T cp RR
EL
A
=
( has an average value of
kg
kcal
550 and
cp =
C kg
kcal
1 .
15
The concentration of salt X in steam EL has been
considered zero.
By combining Eq. 4, Eq. 6, Eq. 8, it
is possible to express the BD as a
function of EL and Nc as follows:
Eq. 9: BD as a function of EL and Nc
1
=
Nc
EL
BD
This equation is fundamental,
because Blowdown can be determined
by knowing Evaporation Losses and
Number of cycles.;
Blowdown is the key parameter for
economical and energy reasons.
Economics of the whole system is
driven by Blowdown because, apart
from evaporation losses, it is actually a
waste stream used to control maximum
allowable concentration of salts so:
the lower the Blowdown, the lower
the waste stream
the lower the Blowdown, the closer
the actual working conditions related
to the maximum acceptable
concentration of substances likely to
precipitate.
From an energy & economical point
of view, a lower blowdown means lower
makeup, so less expenses for water
supply and chemical treatment.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
31
4.2. A practical Example (1)
In this paragraph a practical
calculation will be shown to familiarise
with key parameters and their meaning.
An open evaporative cooling
system has the operating
characteristics as summarised in Table
4-2.
Table 4-2: initial set of parameters (1).
Parameter Units
Tot. Volume 3,000 m
3
/hr
Recirculation
Rate
9,000 m
3
/hr
Temperature
Difference
in 29C out
22C
C
Number of
Concentration
2.5
These parameters can now be used
to determine the Evaporation Losses
(EL):
115
550
7 1 9000
=
=
A
=
T cp RR
EL [m
3
/h]
and the Blow down rate:
4 . 76
5 . 1
115
1 5 . 2
115
1
= =
=
Nc
EL
BD [m
3
/h].
The Make Up is the sum of all the
streams leaving the system:
4 . 191 4 . 76 115 = + = + = BD EL MU
[m
3
/h].
At this point, the complete set of
parameters is available in
Table 4-3.
Table 4-3: complete set of parameters
(1).
Parameter Units
Tot. Volume 3,000 m
3
/hr
Recirculation
Rate
9,000 m
3
/hr
Temperature
Difference
in 29 out 22 = 7 C
Evaporation
Losses
115 m
3
/hr
Blow Down 76.4 m
3
/hr
Make Up 191.4 m
3
/hr
4.3. A practical Example (2)
As blowdown was stated to be the
key operating parameter, in this
paragraph another NC will be
considered.
The difference in the set of
parameters will be clearly visible in
terms of energy and economics.
The same open evaporative cooling
system has now the operating
characteristics as summarised in Table
4-4.
Table 4-4: initial set of parameters (2).
Parameter Units
Tot. Volume 3,000 m
3
/hr
Recirculation
Rate
9,000 m
3
/hr
Temperature
Difference
in 29C out
22C
C
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
32
Number of
Concentration
1.5
These parameters can now be used
to determine the Evaporation Losses
(EL):
115
550
7 1 9000
=
=
A
=
T cp RR
EL [m
3
/h]
same as Case 1, and the Blow down
rate:
230
5 . 0
115
1 5 . 1
115
1
= =
=
Nc
EL
BD [m
3
/h]
considerably higher than that for Case
1.
Again, The Make Up is the sum of
all the streams leaving the system:
345 230 115 = + = + = BD EL MU [m
3
/h].
At this point, the complete set of
parameters is available in Table 4-5.
Table 4-5: complete set of parameters
(2).
Parameter Units
Tot. Volume 3,000 m
3
/hr
Recirculation
Rate
9,000 m
3
/hr
Temperature
Difference
in 29 out 22 = 7 C
Evaporation
Losses
115 m
3
/hr
Blow Down 230 m
3
/hr
Make Up 345 m
3
/hr
The different results form the two
cases are summarised in
Table 4-6.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
33
Table 4-6: results comparison between
Case 1 and Case 2.
Parameter Case 1 Case 2 Units
Blow Down 76.4 230 m
3
/hr
Make Up 191.4 345 m
3
/hr
Number of
Concentration
2.5 1.5
By comparing the results from Case
1 and Case 2, the BD passed from 115
to 230 [m
3
/h] and MU from 191.4 to
345 [m
3
/h].
As seen and demonstrated
previously, the blowdown rate is
directly related to the NC.
