INDUSTRIAL DEHUMIDIFIERS
FD
SERIES
TECHNICAL MANUAL
FD750/980 Rev.12.2012
FD
Index
DECLARATION OF CONFORMITY .................................................................................................................. 4 Dehumidifiers FD750 / FD980 series ........................................................................................................ 4 UTILITY AND CONSERVATION OF THE MANUAL .......................................................................................... 5 NORMS REFERENCES ................................................................................................................................ 5 GENERAL SAFETY NORMS ........................................................................................................................ 5 PERSONAL PROTECTIVE EQUIPMENT ....................................................................................................... 6 UNIT DESCRIPTION ....................................................................................................................................... 7 Frame: ...................................................................................................................................................... 7 Refrigerant circuit..................................................................................................................................... 7 Condenser and evaporators ..................................................................................................................... 7 FINNED PACK ........................................................................................................................................ 7 FINS....................................................................................................................................................... 7 TUBES ................................................................................................................................................... 7 Compressor .......................................................................................................................................... 7 FANS ..................................................................................................................................................... 8 ELECTRIC BOX ....................................................................................................................................... 8 MICROPROCESSORS ............................................................................................................................. 8 VERSIONS...................................................................................................................................................... 8 AVAILABLE MODELS AND THEIR ACCESSORIES ........................................................................................ 8 TECHNICAL DATA FD.................................................................................................................................... 9 DRYING CAPACITY ...................................................................................................................................... 10 FAN PERFORMANCE ................................................................................................................................... 12 FUNCTIONING LIMITS ................................................................................................................................. 12 PERFORMANCE TABLES FD360 ................................................................................................................... 13 PERFORMANCE TABLES FD520 ................................................................................................................... 14 CONTROL AND SAFETY DEVICES ................................................................................................................. 15 CONTROL DEVICES.................................................................................................................................. 15 HUMIDITY CONTROL SWITCH................................................................................................................. 15 SAFETY DEVICES...................................................................................................................................... 15 HIGH PRESSURE SWITCH ........................................................................................................................ 15 LOW PRESSURE SWITCH ......................................................................................................................... 15 DEFROST THERMOSTAT.......................................................................................................................... 15 CONTROL DEVICE OF THE PHASE SEQUENCES ....................................................................................... 16 HYGROSTAT ............................................................................................................................................ 16 THERMOSTAT ............................................................................................. Error! Bookmark not defined. INSPECTION, TRANSPORT AND SITE HANDLING ........................................................................................ 17
FD750/980 Rev.12.2012
FD
INSPECTION ............................................................................................................................................ 17 LIFTING AND SITE HANDLING ................................................................................................................. 17 UNPACKING ............................................................................................................................................ 17 LOCATION ............................................................................................................................................... 18 INSTALLATION ............................................................................................................................................ 18 CLEARANCES ........................................................................................................................................... 18 MAINTENANCE AND PERIODIC CHECKS ..................................................................................................... 19 IMPORTANT WARNINGS ........................................................................................................................ 19 CONNECTION TO THE CONDENSED WATER DRAINAGE FITTING ............................................................... 20 DUCT WORK UNIT CONNECTION ............................................................................................................... 