XLe Model: HE-XE105

12 Digital Inputs DC / 12 Digital DC Outputs / 2 Analog Inputs (High Resolution) / 2 Analog Outputs
1 Specifications
Digital Input DC Inputs per Module Input Voltage Range Absolute Max. Voltage Input Impedance Input Current Lower / Upper Threshold Min / Max Upper Threshold OFF to ON Response ON to OFF Response HSC Max. Switching Rate 12 (including 4 HSC inputs) 12 VDC / 24 VDC 35 VDC Max. 10 k Positive Logic Negative Logic 0.3 mA / 0.8 mA -2.1 mA / -1.6 mA 3 VDC / 8 VDC 1 ms 1 ms 10 kHz Totalizer/Pulse, Edges 5 kHz Frequency/Pulse, Width 2.5 kHz Quadrature

Panel Cut-Out and Dimensions

Refer to the XLe User Manual for panel box information and a handy checklist of requirements. Notes: The tolerance to meet NEMA standards is 0.005 (0.1 mm). Max. panel thickness: 5 mm.

Ports / Connectors / Cables

Digital DC Outputs Outputs per Module Commons per Module Output Type Absolute Max. Voltage Output Protection Max. Output Current per point Max. Total Current Min / Max Output Supply Voltage Max. Voltage Drop at Rated Current Max. Inrush Current Min. Load OFF to ON Response ON to OFF Response Output Characteristics 12 (2 configurable PWM outputs) 1 Sourcing / 10 K Pull-Down 5 A continuous Short Circuit 0.5 A 4 A Continuous 10 VDC / 30 VDC 0.25 VDC 650 mA per Channel nome 1 ms 1 ms Current Sourcing (Pos logic)

To Remove Back Cover unscrew 4 screws located on the back of the unit. I/O Jumpers: (Not Shown): I/O Jumpers (JP) are located internally. To access, remove back cover of unit. Wiring Connectors (J1 / J2): I/O Jumpers (JP1 / JP2), and External Jumpers (RS-485) are described in the Wiring and Jumpers section of this document. Memory Slot: Uses Removable Memory for data logging, screen captures, program loading and recipes. Novus Part No.: HE-MC1 Serial Communications: MJ1: (RS-232 / RS-485) Use for Cscape programming and Application-Defined Communications. MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.

Analog Inputs, High Resolution Number of Channels Input Ranges (Selectable) 2 0 - 10 V / 020 mA / 420 mA / 100 mV RTD: Pt100 T/C: J / K / T / N / E / R / S / B 10 VDC: -0.5 V to +15 V mA: -0.5 V to +6 V RTD and T/C: +/- 24 V Current Mode: Voltage Mode: 100 / 35 mA max. 500 k / 35 mA max. 10 V / 20 mA / 100 mV: 14 Bits RTD and T/C: 16 Bits 10 V / 20 mA / 100 mV: 32000 counts RTD and T/C: 20 counts / C 35 mA 50 nA RTD J Temperature range K/N T E B/R/S Max. Error at 25C (* excluding zero) (** After warm up time of one hour) RTD Excitation Current General Specifications Required Power (Steady State) Required Power (Inrush) Primary Power Range Relative Humidity Clock Accuracy Operating Temperature Terminal Type Weight 130 mA @ 24 VDC 30 A for 1 ms @ 24 VDC 10 ~ 30 VDC 5 to 95% Non-condensing +/- Seven Minutes/Month at 20 C 0 C to +50 C Screw Type, 5 mm Removable 354 g Note: Highest usable frequency for PWM output is 65 kHz NOVUS PRODUTOS ELETRNICOS LTDA. -200~850 C / -328~1562 F -210~750 C / -346~1382 F -240~1370 C / -400~2498 F -240~400C / -400~752 F -200~900 C / -328~1652 F 0~1600 C / 32~2912 F mA / 10 V 0.1 %* RTD 1 C 100 mV 0.05 % T/C 0.2 %** 0.25 mA MJ2 Pinouts in Full and Half Duplex Modes

Power Connector and Can Connector

Safe input voltage range Input Impedance (Clamped @ -0.5 V to 12 VDC) Nominal Resolution % AI full scale Max. Over-Current Open T/C Detect Current

Serial Communications:

MJ1: (RS-232 / RS-485) Use for Cscape programming and Application-Defined Communications. MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.