Because the design of a Cooling
Water treatment is based on the BD, it
can be understood that a limited BD
means lower consumption of chemicals,
as well as a saving in water discharge
and consequent make up.
5. Common issues in Cooling
System
The design and operational
conditions of a cooling system have a
relevant impact on water chemistry.
This means that scaling/fouling,
corrosion and microbiological behaviour
of a cooling water, can greatly influence
both design and operating settings.
All the preliminary characteristics
of water given in the Water
Fundamentals chapter will now be
associate to chemical and biological
behaviour.
5.1. Scaling in Cooling Water
Water formed deposits result from
naturally occurring minerals
precipitating from water to form scale.
The most common scales are
calcium carbonate, calcium sulphate
and silica or silicates.
Many factors affect the formation
of scale, such as the mineral
concentration in the cooling water:
water temperature, pH, availability of
nucleation sites (the point of initial
crystal formation) and the time allowed
for scale formation to begin after
nucleation occurs.
Calcium carbonate and magnesium
hydroxide, for example, are inversely
temperature soluble so, the higher the
temperature, the lower their solubility.
Scale build-up on surfaces can be
extremely hard and difficult to remove
(Fig: 5-1 shows a series of tubes
affected by scale).
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
34
Fig: 5-1: tube walls affected by scale.
Scaling will drastically reduce heat
transfer capacity and system energy
efficiency.
A useful index for the evaluation of
the scale forming or corrosive
behaviour of a given water is the
Langelier Saturation Index LSI.
The LSI expresses the degree of
saturation of water as related to
calcium carbonate solubility.
LSI is then a calculated number
used to predict the calcium carbonate
(CaCO
3
) stability of a water;
In other words it means that a water
will precipitate, dissolve, or be in
equilibrium with calcium carbonate.
The Langelier saturation level
approaches the concept of saturation
using pH as a main variable, and the
LSI can be interpreted as the pH
change required to bring water to
equilibrium.
Three conclusions may be given
depending on the value of the LSI as
follows:
1. If LSI is negative: No potential to
scale, the water will dissolve
CaCO
3
.
2. If LSI is positive: Scale can form
and CaCO
3
precipitation may
occur.
3. If LSI is close to zero: Borderline
scale potential. Water quality or
changes in temperature, or
evaporation could change the
index.
In order to calculate the LSI, it is
necessary to know:
the alkalinity (mg/l as CaCO
3
)
the calcium hardness (mg/l Ca
2+
as CaCO
3
)
the total dissolved solids (mg/l
TDS)
the actual pH
and the temperature of the water
(C).
A useful and practical expression for
the LSI, calculated at the maximum
skin temperature (60C) is the
following:
Eq. 10: LSI practical formula.
LSI
(60C)
= pH 11.32 + log
10
(CaH
*
Alk)
where CaH stands for Calcium
Hardness.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
35
As an example, if the analyses of a
water were the following,:
pH = 8.7
CaH = 405 ppm (CaCO
3
)
Alkalinity = 4405 ppm (CaCO
3
)
substitute them into the LSI @ 60C
equation, the result would be:
LSI
(60C)
= 8.7 11.3 + 5.2 = 2.6
The LSI is positive: Scale can form
and CaCO
3
precipitation may occur.
At LSI > 2.5, the water is
definitively scale-forming and no
antiscale/antifouling chemicals will be
able to work properly.
If this happened there would be two
alternatives (scenarios) to apply:
1. Reduction of NC
or,
2. Addition of Acid (controlled pH)
to lower pH and reduce alkalinity
according to the following
chemical equation:
Eq. 11: Acid Addition for controlled pH.
H
2
SO
4
+Ca(HCO
3
)
2
=CaSO
4
+2H
2
O +
2CO
2
The calcium bicarbonate is
converted to volatile carbon dioxide and
calcium
sulphate (Calcium sulphate is more
soluble than calcium carbonate).
If the makeup water is high in
sulphates, hydrochloric acid may be
used to reduce the alkalinity but,
chloride ions may cause problems
because they can penetrate oxide films,
setting up local anodic cells and causing
corrosion (for details refer to paragraph
5.2).
Monitoring of scale can be
performed by:
scale coupons
Fig: 5-2: scale coupons of different
shapes and sizes.
