FAQs
Some of my Flex I/O Chassis Modules require both 24VDC and consume Flexbus current. How do these affect the sizing of my Flex I/O Power Supply?
Definitions -
Module Supply Voltage: This is typically either 120VAC or +24VDC nominal voltage that is supplied from an external power source wired to the module terminal base.
Flexbus current: This is the "logic current" consumed by the module. The Flex Adapter provides a +5VDC supply via it's internal connector through the successive module terminal base connectors that are attached to it.
Flexbus current consumed by a module has NO affect on the sizing of the Flex I/O Power Supply.
Flex I/O chassis Flexbus current is limited by what current the adapter 5VDC supply can support across the terminal base internal Flexbus connectors .
The adapter can supply 640mA max @ 5VDC (1794-ASB/1794-ACN(R)15) and because no more than 8 Flex modules can be connected to an adapter, no combination of 8 Flex modules will ever draw more than the adapter can supply.
The 1794-PS1 Flex I/O Power Supply is capable of supplying 1A maximum @24VDC and the output surge current of the 1794-PS1 is sufficient to drive 3 adapters (surge of 23A for 2ms each) operating @ 24VDC..
The 1794-PS13 Flex I/O Power Supply is capable of supplying 1.3A maximum @24VDC and the output
surge current of the 1794-PS13 is sufficient to drive 4 adapters (surge of 23A for 2ms each) operating @ 24VDC
The 1794-PS3 Flex I/O Power Supply is capable of supplying 3A maximum1 @24VDC and the output surge current of the 1794-PS3 is sufficient to drive 6 adapters (surge of 23A for 2ms each) operating @ 24VDC
Non-AB DC power supplies can also be utilized but should operate within the specifications required for the devices they are powering.
Size the power supply by calculating the total current consumed by summing the currents for each of the modules used below for the power supply operating voltage applied.
Adapters
1794-ASB/D
1794-ASB/E
330mA @ 24VDC
(730mA @ 12VDC)
1794-ACN(R)15
ControlNet Adapter
1794-AENT/A
Ethernet/IP Adapter
1794-AENT/B
Ethernet/IP Adapter
The following Flex Input Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed:
1794-IB8
1794-IB16
1794-IV16
1794-IB32
1794-IB16D
The following Flex Output Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed PLUS the total current consumed by their loads. Note that the load current is limited by the maximum load current and surge listed.
Module:
Module:
Module:
Module:
Module;
Module:
80mA @ 24VDC
1794-OW8 Load:
Module:
rated power and has NO impact on power supply sizing. (See module output specification)
Module:
Module:
The following Flex modules have a combination of inputs and outputs. The current load should be determined as described previously for the combined input and output specifications listed.
1794-IB10XOB6
Inputs:
Module:
1794-IB16XOB16P
Inputs:
Module:
The following Flex Analog Input Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed. In addition, adequate power must be supplied to the 1794-IE8 and 1794-IF4I This power
transmitters to deliver input terminal voltage or drive 20mA into the input impedance listed.
source may be the same as the module power and can be included in the power supply calculation.
1794-IE8/B Input:
Module:
60mA @ 24VDC
1794-IE12 Input:
Module:
30mA @ 24VDC
1794-IF4I Input:
Module:
80mA @ 24VDC
1794-IR8
Module:
140mA @24VDC
1794-IRT8/A Module:
85mA @24VDC
1794-IRT8/B Module:
95mA @24VDC
1794-IT8
Module:
150mA @24VDC
1794-IE8H
Module:
295mA @24VDC
The following Flex Analog Output Modules require supplied +24VDC (19.2-3.12 VDC) and consume the currents listed PLUS the total current consumed by their loads. Note that the load current is limited by maximum current or resistive load permitted per channel.
1794-OE4 Module: Output: 70mA @ 24VDC 3mA per channel maximum current load on voltage output
15 - 750 ohm per channel resistive load for mA output 1794-OE12 Module: 320mA @ 24VDC
Output:
1794-OF4I Module: Output: 210mA @ 24VDC 3mA per channel maximum current load for voltage output
The following Analog Flex modules have a combination of analog inputs and outputs. The current load should be determined as described previously for the combined module and output specifications listed. Note that the output load current is limited by maximum current or resistive load permitted per channel. In addition, adequate power must be supplied to the 1794-IE8 and 1794-IF4I transmitters to deliver input terminal voltage or drive 20mA into the input impedance listed. This power source may be the same as the module power and can be included in the power supply calculation.
1794-IE4XOE2 Module: Inputs: 70mA @ 24VDC 100 Kohm input impedance on voltage input
238 ohms input impedance on current input Outputs: 3mA per channel maximum current load on voltage output
1794-IE8XOE4 Module: Inputs: 140mA @ 24VDC > 1 Mohm input impedance on voltage input
< 100 ohms input impedance on current input Outputs: 3 mA per channel maximum current load on voltage output
1794-IF2XOF2I Module: Inputs: 150mA @ 24VDC > 1 Mohm input impedance on voltage input
< 100ohms input impedance on current input Outputs: 3mA per channel maximum current load for voltage output
Counter Modules
The following counter modules require module power, transmitter input power and in some cases output load power. In those cases it is recommended that a separate power supply be used for output load power for noise immunity.
1794-ID2
Module:
Inputs:
1794-IP4
Module:
Inputs:
1794-IJ2
Module;
Inputs:
9mA @ 2VDC (2-9mA) per input Load: 1.0A max per output
Outputs:
1794-VHSC Inputs:
Module:
100mA @ 24VDC
@ 15VDC) per input Outputs: Load: 0.5A max per output @ 5VDC; 1.0A max per
1 Horizontal mounting; 2.8A maximum all other mountings; see derating current in Installation Manual.