Anda di halaman 1dari 2

CLIENT: PROJECT TITLE: PROJECT LOCATION: UNIT NUMBER: PROJECT NUMBER: CLIENT PROJECT NUMBER: Abbreviations & Symbols

GENERAL
(See PIP PIC001 Appendix A-1 for additional abbreviations) AMB - Ambient ATM - Atmospheric BAS - Basis F - Degrees Fahrenheit C - Degrees Celsius GALV - Galvanized IN - Inch N/R - Not Required OPER - Operating PRES - Pressure PSIG - Pounds Per Sq. Inch (Gage) PWHT - Post Weld Heat Treatment REL - Relief REV - Revision SERV - Service STR - Stress TEMP - Temperature THK - Thickness Y/N - Yes/No

PIPING LINE LIST


LEGEND AND GENERAL NOTES
Insulation Types:
(See PIP INEG2000 for detailed description) AC CC CP FP HC PF PP PS TR Acoustic Control Cold Service Condensation Control Fire Protection Heat Conservation Freeze Protection Personnel Protection Process Stability Traced (See Tracing Type) A - 100% Radiographic Examination. High Pressure or Severe Cyclic service. High Pressure: "Service where owner specifies chapter IX for design and construction." B - 20% Radiographic Examination. Category M Fluid Service. "Can produce irreversable harm to humans when exposed to small quantities." Client Defined. C - 5% Radiographic Examination. Outside of the rules of categories D, M, Severe Cyclic. Includes Caustic D - 0% Radiographic Examination. Category D Fluid Service. When cycles in the system exceed 7000 in the life of the <150 psi, between -20 and 366 degrees Fahrenheit.

By: Checked: Approved: Issue Date: Page: Revision: GENERAL NOTES

Fluid State/Condition:
L M S SF SL V Liquid Multiphase Solid Slug Flow Slurry Vapor

X-Ray Symbols (NDE Level):

1)

Pressure - Temperature limitations for flanges shall conform to the following: a) ASME B16.1 for 125 and 250 lb. cast iron flanges. b) ASME B16.5 for all steel flange sizes & ratings up to 24 inches. c) ASME B16.47 for steel flange sizes & ratings above 24 inches Unless noted otherwise, the following shall conform to ASME B31.3 or other industry standards as applicable: a) Determination of piping design pressure and temperature. b) Calculation of pipe wall thickness. c) Determination of piping test pressure. d) Pipe fabrication, heat treatment (when required), inspection, and leak testing. Wall thicknesses for pipe in vacuum services and lines which are jacketed shall be calculated for external pressure per Note 2. All buried pipe shall be protected against corrosion in accordance with the requirements of the applicable job specification. For all transitions between above ground and below ground piping, protective coating requirements shall be maintained for 12" minimum above grade.

2)

Stress Relief Basis (per ASME B31.3):


A B C N - Process Requirement - Per ASME B31.1/ASME B31.3. - Client Requirements - None Required

3)

Heat Tracing Types: Fluid Category (per ASME B31.3):


D M H N HC Category D fluid service Category M fluid service High Pressure fluid service Normal service High Cyclical (See PIP INEG1000 for detailed description) CJ - Chilled Fluid Jacketed CT - Chilled Fluid ET - Electric HJ - Hot Fluid Jacketed HT - Hot Fluid SJ - Steam Jacketed ST - Steam

Paint Systems:
(See PIP CTCE1000 for detailed environment selection criteria for pipe.) 4)

Design Conditions Basis Code:


Number designation indicates operating condition inside the following short term limits. 1 - Short term upset, maximum of 10 hours per upset & 100 hours per year. Maximum allowable pressure overstress is 33% of design. 2 - Short term upset, maximum of 50 hours per upset & 500 hours per year. Maximum allowable pressure overstress is 20% of design. 3 - Short term self limiting (i.e. PSV accumulation), maximum of 50 hours per upset and 500 hours per year. Maximum allowable pressure overstress is 20% of design. This case permits process to match piping design to equipment design and let the short term upset handle the accumulation.