Fouling Factor Calculation
Pilot Heat Exchangers
Fig: 5-3: pilot heat exchanger.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
36
5.2. Corrosion in Cooling Water
Cooling Systems are exposed to
many types of corrosion, from general
electrochemical corrosion, to pitting
caused by deposits, electrolysis, or
microorganisms.
Electrochemical corrosion takes
place when a metal is placed in an
aqueous environment (H
2
0).
Several chemical (and physical)
reactions will occur.
At the Anode (the negative side of
the electrochemical cell, an oxidation
occurs), the metal dissolves (Fe = Fe
2+
+ 2e
-
) and, at the Cathode, a reduction
reaction takes place (O
2
+ H
2
O + 4e
-
=
4OH
-
).
The overall corrosion process in
cooling water systems is then:
2Fe(OH)
2
+ 1/2O
2
Fe
2
O
3
H
2
O + H
2
O,
with formation of rust (Fe
2
O
3
H
2
O)
whose mechanical and thermal
properties are definitively not
comparable with those of steel.
Fig: 5-4 shows corrosion processes
in details and Fig: 5-5 shows a
corrosion-coupon severely affected by
corrosion.
Fig: 5-4: electrochemical corrosion
process.
Fig: 5-5: a corrosion coupon severely
affected by electrochemical corrosion.
Factors contributing to corrosion
are:
Conductivity (also referred to
chlorides content).
Fig: 5-6: corrosion rate vs.
conductivity.
pH: extreme values of pH
should be avoided.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
37
Fig: 5-7: corrosion rate vs. pH.
Oxygen: as it is an oxidising
agent it will contribute to Redox
reactions.
Fig: 5-8: corrosion as a function of
oxygen content and temperature.
Free Chlorine residual.
Corrosion can reduce the life-span
of equipment by years, requiring
expensive replacement.
Corrosion can lead to costly
equipment repairs and production
downtime.
Its related deposits lead to reduced
capacity and wasted energy because of
heat transfer efficiency losses.
Corrosion monitoring is performed
by the insertion of selected corrosion
coupons.
These coupons are weighted before
insertion and left in the circuit, by
means of a proper coupon-rack, for a
given period.
Fig: 5-9: corrosion (and scale) coupon
rack.
Once removed, they are cleaned by
acid pickling and weighted again.
The comparison between initial, final
weight, exposure time and Area Factor
of the coupon, give the corrosion rate
expressed by Milli-Inch per Year MPY,
or millimetres per Year mmY.
Sometimes, on-line corrosion-
meters are applied to circuits and give
instant corrosion rate.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
38
5.3. Fouling in Cooling Water
Fouling occurs when solid materials
form or contribute to the formation of
deposit on equipment surfaces.
They are introduced to the system
as suspended solids and may enter by
the makeup water, from corrosion by
products, or as airborne materials.
Examples include mud, sand, silt,
clay oils, debris, organics, microbes,
etc.
These materials adhere to heat
transfer surfaces and reduce heat
transfer and water flow.
5.4. Microbiological Growth,
Contamination and Induced
Corrosion
Microbial problems associated with
industrial cooling water systems are
caused by algae, fungi, and bacteria.
Bacteria are single-celled
organisms that have a simple structure.
All life processes are carried out
within a single cell, which is generally
only 1-5 mm in length (Fig: 5-10 shows
rod-shaped bacteria).
Fig: 5-10: rod shaped bacteria.
The Fungi are filamentous
organisms, much larger than bacteria.
They can produce a network of
interlacing filaments (filamentous fungi)
or exist at a unicellular state (see Fig:
5-11).
Fig: 5-11: Unicellular (left) and
Filamentous Fungi (right).
Algae are photosynthetic organisms
like green plants; they require sunlight
to provide the energy for growth, using
specialized pigments called chlorophylls
to trap the light energy.
Many different species may exist in
cooling water systems:
Aerobic bacteria need oxygen to
grow and reproduce, using it as an
electron acceptor for the oxidation of
organic and inorganic compounds.
This biological process is known as
respiration.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
39
Some species of microorganisms
can grow in the absence of oxygen,
using fermentation of organic
compounds as a source of energy.
These organisms are described as
Facultatively Anaerobic.
The small number of
microorganisms that are able to break
down organic compounds or carbon
dioxide only in the absence of oxygen
are described as Anaerobic.
Oxygen is actually toxic to many of
these organisms. Anaerobic metabolism
is commonly found in many bacterial
and fungal species.
