0,01 0,10 0,01 0,06 0,01 0,01 0,01 0,08 0,01 0,06 0,01 0,01 0,01 0,02 0,01 0,02
[%]
0,09 0,28 0,04 0,90 0,04 0,53 0,05 0,07 0,07 0,18 0,02 0,27 0,03 0,03 0,02 0,13 0,02 0,09 0,02 0,03 0,02 0,11 0,02 0,13 0,01 0,01 0,01 0,02 0,01 0,02
[%]
0,09 0,33 0,03 0,89 0,03 0,48 0,05 0,07 0,06 0,19 0,02 0,28 0,03 0,03 0,02 0,12 0,03 0,10 0,03 0,03 0,02 0,14 0,03 0,11 0,01 0,01 0,01 0,02 0,01 0,02
32* 33* 34* 35* 36* 37* 38* 39* 40* 41* 42* 43* 44* 45* 46* 47* 48* 49*
0,59 0,58 0,57 0,56 0,55 0,54 0,53 0,52 0,51 0,50 0,50 0,49 0,48 0,48 0,47 0,47 0,46 0,46
0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,02 0,01 0,02
0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,02 0,01 0,03 0,01 0,01 0,01 0,02 0,01 0,01
0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,03 0,01 0,03 0,01 0,02 0,01 0,02 0,01 0,01
0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,02 0,01 0,02
0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,02 0,01 0,03 0,01 0,01 0,01 0,02 0,01 0,01
0,01 0,01 0,01 0,02 0,01 0,02 0,01 0,01 0,01 0,03 0,01 0,03 0,01 0,02 0,01 0,02 0,01 0,01 0,01
0,01 0,01 0,01 0,01 0,01 50* 0,45 th *For harmonics higher than 25 the formula for the harmonic limit is 0,2+0,5(25/h) [%] [5].
Table 2-4 contains limits for particular harmonics defined in [5] and statistical parameters of recorded data. Distribution of the harmonics is also visible in Fig, 2.5. Performed measurements has detected no values over the limit.
Fig, 2.6. Visualization of THDV variation Table 2-5. Assessment of THDV variation THDV assessment min THDV
10min
Visualization of the recorded set of total harmonics distortion in voltage is shown in Fig. 2-6, [5] indicates THD of the supply voltage (including all harmonics up to the order 40) shall be less than or equal to 3 %. Table 2-5 contains the statistical parameters of THDV which confirmed that in the investigated case requirements are fulfilled, 95% of the recorded THDV coefficient hold in
range from 0,83% to 0,88%, Moreover 100% of the recorded values follow by the standard expectation.
Table 2-6. Assessment of supply voltage variation Voltage assesment min U10min Percentile 95% max VL1 [V] 67609,00 69407,25 69677,00 VL2 [V] 67837,00 69648,00 69948,00 VL3 [V] 67683,00 69441,50 69698,00
Visualization of the recorded set of supply voltage values is shown in Fig, 2.7. The [5] indicates that under normal operating conditions: - during each period of one week 95 % of the 10 min mean r.m.s. values of the supply voltage shall be within the range of Un 10 %, i.e. in the range 57157,68 69859,38 V. Table 2-6 contains statistical parameters which confirmed that in the investigated case requirements for r.m.s. supply voltage standards are fulfilled, 95% of the recorded r.m.s.,
values hold in range from 69407,25 V to 69648,00 V Moreover 100% of the recorded values follows by standard expectation, i.e. are within the range of 50806,82 V 76210,23 V.
2.7.Events
During the assessment period the following events were detected:
Overvoltages Designation Number Maximum value [V] Maximum duration L1 1 69879 4h 56m 26s L2 4 70136 8h 51m 14s L3 1 69900 6h 9m 33s L123-N 4 70136 8h 51m 14s
Details of recorded events Event Location Detection Date & Time 21.11.2010 00:45:43,71 21.11.2010 00:45:43,71 21.11.2010 00:51:22,33 21.11.2010 03:05:31,08 21.11.2010 04:18:47,43 21.11.2010 05:00:50,17 22.11.2010 00:47:40,70 22.11.2010 00:47:40,70 22.11.2010 00:53:02,94 22.11.2010 08:33:09,62 22.11.2010 08:33:09,62 23.11.2010 13:20:18,80 23.11.2010 18:55:21,73 24.11.2010 01:43:38,14 24.11.2010 01:43:38,14 24.11.2010 09:15:00,91 24.11.2010 14:27:37,11 24.11.2010 15:38:24,90 25.11.2010 02:05:16,99 Duration Value
Voltage Swells Voltage Swells Voltage Swells Voltage Swells Voltage Swells Voltage Swells Voltage Swells 3-ph Voltage Swells 3-ph Voltage Swells 3-ph Voltage Swells 3-ph RMS Upper Limit RMS Upper Limit RMS Upper Limit RMS Upper Limit RMS Upper Limit h06 Harmonics h06 Harmonics h06 Harmonics h06 Harmonics
6h 9m 33s 4h 56m 26s 8h 51m 14s 5h 16m 0s 4h 8m 3s 4h 5m 8s 8h 51m 14s 5h 16m 0s 4h 8m 3s 4h 5m 8s 4h 44m 5s 10h 19m 45s 6h 11m 40s 4h 33m 42s 4h 23m 59s 200,06ms 200,05ms 199,88ms 999,77ms
6,99e+04 [V] 6,988e+04 [V] 7,014e+04 [V] 7,003e+04 [V] 6,999e+04 [V] 6,991e+04 [V] 7,014e+04 [V] 7,003e+04 [V] 6,999e+04 [V] 6,991e+04 [V] 6,987e+04 [V] 7,012e+04 [V] 7,001e+04 [V] 6,996e+04 [V] 6,989e+04 [V] 0,5343 [%] 0,5235 [%] 0,501 [%] 0,5519 [%]
h06 Harmonics h06 Harmonics h06 Harmonics h06 Harmonics h12 Harmonics
V L1 V L1 V L1 V L3 V L1
25.11.2010 02:05:16,99 25.11.2010 02:05:19,01 25.11.2010 05:29:01,27 25.11.2010 07:55:14,98 25.11.2010 12:44:23,45
0,5788 [%] 0,5491 [%] 0,5054 [%] 0,5294 [%] 0,7392 [%]
3. Literature
[1] IEC 61000-4-30:2008, Electromagnetic compatibility (EMC): Testing and measurement techniques -Power quality measurement method [2] Bollen M,H,J, Irene Yu-Hua Gu, Signal Processing of Power Quality Disturbances, 2006 The Institute of Electronics and Electrical Engineers, Inc [3] EN 50160: Voltage characteristics of electricity supplied by public distribution networks [4] IEC 60034-1: Rotating electrical machines: 7 Electrical operating conditions [5] Regulations of the operation and exploitation of the distribution network