Anda di halaman 1dari 2

KVTR

Auto-Reclose Relays

Technical Data
Ratings Inputs: Auxiliary voltage (Vx) Frequency Output: Field voltage Burdens AC auxiliary voltage DC auxiliary voltage Opto-isolated inputs Eight - energised from 48V field voltage Contacts Output relays Contact ratings Output relays Eight single make Make: 30A and carry for 0.2s Carry: 5A continuous Break: 50W resistive 25W inductive (L/R = 0.04s at 300V max) KVTR relays are available for single or multi-shot, three-pole auto-reclosing of a circuit breaker on distribution or transmission systems. Standard schemes incorporate maintenance lockout with pre-lockout alarm and user-selectable interlocks for an external synchronism check/dead bus charge/dead line charge relay and a spring charged or equivalent contact on the circuit breaker. User selectable software logic functions allow the schemes to be configured to meet the requirements of most distribution and transmission systems. A feature of KVTR relays is that the operating logic is designed as a ladder diagram, enabling the provision in some cases, of a dedicated application program to suit customers' specific requirements. 6VA 4W 24/125V or 48/250V ac or dc 50/60Hz 48V dc (current limit: 60mA)

Communication port (K-Bus) Transmission Format Baud rate Cable details Cable loading Synchronous (RS485 voltage levels) HDLC 64kbit/s 1000m screened, twisted pair 32 units (multidrop system)

Voltage withstand Insulation IEC 255-5 2kVrms for one minute between all terminals and case earth. 2kV for one minute between terminals of independent circuits including contact circuits. 1.5kV across open contacts of output relays. 1kV for one minute across open contacts of the watchdog relay. 5kV peak, 1.2/50s, 0.5J between all terminals and all terminals to case earth. 2.5kV peak between independent circuits and case.

High voltage impulse IEC 255-5 High frequency disturbance IEC 255-22-1/2 Environmental withstand Temperature IEC 68-2-1 IEC 68-2-2 Humidity IEC 68-2-3 Enclosure protection IEC 529 Vibration IEC 255-21-1

Storage and transit: _25 to +70C Operating: _25 to +55C 56 days at 93% rh and 40C IP50 (dust protected) 0.5g between 60Hz and 600Hz 0.07mm peak to peak between 10Hz and 60Hz. 10,000 operations minimum.

Mechanical durability Cases KVTR relays

Midos Size 4

GEC ALSTHOM T&D PROTECTION & CONTROL LIMITED St Leonards Works, Stafford ST17 4LX, England Tel: 01785 223251 Telex: 36240 Fax: 01785 212232

Our policy is one of continuous product development and the right is reserved to supply equipment which may vary from that described. 1995 GEC ALSTHOM T&D Protection & Control Limited.

Publication R6505B

079510 ICA Printed in England.