Respiration generates more energy
for the organism than anaerobic
fermentation and results in greater
microbial growth.
Some of the problems this living
matter causes, include severe bacterial
slimes and fouling, hydrogen sulphide
(H
2
S), underdeposit corrosion and
health hazards.
Underdeposit corrosion is one of
the most serious concern for cooling
systems;
corrosion takes place below the
microbiological layer that the organisms
develop to protect and feed
themselves.
As the corrosion phenomena is
hidden by biological fouling, it would
not be noticed easily.
Strictly anaerobic bacteria, growing
well only in the absence of oxygen;
such as species of sulphate reducing
bacteria (S.R.B.) are responsible for
severe Microbiological Induced
Corrosion processes:
MIC refers to corrosion that is
influenced by the presence and
activities of micro-organisms and/or
their metabolites (the products
produced in their metabolism).
Bacteria, fungi and other micro-
organisms can play a major part in
corrosion; the mechanisms potentially
involved in MIC are summarized as:
Cathodic depolarization, whereby
the cathodic rate limiting step is
accelerated by micro-biological
action.
Formation of occluded surface cells,
whereby micro organisms form
"patchy" surface. Sticky polymers
attract and aggregate biological and
non-biological species to produce
crevices and concentration cells, the
basis for accelerated attack.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
40
Fixing of anodic reaction sites,
whereby microbiological surface
colonies lead to the formation of
corrosion pits, driven by microbial
activity and associated with the
location of these colonies (see Fig:
5-12, Fig: 5-13 and Fig: 5-14 for
corrosion coupons).
Fig: 5-12: microbiological induced
corrosion MIC.
Fig: 5-13: corrosion coupon affected by
MIC prior to pickling.
Fig: 5-14: corrosion coupon affected by
MIC after pickling: under deposit
corrosion occurred.
Underdeposit acid attack, whereby
corrosive attack is accelerated by
acidic final products of the MIC
"community metabolism", principally
short-chain fatty acids.
Monitoring of microbiological
activity can be performed in several
ways, according to the species being
investigated:
Vials: for Aerobic and
Anaerobic/SRB
16
bacteria
Fig: 5-15: VIALS for Aerobic Bacteria.
Original colour is Red, in presence of
aerobic bacteria vials turn into yellow.
Fig: 5-16: VIALS for Anaerobic
Bacteria. Original colour is Yellow, in
presence of anaerobic bacteria vials
become turbid and black if S.R.B. exist.
16
Sulphate Reducing Bacteria.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
41
Easicult TTC Slides for Aerobic
bacteria.
Fig: 5-17: Easicult TTC Slide and its
comparison chart.
The two methods, either by Vials or
TTC Slides, express the result in terms
of Colony Forming Unit/ml C.F.U./ml.
For example, Fig: 5-15 shows the
colour changed at the third vial; this
means that the C.F.U./ml is 10
3
.
The fastest method for
microbiological analyses is by means of
luminoscan; in this portable
instrument, selected reagents are used
to evaluate the microbiological activity
in few seconds.
The Luminometer is shown in Fig:
5-18
Fig: 5-18: Luminometer for quick
analyses.
Microbiological control performance
can be evaluated by comparing the
results with Table 5-1:
Table 5-1: comparison table for
microbiological control.
C.F.U/ml Comments
0 10 No pollution
10 - 10
2
Under Control
10
2
- 10
4
Attention Threshold
> 10
4
Immediate Action
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
42
6. Common chemical
treatments programmes in
cooling systems
In this chapter a brief description of
the chemicals and technologies used for
the control of water in cooling system is
given.
The fundamental issues to deal
with, as described in the previous
paragraphs, will be highlighted.
6.1. Scaling and Fouling Control
Programmes
Scale & Fouling
Inhibitors/Dispersant (also called
Deposit Control Agent - DCA) are
complex chemical compounds, dosed at
sub-stoichiometric amounts, that have
very marked effects on the growth rate
of crystals deposited in a scaling
environment.
These threshold inhibitors act by
adsorbing onto the growing crystals and
distorting the lattice, which disrupts the
crystal growth process.
This crystal distortion prevents
deposition, and the highly irregular
stressed crystals tend to slough off as
crystal growth occurs (see Fig: 6-1 and
Fig: 6-2).
Fig: 6-1: undistorted lattice (left) and
microscope picture (right) of
precipitating crystals.
