ENGINEERING GUIDE

ECA / EUSA

EG 16-4-1.1
Page 1 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

Changes shown by

SCOPE
1.1 1.2 This Engineering Guide covers preferred methods for grounding equipment and structures. Applicable grounding system shown in Figures 1 through 22 should be used and specified on drawings and sketches. Grounding requirements are covered in IP 16-4-1.

INSTALLATION
2.1 Ground rods are to be located and installed as follows: a. The horizontal distance from the point where a ground wire goes underground to a ground rod connection is not greater than 5 ft. In addition, the horizontal distance between ground rods is 10 ft minimum. b. Ground rods are installed before attaching connector and wire. c. Ground rods are driven in undisturbed soil to their full length. d. Installations are backfilled only after Owner's Inspector has approved the installation. 2.2 2.3 Conduit assemblies, clamps,connectors and wire or cable connections to these items shall all be wrench tight. After installation,all ground wire connections shall be completely covered with protective coating, described herein under MATERIALS." Connectors and cable shall be free of dirt and dry before coating is applied.

MATERIALS
3.1 Grounding conductors: stranded copper bare or insulated with a minimum of 600v, PVC, NEC Type THW Insulation. Minimum sizes for underground and aboveground conductors shall be #2/0 Awg for main ground wires and #2 Awg for all branch grounding connections to equipment. Ground rods: 3/4 in. diameter by 10 ft long, copperweld", Hubbard Co. #9450 or equal. Clamps for ground rod: pure wrought copper, compression connectors, equal to Burndy Company's Type YGL" in sizes as shown in Table 1, below, or welded per Figures 14 and 15 on page 17. TABLE 1
ROD SIZE 1/2 - 5/8 1/2 - 5/8 5/8 - 3/4 5/8 - 3/4 5/8 - 3/4 CONDUCTOR SIZE (AWG) 6 Sol.-2 Str. 6 Sol.-2 Str. 6 Sol.-2 Str. 2 Str.-250MCM 250MCM-500MCM BURNDY CAT. NO. YGL29C2 YGL29C29 YGL34C2 YGL34C29 YGL34C34

3.2 3.3

TABLE 2
CONDUCTOR SIZE (AWG) RUN 6 Sol.-2 Str. 1 Str.-250MCM 2 Str.-250MCM 250MCM-500MCM 250MCM-500MCM 250MCM-500MCM TAP 6 Sol.-2 Str. 6 Sol.-2 Str. 2 Str.-250MCM 6 Sol.-2 Str. 2 Str.-250MCM 250MCM-500MCM YGL2C2 YGL29C2 YGL29C29 YGL34C2 YGL34C2 YGL34C34 BURNDY CAT. NO.

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 2 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

TABLE 3
PIPE SIZE 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 3-1/2 4 in. BURNDY NO. GAR 1426-TN GAR 1626-TN GAR 1526-TN GAR 1726-TN GAR 1826-TN GAR 1926-TN GAR 2026-TN GAR 2126-TN GAR 2226-TN

TABLE 4
CABLE SIZE 2 Str. 2/0 Str. 4/0 Str. 250MCM 500MCM BURNDY NO. YGA2C-2N YGA26-2N YGA28-2N YGA29-2N YGA34-2N

3.4

Connectors for grounding cable to pipe: copper alloy body, tin plated, with silicon bronze U-bolt, lockwashers, and nuts; cable range No. 4 Awg solid through No. 2/0 Awg stranded, equal to Burndy Company's Type YGA" connectors in the sizes shown in Table 3 above. Cable connectors: be pure wrought copper, compression connectors equal to Burndy Company's Type YGL" in the - sizes shown in Table 2 on page 1. Connectors for grounding cable to flat bar: copper alloy body, tin plated, with silicon bronze bolt, nut, and lockwasher, for cable range No. 4 Awg solid through No. 2/0 Awg stranded, equal to Burndy Company's No. GB-26 except bolt shall be long enough for connector to grip 1/2 in. thick bar. Lugs for cable: pure wrought copper, compression connectors equal to Burndy Company's Type YGB" in the sizes shown in Table 4 above. Hubs: Myers Company's Type ST" or STA" in the following sizes: TABLE 5
CONDUIT SIZE 1/2 in. 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 3-1/2 in. 4 in. MYERS COMPANY NUMBER ST-1 Or STA-1 ST-2 Or STA-2 ST-3 Or STA-3 ST-4 Or STA-4 ST-5 Or STA-5 ST-6 Or STA-6 ST-7 Or STA-7 ST-8 Or STA-8 ST-9 Or STA-9 ST-10 Or STA-10