PIN 8 7 6 5 4 3 2 1

MJ1 Pins MJ2 Pins Signal Direction Signal Direction TXD OUT TXD OUT RXD IN RXD IN 0V GROUND 0V GROUND +5 / 60 mA OUT +5 / 60 mA OUT RTS OUT TXOUT CTS IN TX+ OUT RX- / TXIN / OUT RXIN RX+ / TX+ IN / OUT RX+ IN

PIN 8 7 6 5 4 3 2 1

MJ2 Full Duplex Mode Signal Direction TxD OUT RxD IN 0V GROUND +5 V OUT TxOUT Tx+ OUT RxIN Rx+ IN

MJ2 Half Duplex Mode Signal Direction TxD OUT RxD IN 0V GROUND +5 V OUT TxOUT Tx+ OUT Tx- / RxIN/OUT Tx+ / Rx+ IN/OUT
1/2

Wiring and Jumpers

I/O Jumpers Settings (JP1, JP2, JP3 and JP4) The jumpers JP1, JP2, JP3 and JP4 are located in the connectors PCB internal to the controller.

Wire according to the type of inputs / outputs used, and select the appropriate jumper option. Wiring Specifications For I/O wiring (discrete): 0.8 mm2 (18 AWG) or larger. For shielded Analog I/O wiring: 0.8 mm2 (18 AWG) or larger. For CAN wiring: 0.2 mm2 (24 AWG) or larger. Use copper conductors in field wiring only, 60/75 C Orange Connector (J1) J1 Orange Connector I1 I2 I3 I4 I5 I6 I7 I8 H1 H2 H3 H4 NC NC 0V Black Connector (J2) J2 Black Connector 0V V+ NC Q12 Q11 Q10 Q9 Q8 Q7 Q6 Q5 Q4 Q3 Q2 Q1 Name Ground V+ No connect OUT 12 OUT 11 OUT 10 OUT 9 OUT 8 OUT 7 OUT 6 OUT 5 OUT 4 OUT 3 OUT 2 / PWM2 OUT 1 / PWM 1 Name IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 HSC1 / IN9 HSC2 / IN10 HSC3 / IN11 HSC4 / IN12 No connect No connect Ground

JP1 Digital DC Logic Positive Logic (*) Negative Logic

JP2 JP3 Analog Input Setting T/C 100 mV JP4 Analog Output Setting: Voltage or Current (*) Default Notes: When using JP2 / JP3 (inputs) or JP4 (output), each channel can be independently configured. For example, JP2 can be configured for 10 V and JP3 can be configuredas an RTD. External DIP Switch Settings (or Jumpers Settings) Some XLes have jumpers to set RS-485 port termination, though most use DIP Switches. The External Jumpers or DIP Switches are used for termination of the RS-485 ports. The XLe is shipped un-terminated. To terminate, select one of the jumpers shipped with the product and insert it based upon the option that is desired or, select the switch and configure based upon the option that is desired. DIPSW3: FACTORY USE ONLY (tiny bootloader firmware downloading). NOT TO BE USED FOR NORMAL OCS OPERATIN. DIPSW2: MJ2 Termination (Default none) DIPSW1: MJ1 Termination (Default none)
001XLE037-R1

RTD (Pt100)

V / mA (*)

VOLTAGE (V)

CURRENT (mA) (*)

Orange Connector (J3) J3 Orange Connector T1 + T1 T2 + T2 AQ1 AQ2 0V MA1 V1 0V MA2 V2 0V Name IN1 + : T/C / RTD / 100 mV IN1 - : T/C / RTD / 100 mV IN2 + : T/C / RTD / 100 mV IN2 - : T/C / RTD / 100 mV OUT1: 10 V / 4-20 mA OUT2: 10 V / 4-20 mA GROUND IN1: 0-20 mA / 4-20 mA IN1: 0-10 V GROUND IN2: 0-20 mA / 4-20 mA IN2: 0-10 V GROUND

Safety

When found on the product, the following symbols specify: Warning: Electrical Shock Hazard. Warning: Consult user documentation.

Analog input and output connectios (J3):

This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous locations only WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I, Division 2 WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections. WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible. WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards. WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure indicates a defective condition that will not clear by replacing the fuse. WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.

Technical Support

For assistance and manual updates, contact Technical Support at the following locations: e-mail: suporte@novus.com.br You can find the complete documentation at www.novus.com.br. NOVUS PRODUTOS ELETRNICOS LTDA. 2/2