Fig: 6-2: distorted lattice by addition of
DCA (left) and microscope picture
(right) of non precipitating crystals.
The most commonly used threshold
scale inhibitors are inorganic
polyphosphates, organophosphorous
compounds, synthetic organic
dispersants and natural organic
dispersants.
In Fig: 6-3, the working
mechanism of dispersing agents is
shown: first, adsorption of the
dispersing agent molecule occurs.
Fig: 6-3: adsorption (left) and
stabilisation/dispersion (right) process
of DCA.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
43
This is followed by both crystal
structure modification and by a charge
repulsion mechanism of negative
charges, which leads to
destabilization/dispersion of the
crystals.
6.2. Corrosion Control
Programmes
Corrosion inhibitors are added to
water systems to reduce the corrosion
rate of metals to a negligible level.
Corrosion Inhibitors are chemicals
that react with a metallic surface, or
the environment this surface is exposed
to, by giving the surface a certain level
of protection.
Inhibitors often work by adsorbing
themselves on the metallic surface,
protecting it by forming a film; they are
normally distributed from a solution or
dispersion.
The two most common ways for
inhibiting corrosion are related to the
reactions taking place at the Anode
(oxidation) and at the Cathode
(reduction).
However, the other common way
to protect metal surface from corrosion,
consists of the development of films
on metals surface.
Anodic inhibitors aim at developing a
stable, tightly adherent layer of -
iron oxide film on the surface by
causing a large anodic shift of the
corrosion potential, forcing the
metallic surface into the passivation
range (see Fig: 6-4).
Fig: 6-4: anodic film on tube wall.
Organic or inorganic compounds
molecules, such as ortho-phosphates
(@ high levels), phosphonates, nitrites
and molybdates are anodic inhibitors.
Cathodic inhibitors work by either
slowing the cathodic reaction itself,
or selectively precipitating on
cathodic areas to increase the
surface impedance and limit the
diffusion of reducible species
(hydrogen gas evolution is
prevented), to these areas.
Fig: 6-5: cathodic film on tube wall
The precipitate is less tenacious
and more porous than that of the anode
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
44
film; organic or inorganic compounds
molecules, such as ortho-phosphates
(@ low levels), polyphosphates and
metals like zinc, are cathodic inhibitors.
6.3. Microbiological Growth
Control Programmes
The issues associated with
biofouling have involved the use of
chemicals known as Biocides and
certain surfactant chemicals known as
Biodispersants.
Biocides are chemicals that kill living
organisms or inhibit their ability to
grow and reproduce.
A chemical can be a growing
inhibitor to certain organisms at a low
concentration and act as a killing
biocide to the same organisms at a
higher concentration, over a definite
time period (e.g., 6-12 hours).
This way of using biocides is known
as Shock Dosage, while growing
inhibitors are generally added
continuously to the system at lower
levels.
Biocides are classified as:
non-oxidizing biocides because they
do not oxidize other chemicals or
oxidize them only very slightly.
Biocides are classified as:
oxidizing biocides (e.g., chlorine)
since they very strongly oxidize
many organic and inorganic
molecules, becoming reduced
themselves.
Another class of chemicals that can
be used to remove microbial slimes are
surfactants commonly known as
Biodispersants.
They allow other chemicals to
contact surfaces and deposits to some
extent.
Biodispersants increase the
effectiveness of biocides by allowing the
biocides to penetrate the microbial
slime, killing the microbial cells and
eventually causing sloughing of the
slime.
Quaternary ammonium salts and
amine salts (being cationic), attach to
the negatively charged molecules in the
slime layer and reduce the surface
tension, thus allowing water to contact
the slime layers to a greater extent.
The addition of an oxidizing biocide
helps break them up further by
oxidizing the exposed charged atoms
on the slime layers.
The oxidizing inorganic biocides,
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
45
such as Chlorine, may be fed on a
continuous basis to maintain a free or
total residual level (Fig: 6-6).
Fig: 6-6: chlorination break point.
Free residual chlorine, present as
hypochlorous acid, is a much more
effective and faster-acting biocide than
combined chlorine, present as
chloramines, (e.g., NH
2
CI).
Because microorganisms find it
difficult to adapt to chlorine, it is
possible to feed chlorine on a
continuous basis.