20 REFRIGERANT CONNECTIONS FOR TCR VERSIONS..................................................................................... 21 REFRIGERANT LAY-OUT VERSION FD-FDS .................................................................................................. 22 ELECTRICAL CONNECTIONS ........................................................................................................................ 23 Generality ............................................................................................................................................... 23 Main supply connection ......................................................................................................................... 24 START UP .................................................................................................................................................... 24 PRE-START CHECK................................................................................................................................... 24 Before to proceed to start up, close electrical line main switch (not supplied with the unit): the green led (line) will be lit up. ................................................................................................................................ 24 SIGNALLING LEDS PANEL ........................................................................................................................ 25 MACHINE STOP (STAND BY) ................................................................................................................... 25 REMOTE CONTROL ................................................................................................................................. 26 GENERAL OBSERVATIOTIONS AND ADVISE ................................................................................................ 26 DISPOSAL OF THE UNIT AT END OF ITS LIFE ............................................................................................... 27 TROUBLE SHOOTING .................................................................................................................................. 27 UNIT UNDER ALARM .............................................................................................................................. 27 ELECTRIC DIAGRAM .................................................................................................................................... 30 DRAWINGS (lay out) ................................................................................................................................... 32 DIMENSIONAL DRAWINGS DIMENSIONAL DRAWINGS DIMENSIONAL DRAWINGS FD750 / 980 ............................................................................................... 34 STANDARD OUTSIDE CONDENSER ............................................................ 35 SILENT OUTSIDE CONDENSER ................................................................... 36
FD750/980 Rev.12.2012
FD
DECLARATION OF CONFORMITY
FRAL Company s.r.l. Viale dellIndustria e dellArtigianato 22/c 35010 Carmignano di Brenta PD hereby declares that the following products:
have been designed, manufactured and distributed according to safety and electro-magnetic compatibility of the European Norms and Regulations:
MACHINES NORMS 2006/42/CE; SECURITY REGULATIONS FOR LOW TENSION APPLIANCES 2006/95/CE; ELECTROMAGNETIC COMPATIBILITY (EMC) 2004/108/CE. It is hereby certified that this Dehumidifier conforms to the: IEC Regulations CEI-EN 60335-2-40, CEI-EN 55014-1, 55014-2. The machine is built according to RoHS European Norms
FD750/980 Rev.12.2012
FD
NORMS REFERENCES
The machines described in this manual hav been designed according to the pertinent CE Norms, in conformity with the MACHINES DIRECTIVES cited in the previous paragraph. The machines are also complying with the essential requirements of the following European Rules and Directives: Machine Safety Norms 89/392 CEE, Electrical Safety Rules for the Low Tension Appliances 2006/95 CEE, Electromagnetic Compatibility Norms2004/108 CEE, Under Pressure Devices 97/23/CE.
FD
Attention: before every operation of servicing on the unit, be sure that the electric supply is disconnected.
Never sprinkle water over the unit and its electrical components.
SAFETY SIGNS The equipment features the following safety signs, which must be complied with:
General hazard
FD750/980 Rev.12.2012
FD
UNIT DESCRIPTION
Frame:
All FD units are made from galvanised thick sheet metal, painted with polyurethane powder enamel at 180C to ensure the best resistance against the atmospheric agents. The frame is self-supporting with anodized extruded aluminum profiles. The drip tray is present standard in all FD units and its in stainless steel.
Refrigerant circuit
The refrigerant gas used in these units is R407C. The refrigerant circuit is made in according to ISO 97/23 concerning welding procedures and PED regulation. The refrigerant circuit includes: filter drier, Schrader valves form maintenance and control, pressure safety device (according to PED regulation). thermal expansion valve with external equalizer. solenoid valve compressor.
It consist of copper tubes mechanically expanded into aluminium or copper fins provided with full collars that allow their regular spacing. The best heat transmission is guaranteed by the fin collars that completely cover the tubes.
FINS
They are manufactured by high precision pressing of aluminium, aluminium epoxy painted, copper or pretinned copper sheets. The fin shape is slightly corrugated in order to improve the heat exchange transmission coeffi cient without heavily affecting the air pressure drop. Furthermore a good water draining is assures and the inside dust accumulation is avoided.
TUBES
For the heat exchangers high quality copper tubes are used. The tubes are suitable for the majority of the primary refrigerants in both cold and warm working conditions.
Compressor
The compressor is scroll type with crankcase heater and thermal overload protection by a klaxon embedded in the motor winding. The characteristics of the compressor are the follow: 1. High efficiency for saving energy consumption
FD750/980 Rev.12.2012
FD
2. Low sound level quiet operation 3. Applied HFC refrigerant for protecting environment 4. High reliability, long lifetime.
FANS
The electric switch board is made according to electromagnetic compatibility norms (2004/108 CEE) and Electrical Safety Rules for the Low Tension Appliances 2006/95 CEE. Inside the electric box there are the following components: 1. Main switch 2. Phase Sequenze relay; 3. General disconnector with fuses; 4. Compressor Contactors; 5. Relay; 6. Terminals for remote control.
MICROPROCESSORS
The microprocessors check all the function of the machine like: General functioning, automatic defrost system, alarms and set point of the humidty and temperature (temperature only for TCR Version).