3.5 3.6

3.7 3.8

3.9

Protective coating material: W. R. Grace & Company's NO-OX-ID A Special" or equal approved by Owner.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA 3.10

EG 16-4-1.1
Page 3 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

Grounding end bushings: O-Z/Gedney Company's Type BLG" or equal, in the sizes shown in Table 6, below. TABLE 6
CONDUIT SIZE 1/2 in. 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 3-1/2 in. 4 in. 5 in. 6 in. O-Z/GEDNEY'S NUMBER BLG-0504 BLG-0704 BLG-1104 BLG-1204 BLG-1504 BLG-2004 BLG-2604 BLG-3104 BLG-3604 BLG-4104 BLG-5104 BLG-6104

4/95 6/00

Revision Memo Revision 0 - Original Issue of Engineering Guide This Engineering Guide replaces EXES 16-4-1-1C, Rev. 1. Revision 1 This is a reaffirmation of EG 16-4-1.1, Rev. 0, 4/95. Minor editorial changes only.

Exxon Company, U.S.A., Exxon Chemical Americas, 1995, 2000

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 4 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 1 PANELBOARD WITH MAIN CIRCUIT BREAKER IN SEPARATE HOUSING

SERVICE CONDUCTOR #2 Or SMALLER #1 Or #1/0 #2/0 Or #3/0 #4/0 Thru 350MCM

GROUND WIRE & JUMPER #8 #6 #4 #2

CONDUIT FOR GROUND WIRE 1/2 1/2 1/2 in. 3/4 ft

Ground Wire to be PVC insulated.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 5 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 2 TYPICAL GROUND WELL

Notes: (1) Main loops to be #2/0 Awg cable bare or, type THW, medium-hard drawn stranded copper. (2) Ground connector 3/4 in. rod to #2 or #2/0 conductor to be Burndy #GAR6426 or equal. For connection to 2 or 3 equal conductors use Burndy #GK6426 or equal. (3) Branches to be #2 Awg cable, type THW, medium-hard drawn stranded copper. (4) For extended rods use threaded ground rods in 10 ft length with coupling and driving stud. (HUBBARD #9535 & 29535) (5) The concrete indicated under bell of pipe may be omitted - in unpaved areas where no vehicular traffic is anticipated.

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 6 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 3 WALL OR COLUMN MOUNTED GROUND BUS


1/2"-13 Cinch Anchor Red Head #S-12 or Equal

1/2"-13 Silicon Bronze Bolt & Washer Plan - Wall Mounted

9/16" j Hole for 1/2"-13 Bolt

5" for Fire Proofed Columns

5" (TYP.)

Steel Column

Braze to Steel Column

Plan - Column Mounted Drill & Tap for 1/2"-13 Bolt (TYP. 5 Places) Burndy #KC26 Servit Post Connector 1/4" X 2" Copper Bus Bar

#2/0 Awg THW, Cu. Cable (Tap) 1" Galv. Steel Bushing Use PVC Conduit Outdoors Top of Column FTG. or Floor Slab

#2/0 Awg THW, Cu. Cable (Branch) Galv. Steel Conduit Use PVC Conduit Outdoors Extend Cond. Below Paving, Terminate, and Continue Ground Wire by Direct Burial.