Bromine (as hypobromic acid,
HBrO) shows higher oxidising
properties, respect to chlorine, at a
given pH.
Sodium Hypochlorite and
Hypobromine reactions are the
following:
NaClO OCl
-
+ Na
+
and
NaBrO OBr
-
+ Na
+
.
Fig: 6-7 shows chlorine and
bromine dissociation curve vs. pH.
Fig: 6-7: chlorine and bromine
dissociation curve vs. pH.
Because the amount of bromine
un-dissociated molecule (the effective
biocide), at a given pH is higher than
that of hypochloric acid (see Fig: 6-7),
bromine should then be preferred as
oxidising biocide.
The main drawback with the
oxidizing biocides is their high reactivity
to reduce compounds such as iron, H
2
S
and organic matter so, there may be
little residual left to control
microorganisms in case of process
(hydrocarbons) leaks.
They do not effectively penetrate
and disperse microbial slimes.
These facts imply that chlorine is
supplemented by the addition of non-
oxidizing biocides and dispersants in
many systems.
Examples of useful oxidizing
biocides are:
halogens such as chlorine (Cl
2
)
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
46
chlorine dioxide (ClO
2
)
hydrogen peroxide (H
2
O
2
)
ozone (O
3
)
Peracetic Acid
and chlorine, bromine donors such
as chlorinated isocyanurates and
hydantoins.
Non-oxidizing biocides are organic
molecules that react with various parts
of the microbial cell, generally at a
specific site.
The most common groups of
nonoxidizing biocides are:
aldehydes
organo-sulphur biocides
organo-nitrogen biocides
and
amine salts.
7.1. Cooling System: CHIMEC
Analyses
The aim of performing routine
water analyses, is to check whether the
proposed dosages of product is correct.
By doing so, not only it will be
possible to take corrective actions, but
also to monitor the performance of the
treatment.
The analyses include:
characterisation of make up and
recirculating water
specific analyses for CHIMEC
products
microbiological counts
Common set of analyses and their
use are shown in Table 6-1.
Table 6-1: CHIMEC Routine Analyses.
Parameters
Water
Characterisation
pH, Alkalinity and
Hardness for the
calculation of Langelier
Saturation Index LSI.
Chlorides, Sulphates
and Iron.
Concentration Number
Nc based on Chlorides
and Calcium.
Microbiology
VIALS or TTC count for
microbiological activity
monitoring
System
Parameters
Calculated Evaporation,
NC, BD, MU and
Temperatures.
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
47
CHIMEC S.p.A. Water Technology Unit - Cooling Systems Operators Handbook -
48
7. Troubleshooting of Cooling
Systems
The information here in presented,
are intended only as a support for
cooling systems operators.
As an integrated CHIMECs policy,
this document will introduce the
operators to a list of:
Problems found
Possible Causes
Suggested Solutions to
problems
that may be common in cooling
systems operating conditions.
The Table below (Table 6-1),
provides common Troubleshooting Tips
for the following steps:
Cooling Water
Once again, the information here in
reported, should always be supported
by the experience of the operators.
Table 7-1: Cooling Water Troubleshooting
Problem Found Possible Causes Suggested Problems Solution
Too High pH Water
17
Number of Concentration
Approaching Chemical & Physical
Limits
Acid Addition Inadequate
Increase Blowdown Rate
Check/Increase Acid Injection
Rate
Lower pH Water
No Concentration Occurs
Acid Injection Exceeds Limits
Reduce Blowdown Rate
Check/Reduce Acid Injection
Rate
Coupons affected by
Scale
High pH
Number of Concentration
Approaching Chemical & Physical
Limits
Low Antiscale Dosage
Increase Blowdown Rate
Check/Increase Antiscale
Injection Rate
Coupons affected by
corrosion
Low pH
Low Corrosion Inhibitor Dosage
Microbiological Induced
Corrosion M.I.C.
Check/Lower Acid Injection
Check/Increase Corrosion
Inhibitor Injection Rate
Refer to Microbiological Growth
Microbiological
Growth
Presence of Nutrients, Process
(Hydrocarbons) Leaks
Long Retention Time
Low Biocide(s) Dosage
Check/verify/reduce availability
of Nutrients and/or Process
Leaks
Check/Verify Systems Streams
Check/Increase Biocide(s)
Injection Rate and/or Shock
Frequency/Dosage.
17
Values are referred to design conditions.