VERSIONS
AVAILABLE MODELS AND THEIR ACCESSORIES
HOT GASDEFROST VERSION (S): The frost which covers the battery, obtrsucts the passage of the air, reduces the air contact surface and, consequently, the performance; if the frost accumulation is excessive, it can seriously damage the whole system. All units are provided with Desfrost System. The standard versions have their defrost simply throughly the periodic stop of the compressor, using the heat of the environment itself. In the versions with Hot Gas Defrost System, the defrosting is controlled by the electronic system in combination with a thermostat, the bulb of which is installed inside the evaporator. The defrosting phase in the Hot Gas System takes place only when the thermostat activates it in presence of freeze. During the defrosting time the DEFROST light is ON. TEMPERATURE CONTROL VERSION (FD TCR): The units of the control temperature version are equipped with external remote condenser that is connected with the dehumidifier. The use of the remote condenser allows the control of the temperature and humidity at the same time, operating in cooling or dehumidifying mode. For to use both the functions is needs to have a thermostat and a hygrostat.
FD750/980 Rev.12.2012
FD
TECHNICAL DATA FD
Mod. Drying capacity (1) Cooling capacity
(at inside 26C out side 30C)
750 L/24h kW kW kW A m3/h 750 // 9,0 11,0 22 6.200 1,7 200 6,5 67 5 - 35 C 1 35 (6) 40 - 99 1580 1260 1130 230 400/3 +N/50
980 980 // 11,0 13,0 28 8.500 2,3 200 7,5 70 5 - 35 1 35 (6) 40 - 99 2000 1300 1600 320 400/3 +N/50
750 TCR 750 26 9,0 11,0 23,3 6.200 1,7 200 // 67 5 - 35 1 35 (6) 40 - 99 1580 1260 1130 230 400/3 +N/50
980 TCR 980 31,5 11,0 13,0 29,7 8.500 2,3 200 // 70 5 - 35 1 35 (6) 40 - 99 2000 1300 1600 320 400/3 +N/50
Nominal power consumption(3) Maximum power consumption(4) Max.current consumption(4) Nominal Air flow Available static pressure R407C refrigerant charge Sound pressure level (3 mt free field) (5) Temperature operating range(6) Humidity operating range Condensate draining connection Length Depth Heigth Operating weight Nominal power supply
(1) (3) (4)
m3/s Pa Kg dB(A)
% INCH mm mm mm Kg V/ph/ Hz
Referred to: inlet air temp. 32 C relative humidity 90% Referred to: inlet air temp. 25 C relative humidity 60% Referred to: inlet air temp. 35 C relative humidity 95%
FD750/980 Rev.12.2012
FD
(5) (6) Sound power level calucated according to ISO 3746 S version with hot gas defrost
FD750/980 Rev.12.2012
10
FD
DRYING CAPACITY
Ambient temperature C
30
25
80%
10
15
20
FD 750
140 270 410 510 670 860 1000
Ambient temperature C
30
25
80%
10
15
20
FD 980
140 270 410 510 670 860 1000
FD750/980 Rev.12.2012
11
FD
FAN PERFORMANCE
AIR FLOW WITH DIFFERENT HEAD PRESSURES
Available head pressure (Pa) Air flow cm/h FD750 (Mid . fan speed) Air flow cm/h FD980 (max. fan speed) 160 6.200 170 6.000 180 5.800 190 5.600 200 5.500 210 5.400 230 5.300
8.500
8.300
8.200
8.100
8.100
8.000
8.000
FUNCTIONING LIMITS
Following Diagram represents FD units application . It is strongly recommended to let the units operate within the below reported limits. Exceeding these limits it is not granted neither normal operation nor unit reliability and integrity (for special applications, please contact our Company).
In standard unit applications Table, on the left side is indicated operating limit extension, if unit is provided with hot gas defrost.
