Anda di halaman 1dari 7

19435 - Sizing the Flex I/O Power Supply

Access Level: TechConnect Date Created: 02/21/2001 09:18 AM Last Updated: 03/01/2013 03:28 PM

Sizing the Flex I/O Power Supply

FAQs

How do I size my Flex I/O Power Supply?

Some of my Flex I/O Chassis Modules require both 24VDC and consume Flexbus current. How do these affect the sizing of my Flex I/O Power Supply?

Definitions -

Module Supply Voltage: This is typically either 120VAC or +24VDC nominal voltage that is supplied from an external power source wired to the module terminal base.

Flexbus current: This is the "logic current" consumed by the module. The Flex Adapter provides a +5VDC supply via it's internal connector through the successive module terminal base connectors that are attached to it.

Flexbus current consumed by a module has NO affect on the sizing of the Flex I/O Power Supply.

Flex I/O chassis Flexbus current is limited by what current the adapter 5VDC supply can support across the terminal base internal Flexbus connectors .

The adapter can supply 640mA max @ 5VDC (1794-ASB/1794-ACN(R)15) and because no more than 8 Flex modules can be connected to an adapter, no combination of 8 Flex modules will ever draw more than the adapter can supply.

Sizing the Flex I/O Power Supply -

The 1794-PS1 Flex I/O Power Supply is capable of supplying 1A maximum @24VDC and the output surge current of the 1794-PS1 is sufficient to drive 3 adapters (surge of 23A for 2ms each) operating @ 24VDC..

The 1794-PS13 Flex I/O Power Supply is capable of supplying 1.3A maximum @24VDC and the output

surge current of the 1794-PS13 is sufficient to drive 4 adapters (surge of 23A for 2ms each) operating @ 24VDC

The 1794-PS3 Flex I/O Power Supply is capable of supplying 3A maximum1 @24VDC and the output surge current of the 1794-PS3 is sufficient to drive 6 adapters (surge of 23A for 2ms each) operating @ 24VDC

Non-AB DC power supplies can also be utilized but should operate within the specifications required for the devices they are powering.

Size the power supply by calculating the total current consumed by summing the currents for each of the modules used below for the power supply operating voltage applied.

Adapters

1794-ASB/D

Remote I/O Adapter

330mA @ 24VDC (450mA @ 19.2VDC)

1794-ASB/E

Remote I/O Adapter

330mA @ 24VDC

(730mA @ 12VDC)

1794-ACN(R)15

ControlNet Adapter

400mA maximum @ 24VDC

1794-AENT/A

Ethernet/IP Adapter

400mA maximum @ 24VDC

1794-AENT/B

Ethernet/IP Adapter

440mA maximum @ 24VDC

Discrete Input & Modules

The following Flex Input Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed:

1794-IB8

8mA @ 24VDC (2-11mA) per input

1794-IB16

8mA @ 24VDC (2-12mA) per input

1794-IV16

8mA @ 24VDC (2-11mA) per input

1794-IB32

4.1mA @ 24VDC (2-6mA) per input

1794-IB16D

8.2mA @ 24VDC (2-12.1mA) per input

Discrete Output Modules

The following Flex Output Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed PLUS the total current consumed by their loads. Note that the load current is limited by the maximum load current and surge listed.

1794-OB8 Load: Surge:

Module:

25mA @ 24VDC (20-35mA)

500mA max/output 2A for 50ms, repeatable every 2s

1794-OB16 Load: Surge:

Module:

49mA @ 24VDC (38-65mA)

500mA max/output 2A for 50ms, repeatable every 2s

1794-OB16P Load: Surge:

Module:

60mA @ 24VDC (25-75mA)

500mA max/output 1.5A for 50ms, repeatable every 2s

1794-OV16 Load: Surge:

Module:

49mA @ 24VDC (38-65mA)

500mA max/output 2A for 50ms, repeatable every 2s

1794-OV16P Load: Surge:

Module;

49mA @ 24VDC (38-65mA)

500mA max/output 2A for 50ms, repeatable every 2s

1794-OB8EP Load: Surge:

Module:

80mA @ 24VDC

2.0A max/output 4A for 10ms, repeatable every 3s

1794-OW8 Load:

Module:

125mA maximum @ 24VDC

Output load current limited by output voltage at

rated power and has NO impact on power supply sizing. (See module output specification)

1794-OB32P Load: Surge:

Module:

219mA @ 24VDC (104-278mA)

500mA max/output 2A for 50ms, repeatable every 2 seconds

1794-OB16D Load: Surge:

Module:

21mA @ 24VDC (16-26mA)

500mA max/output 2A for 50ms, repeatable every 2 seconds

Combination Discrete Modules

The following Flex modules have a combination of inputs and outputs. The current load should be determined as described previously for the combined input and output specifications listed.