5)

Test Method:
(See PIP PNSC0021 for detailed description) P - Pneumatic S - In Service test at normal operating pressure H - Hydrotest O - Other (see remarks)

Stress Analysis Level Codes:


(See PIP PNC00004 for detailed description) I - Visual Analysis II - Formal Analysis III - Comprehensive Analysis

Line Service Codes


AV BA BD BFW BRR BRS CC CF CHS CV CWR CWS DMW DR DS DW ER FF FG FO FW ATMOSPHERIC VENT BREATHING AIR BLOWDOWN BOILER FEED WATER BRINE RETURN BRINE SUPPLY CONTAMINABLE CONDENSATE COLD FLARE CHEMICAL SEWER COLD VENT COOLING WATER RETURN COOLING WATER SUPPLY DEMINERALIZED WATER DRAIN DILUTION STEAM DRINKING WATER ETHYLENE REFRIGERANT FLUSHING FLUID FUEL GAS FUEL OIL FIRE WATER GLR GLS H HS IA IS LNG LO LPG LS ME MR MS N NA NAS NG NH OWS OX P PA (See PIP PIC001 Appendix A-3) GLYCOL RETURN GLYCOL SUPPLY HYDROGEN HIGH PRESSURE STEAM INSTRUMENT AIR INTERMEDIATE PRESSURE STEAM LIQUIFIED NATURAL GAS LUBE OIL LIQUIFIED PETROLEUM GAS LOW PRESSURE STEAM METHANOL MIXED REFRIGERANT MEDIUM PRESSURE STEAM NITROGEN CAUSTIC CAUSTIC SEWER NATURAL GAS AMMONIA OILY WATER SEWER OXYGEN GENERAL PROCESS PLANT AIR PC PR PW QO RS RV RW SC SG SO SS STS SW SWR SWS TWR TWS VC VE WF WO WW PROCESS CONDENSATE PROPYLENE REFRIGERANT PROCESS WATER QUENCH OIL RECOVERED SLOPS RELIEF VENT RAW WATER STEAM CONDENSATE SYNTHESIS GAS SEAL OIL SANITARY SEWER STORM SEWER SERVICE WATER SEA WATER RETURN SEA WATER SUPPLY TEMPERED WATER RETURN TEMPERED WATER SUPPLY VACUUM CONDENSATE VACUUM EXHAUST WARM FLARE WASH OIL WASTE WATER

Letter designation indicates operating condition outside of short term limits. A - Relief accumulation pressure (A, A1, A2 or A3 case, see above for definition) B - Maximum pump suction plus normal D P (B, B1, B2 or B3 case, see above for definition) C - Normal pump suction plus maximum D P (C, C1, C2 or C3 case, see above for definition) D - Maximum pump suction, plus maximum D P (Tower OH pumps only) (D, D1, D2 or D3 case, see above for definition) E - Steam out conditions (E, E1, E2 or E3 case, see above for definition) F - Compressor maximum discharge pressure (F, F1, F2 or F3 case, see above for definition) G - Operating and safety margin (G, G1, G2 or G3 case, see above for definition) H - Other (See Remarks) (H, H1, H2 or H3 case, see above for definition) R - Auto refrigeration (R, R1, R2 or R3 case, see above for definition)

CLIENT: PROJECT TITLE: PROJECT LOCATION: UNIT NUMBER: PROJECT NUMBER: CLIENT PROJECT NUMBER:
SERVICE CODE UNIT/ AREA NO. LINE NO. LINE SIZE LINE CLASS (SPEC) INSULATION P&ID NUMBER FLUID CATEGORY FLUID STATE FROM TO

PIPING LINE LIST


U.S. CUSTOMARY UNITS
SPECIFIC GRAVITY OPERATING CONDITIONS FLEX TEMP DESIGN CONDITIONS SYSTEM NUMBER TEST MIN. REQ'D WALL THK. (in) STRESS RELIEF (PWHT) (Y/N) BASIS NOMINAL WALL THK. CORR. HEAT ALLOW. TRACE NDE LEVEL PAINT

By: Checked: Approved: Issue Date: Page: Revision:


STRESS ANALYSIS LEVEL I II III STRESS CALC NO. PRIORITY PIPING REMARKS REV. NO.

TYPE/ (in) CODE

THK (in)

PRES (psig)

TEMP (F)

MIN (F)

MAX (F)

PRES (psig)

TEMP (F)

BASIS CODE

PRES (psig)

METHOD

(in/sch)

(in)