FD750/980 Rev.12.2012
12
FD
PERFORMANCE TABLES FD750
Ambient temperature Dehumidification capacity [l/24h] 116 155 210 295 305 459 Dehumidification capacity [l/24h] 156 209 250 418 483 593 Dehumidification capacity [l/24h] 181 242 307 505 573 700 Dehumidification capacity [l/24h] 230 296 464 606 637 810 Input power Air temperature increase Thermal load in ambient [kW] 8,7 12,8 17,4 18,3 25,4 30,0 Thermal load in ambient [kW] 12 16,8 20,8 26,0 31,3 38,6 Thermal load in ambient [kW] 14,3 20,2 24,5 30,5 37,6 45,7 Thermal load in ambient [kW] 17,3 18,1 27,7 36,0 42,7 48,2
[kW] [C] Relative humidity 50% 5,4 7,1 5,9 10,5 6,4 17,4 6,5 18,3 7,3 25,4 9,3 30,2 Input power Air temperature increase
[kW] [C] Relative humidity 60% 5,6 9,8 6,2 13,7 6,5 16,9 7,4 21,3 8,8 25,5 9,9 31,5 Input power Air temperature increase
[kW] [C] Relative humidity 70% 5,6 11,6 6,2 16,5 6,4 20 6,7 24,9 9,3 30,7 9,9 37,3 Input power [kW] 5,7 6,0 6,8 8,0 9,7 11,0 Air temperature increase [C] 14,2 14,8 22,7 29,4 30,8 39,4
FD750/980 Rev.12.2012
13
FD
PERFORMANCE TABLES FD980
Ambient temperature Dehumidification capacity [l/24h] 135 181 244 343 343 533 Dehumidification capacity [l/24h] 181 243 291 486 561 688 Dehumidification capacity [l/24h] 211 281 357 584 665 813 Dehumidification capacity [l/24h] 267 344 539 705 798 941 Input power Air temperature increase Thermal load in ambient [kW] 11,7 17,3 23,4 24,7 34,3 40,7 Thermal load in ambient [kW] 16,2 22,7 28,0 35,3 42,2 52,0 Thermal load in ambient [kW] 19,3 27,2 33,1 41,2 50,8 61,6 Thermal load in ambient [kW] 23,4 24,5 37,4 48,6 57,6 65,0
[kW] [C] Relative humidity 50% 6,3 9,6 6,8 14,0 7,4 19,0 7,6 20,0 8,5 28,0 10,8 33,2 Input power Air temperature increase
[kW] [C] Relative humidity 60% 6,5 13,3 7,2 18,5 7,6 22,9 8,6 28,7 10,3 34,5 11,5 42,5 Input power Air temperature increase
[kW] [C] Relative humidity 70% 6,5 15,7 7,2 22,2 7,4 27,0 7,7 33,6 10,8 41,5 11,5 50,3 Input power Air temperature increase
[kW] [C] Relative humidity 80% 6,6 19,0 7,0 20,0 7,9 30,5 9,4 39,7 11,3 47,0 12,8 53,1
FD750/980 Rev.12.2012
14
FD
CONTROL AND SAFETY DEVICES
CONTROL DEVICES
All the control devices are tested on factory before the unit is delivered. Their operating mode is described in the following paragraphs.
SAFETY DEVICES
All the safety devices are set and tested on factory before they are delivered. Their operating mode is described in the following paragraphs. All service operations on control and safety devices must be done by TRAINED PEOPLE ONLY: wrong setting values of the mentioned devices could cause serious damage to the unit and injuries to the people.
DEFROST THERMOSTAT
This device signals to electronic control that defrost procedure is needed. When defrost cycle is activated, defrost thermostat will control its conclusion.
CONTROL DEVICES High pressure switch (bar) Low pressure switch (bar) Defrost temperature switch (C) ACTIVATION DIFFERENTIAL REINSERTION
29 0.7 1
7.7 2.2 3
FD750/980 Rev.12.2012
15
FD
CONTROL DEVICE OF THE PHASE SEQUENCES
Since the SCROLL compressors can function only in one rotating direction, this device controls that the phases be correctly connected. In case they may not be correctly connected, the machine will not start, a light will begin to flash in the relays and on the panel the green light ALARM will be ON ,
HYGROSTAT
The hygrostat enables or disables unit operation depending on the humidity value desired. To verify its correct operation, rotate the control knob clock wise (or set the desired value through the instrument keyboard if keyboard instrument should be present) and set the humidity desired value close to lower limit. At this point verify that fan and compressor (after a time delay) will be started in sequence. Verify as well that the unit is stopped when humidity set is reached.
FD750/980 Rev.12.2012
16
FD
INSPECTION, TRANSPORT AND SITE HANDLING
INSPECTION
After receiving the unit, immediately check its integrity. The unit left the factory in perfect condition; any eventual damage must be questioned to the carrier and recorded on the Delivery Note before it is signed. Our firm must be informed, within 8 days, of the extent of the damage. The Customer must prepare a written statement of any severe damage.
UNPACKING
When unpacking the unit pay attention not to damage the unit. The package is made up by different materials: wood, paper, nylon etc. Its a good rule to keep them separately and deliver to the proper collecting centre in order to reduce their environmental impact.
FD750/980 Rev.12.2012
17
FD
LOCATION
Consideration must be given to the following points when determining the most suitable site for the unit installation: location arrangement in order to guarantee adequate air flow (no narrow spaces) electrical power sup ply location; accessibility for servicing/maintenance and repair of the unit and/or its components; floor loading strength and ability to support the operating weight of the unit; possible objection to operating noise.