Elevation - Wall Mounted Ground Bus (Column Mounted Ground Bus Similiar)

Notes: (1) Equipment ground shall be obtained through conduit system at Baton Rouge and Baytown; through ground wire inside conduit at Benicia, and through a supplemental ground rod at Baton Rouge, unless otherwise specified. (2) When grounding electric motors, where conduit is used for ground return; if switch, motor and pushbutton are connected with rigid conduit and all threads are made up tight, no additional grounding is required at motor or pushbutton. (3) When sealtight flexible conduit is used, a separate external bonding jumper shall be installed around flexible conduit. See Figure 22. (4) Low voltage is below 600 volts.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 7 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 4 GROUNDING ELECTRIC MOTORS WHERE CONDUIT IS NOT USED FOR GROUND RETURN

MOTOR HORSEPOWER 1/2 To 10 15 20 To 50 60 To 100 125 To 200

GROUND RETURN CONDUCTOR SIZE #12* #10* #8* #6* #2*

BURNDY GROUND LUG CAT. NO. YAV10 YAV10 YAV8C-L YAV6C-L YAV2C-L

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 8 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 5 PANELBOARD WITH NO SEPARATELY ENCLOSED MAIN CIRCUIT BREAKER

SERVICE CONDUCTOR #2 Or SMALLER #1 Or #1/0 #2/0 Or #3/0 #4/0 Thru 350MCM

GROUND WIRE & JUMPER #8 #6 #4 #2

CONDUIT FOR GROUND WIRE 1/2 in. 1/2 in. 1/2 in. 3/4 in.

Ground wire to be PVC insulated.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 9 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 6 GROUNDING STRUCTURES

Column or Support Column or Support Foundation

Burndy #KC26 or Equal

#2/0 Cu. Ground Wire 1" Cond.

Column or Support Foundation

Drill & Tap Column for 1/2"-13 Bolt & Install Burndy #KC26 Servit Post Connector or Equal. Coat with No-Ox-Id Compound After Installation.

Top of Concrete Paving or Finished Grade

1" PVE Conduit

#2/0 Copper Ground Wire

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 10 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 7 (TYPICAL FOR ALL SWITCH RACKS)

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 11 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 8 GROUNDING FIREPROOFED STRUCTURES (FOR ALTERNATE ASSY. - SEE FIGURE 3)

Fireproofing Material

Field Weld Steel Column 3/4" j Steel Rod Welded To Column Before Fireproofing Is Applied. Drill & Tap Rod for 3/8"-16 Bolt.

Paint with No-Ox-Id Grease After Installation

Ground Connector Burndy #K2C22B1 or Equal

#2 Awg. THW Ground Cable to Ground Rod or Ground Bus

PVC Sleeve

Column Foundation

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 12 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 9 GROUNDING STORAGE TANKS (TYPICAL FOR 2 CONNECTIONS 180 APART)

Storage Tank

3" x 1/4" x 0' - 3" Steel Angle - Drill & Tap for 3/8"-16 Bolt Field Weld

Top of Tank FDN. or Finished Grade

Install Burndy #KC22 or Equal - Coat with No-Ox-Id Compound After Installation

#2 Cu. Ground Cable to Ground Rod or Bus

1" PVC Sleeve (18" Long - TYP.)

Note:

See IP 16-4-1 for grounding requirements.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 13 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 10 GROUNDING FOR MOTOR CONTROL CENTERS

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 14 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 11 GROUNDING SPHERES

Notes: (1) See IP 16-4-1, Par. 9.8b for grounding requirements. (2) Install 1 in. PVC conduit sleeve and bushing where area is to be paved.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 15 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 12 INSULATING FLANGES

Notes: (1) Insulating kits and materials will be specified on the project piping drawings. (2) All edges of gaskets & washers are to be sealed with protective coating. Joint is to be wrapped with insulating tape.

