Storage tank
Roof of this building is attached via central gutter (size of 600 mm in depth) 60% of the water collected will flow into central gutter
Rainwater flow into two of 150 mm rainwater downpipe. Collected water will discharge to the perimeter drain at ground level
Header tank
Rainwater from downpipe The water is store in underground storage tank Underground storage tank
Toilet flushing
Tank installation
Internal plumbing
Conveyance system
pump
Storage tank
Toilet flush
Installation of Detention Storage Cum Rainwater Harvesting System at DID Headquarters, Kuala Lumpur
JPS Hq. Hq. Building Roof Area: Total JPS Hq. Hq. staff: Average water use per person: Total water use per day: storage tank size:
(Say 3 days water storage):
Installation of Detention Storage Cum Rainwater Harvesting System at DID Headquarters, Kuala Lumpur
Reliability (%) 57.53 60.74 63.64 66.31 67.95 69.67 70.93 72.02 72.98
Reliabilty (%)
100 90 80 70 60 50 40 30 20 10 0 0 20 40 60 80 100 120 140 Reliability (%)
Installation of Detention Storage Cum Rainwater Harvesting System at DID Headquarters, Kuala Lumpur
To determine the critical storm duration for Detention Storage Size Required
Cs = 1 Qbefore (PSD)
c d 6.09 17.61 33.39 53.05 76.33 103.09 133.20 166.59 203.18 242.93 285.77 331.67 380.60 SSR (m3) 40.81 52.04 57.46 60.14 61.26 61.40 60.88 59.92 58.66 57.20 55.61 53.94 52.25
td (min) 5 10 15 20 25 30 35 40 45 50 55 60 65
I (mm/h) T= 10 yr
380 263 208 175 152 135 122 111 103 95 89 84 79
Runoff Coeff 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91
Area (m2) 1688 1688 1688 1688 1688 1688 1688 1688 1688 1688 1688 1688 1688
Qd (l/s) 162.2 112.3 88.8 74.5 64.7 57.5 51.9 47.5 43.8 40.7 38.0 35.8 33.8
41.1 41.1 41.1 41.1 41.1 41.1 41.1 41.1 41.1 41.1 41.1 41.1 41.1
124.94 237.61 340.61 434.88 520.94 599.14 669.75 732.95 788.90 837.74 879.56 914.46 942.52