INSTALLATION
CLEARANCES
Absolute care must be taken to ensure adequate air volume to the air intake and fan discharge, and to avoid air recirculation through the unit that will deeply reduce its performances. For these reasons it is necessary to observe the following clearances (see the pictures in the following pages):
A 500 500
B 800 800
C 800 800
D 800 800
E 800 800
A B C
18
FD
MAINTENANCE AND PERIODIC CHECKS
IMPORTANT WARNINGS
WARNING: Inside the unit some moving components are present. Be very careful when operating in their surroundings even if the electric supply is disconnected. WARNING: The unit should be installed so that maintenance and/or repair services be possible. The warranty does not cover costs due to lifting apparatus, platforms or other lifting systems required by the warranty interventions.
WARNING: The top shell and discharge line of compressor are usually at high temperature level. Be very careful when operating in their surroundings. WARNING: Aluminium coil fins are very sharp and can cause serious wounds. Be very careful when operating in their surroundings.
WARNING: After servicing operation close the unit with cover panels, fixing them with locking screws.
All this operation described in this chapter MUST BE DONE BY TRAINED PEOPLE ONLY Before every operation of servicing on the unit, be sure that the electric supply has been disconnected. In the inner side of the unit movable parts are present. Be very careful when operating in their surroundings.
Aluminium coil fins are very sharp and can cause serious wounds.
After servicing operations, close the unit with cover panels, fixing them locking screws.
with
19
FD
CONNECTION TO THE CONDENSED WATER DRAINAGE FITTING
Connect condensed water drainage fitting ( M) to a draining pipe. It should be always avoided to form a doubble siphon, which could obstruct the water flowing with the consequent risk of flooding the area.
FD
REFRIGERANT CONNECTIONS FOR TCR VERSIONS
The maximum distance between the two units should be 12 mt, The diameter of liquid pipe is 14 mm of gas pipe 22mm. For each mt of piping line add 145 grams of R407c. Vertical distance between the units (Hv): -2m(*)<Hv<+8m [(*)with siphone] Cause the oil during exchange of function (from dehumidifing to cooling) can return to the machine the pendence of piping towards the indoor unit should be minimum 2% Wiring connection between the units: 3x1.5mm+ground,for power cable section look machine absorption
Front Panel
Front Panel
21
FD
REFRIGERANT LAY-OUT VERSION FD-FDS AND TCR VERSION
Only for S version Condenser Evaporator Liquid line filter Low pressure switch High pressure switch Manual valve Liquid separator
Expansion Valve Solenoid valve One way valve Centrifugal fan Motor axial fan Liquid receiver Charge valve Capillary
22
FD
ELECTRICAL CONNECTIONS
Generality
Power supply Auxiliary circuit V/~/Hz V/~/Hz 400 / 3 / 50 230 / 1 / 50 Control circuit Fans power supply V/~/Hz V/~/Hz V/~/Hz V/~/Hz 230 / 1 / 50 230 / 1 / 50 400 / 3 / 50 400 / 3 / 50
Remote condenser fan supply (FD750 version) Remote condenser fan supply (FD980 version)
This machines series belongs to the electric appliances functioning at low tension (230/400 V).
It must be verified that electric supply is corresponding to the unit electric nominal data (tension, phases, frequency) reported on the label in the front panel of the unit. Power connections must be made using a three-wire cable + neutral wire + ground cable. Power cable and line protection must be sized according norm and laws according with absorbed current of the machine (see technical data). The line voltage fluctuations must not be more than 5% of the nominal value, while the voltage unbalance between one phase and another must not exceed 2%. If those tolerances should not be respected, please contact our Firm to provide proper devices. Electric supply must be in the limits shown: in the opposite case warranty will terminate immediately.
Electrical connections therefore must be always done according to the instructions reported on the wiring diagram enclosed with the unit and norms and laws.
23
FD
Ground connection is compulsory. Installer must connect ground cable with a dedicated terminal on the apposite terminal block.
START UP
PRE-START CHECK
Check that all power cables are correctly connected and all terminals are fastly fixed.