1794-IB10XOB6

Inputs:

8mA @ 24VDC (2-11mA) per input

Outputs: Load: Surge:

Module:

19mA @ 24VDC (15mA @ 19.2VDC; 24mA @ 30VDC; 25mA @ 31.2VDC)

2.0A max/output 4A for 50ms, repeatable every 2s

1794-IB16XOB16P

Inputs:

8.8mA @ 24VDC (2-12.1mA) per input

Outputs: Load: Surge:

Module:

28mA @ 24VDC (27mA @ 19.2VDC; 29mA @ 30VDC; 29mA @ 31.2VDC)

0.5A max/output 1.5A for 50ms, repeatable every 2s

Analog Input Modules

The following Flex Analog Input Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed. In addition, adequate power must be supplied to the 1794-IE8 and 1794-IF4I This power

transmitters to deliver input terminal voltage or drive 20mA into the input impedance listed.

source may be the same as the module power and can be included in the power supply calculation.

1794-IE8/B Input:

Module:

60mA @ 24VDC

100 Kohm impedance on voltage input

238 ohm input impedance on current input

1794-IE12 Input:

Module:

30mA @ 24VDC

> 1 Mohm impedance on voltage input

< 100 ohms input impedance on current input

1794-IF4I Input:

Module:

80mA @ 24VDC

> 1 Mohm input impedance on voltage input

< 100 ohms input impedance on current input

1794-IR8

Module:

140mA @24VDC

1794-IRT8/A Module:

85mA @24VDC

1794-IRT8/B Module:

95mA @24VDC

1794-IT8

Module:

150mA @24VDC

1794-IE8H

Module:

295mA @24VDC

Analog Output Modules

The following Flex Analog Output Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed PLUS the total current consumed by their loads. Note that the load current is limited by maximum current or resistive load permitted per channel.

1794-OE4 Module: Output: 70mA @ 24VDC 3mA per channel maximum current load on voltage output

15 - 750 ohm per channel resistive load for mA output 1794-OE12 Module: 320mA @ 24VDC

Output:

3mA per channel maximum cuurent load on voltage output

0 - 750 ohm per channel resistvie laod for mA output

1794-OF4I Module: Output: 210mA @ 24VDC 3mA per channel maximum current load for voltage output

0 - 750 ohm per channel resistive load for mA output

1794-OE8H Module: 255mA @ 24VDC

Combination Analog Modules

The following Analog Flex modules have a combination of analog inputs and outputs. The current load should be determined as described previously for the combined module and output specifications listed. Note that the output load current is limited by maximum current or resistive load permitted per channel. In addition, adequate power must be supplied to the 1794-IE8 and 1794-IF4I transmitters to deliver input terminal voltage or drive 20mA into the input impedance listed. This power source may be the same as the module power and can be included in the power supply calculation.

1794-IE4XOE2 Module: Inputs: 70mA @ 24VDC 100 Kohm input impedance on voltage input

238 ohms input impedance on current input Outputs: 3mA per channel maximum current load on voltage output

15 - 750 ohms per channle resistive load for mA output

1794-IE8XOE4 Module: Inputs: 140mA @ 24VDC > 1 Mohm input impedance on voltage input

< 100 ohms input impedance on current input Outputs: 3 mA per channel maximum current load on voltage output

0 - 750 ohms per channle resistive load for mA output

1794-IF2XOF2I Module: Inputs: 150mA @ 24VDC > 1 Mohm input impedance on voltage input

< 100ohms input impedance on current input Outputs: 3mA per channel maximum current load for voltage output

0 - 750 ohms per channel resistive load for mA output

Counter Modules

The following counter modules require module power, transmitter input power and in some cases output load power. In those cases it is recommended that a separate power supply be used for output load power for noise immunity.

1794-ID2

Module:

75mA @ 24VDC (150mA @12VDC)

Inputs:

15mA @ 24VDC (3mA @ 6VDC; 9mA @ 12VDC) per input

1794-IP4

Module:

75mA @ 24VDC (150mA @12VDC)

Inputs:

15mA @ 24VDC (3mA @ 6VDC; 9mA @ 12VDC) per input

1794-IJ2

Module;

180mA @ 24VDC (220mA @ 19.2VDC; 140mA @31.2VDC)

Inputs:

9mA @ 2VDC (2-9mA) per input Load: 1.0A max per output

Outputs:

Surge: 2A for 50ms, repeatable every 2s

1794-VHSC Inputs:

Module:

100mA @ 24VDC

10.2mA @ 24VDC (19.1 @ 5VDC; 25.7 @ 6VDC; 6.1mA

@ 15VDC) per input Outputs: Load: 0.5A max per output @ 5VDC; 1.0A max per

output @ 12-24VDC per output

1 Horizontal mounting; 2.8A maximum all other mountings; see derating current in Installation Manual.