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 16 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 13 INSTRUCTION! FOR THERMOWELD TYPE GROUNDS

GENERAL INSTRUCTIONS: (1) All surfaces that are to be welded must be bright, clean & dry. (2) Place mould over clean surface with end of conductor under center of tap hole. (3) Cover tap hole with metal disk and empty powder into crucible so that starting powder is at the top of the crucible. Do not attempt to mix or stir powder. (4) Use flint gun to ignite starting powder. (5) After approximately 10 seconds remove mold and clean slag from crucible before making next weld. (6) Make sure that mold is dry, preheat with torch if required. WELDER TYPE CC2 CC2 CC2 CS3 CS3 CR1 CR1 CR2 CONNECTION TYPE #2/0 To #2/0 Tap #2/0 To #2 Tap #2 To #2 Tap #2/0 To Steel #2 To Steel #2 To 3/4 in. GND Rod #2/0 To 3/4 in. GND Rod #2/0 To 3/4 in. GND Rod THERMOWELD CAT. NO. M-232 M-235 M-223 M-591 M-588 M-5781 M-516 M-559 THERMOCHANGE HANDLE TYPE 8106 8106 8106 8106 8106 8106 8108 8106 CARTRIDGE SIZE # 90 # 45 # 45 # 90 # 45 # 90 # 90 # 115

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 17 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 14 THERMOWELD GROUND ROD

FIGURE 15 THERMOWELD GROUND ROD

FIGURE 16 THERMOWELD CABLE TAPS

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 18 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 17 GROUNDING OF TANK CARS AND TANK TRUCKS AT LOADING RACKS

PIPE SIZE 1 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 3-1/2 in. 4 in. Note: Special Note:

S.R. BROWNE CO. CAT. NO. JR-150-8 JR-150-12 JR-150-16 JR-150-20 JR-150-24 JR-150-32 JR-150-48 Pipe surface are to be wire brushed and thoroughly cleaned before clamping. Paint clamps and 4 in. on either side with protective coating. Cargo tanks (Tank Trucks) in which flammable vapors are to be present, while being loaded through top domes, should be electrically bonded to fill stem piping. For tank car loading, bonding to tracks should be adequate.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 19 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 18 GROUNDING FOR TANK TRUCKS LOADING & UNLOADING

PLAN VIEW

PIPE SIZE 1 ft 1-1/2 in. 2 in. 2-1/2 in. 3 in. 4 in. 6 in. VIEW A - A"

S.R. BROWNE CO. CAT. NO. JR-150-8 JR-150-12 JR-150-16 JR-150-20 JR-150-24 JR-150-32 JR-150-48

Note: Surfaces are to be wired brushed and thoroughly cleaned before clamping. Paint Clamps and 4 in. on either side with protective coating.

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 20 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 19 GROUNDING OF LOADING RACKS

PIPE SIZE 1 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 3-1/2 in. 4 in.

S.R. BROWNE CO. CAT. NO. JR-150-8 JR-150-12 JR-150-16 JR-150-20 JR-150-24 JR-150-32 JR-150-48

PLAN

ELEVATION
Note: Surfaces are to be wired brushed and thoroughly cleaned before clamping. Paint Clamps and 4" on either side with protective coating.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 21 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 20 GROUNDING RAILROAD TRACKS AT LOADING RACKS

ECA / EUSA Regional Engineering Guide

EG 16-4-1.1
Page 22 of 23 Rev. 1 June 2000

ENGINEERING GUIDE Electrical Grounding


(This practice is appropriate for attachment to Inquiry or Purchase Document)

ECA / EUSA

FIGURE 21 CONDUIT ENTRY DETAIL

CONDUIT GROUNDING DETAIL FOR FIREPROOF PULLBOXES

Note: For fireproof boxes use 3-1/2 in. long stud.

ECA / EUSA Regional Engineering Guide

ENGINEERING GUIDE
ECA / EUSA

EG 16-4-1.1
Page 23 of 23 Rev. 1 June 2000

Electrical Grounding
(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 22 FLEXIBLE CONDUIT BONDING DETAIL


FLEXIBLE CONDUIT SIZE 1/2 in. 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 4 in. BONDING JUMPER MINIMUM AWG SIZE #12 #10 #8 #6 #6 #4 #2 #2 #2/0

ECA / EUSA Regional Engineering Guide