The voltage at the phase R S T clamps must be the one indicated on the unit label 5% tolerance. If this should not happen, please, contact our Factory. Caution: before proceeding to start up, check that all the cover panel be located in the proper position and locked with fastening screws. Before to proceed to start up, close electrical line main switch (not supplied with the unit): the green led (line) will be lit up. All the units are provided with microprocessor control that manages all the various functions of the unit. To start the unit, activate humidity switch by rotating the knob or by pressing the instrument keyboard, depending on the type of instrument installed): the green light (WORKING) will be ON. For temporary stop (night-time, weekend, etc.) never break the power supply and strictly follow the procedures illustrated at paragraph 4.6
24
FD
SIGNALLING LEDS PANEL
Units are provided with signalling light panel that indicates unit operational status. Below is reported a brief description of their meaning.
Electrical supply RED Light (POWER): indicates that unit is properly electrically supplied.
Compressor RED Light (WORKING): indicates humidistat call and running compressor status.
25
FD
REMOTE CONTROL
It is possibile to use a remote control with the machine. In this case must be used a remote humidostat to be connected to the terminal boxes of the electric panelboard in place of the standard humidostat. It is also possible to have an ON-OFF switch to be electrically connected in series to the humidostat.
Check that safety and control devices are working correctly (monthly).
Make sure that all the terminals on the electric board and on the compressor be well locked. Periodic cleaning of the sliding terminals of the contactors should be done: if any damage is found, please replace the contactors (monthly). Make sure that there is no oil leakage from compressor (monthly).
Check that the electric resistance in the compressor crankcase be properly functioning (monthly: low temperature units only).
Clean finned coils filters with compressed air in the opposite direction of the airflow. If filters should be fully clogged, clean them with a water jet to be sprayed against the air flow side(monthly or more frequently if the unit operates on a dusty environment).
Check mounting of fan blades and their balancing (every 4 months). POWER SAVINGS To reduce power consumption, take care of following suggestions : Make sure that room in which unit should operate has doors and windows firmly closed;
Set the humidity control switch to the proper value: lower set values than necessary (even few points) may cause great capacity loss with consequently longer operating periods: it is advisable to set humidity values below 60% only if strictly necessary. For the machine which has a second condenser (monoblock or split system) check every month if the heat exchanger is clean and free from room dust, and check the efficiency of the motorfan. 26
FD
DISPOSAL OF THE UNIT AT END OF ITS LIFE
Once the unit is arrived at the end of its life and needs to be removed or replaced, the following operations are recommended: The unit refrigerant has to be recovered by trained people and sent to proper collecting centre; Ccompressor lubricating oil has to be recovered and sent to proper collecting centre;
the frame and various components, if no longer usable , have to be dismantled and subdivided according to their nature; in particular, copper and aluminium, which are present in conspicuous quantity in the unit.
These operations allow easy material recovery and recycling process, reducing environmental impact. It is recommended to follow the pertinent norms in the disposal of the wasted materials.
TROUBLE SHOOTING
In the following pages are reported the most common troubles that can cause the unit to stop or to operate in an uncorrect way. Concerning the solutions, it is necessary to take an extreme care on the actions to adopt: an excessive confidence may cause serious accidents to inexperienced people. It is advisable, once the cause is detected, to contact our servicing people or trained people only.
27
FD
PROBLEM A
Provide power supply, replace fuses
LED ON
PROBABLE CAUSE
CORRECTIVE ACTION
None
Humidistat on set
Let the compressor cool down, replace compressor defective, replace fan defective
Any led
PROBLEM B
LED ON
PROBABLE CAUSE
CORRECTIVE ACTION
Fan starts, compressor does not start, but red alarm led
Any led
28
FD
PROBLEM C
Clean filter and reset unit
LED ON
PROBABLE CAUSE
CORRECTIVE ACTION
Red alarm led Fan starts, compressor does not start, but red alarm led is on Red alarm led
Open panel, low air flow, suction side obstructed, high pressure switch on
Close the panel, clear Suction side, reset high pressure switch
Any led
29
FD
ELECTRIC DIAGRAM
30
FD
31
FD
32
FD
DRAWINGS (lay out)
DUCTING INSTALLATION
WALL INSTALLATION
CEILING INSTALLATION
ON TROLLEY
33
FD
DIMENSIONAL DRAWINGS FD750 / 980
34
FD
DIMENSIONAL DRAWINGS STANDARD OUTSIDE CONDENSER
FOR THE CORRECT SIZE LOOK THE TABLE IN PAG.10..IT IS ONLT A SAMPLE
35
FD
DIMENSIONAL DRAWINGS SILENT OUTSIDE CONDENSER
FOR THE CORRECT SIZE LOOK THE TABLE IN PAG.10..IT IS ONLT A SAMPLE
36